This document is a Standard Operating Procedure (SOP) that establishes guidelines for water treatment of heating, ventilation, and air conditioning (HVAC) systems at VA Palo Alto Health Care System. The procedure, numbered SOP 138-21-31 and effective December 9, 2021, governs the treatment of cooling towers in both open and closed-loop HVAC systems to prevent bacteria growth and maintain water safety in compliance with industry standards. The Maintenance and Repair Supervisor and Air Conditioning Shop Supervisor are responsible for oversight and execution of the monitoring program, with authority to hire contractors if staffing shortages exist.

The procedure requires weekly testing and recording of open and closed-loop HVAC cooling towers for pH level, total dissolved solids (TDS) of incoming tower water, and organophosphonate levels. Bacteria readings must be taken regularly with adjustments to microbiocide chemicals as needed to prevent bacterial growth. Chilled water, heating hot water, and condenser water closed-loops require monthly inspection and testing with recorded readings and necessary chemical additions. Applicable meters must be read to document water and sewage usage levels. The SOP references ASHRAE guidelines on minimizing Legionellosis risk and NFPA Standard 214 for water-cooling tower standards. The procedure is scheduled for recertification on or before December 31, 2026. The document also includes a Director's Memorandum rescinding the previous HCSM No. 138-18-31 dated September 1, 2008, with the information consolidated into this SOP effective December 9, 2021.

View the file

Other files for this federal contract opportunity

Other files attached to F103--HVAC Cooling Towers Testing and Maintenance, newest first.
File Type Posted
36C26126Q0576 0003.docx DOCX document
36C26126Q0576 0002.docx DOCX document
36C26126Q0576 0001.docx DOCX document
Attachment 7 WD 2015-5641 Santa Clara County.pdf PDF
Attachment 5 WD 2015-5623 Alameda County.pdf PDF
Attachment 2 General Duty Clause Section 5a1.pdf PDF
Attachment 1 VHA DIRECTIVE 1061.4.pdf PDF
36C26126Q0576.docx DOCX document
Attachment 6 WD 2015-5637 San Mateo County.pdf PDF
Attachment 4 SOP 138-21-05.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HEATING, VENTILATION, AND AIR CONDITIONING WATER TREATMENT

STANDARD OPERATING PROCEDURE

SOP 138-21-31

VA Palo Alto Health Care System Palo Alto, CA 94304

Signatory Authority:

Chief of Engineering Service

Responsible Owner:

Maintenance and Repair (M&R) Supervisor

1. PURPOSE AND AUTHORITY

Service Line:

Engineering Service

Effective Date:

December 9, 2021

Recertification Date:

December 31, 2026

This standard operating procedure (SOP) establishes guidelines to govern the water treatment of the cooling towers to prevent bacteria growth in VA Palo Alto Health Care System (VAPAHCS) open and closed loop heating, ventilation, and air conditioning (HVAC) systems. Engineering Service will comply with water treatment industry standards and maintain a high-quality level of water safety.

2. PROCEDURES

a. Each open or closed-loop HVAC cooling tower will be tested weekly, and test results shall be recorded. Testing will be conducted and recorded for the following:

(1) pH level of water

(2) Total Dissolved Solids (TDS) of incoming tower water; and

(3) Testing for Organophosphonate level.

b. The difference in readings of TDS and Organophosphonate levels will be used to calculate and adjust chemical composition of the cooling tower water.

c. A bacteria reading will be taken and depending on the results, the microbiocide chemicals will be altered to maintain the prevention of bacteria in the water.

d. Applicable meters will be read to document water and sewage usage levels at the facility.

DECEMBER 9, 2021 SOP 138-21-31

e. Chilled water, heating hot water, and condenser water closed-loops will be inspected and tested monthly. The readings will be recorded and chemicals will be added as necessary.

3. ASSIGNMENT OF RESPONSIBILITIES

a.The Maintenance and Repair Supervisor is responsible for oversight and compliance of the monitoring requirements as required by VHA, ASHRAE, and NFPA guidelines.

b.The Air Conditioning Shop Supervisor is responsible for the cooling tower and closed loop maintenance program. If staffing shortages exist, the supervisor will hire a contractor to perform work to maintain compliance.

4. DEFINITIONS

a.COOLING TOWER (OPEN): The mechanical system to remove of heat from a chilled water system that passes directly through the condenser vessel and then is exposed to air when it passes through the cooling tower for evaporative cooling b.COOLING TOWER (CLOSED): Similar in design to the open loop tower, but the water that passes through the condenser is sealed and pressurized (closed loop), and a separate body of water passes over the tubes causing a heat exchange and thus, removal of heat.

c. CLOSED-LOOP SYSTEM: Refers to a chilled water, heating hot water, or heat rejection loop that is sealed and pressurized and treated by use of a chemical jar or pot feeder.

5. REFERENCES

a. ASH RAE guidelines: Minimizing the Risk of Legionellosis Associated with Building Water Systems.

b. NFPA Standard 214: Standard on Water-Cooling Tower Latest Edition.

6. REVIEW

This SOP must be reviewed at recertification and including when there are changes to service-level privacy assessments.

7. RECERTIFICATION

This SOP is scheduled for recertification on or before the last working day of December 2026. This SOP will continue to serve as local policy until it is recertified or rescinded. In

DECEMBER 9, 2021 SOP 138-21-31

the event of contradiction with national policy, the national policy supersedes and controls.

8. SIGNATORY AUTHORITY

Digitally signed by JAMES

JAMES P. P. CROWE 1726175

CROWE 1726175 Date: 2021.12.10 16:45:51 -0800'

James P. Crowe Chief of Engineering Service Date Approved:

NOTE: The signature remains valid until rescinded by an appropriate administrative action.

DISTRIBUTION: SOPs are available at https://dvadov.sharepoint.com/sites/PAL/memoranda/Pades/Policies.aspx.

NOTE: This is an internal VA website that is not available to the public.

RESCISSION OF HEALTH CARE SYSTEM MEMORANDUM (HCSM) NO. 138-18-31,

OPERATING ROOM HEATING, VENTILATION, AND AIR CONDITIONING WATER

TREATMENT POLICY

VA Palo Alto Health Care System Palo Alto, CA 94304

Signatory Authority:

VA Palo Alto Health Care System Director

Director's Memorandum 138-18-31R

Rescinded Document:

HCSM No. 138-18-31, Heating, Ventilation, and Air Conditioning water Treatment Policy, dated September 1, 2008 (Issue August 1,2018)

Effective Date:

December 9, 2021

1.By direction of the VA Palo Alto Health Care System (VAPAHCS) Director, 138-18- 31, Heating, Ventilation, and Air Conditioning Water Treatment Policy, dated September 1, 2008, is rescinded.

2. The information has been moved to standard operating procedure. It is available at:

https://dvagov.sharepoint.com/sites/PAL/memoranda/Pages/Policies.aspx.

3. This Director's Memorandum will be archived as of December 2022. However, the rescission information will remain in effect.

4. SIGNATORY AUTHORITY

Lisa M. Howard VA Palo Alto Health Care System Director Date Approved:

NOTE: The signature remains valid until rescinded by an appropriate administrative action.

DISTRIBUTION: Rescissions are available at:

https://dvagov.sharepoint.com/sites/PAL/memoranda/Pages/Policies.aspx

NOTE: This is an internal VA website that is not available to the public.

Page 1
Page 2
Page 3
Page 4

File details come from the government source that posted it. Updated .