Attachment 3 - 2025 South Side Drawings.pdf

PDF 166 KB Posted

Attached to
B. 2025 Electrical Investigation Tie-Breaker
Solicitation number
Not on record
Issued by

About this file

This is an electrical one-line diagram for Peterson Air Force Base in Colorado, prepared by The Benham Group Architect-Engineer in Oklahoma City. The diagram was designed in April 1992 under U.S. Army Corps of Engineers contract DACA 45 92-C-L075 for the Centralized Integration Support Facility (Category Code 141-764, Drawing AF 610-31-01).

The electrical system includes a 12.47 kV primary service from Colorado Springs Department of Utilities with metering at 12.5 kV, stepping down to 480Y/277V and 208Y/120V through multiple pad-mounted transformers rated 150 kVA at 5.75% impedance. The distribution includes three unit substations with 3000 ampere buses, 600 ampere air interrupters rated 15 kV, and multiple feeder circuits serving various loads including a 125 kW 480-volt 3-phase emergency generator with automatic transfer switch and bypass isolation transfer switch. Secondary systems include two sanitary sewage lift stations with duplex pump controls, security lighting with 3-phase 200 ampere contactor, antenna power loads rated 500 KW with 3-pole 800 ampere circuit breaker, and distributed loads ranging from 30 KVA to 112.5 KVA. The feeder schedule specifies 20 distinct circuits with wire sizes from #12 through 1000 Kcmil copper conductors in conduit ranging from 1/2 inch to 3.5 inches, with concrete-encased ducts for primary underground cables and transient suppression units on transformer secondaries.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3000A. 480V., 3Ø,4W. BUS

K

K

VS

V

288/120V.

D2

2000/2666KVA.,

12470V.-480/277V.,3Ø,4W.

Z=5.75%

600A., 15KV.,

AIR

INTERRUPTER

125E

(SM-5)

3000A. 480Y/277V., 3Ø,4W. BUS

100% NEUTRAL BUS

GROUND BUSZ=5.75%

12470V.-480/277V.,3Ø,4W.

2000/2666KVA.,

3000K

FEEDER F1

UNIT SUBSTATION-D

GROUND BUS

L.A.

9KV.

STA. TYPE

F1

SWITCHSWITCH

F1

STA. TYPE

9KV.

L.A.

(SM-5)

125E

INTERRUPTER

AIR

600A., 15KV.,

N.O.

C H L-

S P A R E

S P A R E

GF

GF

GF

AD

KWH

D

SEC. L.A. & SURGE

CAPACITOR

D

KWH

AD

V

VS

288/120V.

D1

SEC. L.A. & SURGE

CAPACITOR

LINK

REMOVABLE

U.S. GOVERNMENT PRINTING OFFICE - 1987-755-756

D

C

B

A

D

C

B

A

$$ - THINK VALUE ENGINEERING - $$

Descriptions

Architect-Engineer

Submitted by:

Drawing Code:

Date:

DACA 45 92-C-L075

Contract No.:

DACA 45 92 B 0048

Spec. No.:

Symbol Revisions

Date Approved

U.S. ARMY ENGINEER DISTRICT

CORPS OF ENGINEERS

OMAHA, NEBRASKA

Designed by:

Drawn by:

Checked by:

Reviewed by: Scale: Sheet reference number:

THE BENHAM GROUP

ARCHITECT-ENGINEER

OKLAHOMA CITY, OKLAHOMA

PETERSON AIR FORCE BASE COLORADO

CENTRALIZED INTEGRATION SUPPORT FACILITY

CATEGORY CODE 141-764

AF 610-31-01

AS SHOWN

ELECTRICAL

ONE-LINE DIAGRAM

5E01

CED

NJS

JHG

APRIL 1992

15Kv. PAD MTD. SW. GR.

MS F1 F2

FUT.

EXPANSION

15Kv. SW. GR.

DRY TYPE

UNIT

SUPPRESSION

TRANSIENT TRANSIENT

SUPPRESSION

UNIT

DRY TYPE

S P A R E

C H L-

C H L-

C H L-

BP

ATS

EM

H

MCC-1

L

EM

EG

EMT

2T5

2L5

2H4

A AAA

2H3

2L4

2T42T3

2L3

2H2

A A AA

2H1

2L1

2T1 2T2

2L2

AA

1H8

1L8

1T8

1T7

1L7

1H7

A AAA

1H1

1L1

1T1 1T2

1L2

1H2

A A

1H3

1L3

1T3

AAAA AA AA AAAA AA A A AA

1H4

1L4

1T4

AA

1T5

1L5

1H5

A A

1T6

1L6

1H6

A A

D ra w in g:

X

0.

O K C

EL

EC

5E

Sa ve d:

3/

4:

B y:

N

S D im Sc al e:

.0

MCC-2

AA AA

EG

HS HPA

TS

PEPE

PARKING

AREA

CONTACTOR CHPA, 3P200A 22K

BLDG. EXTERIOR

SECURITY LTG.

CONTACTOR CHS, 3P60A 15K

CABLES FURNISHED

WITH PUMPS

SEWAGE

LIFT PUMPS

DUPLEX PUMP CONTROL

PANEL FURNISHED WITH

PUMPS

B P

A

TS

125KW 480 VOLT 3Ø

EMERGENCY GENERATOR

3 POLE, 225 AMP MAIN OUTPUT CIRCUIT BREAKER

FURNISHED WITH GENERATOR

3 POLE, 260 AMP, 480 VOLT

BYPASS ISOLATION TRANSFER

SWITCH IN NEMA "4" ENCLOSURE.

15KVA 1Ø, 480-120/240 VOLT

WEATHERPROOF PACKAGED

POWER SUPPLY FOR

CIRCUIT BREAKER SIZES

SEE SHEET 8E01D

KWH

DRAWOUT

VT

277:120V (3)

McGRAW

150 kVA 3Ø 12.47kV-480Y/277V.

PAD MTD. TRANSFORMER

5.75%Z OIL-IMMERSED

9kV.

LA

3#4/0, 1#4GND.

ENCLOSURE MOUNTED ON TRANSFORMER ENCLOSURE

3 POLE, 225 AMP MAIN CIRCUIT BREAKER IN NEMA "4"

LOOP FEED

ARRANGEMENT

GROUND ROD

SANITARY SEWAGE LIFT STATION NO. 2

SANITARY SEWAGE LIFT STATION NO. 1

GROUND ROD

ARRANGEMENT

LOOP FEED

3 POLE, 225 AMP MAIN CIRCUIT BREAKER IN NEMA "4"

ENCLOSURE MOUNTED ON TRANSFORMER ENCLOSURE

1#4GND.

3#4/0, LA

9kV.

5.75%Z OIL-IMMERSED

PAD MTD. TRANSFORMER

12.47kV-480Y/277V.

150 kVA 3Ø

(3) 277:120V

VT

DRAWOUT

KWH

D SEE SHEET 8E01

CIRCUIT BREAKER SIZES

POWER SUPPLY FOR

WEATHERPROOF PACKAGED

15KVA 1Ø, 480-120/240 VOLT

SWITCH IN NEMA "4" ENCLOSURE.

BYPASS ISOLATION TRANSFER

3 POLE, 260 AMP, 480 VOLT

FURNISHED WITH GENERATOR

3 POLE, 225 AMP MAIN OUTPUT CIRCUIT BREAKER

EMERGENCY GENERATOR

125KW 480 VOLT 3Ø

A

TS B

P

PUMPS

PANEL FURNISHED WITH

DUPLEX PUMP CONTROL

LIFT PUMPS

SEWAGE

WITH PUMPS

CABLES FURNISHED

EG

D

KWH

DRAWOUT

VT

120:120V (3)

150 kVA 3Ø 12.47kV-208Y/120V.

PAD MTD. TRANSFORMER

5.75%Z OIL-IMMERSED

9kV.

LA

LOOP FEED

ARRANGEMENT

GROUND ROD

ECB

L

SGR

9 1

SIGN &

GAS

REGULATOR

ENTRY CONTROL BUILDING

400/5

200/5

200/5

600A. 150E

3-1/C#1, 15kV COPPER SHIELDED EPR OR XLP WITH

133% INSULATION. NEUTRAL CONDUCTOR SHALL BE

600 VOLT #1 TYPE THW INSTALLED IN 1-4" CONCRETE

ENCASED DUCT WITH 1-4" DUCT AS SPARE.

12,5kV PRIMARY METERING

STATION BY COLORADO

SPRINGS DEPT. OF

UTILITIES

1000Kcmil UNDERGROUND

CABLE BY COLORADO

SPRINGS DEPT. OF

UTILITIES.

CO. TO MAKE PROPER TERMINATION.

SLACK ENDS OF CABLES FOR UTILITY

CONTRACTOR TO PROVIDE SUFFICIENT

3-1/C 1000Kcmil, 15kV COPPER SHIELDED EPR OR

XLP WITH 133% INSULATION. NEUTRAL CONDUCTOR

SHALL BE 600 VOLT 1000Kcmil TYPE THW

INSTALLED IN 1-6" CONCRETE ENCASED DUCT WITH

1-6" DUCT AS SPARE.

SPARE

1-4" DUCT AS SPARE.

INSTALLED IN 1-4" CONCRETE ENCASED DUCT WITH

SHALL BE 600 VOLT 250Kcmil TYPE THW

XLP WITH 133% INSULATION. NEUTRAL CONDUCTOR

3-1/C 250Kcmil, 15kV COPPER SHIELDED EPR OR

LIGHTING

16 16 3 3 1919193

18 18 18 18 18 18

17 17 17 17 17 17

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

KVA

*1

112.5

KVA

*1

112.5

KVA

*1

KVA

*1

KVA

*1

*1

KVA

AP 4

3P225A APCB

ANTENNA

POWER

500KW

3P800A 35K

11 11

10 10

3 3 3 15 19 19

800 800

800 800

NOTES:

*1. TRANSIENT SUPPRESSION UNIT. CONNECTED TO SECONDARY LUGS OF

DRY TRANSFORMER.

FEEDER SCHEDULE

NUMDER WIRE AND CONDUIT SIZE

3-#1/0, 1-#4/0 NEUT. 1-#6 GND. 2"C.

3-#4 & 1-#8 GND., 1 ˜ "C.

3-3š "C. Ea�4-350Kcmil & 1#1/0 GND.

3-#1/0 & 1-#6 GND., 1 š "C.

3-#4/0, 1-500Kcmil NEUT., 1-#4 GND. 3"C.

3-#4/0, 1-#4 GND., 3"C.

2-#3, 1-#3 GND., 1 ˜ "C.

6-#3, 1-#3 GND., 2"C.

2-4" CONCRETE ENCASED DUCTS Ea.�4-250Kcmil & 1-#2 GND.

4-#4/0, 1-#4 GND., 3"C.

3-#12, 1-#12 GND., œ"C.

3-#6, 1-#10 GND., 1 ˜ "C.

4-#1, 1-#8 GND., 1 š "C.

4-#4, 1-#10 GND. 2"C.

4-500Kcmil, 1-#3 GND., 3š "C.

2-3"C. Ea. �3-350Kcmil & 1-#1 GND.

2-2š "C Ea. �3-#3/0, 1-300Kcmil NEUT. & 1-#3 GND.

3-#2/0, 1-#6 GND. 2"C.

4-500Kcmil & 1-#3 GND., 3š "C.

3-250Kcmil, 1-500Kcmil NEUT. & 1-#4 GND., 3"C.

METAL ENCLOSED

600 VOLT 250Kcmil TYPE THW INSTALLED IN 4" CONDUIT.

133% INSULATION. NEUTRAL CONDUCTOR SHALL BE

3-1/C 250Kcmil, 15kV COPPER SHIELDED EPR OR XLP WITH

MAIN OUTPUT

CIRCUIT BREAKER

FURNISHED WITH

GENERATOR

(3)

(3)

(3)

600A.

250E. 150E.

3 POLE, 800 AMP

L S

L S

SEE PLAN

ON SH. 1E05

3P30A. FOR 3 PHASE

480V. SERVICE. HEAVY

DUTY FUSIBLE SINGLE

THROW SAFETY SWITCH

WITH FUSES AS REQ'D

FOR MOTOR HP FUR-

NISHED IN NEMA-3R

ENCLOSURE WITH EN-

CLOSURE & OPERATING

HANDLE PADLOCKED,

KEYED ALIKE.

ELEC. SERVICE

TO FIRE

SECURITY GATE

65K RMS SYM A.I.C. 65K RMS SYM A.I.C.

NF

1L9

TO FIRE ALARM CONTROL

PANEL. (SMOKE DAMPERS

TO CLOSE ON FIRE ALARM)

CONTACTOR SD 3P20A

ROUTE EML-35, 37, 39

CCT'S. THROUGH THIS

CONTACTOR

TYPE NX

OR EQUAL

12A.

12A.

McGRAW

TYPE NX

OR EQUAL

12A.

McGRAW

TYPE NX

OR EQUAL

"AS BUILT"

"AS BUILT"

--- REVISED TO SHOW "AS BUILT" CONDITIONS 4-1-94 BCK\RGL