Attachment 3 - PWS App B - GPRG ITM Mandatory Freqs..pdf
PDF 371 KB Posted
- Solicitation number
- FA568224Q8089
About this file
This document is an Appendix B titled "GPRG ITM Mandatory Frequencies" that provides details on the inspection, functional testing, and maintenance requirements for the gas pressure reducing groups (GPRG) of the gas distribution system at Aviano Air Base, Italy.
The key details are:
- The document specifies the mandatory inspection, functional testing, and maintenance frequencies for GPRG based on the upstream pressure and nominal flow rate.
- For GPRG with nominal flow rate greater than 1200 kW, inspections are required every 0.04 years, functional tests every 0.04 years, and maintenance every 0.04 years.
- For GPRG with nominal flow rate less than or equal to 1200 kW, inspections are required every 0.04 years, functional tests every 0.04 years, and maintenance every 0.04 years.
This Appendix B is referenced in the Performance Work Statement (PWS) for the Maintenance and Repair of Gas Distribution System at Aviano AB, Italy contract opportunity, Solicitation Number FA568224Q8089, issued by the U.S. Air Force United States Air Forces in Europe - Air Forces Africa.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX B
GPRG ITM Mandatory Frequencies
MAINTENANCE AND REPAIR OF GAS DISTRIBUTION SYSTEM
AT AVIANO AB, ITALY
Pressione a monte Upstream pressure
Bar
Portata nominale dei sistemi di controllo della pressione Nominal flow rate of Gas Pressure Reducing Groups
Qnom > 1200 KW Qnom ≤ 1200 KW
Ispezioni Inspections
Verifiche funzionali Functional Tests
Manutenzione Maintenance
Verifiche funzionali Functional Tests
Manutenzione Maintenance
0.04 < P ≤ 0.5 *) 1 ogni 2 anni 1 every 2 years
1 ogni 8 anni 1 every 8 years
1 ogni 3 anni 1 every 3 years
Secondo necessitá According to need 0.5 < P ≤ 5 *) 1 ogni anno
1 per year 1 ogni 7 anni 1 every 7 years
1 ogni 2 anni 1 every 2 years
5 < P ≤ 12 *) 1 ogni anno 1 per year
1 ogni 5 anni 1 every 5 years
1 ogni anno 1 every year
*) Le ispezioni devono essere effettuate nell’intervallo tra due verifiche funzionali successive *) The inspections must be performed in the interval between two subsequent functional tests
Nota Per i sistemi di controllo della pressione con portata nominale Qnom ≤ 1200 KW, il primo ciclo di verifiche funzionali dovrá essere eseguito entro il primo anno del presente contratto
Note For the Gas Pressure Reducing Groups with nominal flow rate Qnom ≤ 1200 KW, the first cycle of functional test shall be performed within the first year of present contract
27 August 2024
File details come from the government source that posted it. Updated .