ATTACHMENT 3 - Environmental Narrative.pdf

PDF 4 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Data Center Construction - St. Louis JB - Project 657-21-709JB
Solicitation number
36C77625B0008
Issued by

About this file

This is an environmental narrative document for the EHRM Infrastructure Upgrades Data Center project at Jefferson Barracks VA Medical Center in St. Louis, MO. The document details environmental assessments conducted by Riverfront Safety & Health, LC, a Service-Disabled Veteran Owned Small Business, focused on asbestos and lead identification surveys in Building 1 Room GC11 and Building 56 Rooms BB102, BB121, and the Generator Outhouse.

The assessment findings revealed no asbestos-containing materials in Building 56 or its generator house, but multiple asbestos-containing materials were identified in Building 1, Room GC11, including asbestos pipe insulation, mudded fittings, floor tile, black mastic, and exterior surfacing material. Lead testing was conducted using XRF sampling methods, with none of the 23 readings exceeding the EPA threshold of 1.0 mg/cm². The document includes detailed laboratory analysis reports from EMSL Analytical Inc., chains of custody, and professional certifications for the inspectors who conducted the surveys. Any work impacting the identified asbestos materials must be performed by a licensed abatement contractor.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EHRM INFRASTRUCTURE UPGRADES DESIGN

JEFFERSON BARRACKS – ST. LOUIS, MO

PROJECT #: 657-21-709JB

Environmental Narrative 10MAY24

Environmental 1

VA PROJECT NUMBER

PROJECT NAME

SUBMITTAL

657-21-709JB

EHRM Infrastructure Upgrade: Data Center 100% Construction Documents

SUBJECT Environmental Design Narrative

Project Overview and Background

Riverfront Safety & Health, LC (Riverfront), a Service-Disabled Veteran Owned Small Business, has provided the required limited asbestos & lead identification field surveys and historical records review in support of the 100% Construction Documents phase of the EHRM Infrastructure Upgrade: Data Center Project (VA Project 657-21-709JB) located at the Jefferson Barracks VA Medical Center, St. Louis, MO (The Project). The current limited asbestos and lead survey was performed using project scope of work documents, basis of design and drawings.

Field Investigation Objectives

Project objectives are as follows:

The overall intent of this project is to upgrade and improve the Electronic Health Record Modernization (EHRM) infrastructure of the Jefferson Barracks, MO Healthcare campus as part of the ongoing national VA EHRM initiative.

The A/E has begun assessing the current data center in Building 1 and the new data center in Building 56. The A/E has also noted the cutover from the GC11 DC and will integrate ongoing projects with this design to ensure the plan remains united and coordinated to minimize impacts to campus operations. The A/E noted on initial discussions the following key aspects which are further discussed herein:

1. VA audio visual department requirements must be accounted for in this design and layout.

a. Inclusion of these active servers will be considered for outages and disruptions during phasing of this project.

2. Integration of biomed server racks

3. Consolidation of OI&T equipment from Building 1, GC11

4. Redesign of power distribution

5. Redesign of HVAC system

6. Correction of known plumbing issues, specifically the backflow of fluids into the floor plenum from floor drain.

RSH understands that the field assessment is limited to:

Building 1: Room GC11 Building 56: Room BB102, Room BB121, and Generator Outhouse

Field Investigation Summary

Riverfront provided inspection personnel accredited under the Asbestos Hazard Emergency Response Act (AHERA), U.S. Environmental Protection Agency Model Accreditation Program for Asbestos Building Inspectors to perform the following:

Verify the presence, location, quantity, appearance, and condition of all applicable building materials exhibiting asbestos, lead and mold containing materials within areas of scheduled work at the Jefferson Barracks VA Facility, identified by the VA as likely to be impacted during this project. Areas likely to be impacted by The Project are limited to Building 1, Room GC11 and Building 56, Room BB102, BB121 and the Generator Outhouse.

The project specific limited asbestos survey was performed by Mr. Blaine Gravagna and Mr. Travis Carter on May 1, 2, and 9, 2024. Both inspectors are accredited under the Asbestos Hazard Emergency Response Act (AHERA), U.S. Environmental Protection Agency Model Accreditation Program for Asbestos Building Inspectors. Both Mr. Carter and Mr. Gravagna performed lead sampling under the direction of Mr. Charles Davis who is an EPA certified Missouri licensed Lead Risk Assessor. All work was performed under the supervision of a Certified Industrial Hygienist (CIH), Mr. Justin R. Rhyneer to ensure standard EPA- NESHAP/AHERA/OSHA field inspection and sampling methods were employed for representative project

PROJECT NAME

SUBMITTAL

657-21-709JB

EHRM Infrastructure Upgrade: Data Center 100% Construction Documents

SUBJECT Environmental Design Narrative

Environmental 2 inspection. Laboratory results from this confirmation sampling can be found in Appendix A. Principal contacts for this project were Kyle Florian of the VA Medical Center and Leo Thomas from SpeesDB. Based on records review and visual observations at the time of the field investigation, the following items were noted:

Mold impacted building materials are not anticipated and where present are a highly localized condition. Areas will be visually inspected for suspect mold growth on materials located within or near the projected pathways of work.

As a general course of action, reuse of existing wall penetrations and pathways is recommended.

Areas within chases and exterior wall voids are normally suspected of covering asbestos containing materials. Where plaster or drywall ceilings are present, it is generally assumed, asbestos pipe insulation and/or mudded fittings associated with domestic water, chilled water, or perimeter heat systems will also be present above them. All historical plaster is presumed to cover asbestos TSI or other asbestos-containing materials.

Asbestos containing stucco and lead based paint are frequently present on the exterior of buildings.

Asbestos mastic and lead based paint are commonly discovered on the interior foundation walls as well. Any exterior stucco and associated caulks are considered suspect asbestos containing materials. These areas were of particular importance to survey during the onsite inspection to ascertain what building materials will be impacted where new building penetrations are necessary.

Field assessment was limited to areas within Building 1, Room GC11 and Building 56, Room BB102, BB121 and the Generator Outhouse. Any work outside of these areas, in other rooms and/or buildings, and in duct banks or other existing pathways may disturb unknown environmental hazards.

Asbestos Containing Materials – Assessment & Inspection Results

Riverfront personnel collected a total of 38 representative samples of suspected asbestos containing materials related to The Project. The suspect materials, which were similar in general appearance and age of construction, were grouped into homogeneous material sets and sampled. Practical precautions were used in collecting samples to ensure the safety of all personnel. All samples were transferred via written chain-of -custody, to EMSL, an AIHA & NVLAP accredited laboratory, for analysis. A minimum of three samples were collected of all suspect asbestos containing building materials. All samples were analyzed using polarized light microscopy (PLM) analysis with dispersion staining (DS) according to U.S.

Environmental Protection Agency (EPA) Method 600 IR-93/116 which is presently recommended by the EPA. Asbestos Containing Materials are defined by EPA as having greater than 1% asbestos as measured by PLM methods. Zero (0) of the 32 suspect asbestos samples collected were identified as asbestos containing materials by PLM analysis.

While there are no known environmental hazards within Building 56 or the Building 56 generator house, multiple asbestos-containing building materials exist within Building 1, Room GC11. These materials include asbestos pipe insulation and/or asbestos mudded fittings, asbestos floor tile and asbestos black mastic, and exterior asbestos surfacing material. These materials should be avoided and protected as necessary during the course of work. Any work likely to impact these materials must be performed by a licensed abatement contractor.

Please see attached Appendix A for laboratory analytical reports.

Lead Containing Materials – Assessment & Inspection Results

SUBMITTAL

657-21-709JB

EHRM Infrastructure Upgrade: Data Center 100% Construction Documents

SUBJECT Environmental Design Narrative

Environmental 3

A targeted lead inspection was performed on representative indoor building components to identify lead-based paint on primary substrates likely to be impacted by The Project. Primary components analyzed included, but are not limited to drywall, CMU, concrete, ceramic wall and floor tiles, plaster ceilings, metal data racks, and metal pipe components.

Riverfront collected lead readings from targeted surfaces to identify the presence of lead-based paint (LBP), which is defined by the EPA as greater than or equal to 1.0 mg/cm2 lead by surface loading (as tested by an XRF instrument). EPA/HUD compliant XRF (X-Ray Fluorescence) sampling methods, which are non-destructive, were employed for this project assessment.

It is stressed that this sampling was intended to identify the presence of lead-based paint and/or lead glazed tiles within readily accessible areas of the buildings which may become disturbed during future construction and activities and associated with this particular project design, and not necessarily an EPA- HUD type “surface-by- surface” inspection. An EPA-HUD trained Lead Inspector/Risk Assessor collected all readings.

The RSH inspection team gathered a total of 23 readings including instrument calibration readings. Of these, 0 readings (0 materials) were above the 1.0 mg/cm2 threshold. Materials showing elevated levels included:

Please see the included Table 1 for the full RSH asbestos bulk sampling, Table 2 for the full RSH Lead XRF sampling, Appendix A for asbestos laboratory analytical reports, sample chains of custody, and Appendix B for professional certifications.

Riverfront appreciates the opportunity to assist with this project. It is our intent that this information will assist with project development at this phase. Please feel free to contact us with any questions or concerns.

Sincerely, May 14, 2024 Justin R. Rhyneer, CIH Date Principal

Table 1: RSH Field Sampling ACM Bulk Sampling Summary Table Table 2: RSH Field Sampling Lead XRF Sampling Summary Table Appendix A: Asbestos Laboratory Results Appendix B: Professional Certifications

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBMITTAL 100% Construction Documents SUBJECT Environmental Design Narrative – Table 1

Environmental –1

TABLE 1: ACM SAMPLING SUMMARY

Field Sampling on May 1st, 2nd, and 9th 2024

Sample No.

Material Description

Sample Location

Category Homogenous Area

Condition Quantity Asbestos Content

SH1938-

050124-

A1 Red Fire Stop Room BB102

(Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A2

Dark Red Fire Stop with

Metallic Flake

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A3

Dark Red Fire Stop with

Metallic Flake

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A4

Dark Red Fire Stop with

Metallic Flake

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A5

2’x4’ CT Fiberglass

Rough Room BB102 Friable Building 56 Good None

Detected

SH1938-

050124-

A6

2’x4’ CT Fiberglass

Rough Room BB102 Friable Building 56 Good None

Detected

SH1938-

050124-

A7

2’x4’ CT Fiberglass

Rough Room BB102 Friable Building 56 Good None

Detected

SH1938-

050124-

A8

White Penetration

Caulk Room BB102

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A9 Joint Compound Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A10 Joint Compound Room BB102

(Wall 3) Friable Building 56 Good None Detected

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBMITTAL 100% Construction Documents SUBJECT Environmental Design Narrative – Table 1

Environmental - 2

TABLE 1: ACM SAMPLING SUMMARY

Field Sampling on May 1st, 2nd, and 9th 2024

Sample No.

Material Description

Sample Location

Category Homogenous Area

Condition Quantity Asbestos Content

SH1938-

050124-

A11 Joint Compound Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A12 Drywall Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A13 Drywall Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A14 Drywall Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A15 Drywall Tape Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A16 Drywall Tape Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A17 Drywall Tape Room BB102

(Wall 3) Friable Building 56 Good None Detected

SH1938-

050124-

A18

Pedestal Adhesive (Data

Tower)

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A19

Pedestal Adhesive (Data

Tower)

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A20

Pedestal Adhesive (Data

Tower)

Room BB102 (Wall 3)

CAT II

Non-

Friable Building 56 Good None

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBMITTAL 100% Construction Documents SUBJECT Environmental Design Narrative – Table 1

Environmental - 3

TABLE 1: ACM SAMPLING SUMMARY

Field Sampling on May 1st, 2nd, and 9th 2024

Sample No.

Material Description

Sample Location

Category Homogenous Area

Condition Quantity Asbestos Content

SH1938-

050124-

A21

White Fiberglass Seam Sealant Room BB102

CAT I

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A22

White Fiberglass Seam Sealant Room BB102

CAT I

Non-

Friable Building 56 Good None

Detected

SH1938-

050124-

A23

White Fiberglass Seam Sealant Room BB102

CAT I

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A1

Grey Concrete Gap Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A2

Grey Concrete Gap Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A3

Grey Concrete Gap Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A4

White Brick Grout

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A5

White Brick Grout

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A6

White Brick Grout

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A7 Tan Brick Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Environmental - 4

TABLE 1: ACM SAMPLING SUMMARY

Field Sampling on May 1st, 2nd, and 9th 2024

Sample No.

Material Description

Sample Location

Category Homogenous Area

Condition Quantity Asbestos Content

SH1938-

050224-

A8 Tan Brick Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050224-

A9 Tan Brick Caulk

Generator Outhouse Exterior

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-1

Green Pipe Dope CWS Room BB121

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-2

Green Pipe Dope CWR Room BB121

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-3

Green Pipe Dope CWR Room BB121

CAT II

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-4

White Fiberglass Seam Sealant

CWS

Room BB121

CAT I

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-5

White Fiberglass Seam Sealant

CWS

Room BB102

CAT I

Non-

Friable Building 56 Good None

Detected

SH1938-

050924-6

White Fiberglass Seam Sealant

CWS

Room BB102

CAT I

Non-

Friable Building 56 Good None

Detected

Notes:

1) Positive ACM samples are noted in bold type.

2) An asbestos-containing material is defined as a material that contains greater than 1% asbestos.

3) A friable asbestos-containing material is a material than can be pulverized, crumbled, or reduced to powder by hand pressure. Likewise, a non-friable asbestos-containing material is a material than cannot be pulverized, crumbled, or reduced to powder by hand pressure.

VA PROJECT NUMBER

PROJECT NAME

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBMITTAL 100% Construction Documents SUBJECT Environmental Design Narrative – Table 1

Environmental - 1

TABLE 2: LEAD XRF SAMPLING SUMMARY

Field Sampling on May 1st, 2024

Sample No.

Floor Area Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

2214 PRECALIBRATION 1.0

2215 PRECALIBRATION 1.3

2216 PRECALIBRATION 1.2

2217 BUILDING 56

1ST FLOOR

ROOM

BB102 1 WALL DRYWALL INTACT BEIGE 0

2218 BUILDING 56

1ST FLOOR

ROOM

BB102 2 WALL DRYWALL INTACT BEIGE 0.1

2219 BUILDING 56

1ST FLOOR

ROOM

BB102 3 WALL DRYWALL INTACT BEIGE 0.1

2220 BUILDING 56

1ST FLOOR

ROOM

BB102

FIRE

SPRINKLER

LINE

METAL INTACT RED -0.3

2221 BUILDING 56

1ST FLOOR

ROOM

BB102 MIDDLE DATA RACK METAL INTACT BLACK 0

2222 BUILDING 56

1ST FLOOR

ROOM

BB102 LEFT DATA RACK CERAMIC INTACT BLACK 0.1

2223 BUILDING 56

1ST FLOOR

ROOM

BB102 RIGHT DATA RACK METAL INTACT BLACK 0

2224 BUILDING 56

1ST FLOOR

ROOM

BB102 FLOOR TILES CERAMIC INTACT OFF

WHITE -0.3

2225 BUILDING 56

1ST FLOOR

ROOM

BB102 FLOOR TILES CERAMIC INTACT GREEN 0.5

2226 BUILDING 56

1ST FLOOR

ROOM

BB102

ELECTRIC

PANEL METAL INTACT GREY 0.1

2227 BUILDING 56 Generator Outhouse WALL CMU INTACT BEIGE 0.1

2228 BUILDING 1

BASEMENT

ROOM

GC11 WALL CERAMIC INTACT WHITE -0.1

2229 BUILDING 1

BASEMENT

ROOM

GC11 WALL PLASTER INTACT BEIGE 0.1

2230 BUILDING 1

BASEMENT

ROOM

GC11 WALL PLASTER INTACT GREEN -0.1

VA PROJECT NUMBER

PROJECT NAME

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBJECT Environmental Design Narrative – Table 2

Environmental - 2

TABLE 2: LEAD XRF SAMPLING SUMMARY

Field Sampling on May 1st, 2024

Sample No.

Floor Area Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

2231 BUILDING 1

BASEMENT

ROOM

GC11 CEILING PLASTER INTACT GREEN 0.3

2232 BUILDING 1

BASEMENT

ROOM

GC11 CEILING PLASTER INTACT BEIGE 0.1

2233 BUILDING 1

BASEMENT

ROOM

GC11 WALL CONCRETE INTACT WHITE 0.4

2234 POSTCALIBRATION 1.1

2235 POSTCALIBRATION 1.1

2236 POSTCALIBRATION 1.1

Notes:

1) Elevated samples are noted in red type.

2) Elevated samples exceed EPA lead concentration of 1.0 mg/cm2 as measured by XRF.

3) Assumed samples are highlighted.

VA PROJECT NUMBER

PROJECT NAME

657-21-709JB

EHRM Infrastructure Upgrade: Data Center

SUBJECT Environmental Design Narrative – Table 2

OrderID: 392402349

O r d e r I D

P a g e

O f

EMSL Analytical, Inc.

100 Green Park Industrial Court Saint Louis, MO 63123

Tel/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com / saintlouislab@emsl.com

392402349EMSL Order:

Customer ID: RIVF72

Customer PO:

Project ID:

Attention: Phone:Travis Carter (314) 410-5881

Fax:Riverfront Safety & Health, LLC (314) 436-9733

Received Date:11140 South Town Square 05/01/2024 3:30 PM

Analysis Date:Suite 100 05/02/2024

Collected Date:Saint Louis, MO 63101

Project: SH1938 Spees JB Bldg 56 EHRM Data Center

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

SH1938-050124-A1

392402349-0001

None DetectedNon-fibrous (Other)83%Glass17%Various

Non-Fibrous

Homogeneous

SH1938-050124-A2

392402349-0002

None DetectedNon-fibrous (Other)82%Glass18%Various

Non-Fibrous

Homogeneous

SH1938-050124-A3

392402349-0003

None DetectedNon-fibrous (Other)81%Glass19%Various

Non-Fibrous

Homogeneous

SH1938-050124-A4

392402349-0004

None DetectedNon-fibrous (Other)84%Glass16%Various

Non-Fibrous

Homogeneous

SH1938-050124-A5

392402349-0005

None DetectedNon-fibrous (Other)6%Min. Wool94%Various

Fibrous

Homogeneous

SH1938-050124-A6

392402349-0006

None DetectedNon-fibrous (Other)5%Min. Wool95%Various

Fibrous

Homogeneous

SH1938-050124-A7

392402349-0007

None DetectedNon-fibrous (Other)4%Min. Wool96%Various

Fibrous

Homogeneous

SH1938-050124-A8

392402349-0008

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

SH1938-050124-A9

392402349-0009

None DetectedPerlite

Non-fibrous (Other)

26%

74%

White

Non-Fibrous

Homogeneous

SH1938-050124-A10

392402349-0010

None DetectedPerlite

Non-fibrous (Other)

27%

73%

White

Non-Fibrous

Homogeneous

SH1938-050124-A11

392402349-0011

None DetectedPerlite

Non-fibrous (Other)

28%

72%

White

Non-Fibrous

Homogeneous

SH1938-050124-A12

392402349-0012

None DetectedNon-fibrous (Other)31%Cellulose69%Various

Fibrous

Homogeneous

SH1938-050124-A13

392402349-0013

None DetectedNon-fibrous (Other)34%Cellulose66%Various

Fibrous

Homogeneous

SH1938-050124-A14

392402349-0014

None DetectedNon-fibrous (Other)33%Cellulose67%Various

Fibrous

Homogeneous

SH1938-050124-A15

392402349-0015

None DetectedCellulose100%Gray

Fibrous

Homogeneous

SH1938-050124-A16

392402349-0016

None DetectedCellulose100%Gray

Fibrous

Homogeneous

Initial report from: 05/02/2024 20:29:41

Page 1 of 2ASB_PLM_0008_0002 - 2.31 Printed: 5/2/2024 7:29 PM

Tel/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com / saintlouislab@emsl.com

392402349EMSL Order:

Customer ID: RIVF72

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

SH1938-050124-A17

392402349-0017

None DetectedCellulose100%Gray

Fibrous

Homogeneous

SH1938-050124-A18

392402349-0018

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

SH1938-050124-A19

392402349-0019

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

SH1938-050124-A20

392402349-0020

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

SH1938-050124-A21-S

ealant

392402349-0021

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

SH1938-050124-A21-In sulation

392402349-0021A

None DetectedNon-fibrous (Other)5%Glass95%Brown

Fibrous

Homogeneous

SH1938-050124-A22-S

ealant

392402349-0022

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

SH1938-050124-A22-In sulation

392402349-0022A

None DetectedNon-fibrous (Other)4%Glass96%Brown

Fibrous

Homogeneous

SH1938-050124-A23-S

ealant

392402349-0023

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

SH1938-050124-A23-In sulation

392402349-0023A

None DetectedNon-fibrous (Other)7%Glass93%Brown

Fibrous

Homogeneous

Analyst(s)

Sue Ferrario (26) Jeff Siria, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0, CA 2668, OR 4194-001

Initial report from: 05/02/2024 20:29:41

Page 2 of 2ASB_PLM_0008_0002 - 2.31 Printed: 5/2/2024 7:29 PM

OrderID: 392402376

OrderID: 392402376

Tel/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com / saintlouislab@emsl.com

392402376EMSL Order:

Customer ID: RIVF72

Customer PO:

Project ID:

Attention: Phone:Blaine Gravagna (314) 436-9492

Fax:Riverfront Safety & Health, LLC (314) 436-9733

Received Date:11140 South Towne Square, Suite 100 05/02/2024 1:30 PM

Analysis Date:Saint Louis, MO 63123 05/03/2024

Collected Date:

Project: SH1938 Bldg 56 JB

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

SH1938-050224-A1

392402376-0001

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

SH1938-050224-A2

392402376-0002

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

SH1938-050224-A3

392402376-0003

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

SH1938-050224-A4

392402376-0004

None DetectedQuartz

Non-fibrous (Other)

17%

83%

Various

Non-Fibrous

Homogeneous

SH1938-050224-A5

392402376-0005

None DetectedQuartz

Non-fibrous (Other)

18%

82%

Various

Non-Fibrous

Homogeneous

SH1938-050224-A6

392402376-0006

None DetectedQuartz

Non-fibrous (Other)

19%

81%

Various

Non-Fibrous

Homogeneous

SH1938-050224-A7

392402376-0007

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

SH1938-050224-A8

392402376-0008

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

SH1938-050224-A9

392402376-0009

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

Analyst(s)

Sue Ferrario (9) Jeff Siria, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0, CA 2668, OR 4194-001

Initial report from: 05/03/2024 12:48:51

Page 1 of 1ASB_PLM_0008_0002 - 2.31 Printed: 5/3/2024 11:48 AM

OrderID: 392402502

Tel/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com / saintlouislab@emsl.com

392402502EMSL Order:

Customer ID: RIVF72

Customer PO:

Project ID:

Attention: Phone:Blaine Gravagna (314) 436-9492

Fax:Riverfront Safety & Health, LLC (314) 436-9733

Received Date:11140 South Towne Square, Suite 100 05/09/2024 3:15 PM

Analysis Date:Saint Louis, MO 63123 05/10/2024

Collected Date:

Project: Bldg. 56 EHRM

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

050924-01

392402502-0001

None DetectedNon-fibrous (Other)100%Green

Non-Fibrous

Homogeneous

050924-02

392402502-0002

None DetectedNon-fibrous (Other)100%Green

Non-Fibrous

Homogeneous

050924-03

392402502-0003

None DetectedNon-fibrous (Other)100%Green

Non-Fibrous

Homogeneous

050924-04-Sealant

392402502-0004

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

050924-04-Insulation

392402502-0004A

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

050924-05-Sealant

392402502-0005

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

050924-05-Insulation

392402502-0005A

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

050924-06-Sealant

392402502-0006

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

050924-06-Insulation

392402502-0006A

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Analyst(s)

Sue Ferrario (9) Jeff Siria, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0, CA 2668, OR 4194-001

Initial report from: 05/10/2024 14:35:55

Page 1 of 1ASB_PLM_0008_0002 - 2.31 Printed: 5/10/2024 1:35 PM

Missouri Department of Health and Senior Services P.O. Box 570, Jefferson City, MO 65102-0570 Phone: 573-751-6400 FAX: 573-751-6010 RELAY MISSOURI for Hearing and Speech Impaired and Voice dial: 711

Paula F. Nickelson Acting Director

Michael L. Parson Governor www.health.mo.gov

Healthy Missourians for life.

The Missouri Department of Health and Senior Services will be the leader in promoting, protecting and partnering for health.

AN EQUAL OPPORTUNITY / AFFIRMATIVE ACTION EMPLOYER: Services provided on a nondiscriminatory basis.

March 29, 2023

Charles Davis

Riverfront Safety & Health, LLC

11140 S Towne Square Suite 100

St. Louis, MO 63123

Dear Mr. Davis:

The Missouri Department of Health and Senior Services’ Lead Licensing Program has approved your renewal application for a Lead Risk Assessor license.

Enclosed is your Lead Risk Assessor license certificate and photo identification badge. If you intend to perform any regulated lead-bearing substance activities, you must be employed by a licensed Missouri lead abatement contractor. Please have your identification badge with you at all times while conducting lead abatement activities.

Note the date your Lead Risk Assessor license expires. A renewal notice will be mailed to you approximately four months prior to your license expiration date, and your renewal application will need to be completed and submitted to the Program 60 days prior to the expiration date.

A requirement of renewing your application will be attending a Lead Risk Assessor refresher class. A list of Missouri accredited lead abatement training providers will be included with your renewal notice.

For additional information, forms, and training requirements, please visit our website http://health.mo.gov/safety/leadlicensing/index.php.

Please contact the Lead Licensing Program by phone at (573) 526-5873, toll-free at (888) 837-0927, or by email at lead@health.mo.gov if you have any questions concerning this letter or lead abatement regulations in general.

Sincerely, Rachel Landrum

Lead Licensing Program rl:tp http://www.health.mo.gov/ mailto:lead@health.mo.gov

STATE OF MISSOURI

DEPARTMENT OF HEALTH AND SENIOR SERVICES

LEAD OCCUPATION LICENSE REGISTRATION

Issued to:

Charles N. Davis

The person, firm or corporation whose name appears on this certificate has fulfilled the requirements for licensure as set forth in the Missouri Revised Statutes

701.300-701.338, as long as not suspended or revoked, and is hereby authorized to engage in the activity listed below.

Lead Risk Assessor

Category of License

Issuance Date: 7/7/2023

Expiration Date: 7/22/2025

License Number: 190722-300005842

Paula F. Nickelson

Acting Director

Department of Health and Senior Services

Lead Licensing Program, PO Box 570, Jefferson City, MO 65102

United States Department of Commerce National Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2017

NVLAP LAB CODE: 200742-0

EMSL Analytical, Inc.

St. Louis, MO is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:

Asbestos Fiber Analysis

2023-04-01 through 2024-03-31

Effective Dates For the National Voluntary Laboratory Accreditation Program

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.

This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).

Effective 2023-04-01 through 2024-03-31

AIHA Laboratory Accreditation Programs, LLC acknowledges that

EMSL Analytical, Inc.

6340 Castleplace Drive Indianapolis, IN 46250

Laboratory ID: LAP-157245 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs (AIHA-LAP), LLC accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:

LABORATORY ACCREDITATION PROGRAMS

INDUSTRIAL HYGIENE Accreditation Expires: June 01, 2023

ENVIRONMENTAL LEAD Accreditation Expires: June 01, 2023

ENVIRONMENTAL MICROBIOLOGY Accreditation Expires: June 01, 2023

FOOD Accreditation Expires:

UNIQUE SCOPES Accreditation Expires:

Specific Field(s) of Testing (FoT)/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA-LAP, LLC requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA-LAP, LLC website (www.aihaaccreditedlabs.org) for the most current Scope.

Revision19: 09/01/2020

Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC

Date Issued: 05/31/2021

Effective: 11/21/2019 Revision: 8

AIHA Laboratory Accreditation Programs, LLC

SCOPE OF ACCREDITATION

EMSL Analytical, Inc. Laboratory ID: LAP-157245

6340 Castleplace Drive Indianapolis, IN 46250 Issue Date: 05/31/2021

The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory's current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.

The EPA recognizes the AIHA-LAP, LLC ELLAP program as meeting the requirements of the National Lead Laboratory Accreditation Program (NLLAP) established under Title X of the Residential Lead-Based Paint Hazard Reduction Act of 1992 and includes paint, soil and dust wipe analysis. Air and composited wipes analyses are not included as part of the

NLLAP.

Environmental Lead Laboratory Accreditation Program (ELLAP)

Initial Accreditation Date: 09/01/2002

Component, parameter or characteristic tested

Technology sub-type/Detector Method Method Description

(for internal methods only)

Airborne Dust AA NIOSH 7082 N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/APaint AA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/ASettled Dust by Wipe AA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/ASoil AA

EPA SW-846 7000B N/A

A complete listing of currently accredited ELLAP laboratories is available on the AIHA-LAP, LLC website at: http:// www.aihaaccreditedlabs.org

Appendix B.pdf
NVLAP St. Louis 2023-2024.pdf
St. Louis NVLAP cert 2023
St. Louis NVLAP scope 2023

File details come from the government source that posted it. Updated .