Attachment__1_-_Specification_-_Panel_Salient_Characteristics.pdf
PDF 180 KB Posted
- Solicitation number
- 140FC326Q0046
About this file
This document is a Salient Characteristics & Component Assessment for a solar panel and sub-panel replacement requirement (CA-SNLNWRC-SNOBIRD Solar Panel Replacement).
The requirement addresses replacement of a burnt or heat-damaged 400-amp, 600-volt NEMA 3R sub-panel (Square D/Siemens, catalog number P1E30MC400AT, rated 480/277V three-phase, 4-wire, 20"W x 5.75"D x 62"H) and associated electrical components. The contractor must replace damaged circuit breakers (two 100A three-pole, one 20A three-pole, one 80A three-pole), wiring and conductors (approximately 570 feet of 500 MCM copper wire and 190 feet of #2 THHN copper wire rated for up to 600V), and related equipment including conduit/raceways (3" PVC conduit requiring some replacement including a 3" female PVC adapter and chase nipple). Solar panels, modules, inverters, and controllers appear undamaged and require confirmation but may need compatible replacements if incompatible with the new equipment. Existing mounting utilizes OMCO direct-bolt galvanized steel racking.
The contractor must provide a complete and fully operational installation including all labor, supervision, materials, equipment, testing, startup, commissioning, labeling, grounding, bonding, and verification of proper system operation. All replacement equipment must be new, code-compliant, mutually compatible with the existing facility electrical system, and meet or exceed minimum salient characteristics. The contractor shall not reuse any components showing evidence of burning, melting, excessive heat exposure, arcing, or insulation deterioration. A site visit verification chart is provided to document existing data, observed damage, and replacement requirements for all system components.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLAR PANEL - SUB PANEL REPLACEMENT
SALIENT CHARACTERISTICS & COMPONENT
ASSESSMENT
CA-SNLNWRC-SNOBIRD Solar Panel Replacement
1. Purpose
This document identifies the minimum technical information and salient characteristics needed to define the Solar Panel Replacement requirement. The COR should complete or confirm all applicable requirements so prospective contractors’ materials meet or exceed the evaluation of the existing damaged system and propose a complete, compatible, durable, and fully operational replacement.
2. Existing Damaged Components / Field Conditions (Meet or Exceed) Component Existing Rating /
Size
Observed
Condition
Required Action Customer / Site
Data Needed
Solar electrical equipment / panel
400 amp 600 volt sub panel NEMA
3R
Square D/ Siemens sub panel
480/277v 3 phase 4 wire
400 A MAX
Size- 20”W x
5.75”D x 62”H
Catalog number:
P1E30MC400AT
Burnt / fire or heat damaged
Inspect and replace damaged equipment as required
Manufacturer, model, voltage, phases, photos, nameplate data
Breakers
2) 100A 3P breaker
1) 20A 3P breaker
1) 80A 3P breaker
Burnt, damaged, or heat exposed
Replace affected breakers and verify coordination/rating
Amp ratings, interrupting rating, quantity, panel compatibility
Wiring / Conductors
500 mcm coper wire
#2 thhn coper wire
Roughly 570’ of 500 mcm
Roughly 190’ of #2 thhn
500 mcm rating: 60 degree (140f) 320
A, 75degree (167f)
Burnt, melted, or heat damaged
Remove and replace all compromised conductors
Wire size, material, insulation type, length, conduit/raceway condition
380A, 90 degree
(194f)
Rated for up 600V
#2 thhn will be used for ground. 115 amps at the 75 degree c ratings
Solar Panels /
Modules To be confirmed
As for the solar panels/modules, inverters/controllers those all seem to be ok and didn’t have any damage to them.
Replace damaged modules or provide compatible replacement system
Quantity, watts/module, total kW, dimensions, mounting configuration
Inverter / Controller To be confirmed
As for the solar panels/modules, inverters/controllers those all seem to be ok and didn’t have any damage to them.
Replace if damaged or incompatible
Manufacturer/model, input/output voltage, capacity, monitoring requirements
NOTE: The term “400 Amp Solar Panel” should be verified during the site assessment. The 400
Amp rating may refer to a distribution panel, service panel, disconnect, combiner, or other electrical equipment associated with the photovoltaic system.
3. Minimum Salient Characteristics (Solar PV Module System) System Component Minimum
Requirement /
Characteristic
Customer Input Contractor Submittal
Solar PV Modules Quantity; minimum wattage; total system capacity; module technology; efficiency;
dimensions;
environmental rating;
warranty.
TBD Product data sheets
400 Amp Electrical
Equipment
400 A minimum rating where applicable; voltage;
phase; enclosure rating;
bus rating; short-circuit/interrupting rating;
code-compliant construction.
400 amp 600 volt sub panel NEMA 3R
Square D/ Siemens sub panel
480/277v 3 phase 4 wire
400 A MAX
Size- 20”W x 5.75”D x 62”H
Catalog number:
P1E30MC400AT
Manufacturer and model data
Circuit Breakers Correct ampere, voltage, pole, and interrupting ratings; compatible with associated equipment; new and listed for intended use.
2) 100A 3P breaker
1) 20A 3P breaker
1) 80A 3P breaker
Breaker schedule/product data
Wiring and Conductors Proper conductor size and ampacity;
copper/aluminum as specified; insulation and temperature rating; PV-rated wiring where applicable; replace heat-damaged conductors.
500 mcm coper wire
#2 thhn coper wire
Roughly 570’ of 500 mcm
Roughly 190’ of #2 thhn
500 mcm rating: 60 degree (140f) 320 A, 75degree (167f) 380A, 90 degree (194f)
Rated for up 600V
#2 thhn will be used for ground. 115 amps at the
75 degree c ratings
Wire/conductor schedule
Inverter / Charge
Controller
Compatible with PV array and existing electrical system; required input/output voltage;
capacity; efficiency;
monitoring and protective functions.
Provide existing equipment data
Product data and calculations
Mounting / Racking Corrosion-resistant;
compatible with structure and modules; designed for site wind, snow, and environmental loads.
OMCO direct-bolt mounting system, galvanized steel
Manufacturer details
Disconnects / Combiner
/ Protection
Provide required disconnects, combiner equipment, overcurrent protection, grounding, bonding, and surge protection.
Confirm existing configuration
Single-line diagram and product data
System Completion All labor, materials, equipment, accessories, testing, startup, commissioning, and incidental work for a complete operational system.
Confirm operational requirements
Testing/commissioning records
Raceway
3” pvc counduit going to reuse some of the existing conduit and may require some new conduit to be added not sure on the exact footage that will need to be replace at this time.
Will need to replace the
3” female pvc adapter and chase nipple going into new panel.
4. Damage Assessment and Replacement Requirements
• Contractor shall inspect the burnt or heat-damaged 400 Amp electrical equipment, breakers, wiring, connectors, conduit/raceways, and adjacent components.
• All components determined to be damaged, compromised, unsafe, or unsuitable for continued service shall be identified, reported, and replaced with approval of COR and CO as authorized by the contract terms and conditions.
• Replacement equipment shall be new, compatible with the solar photovoltaic system and existing facility electrical system, and properly rated for the intended application.
• The contractor shall not reuse wiring, breakers, terminals, or electrical components that show evidence of burning, melting, excessive heat exposure, arcing, insulation deterioration, or other unsafe conditions.
• Final installation shall include required labeling, grounding, bonding, testing, startup, commissioning, and verification of proper system operation.
5. Customer Information Required Before Solicitation
• Clear photographs of all burnt or damaged equipment, including wide-angle and close-up views.
• Photographs of equipment nameplates and manufacturer/model information.
• Confirmation of what equipment is rated at 400 Amps.
• Existing electrical one-line diagram, panel schedule, or solar system drawings, if available.
• Solar module quantity, wattage, dimensions, and total existing system capacity.
• Breaker quantities and ratings.
• Existing conductor sizes, types, and approximate damaged lengths, if known.
• Inverter, controller, battery, disconnect, combiner, and monitoring equipment information.
• Site-specific access, shutdown, operational, environmental, and scheduling constraints.
6. SOW Salient Characteristics
The Contractor shall furnish all labor, supervision, materials, equipment, tools, transportation, and incidental items necessary to replace the damaged solar photovoltaic system components, including the burnt or heat-damaged 400 Amp electrical equipment, affected breakers, wiring/conductors, and related accessories identified in the contract documents. Replacement equipment shall meet or exceed the minimum salient characteristics specified by the Government and shall be new, code-compliant, mutually compatible, and suitable for the existing facility electrical system and site conditions. The Contractor shall provide a complete and fully operational installation, including testing, startup, commissioning, labeling, and required product and warranty documentation.
7. Site Visit Verification Chart
Item to Verify Existing
Data
Observed
Damage
Replacement
Requirement
Notes / Photo No.
400 Amp equipment
Main/branch breakers
Solar PV wiring
AC conductors
Conduit /raceways
Solar modules
Inverter/controller
Disconnects/combiner
Grounding/bonding
Mounting/racking
Important: Final technical specifications and electrical ratings should be validated by qualified technical personnel based on the existing system, field conditions, applicable codes, and the actual cause and extent of the damage.