Attachment__3_-_Drawing_-_Stamp_Drawing_Ver_3_0.pdf

PDF 4 MB Posted

Attached to
CA-MERCED NWR-Solar Distribution Panel Replacement
Solicitation number
140FC326Q0046
Issued by

About this file

This is a comprehensive set of engineering drawings and technical specifications for a 213.2 kW direct current (DC) / 175.0 kW alternating current (AC) photovoltaic (PV) solar power system installation at a U.S. Department of the Interior, Fish and Wildlife Service property located at 13840 Highway 140, Livingston, California 95334.

The project involves installation of 520 SolarJuice Technology SA410-72MH5 410-watt solar modules mounted on OMCO Choice ground mounts at a 15-degree tilt angle and 180-degree orientation. The system utilizes three SMA inverters: two 62.5 kW SMA Tripower Core 1 units and one 50 kW unit, with integrated DC disconnects and ground fault protection. Electrical infrastructure includes a new 400-amp main distribution board, 300-amp main service breaker, 400-amp PV sub-panel with two 100-amp and one 80-amp three-pole circuit breakers, and a Siemens HF365NRA 400-amp fused AC disconnect with 300-amp fuses. The system is configured with 30 DC strings of solar modules delivering power through underground conduit runs (ranging from 35 to 150 feet) to the inverters, then to the main distribution board via the PV sub-panel. Wire sizing calculations specify 6 AWG, 4 AWG, 3 AWG, and 300 KCMIL copper conductors rated at 75 degrees depending on circuit location. All work must comply with 2019 California Building, Electrical, Energy, Fire, Mechanical, Plumbing, and Green Building codes. The contractor is ECOLECTRICS, located in Austin, Texas. Installation drawings include site maps, electrical one-line diagrams, wire size calculations, system labeling requirements with multiple warning and caution labels, property plan, attachment layout details, and manufacturer data sheets for inverters, modules, and racking systems.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP (SCALE: NTS)

SATELLITE VIEW (SCALE: NTS)

SHEET INDEX

SYSTEM RATING

MAIN SERVICE PANEL BUS SIZE:

MAIN SERVICE BREAKER SIZE:

RACKING: OMCO CHOICE GROUND MOUNT

BUILDING INFORMATION

CONSTRUCTION TYPE: V-B

OCCUPANCY: B

GENERAL NOTES

1. All electrical materials shall be new and listed by recognized electrical testing laboratory

Custom made equipment shall have complete test data submitted by the manufacturer attesting to its safety

2. Outdoor equipment shall be NEMA 3R rated or equivalent

3. All metallic equipment shall be grounded

4. Contractor shall obtain electrical permits prior to installation and shall coordinate all inspections, testing commissioning and acceptance with the client, utility co. and city inspectors as needed.

5. The electrical contractor shall verify the exact locations of service points and service sizes with the serving utility company and comply with all utility companies requirements.

6. Drawings are diagrammatic only, routing of raceways shall be option of the contractor unless otherwise noted and shall be coordinated with other trades.

7. If the roof material or the roof structure not adequate for PV installation, call the engineer of record print to installation. The contractor is responsible to verify that the roof is capable of withstanding the extra weight.

8. If the distances for cable runs are different than shown, the contractor shall notify the electrical engineer to validate the wire size. Final drawings will be red-lined and updated as appropriate.

9. Whenever a discrepancy in quality of equipment arises on the drawing or specifications, the contractor shall be responsible for providing and installing all materials and services required by the strictest conditions noted on the drawings or in the specifications to ensure complete compliance and longevity of the operable system required by the engineer of record.

PHOTOVOLTAIC NOTES:

1. Ground mounted photovoltaic panels and modules shall be tested, listed and identified by recognized testing laboratory

2. Solar system shall not cover any plumbing or mechanical vents

3. Modules and support structures shall be grounded unless racking has integrated ground.

4. Removal of an interactive inverter or other equipment shall not disconnect the bonding connection between the grounding electrode conductor and the photovoltaic source and/or output circuit grounded conductors.

5. All PV modules and associated equipment and wiring shall be protected from physical damage.

6. Live parts of PV source circuits and PV output circuits over 150v to ground shall not be accessible to other than qualified persons while energized.

7. Inverter is equipped with integrated DC disconnect, thus providing ground fault protection

8. All conductors shall be copper and 75 deg rated

9. A single conductor shall be permitted to be used to perform the multiple functions of dc grounding, AC grounding and bonding between AC and DC systems.

10. Non-current carrying metal parts of equipment shall be effectively bonded together. Bond both ends of raceways.

400A

DC 213.200 KW STC

AC 175.000 KW STC

SITE MAP & PV LAYOUT

ELECTRICAL 1-LINE DIAGRAM

ATTACHMENT LAYOUT

SYSTEM LABELING DETAIL

INVERTER DATA SHEET

PROPERTY PLAN

MODULE DATA SHEET

RACKING DATA SHEET

PV 1.0

PV 2.0

PV 3.0

PV 4.0

PV 5.0

D 6.0

D 7.0

D 8.0

EQUIPMENT SUMMARY

PV MODULES:

SOLARJUICE TECHNOLOGY, SA410-72MH (Qty: 520)

INVERTERS:

SMA TRIPOWER CORE 1 62.5 KW (QTY: 2) SMA

TRIPOWER CORE 1 50 KW (QTY: 1)

AC DISCONNECT:

SIEMENS HF365NRA (QTY: 1)

ELECTRICAL INFORMATION

NEW UPGRADED

300A

US Department of the Interior, Fish and Wildlife Service

New@engineerinc.io 01/10/2023

Site:

Owner:

Property Address:

Property Type:

Drawn by:

Date:

NE NE NE 3 8 11 - 13840 HWY 140, LIVINGSTON, CA, 95334

Commercial

GOVERNING CODES

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

WIRE SIZE CALCULTION PV 2.1

THE INSTALLATION OF SOLAR ARRAYS AND

PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH

THE FOLLOWING CODES:

· 2019 California Building Code

· 2019 California Residential Code

· 2019 California Green Building Standard Code

· 2019 California Plumbing Code

· 2019 California Mechanical Code

· 2019 California Electrical Code

· 2019 California Fire Code

· 2019 California Energy Code

· 2016 International Property Maintenance Code

ALL OTHER ORDINANCE ADOPTED BY THE

LOCAL GOVERNING AGENCIES

PG&E SERVICE ADDRESS

NE NE NE 3 8 11 - 13840 HWY 140, LIVINGSTON, CA 95334

PG&E METER SOLAR IS BEING TIED TO:

1010278561

Snobird

FENCE GATE

22'

22'

22'

22'

String#1,#2 -18 Modules

String#3,#4 -18 ModulesString#9,#10 -16 Modules

String#7,#8 -18 ModulesString#11,#12 -16 Modules

String#17,#18 -18 ModulesString#15,#16 -18 ModulesString#13,#14 -16 Modules

String#23,#24 -18 ModulesString#21,#22 -18 ModulesString#19,#20-16 Modules

String#29,#30 -18 ModulesString#27,#28 -18 ModulesString#25,#26 -16 Modules

AC

MDB

30'

E a s t

S i d e

C a n a l

Solar PV Array 5

104 - Solar4 America 410 Watt Modules

OMCO Choice Ground Mount: 15 Deg

Orientation:180 Deg

Solar PV Array 4

104 - Solar4 America 410 Watt Modules

OMCO Choice Ground Mount: 15 Deg

Orientation:180 Deg

Solar PV Array 3

104 - Solar4 America 410 Watt Modules

OMCO Choice Ground Mount: 15 Deg

Orientation:180 Deg

Solar PV Array 2

104 - Solar4 America 410 Watt Modules

OMCO Choice Ground Mount: 15 Deg

Orientation:180 Deg

Solar PV Array 1

104 - Solar4 America 410 Watt Modules

OMCO Choice Ground Mount: 15 Deg

Orientation:180 Deg

IN3

IN2

IN1PVS

(N) AC wiring ~150'

Underground run

3" Schedule # 40 PVC Pipe

18" Min depth

ADU

String#5,#6 -18 Modules

EXISTING PG&E

UTILITY POLE

(N) DC Wiring ~70’ (1” Schedule #40 PVC Pipe)

Strings 9 & 10 underground run to IN2

(N) DC Wiring ~ 35’ (1-1/4” Schedule #40 PVC Pipe)

Strings 5 to 8 underground run to IN1

(N) COMM Wiring ~ 70’ (3/4” Schedule #40 PVC Pipe)

Communication Line from IN1 to IN2

X 18” Min Depth

(N) DC Wiring ~ 35’ (1” Schedule #40 PVC Pipe)

Strings 11 & 12 underground run to IN2

(N) AC Wiring ~ 70’ (1-1/4” Schedule #40 PVC Pipe)

IN2 underground run to PVS

18” Min Depth

(N) DC Wiring ~ 35’ (1” Schedule #40 PVC Pipe)

Strings 19 & 20 underground run to IN2

(N) AC Wiring ~ 105’ (1-1/4” Schedule #40 PVC Pipe)

IN3 underground run to PVS

(N) COMM Wiring ~ 35’ (3/4” Schedule #40 PVC Pipe)

Communication Line from IN2 to IN3

18” Min Depth

(N DC Wiring ~ 35’ (1-1/2” Schedule #40 PVC Pipe)

Strings 25 to 30 underground run to IN3

18” Min Depth

SITE MAP & PV

LAYOUT

PV 1.0

PV SYSTEM AS INDICATED

Scale:Project:

SOLAR MODULES

Model #S4A410-72MH5

EMT type Conduit

Solar Module

___ SolarJuice Technology Inc. 410 Watt

INDEX

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

INVERTER

INVERTER TYPE: Central:

SMA 50.0kW Inverter

Model #SUNNY TRIPOWER

CORE1 50-US (277/480)

INVERTER TYPE: Central:

SMA 62.5kW Inverter

Model #SUNNY TRIPOWER

CORE1 62-US (277/480)

MDB (N) Main Distribution Board400A

(N) Inverter1IN1

PVS..........(N) 400A PV Sub Panel

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

AC............(N) 400A AC Disconnect

PVC type AC Conduit

PVC type DC Conduit

(N) Inverter2IN2

(N) Inverter3IN3

Communication Line

SCALE: 1/16" = 1'-0"

180 °

90 °

270 °

0°

S

W

N

E

Exp. Date: 06/30/2024

Date Certified and Signed:01/10/2023

G

Professional Certification. I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of California.

License No. ____________, Expiration Date: _______________E21531 06/30/2024

PV 2.0

PV SYSTEM AS INDICATED

Scale:Project:

ELECTRICAL 1-LINE

DIAGRAM

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

SMA

Inverter #1

MAKE: SMA AMERICA;

MODEL: STP 50-US-41 [480V]

1 18

STRING 1

1 182

1 18

STRING 3

1 182

STRING 4

STRING 2

1 182

STRING 5

1 182

STRING 6

1 182

STRING 7

1 182

STRING 8

(3) #4 AWG THWN/THWN-2

(1) #8 AWG THWN/THWN-2

(1) #8 AWG GND

1 1/4" EMT, 15 FEET

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

SMA

Inverter #2

MAKE: SMA AMERICA;

MODEL: STP 62-US-41 [480V]

1 16

STRING 13

1 162

1 18

STRING 15

(24) #10 AWG PV WIRE,

(1) #8 AWG GND

2" EMT, 5 FEET

1 182

STRING 16

STRING 14

1 182

STRING 17

1 182

STRING 18

PV MODULES

MAKE: SOLARJUICE TECHNOLOGY INC.

MODEL: SA410-72MH5

QTY: 144

1 16

STRING 9

1 162

1 16

STRING 11

1 162

STRING 12

STRING 10

1 16

STRING 19

1 162

STRING 20

SMA

Inverter #3

MAKE: SMA AMERICA;

MODEL: STP 62-US-41 [480V]

STRING 21

118 2

STRING 23

118 2

STRING 24

STRING 22

STRING 25

116 2

STRING 27

118 2

STRING 28

STRING 26

118 2

STRING 29

118 2

STRING 30

PV DISTRBT. PANEL

400A , 277/480V

INSTALL (2)100A PV

3-POLE C/B

INSTALL 80A PV

3-POLE C/B

400A FUSED AC DISCONNECT

WITH 300A FUSES,

LOCKABLE,BLADE TYPE,

277/480V

NEW

MAIN C/B

300A

(N) GROUNDING

ELECTRODE SYSTEM

MAIN METER

NEW UPGRADED

______ MAIN

DISTRIBUTION

BOARD

277/480V, 3P, 4W

400A

LINE SIDE TAP

(3) #3 AWG THWN/THWN-2

(1) #8 AWG THWN/THWN-2

(1) #8 AWG GND

1 1/4" EMT, 15 FEET

(3) #3 AWG THWN/THWN-2

(1) #8 AWG THWN/THWN-2

(1) #8 AWG GND

1 1/4" EMT, 15 FEET

(3) #3 AWG THWN/THWN-2

(1) #8 AWG THWN/THWN-2

(1) #8 AWG GND

1 1/4" EMT, 15 FEET

(3) #300 KCMIL

(1) #4 AWG THWN/THWN-2

(1) #4 AWG GND

3" EMT, 15 FEET

(3) #300 KCMIL

(1) #4 AWG THWN/THWN-2

(1) #4 AWG GND

3" EMT, 15 FEET

(N) AC wiring ~150'

Underground run

3" Schedule # 40 PVC Pipe

18" Min depth

(N) DC Wiring ~70’ (1” Schedule #40 PVC Pipe)

Strings 9 & 10 underground run to IN2

(N) DC Wiring ~ 35’ (1-1/4” Schedule #40 PVC Pipe)

Strings 5 to 8 underground run to IN1

(N) COMM Wiring ~ 70’ (3/4” Schedule #40 PVC Pipe)

Communication Line from IN1 to IN2

X 18” Min Depth

(N) DC Wiring ~ 35’ (1” Schedule #40 PVC Pipe)

Strings 11 & 12 underground run to IN2

(N) AC Wiring ~ 70’ (1-1/4” Schedule #40 PVC Pipe)

IN2 underground run to PVS

18” Min Depth

(N) DC Wiring ~ 35’ (1” Schedule #40 PVC Pipe)

Strings 19 & 20 underground run to IN2

(N) AC Wiring ~ 105’ (1-1/4” Schedule #40 PVC Pipe)

IN3 underground run to PVS

(N) COMM Wiring ~ 70’ (3/4” Schedule #40 PVC Pipe)

Communication Line from IN2 to IN3

18” Min Depth

(N DC Wiring ~ 35’ (1-1/2” Schedule #40 PVC Pipe)

Strings 25 to 30 underground run to IN3

18” Min Depth

(2) #10 AWG PV WIRE,

(1) #8 AWG GND

(8) #10 AWG PV WIRE,

(1) #8 AWG GND

(4) #10 AWG PV WIRE,

(1) #8 AWG GND

(4) #10 AWG PV WIRE,

(1) #8 AWG GND

(4) #10 AWG PV WIRE,

(1) #8 AWG GND

(12) #10 AWG PV WIRE,

(1) #8 AWG GND

PV MODULES

MAKE: SOLARJUICE TECHNOLOGY INC.; MODEL: SA410-72MH5; QTY: 200

PV MODULES

MAKE: SOLARJUICE TECHNOLOGY INC.; MODEL: SA410-72MH5; QTY: 176

Exp. Date: 06/30/2024

Date Certified and Signed:01/10/2023

G

Professional Certification. I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of California.

License No. ____________, Expiration Date: _______________E21531 06/30/2024

AC DISCONNECT

MAKE: SEIMENS

MODEL: HF365NRA

QTY: 1

PG&E METER NO:

1010278561

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

WIRE SIZE

CALCULATION

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

PV ARRAY RATING WIRE SIZE CALCULATION

PV ARRAY FROM JUNCTION BOX TO INVERTER

Number Modules 520 Type S4A410-72MH5 Solar4 America 410Watt Maximum Current (A) 10.61

Number Inverters 1 SMA 50kW Inverter

SUNNY TRIPOWER

CORE1 50-US (480V) Considers Continuous (A)

10.61 * 1.25 = 13.26

Number Inverters 2 SMA 62.5kW Inverter

SUNNY TRIPOWER

CORE1 62.5-US (480V) Short Circuit Current (A)

13.2625 * 1.25 = 16.58

Total DC Wattage (Watts) Watts STC, (Watts/Module) 520 * 410 = 213200 Raceway Height From Roof (Temp 39+22=61C) 3 1/2" Array Currents I-SC 10.61 A I-MP 10.54 A Temp. Derate Factor (A) 16.58 / 0.71 = 23.35 Module Voltage V-OC 49.1 V V-MP 40.9 V #of wire(#of Strings*2) 24 SYSTEM POWER More Than 3 CCC Adjist. Factor 0.45 Number Of Strings 12 Max Number of Modules Per String 18 Adjusted Conductor Ampacity(A) 23.35 / 0.45 = 51.89

1000V Calculation 49.1 * 18 * 1.12 = 989.86 <= 1000V Max AC Voltage 277/480V Wire Size from NEC Table 310.15(b)16 6 AWG

FROM INVERTER 1 TO PV

SUB PANEL Ambiend Tem Factor Per NEC Table 310.15(b)(2)(a) 0.71 Total Current (A) 64 Max Input Power (Watts) 50000 Consider Continuous (A) 64 * 1.25 = 80 Temperature Adjustment 80 / 0.91 = 87.91 (A) Conductor Size From NEC Table 310.16 4 AWG

FROM INVERTER 2 TO PV SUB PANEL

Total Current (A) 79.5 Total AC Wattage (Watts) 62500

Consider Continuous (A) 79.5 * 1.25 =

99.375 Temperature Adjustment 99.375 / 0.91 = 109.2 (A) Conductor Size From NEC Table 310.16 3 AWG

FROM PV SUB PANEL TO

MAIN DISTRIBUTION BOARD

Total Current (A) 64 + (79.5X2) = 223 Max Input Power (Watts) 175000

Consider Continuous (A) 143.5 * 1.25 =

278.75 Temperature Adjustment 278.75 / 0.91 = 306.31 A Conductor Size From NEC Table 310.16 300 KCMIL

FROM INVERTER 3 TO PV SUB PANEL

Total Current (A) 79.5 Total AC Wattage (Watts) 62500

Consider Continuous (A) 79.5 * 1.25 =

99.375 Temperature Adjustment 99.375 / 0.91 = 109.2 (A) Conductor Size From NEC Table 310.16 3 AWG

PV 2.1

Exp. Date: 06/30/2024

Date Certified and Signed:01/10/2023

G

Professional Certification. I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed

SYSTEM

LABELING DETAIL

PV 3.0

PV SYSTEM AS INDICATED

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

(STICKER TO BE LOCATED ON

CONDUIT WITH DC CURRENT

EVERY 4' HORIZONTALLY OR

10' VERTICALLY AND 1' FROM

EACH SIDE OF A BEND)

(TO BE LOCATED ON

SUB-PANEL ONLY

WHEN SUB-PANEL IS

DEDICATED FOR PV ONLY)

(STICKER LOCATED

INSIDE PANEL

NEXT TO SOLAR BREAKER)

(STICKER LOCATED

INSIDE PANEL

BELOW PV BREAKER)

PV ARRAY

J BOX

INVERTER

INTEGRATED

DC DISCONNECT

PV SUB-PANEL

* if applicable

SUB-PANEL

* if applicable

AC

DISCONNECT

* if applicable

METER

MAIN SERVICE

PANEL

*if applicable

(STICKER LOCATED

ON THE PV SUB PANEL)

CAUTION

AUTHORIZED SOLAR

PERSONNAL ONLY!

CAUTION

SOLAR DC CURRENT PRESENT

DURING DAYLIGHT HOURS

WARNING!

ELECTRIC SHOCK HAZARD.

IF GROUND FAULT IS INDICATED,

NORMALLY GROUNDED

CONDUCTORS MAY BE

UNGROUNDED AND ENERGIZED.

DC DISCONNECT

DC PHOTOVOLTAIC POWER SOURCE

RATED MAX POWER POINT CURRENT- AMPS

RATED MAX POWER POINT VOLTAGE- VOLTS

MAXIMUM SYSTEM VOLTAGE- VOLTS

SHORT CIRCUIT CURRENT- AMPS

WARNING!

ELECTRIC SHOCK HAZARD.

DO NOT TOUCH THE TERMINALS.

TERMINALS ON BOTH THE LINE AND

LOAD SIDES MAY BE ENERGIZED IN

THE OPEN POSITION.

PV LOAD CENTER SIZED FOR PV

BREAKERS ONLY OR RENDERED UNABLE

TO ACCEPT ANY ADDITIONAL LOADS.

PV SUB-PANEL ONLY

AC DISCONNECT

AC PHOTOVOLTAIC POWER SOURCE

RATED AC OUTPUT CURRENT: A MAX

NOMINAL AC OPERATING VOLTAGE: 480 Vac

THIS PANEL FED BY

MULTIPLE SOURCES

(UTILITY & SOLAR)

SOLAR

WARNING!

INVERTER OUTPUT CONNECTION. DO NOT

RELOCATE THIS OVERCURRENT DEVICE

Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque.

Plaques shall be permanently attached to the equipmenq or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacemet, exposure and adhesion requirements of Underwriters

Laboratories marking and labeling system 969(UL969).

278.75

LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6

LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11

LABEL 12

4 51

DIRECTORY

MARKINGS, LABELS AND WIRING SIGNS

A. Purpose: Provide emergency responders with appropriate warning and guidance with respect to isolating solar electric system.

This can facilitate identifying energized electrical lines that connect solar panels to the inverter, as these should not be cut when venting for smoke removal

B. Main Service Disconnect.

1. Residential buildings - The marking main be placed within the main service disconnect. The marking shall be placed outside cover if the main service disconnect is operable with the service panel closed.

2. Commercial buildings - Tha marking shall be placed adjacent to the main service disconnect clearly visible from the location where the level is operated

3. Markings: Verbiage, Format and Type of Material.

a. Verbiage: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED

b. Format: White lettering on a red background. Minimum 3/8 inches letter height. All letters shall be capitalized. Arial or similar font, non bold.

c. Material: Reflective, weather resistant material suitable for the environment (use UL - 969 as standard for weather rating). Durable adhesive materials meet this requirement.

C.Marking Requirements on DC conduit, raceways, enclosures, cable assemblies, DC combiners and junction boxes:

1. Markings: Verbiage, Format and Type of Material.

a. Placement : Markings shall be placed every 10 feet on all interior and exterior DC conduits, raceways, enclosures, and cable assemblies, at turns, above and for below penetrations, all DC combiners and junction boxes

b. Verbiage: CAUTION: SOLAR CIRCUIT Note: The format and type of material shall adhere to "V. V-3b, c" of this requirement.

c. Inverters are not required to have caution markings

1.Marking is required on all interior and exterior DC conduit raceways,enclosures,cable assemblies,and junction boxes,combiner boxes and disconnects.

2.The materials used for marking shall be reflective,weather resistant material suitable for the environment.

Minimum 3/8 "letter height; all upper case letters Arial or similar font; Red background with white lettering.

3.Marcking shall contain the words: WARNING : PHOTOVOLTAIC POWER SOURCE.

4.Marking shall be placed adjacent to the main service disconnect in a location clearly visible from the location where the disconnect is operated

SOLAR PV SYSTEM EQUIPPED

WITH RAPID SHUTDOWN

TURN RAPID SHUTDOWN

SWITCH TO THE

"OFF" POSITION TO

SHUT DOWN PV SYSTEM

AND REDUCE

SHOCK HAZARD

IN THE ARRAY

SOLAR ELECTRIC

PV PANELS

Exp. Date: 06/30/2024

Date Certified and Signed:01/10/2023

G

Professional Certification. I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed

22'

22'

30'

B e r r e e k

E a s t

S i d e n a l

2521'-10"

2035'

762'-4"

383'-4"

1130'-8"

1590'-10"

1440'-3"

1508'-9"

541'-11"

1279'-2"

DRIVEWAY

PROPERTY LINE

AC

MDB

ADU

EXISTING PG&E

UTILITY POLE

PVS

FENCE

GATE

30'

PROPERTY PLAN

PV 4.0

PV SYSTEM AS INDICATED

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

MSP Main Distribution Board

Inverter1IN1

PVS ....................... PV Sub Panel

AC......................... AC Disconnect

Solar Module

Inverter2IN2

Inverter3IN3

SCALE: 1/128" = 1'-0"

180 °

90 °

270 °

0°

S

W

N

E

SNOBIRD SITE

12.9'

8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8'

PRE-ASSEMBLED TILT BRACKETRY SUB-ASSEMBLY

BEAM

FLANGED BOLT

168.91'

12.9'

8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8'

PRE-ASSEMBLED TILT BRACKETRY SUB-ASSEMBLY

BEAM

FLANGED BOLT

168.91'

12.9'

8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8'

PRE-ASSEMBLED TILT BRACKETRY SUB-ASSEMBLY

BEAM

FLANGED BOLT

168.91'

12.9'

8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8'

PRE-ASSEMBLED TILT BRACKETRY SUB-ASSEMBLY

BEAM

FLANGED BOLT

168.91'

12.9'

8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8' 8'

PRE-ASSEMBLED TILT BRACKETRY SUB-ASSEMBLY

BEAM

FLANGED BOLT

168.91'

22'

22'

22'

22'

ATTACHMENT

LAYOUT

PV 5.0

PV SYSTEM AS INDICATED

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

BEAM

FLANGED BOLT

SOLAR MODULE

BEAM

SOLAR MODULE

FLANGED BOLT

W/STAR WASHER

PRE-ASSEMBLED TILT BRACKETRY

SUB-ASSEMBLY

PRE-ASSEMBLED TILT BRACKETRY

SUB-ASSEMBLY

GRADE

FLANGED NUT

MIN 2'-6"

PRE-ASSEMBLED TILT BRACKETRY

SUB-ASSEMBLY

SOLAR MODULE

BEAM

FLANGED NUT

FLANGED BOLT W/SERRATED FLANGE NUTS

8'-8"

4'-11"

12.9'

BEAM

SOLAR MODULE

SMA INVERTER

PRE-ASSEMBLED TILT BRACKETRY

SUB-ASSEMBLY

INVERTER

DATA SHEET

D 6.0

PV SYSTEM AS INDICATED

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Phone number: 512-717-0660 info@ecolectricsusa.com

D 7.0

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

MODULE

DATA SHEET

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

D 8.0

Scale:Project:

Drawn by:New@engineerinc.io

DATE:

01/10/2023

Project Name:

US Department of the Interior, Fish and Wildlife Service Property Adress:

SNOBIRD, NE NE NE 3 8 11 - 13840 HWY

140, LIVINGSTON, CA, 95334

RACKING

DATA SHEET

CONTRACTOR

ECOLECTRICS

Address:275 Lotus Circle

Austin, TX 78737

Sheets and Views
NFWS San Luis Snobird Solar Drawings-0
NFWS San Luis Snobird Solar Drawings-1
NFWS San Luis Snobird Solar Drawings-2
NFWS San Luis Snobird Solar Drawings-+12
NFWS San Luis Snobird Solar Drawings-3
NFWS San Luis Snobird Solar Drawings-4
NFWS San Luis Snobird Solar Drawings-5
NFWS San Luis Snobird Solar Drawings-6
NFWS San Luis Snobird Solar Drawings-7
NFWS San Luis Snobird Solar Drawings-8

Untitled

File details come from the government source that posted it. Updated .