Attachment 2 - B. 2025 North Side Drawings.pdf
PDF 79 KB Posted
- Attached to
- B. 2025 Electrical Investigation Tie-Breaker
- Solicitation number
- Not on record
About this file
This is an electrical one-line diagram for the ADAL Integration Support Facility at Peterson Air Force Base, Colorado, prepared by The Benham Group Architect-Engineer. The drawing, dated November 1, 1993, shows the electrical distribution system design for the facility and is designated as sheet 5E01 in the construction documentation set prepared under U.S. Army Engineer District, Corps of Engineers, Omaha, Nebraska contract DACA 45.
The diagram illustrates a complex electrical system featuring a 2000/2666 KVA transformer with 480Y/277V, three-phase, four-wire output serving multiple distribution panels, motor control centers (NMCC-1, NMCC-2, NMCC-3), and branch circuits throughout the facility. The system includes a ground bus with 100 percent neutral bus capacity, existing and new metal-enclosed 15 kV switchgear, and various protective devices including transient suppression units, circuit breakers rated from 20A to 4000A, and ground fault protection. The drawing specifies contractor requirements including the installation of dielectric unions after penetrating the Sensitive Area Restricted (SAR) area wall and the conference room wall, as well as the provision of an RF-filtered and shielded circuit breaker panel. The existing 15 kV service feeder to the facility is routed through concrete-encased ducts with spare ducts and uses 250 kcmil copper shielded EPR or XLP cables with 133 percent insulation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. GOVERNMENT PRINTING OFFICE - 1987-755-756
D
C
B
A
D
C
B
A
$$ - THINK VALUE ENGINEERING - $$
Descriptions
Architect-Engineer
Submitted by:
Drawing Code:
Date:
DACA 45 CO
Contract No.:
DACA 45
Spec. No.:
Symbol Revisions
Date Approved
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
Designed by:
Drawn by:
Checked by:
Reviewed by: Scale: Sheet reference number:
THE BENHAM GROUP
ARCHITECT-ENGINEER
OKLAHOMA CITY, OKLAHOMA
PETERSON AIR FORCE BASE COLORADO
ADAL INTEGRATION SUPPORT FACILITY
CATEGORY CODE 141-764
AC 610-31-02
AS SHOWN
ELECTRICAL ONE-LINE
DIAGRAM
5E01
RGL
BCK
KAN
93 NOV 01
D ra w in g:
U
E\
5E
Sa ve d:
0/
4:
B y:
B
K
D im Sc al e:
.0
J
TRANSPORTABLE GROUND ANTENNA SYSTEM
CONTROL HEAD #2
JUNCTION BOX
CONTROL HEAD #1
JUNCTION BOX
3P200A.T.
3P200A.F.
BLACK ANT. PLAT
3P100A.F.
3P50A.T. 1P20A.T.
1P20A.F.
RECEPT.RECEPT.
1P20A.F.
1P20A.T.3P100A.T.
3P100A.F.
RED 2RED 1
3P100A.F.
3P100A.T.
65K RMS SYM A.I.C.
600A.
3P800AF
3P225AT
3P800AF
3P500AT
800AF
250AT
3P1600AF
3P1000AT
1600AF
400AT
3P1600AF
3P500AT
800AF
600AT
800AF
300AT
1000AF
1000AT
800AF
800AT
800AF
A AA A AAA AA AA A A AA A A A AA AA A A
TRANSIENT
SUPPRESSION
UNIT
DRY TYPE
MS
CAPACITOR
SEC. L.A. & SURGE
D3
288/120V.
VS
V
AD
KWH
D
GF
AIR
125E
(SM-5)
L.A.
9KV.
F3
SWITCH
UNIT SUBSTATION-ND
FEEDER F3
K 4000AT
4000AF
2000/2666KVA.,
Z=5.75%
4000A. 480Y/277V., 3Ø,4W. BUS
AA
3P175AT
3P400AF
LIFT STA. NO. 1
EXISTING SERVICE TO
CUBICLE
NEW
CUBICLES
EXISTING
F3
250E. 150E.250E.
EXISTING METAL
ENCLOSED 15Kv. SW. GR.
FUT.
F2F1
REMOVABLE
LINK
GF
N.O.
600A., 15KV.,
INTERRUPTER
STA. TYPE
GROUND BUS
12470V.-480/277V.,3Ø,4W. 100% NEUTRAL BUS
4000AF
3000AT
K
FEEDER F3
S P A R E
N1T9
XFMR
*2
C H
IL
LE
R
N O
3P400A N.F.
NEMA 3R
ENCL.
*2
XFMR
N1T1
PANEL
N1H1
N1L1
PANEL
SECT
SECT
N1L1
PANEL
SECT
N1L1
PANEL PANEL
N1L4
SECT
PANEL
N1L4
SECT
SECT
PANEL
N1L4
N1H4
PANEL
N1T4
XFMR
*2 *2
XFMR
N1T6
PANEL
N1H6
N1L6
PANEL
SECT
N1L6D
PANEL
SECT
N1L6D
PANEL
PANEL
N1L6A N1L6B
PANEL
N1L6C
PANEL
N1H7
PANEL
N1T7
XFMR
*2
PANEL
*2
XFMR
N2T3
PANEL
N2H2
N2L3
PANEL
SECT
SECT
N2L3
PANEL
SECT
N2L3
PANEL
PANEL
N2L3A
SECT
SECT
PANEL
N2L3A
N2T3A
XFMR
*2 *2
N2T4
XFMR
N2L4
PANEL
N2L4A
PANEL
N2L4B
PANEL PANEL
N2L5B
PANEL
N2L5A
PANEL
N2L5
XFMR
N2T5
*2 *2
N2T6
XFMR
N2L6
PANEL
N2L6A
PANEL
N2H3
PANEL
NOTES:
*1. NOT USED.
*2. TRANSIENT SUPPRESSION UNIT CONNECTED TO
SECONDARY LUGS OF TRANSFORMER.
CONT. ON
SHEET NO.
5E01A
C O N T.
O N
S H E E T N O E A
TO SWITCHBOARD
"NEM"
PANEL TGA
3P1000AT
NON-AUTOMATIC
TRANSFER SWITCH N-2
FUT.
EXTENSION EXTENSION
EXISTING 15kV SERVICE
FEEDER TO CISF FACILITY
INSTALLED IN 1-4" CONC.
ENCASED DUCT WITH 1-4"
SPARE DUCT.
3-1/C 250kcmil, 15kV COPPER
SHIELDED EPR OR XLP WITH
133% INSULATION. NEUTRAL
CONDUCTOR SHALL BE 600
VOLT 250kcmil TYPE THW
INSTALLED IN 1-4" CONC.
ENCASED DUCT WITH 1-4"
DUCT AS SPARE.
G.F.
N1L7
GFGFGFGFGFGFGFGFGFGFGFGF
800AT
*3. CONTRACTOR SHALL PROVIDE THIS FEED WITH A
DIELECTRIC UNION IMMEDIATLY AFTER PENITRATING
THE S.A.R. AREA WALL.
*4. THIS PANEL SHALL BE AN R.F. FILTERED AND
SHIELDED CIRCUIT BREAKER PANEL. REFERENCE
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
MOTOR
CONTROL
CENTER
NMCC-3
NMCC-2
CENTER
CONTROL
MOTOR
NMCC-1
MOTOR
CONTROL
CENTER
PARALLEL
SEE PLANS
FOR FEEDER
SIZE
3P175AT
3P400AF
JJJJJ
17 25
30 30 30 30 30
SAR
XFMR
N1T7A
PANEL
N1L7A
*2
*4
*3
AREA
13 12
SECT
N1L6F
PANEL
N1L6F
SECT
PANEL
22STSTST
27 26
19 26
*5 *5 *5
*4*4 *4 *4
*5. CONTRACTOR SHALL PROVIDE THIS FEED WITH
A DIELECTRIC UNION IMMEDIATLY AFTER
PENITRATING THE CONFERENCE ROOM WALL.
Model
File details come from the government source that posted it. Updated .