Attachment_2_Winterhaven_BPS_Working_Drawings.pdf

PDF 5 MB Posted

Attached to
IFB 26-0052 - Winterhaven BPS Generator Replacement (Lassen County)
Solicitation number
0000040130
Issued by
Lassen County, California

About this file

Winterhaven Border Station Generator Replacement Project Summary

This is a working drawing and specification document prepared by the California Department of General Services (DGS) for the California Department of Food and Agriculture (CDFA) Winterhaven Border Station, located at 3510 I-8, Winterhaven, California 92283. The project encompasses the complete replacement of an existing propane generator with a new 20kW/25kVA, 240/120V optional standby propane generator rated at 80% power factor, to be installed in a NEMA 3R Level II sound-attenuated aluminum enclosure (Cummins Model C20 N6, F217-2) with a 20-foot exhaust pipe extension. The scope of work includes demolition of the existing propane generator, integrated automatic transfer switch (ATS) and panelboard, associated conduits and conductors, and reconnection of the existing above-ground 120-gallon propane tank to the new generator. Additionally, the project requires installation of a new integrated ATS/panelboard rated at 100A, 240/120V, 1-phase, 3-wire with 16 circuits and NEMA 3R enclosure with switched neutral, complete power and control conduits and conductors, concrete equipment pad installation, grounding systems with minimum two copper-clad ground rods and exothermic welding connections, and site preparation including trench work for underground conduit routing.

The project specifications require compliance with the 2022 California Building Code, California Electrical Code, California Fire Code, and applicable NFPA standards (NFPA 30, 37, 70, and 110). The contractor is responsible for all permitting fees, emissions compliance registration with Imperial County Air Pollution Control District, geophysical survey and utility locating prior to excavation, site investigation to identify existing underground utilities, damage repair for any utilities disturbed during construction, temporary power provision to avoid facility downtime, and comprehensive testing and commissioning of all systems. The contractor must submit shop drawings for approval, provide "as-built" drawings upon completion, coordinate with the equipment manufacturer for final conduit stub-up locations and wiring specifications, and deliver eight hours of operator training to facility staff. All materials must be new, UL-listed, and suitable for the 125°F maximum ambient temperature environment. The project is funded by the State of California through the DGS and CDFA, with the project number 000000000013525 and approval date of January 21, 2026.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

C A D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 T .1

.d w g

P lo t D a te

N o v

:2 p m

P lo tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

SITE PLAN VICINITY MAP

WINTERHAVEN BORDER STATION

GENERATOR REPLACEMENT

DRAWING INDEX

PROJECT INFORMATION

SCOPE OF WORK

APPLICABLE CODES AND STANDARDS

ALL WORK MUST COMPLY WITH THE LATEST APPLICABLE FOLLOWING CODES AND

REGULATIONS, AS ADOPTED AND AMENDED BY LOCAL, CITY, COUNTY, MUNICIPAL

AND STATE REGULATIONS:

- 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.

- 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.

- 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.

NFPA 70 - 2020 EDITION

- 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.

- 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.

- 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.

- 2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 C.C.R.

- 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,

TITLE 24 C.C.R.

- 2022 CALIFORNIA REFERENCE STANDARDS, PART 12, TITLE 24 C.C.R.

- TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

- 2021 NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.

- 2024 NFPA 37 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES

AND GAS TURBINES.

- 2022 NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEM.

REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN 2022 CBC CHAPTER 35 OR

2022 CFC CHAPTER 80. SEE CHAPTER 35 FOR STATE OF CALIFORNIA AMENDMENTS

TO NFPA STANDARDS.

AMERICANS WITH DISABILITIES ACT TITLE II.

PROJECT NUMBER: 000000000013525

N

PREPARED FOR:

DEPARTMENT OF GENERAL SERVICES

REAL ESTATE SERVICES DIVISION

PROJECT MANAGEMENT AND

DEVELOPMENT BRANCH

707 3rd STREET, 4th FLOOR, WEST SACRAMENTO, CA 95605

PROJECT DIRECTOR

JOYESH CHANDRA

PHONE: (916) 926-8906

EMAIL: JOYESH.CHANDRA@DGS.CA.GOV

ADMINISTRATIVE SERVICES DIVISION BUILDING

AND PROPERTY MANAGEMENT UNIT

CALIFORNIA DEPARTMENT OF FOOD AND

AGRICULTURE

1220 NORTH STREET, ROOM 120,

SACRAMENTO, CA 95814

FACILITY PROJECTS AND CONTRACTS LEAD

DONOVAN HARRELL

PHONE: 916-879-6240

EMAIL: DONOVAN.HARRELL@CDFA.CA.GOV

PREPARED BY:

J.C. CHANG & ASSOCIATES, INC.

ENGINEERS, ARCHITECTS AND

PLANNERS

385 VAN NESS AVENUE, SUITE 208

TORRANCE, CALIFORNIA 90501

PHONE: (310) 212-7644

ELECTRICAL ENGINEER OF RECORD

SEVAG AVANESSIAN

LIC. NO. E22793

385 VAN NESS AVE. #208

TORRANCE, CALIFORNIA 90501

ELECTRICAL LEAD ENGINEER

ORLANDO NAJERA -

ONAJERA@JCCAINC.COM

NOT TO SCALE

N

NOT TO SCALE

PROJECT

LOCATION

1. DEMOLISH (E) PROPANE GENERATOR AND INTEGRATED ATS/PANELBOARD.

2. DEMOLISH (E) CONDUITS AND CONDUCTORS ASSOCIATED TO GENERATOR.

3. PROVIDE 20kW/25kVA, 240/120V, 1Ø, 3W, 80% PF, OPTIONAL STANDBY PROPANE

GENERATOR, WITH NEMA 3R LEVEL II SOUND ATTENUATED ENCLOSURE AND

20'-0" EXHAUST PIPE EXTENSION WITH ASSOCIATED SUPPORT BRACKETS.

4. PROVIDE RECONNECTION OF (E) ABOVE GROUND PROPANE TANK PIPES TO

GENERATOR.

5. PROVIDE POWER AND CONTROL CONDUITS AND CONDUCTORS TO GENERATOR.

6. PROVIDE AN INTEGRATED ATS/PANELBOARD RATED 100A, 240/120V, 1PH, 3W,

10KAIC, 16 CIRCUIT, NEMA 3R, SWITCHED NEUTRAL.

SHEET NUMBER SHEET TITLE

GENERAL

T0.1 TITLE SHEET

T0.2 STATE FIRE MARSHAL TRIAGE LIST

ELECTRICAL

E0.1 ELECTRICAL COVER SHEET

E0.2 ELECTRICAL NOTES

E0.3 ELECTRICAL SINGLE LINE DIAGRAM

E0.4 ELECTRICAL SCHEDULES

E0.5 ELECTRICAL OVERALL SITE PLAN

E1.1 ELECTRICAL DEMOLITION PLAN

E2.1 ELECTRICAL NEW WORK PLAN

E3.1 ELECTRICAL GROUNDING DETAILS

E3.2 ELECTRICAL GENERAL DETAILS

E3.3 ELECTRICAL EQUIPMENT DETAILS

E4.1 ELECTRICAL SPECIFICATIONS

TOTAL NUMBER OF SHEETS = 13

MEXICO

COLORADO RIVER

DUNES

ARIZONA

PROJECT

LOCATION

CALIFORNIA

WINTERHAVEN

T0.1

TITLE COVER

SA ON ON

CALIFORNIA DEPARTMENT OF FOOD AND AGRICULTURE

FELICITY

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3919

A D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 T .2

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

T0.2

SFM TRIAGE LIST

SA ON ON

BASIC SIGNAGE REQUIREMENTS FOR FIRE AND LIFE SAFETY

BATTERY/EQUIPMENT/ELECTRICAL/MECHANICAL ROOMS: SIGNAGE AT METERED SERVICE PANELBOARD, PER 2022 CFC 604.3.1.

NO SMOKING: SIGNAGE NEAR THE PROPANE & ADJACENT BUILDINGS, PER 2022 CFC SECTION 5703.5.

2017 NFPA 704 SIGNAGE FOR HAZARDOUS SYMBOLS

STORAGE TANK AND FLAMMABILITY AREAS: SIGNAGE AT GENERATOR & ADJACENT BUILDINGS, PER 2022 CFC 5704.2.3 AND 2017 NFPA 704.

PORTABLE FIRE EXTINGUISHERS, PER 2022 CFC 1203, 2022 CFC CH. 57, 2022 CFC 1204.10, AND 2022 CCR TITLE 19. A LISTED PORTABLE FIRE EXTINGUISHER COMPLYING WITH 906 WITH A MIN. RATING OF 2-A:20-B:C SHALL BE PROVIDED NOT MORE THAN 50 FEET FROM THE GENERATOR, PER 2022 CFC SECTION 1204.10.

ITEM SUBMITTAL REQUIREMENTS SUBMITTAL RESPONSE REFERENCE

1 PROXIMITY TO STRUCTURE & PROPERTY LINES 4'-0" FEET FROM NEAREST BUILDING, 67'-0" FEET FROM PROPERTY LINE E0.5, E2.1

2 OPEN OR ENCLOSED ENCLOSURE

LEVEL 2 ENCLOSED ALUMINUM ENCLOSURE (CUMMINS MODEL#C20 N6, LEVEL 2

F217-2), OUTDOORS.

(OVERALL WEIGHT: 1,081 LBS) (OVERALL DIMENSIONS: L6'-9",W2'-10",H3'-9")

3 CLASS, LEVEL, TYPE AND PURPOSE CLASS 39, LEVEL 2, TYPE 10, OPTIONAL STANDY-BY PDF ATTACHMENT

4 LOCATION/PROTECTION OF TRANSFER SWITCHES

ATS LOCATED OUTDOORS, ADJACENT TO GENERATOR AND INTEGRATED INTO

PANELBOARD ENCLOSURE. PROTECTED BY BOLLARDS AND BUILDINGS.

5 ELEVATION/LOCATION OF EXHAUST

6 FUEL SOURCE TYPE, CONTENTS AND QUANTITY

GENERATOR IS SUPPLIED BY ABOVE GROUND 120-GAL PROPANE TANK.

(@100% LOAD, 2.43-GPH (1-GAL = 43.1-CF @125°F AMBIENT TEMP.)

AND PER NFPA 58 - 80% TANK FILL LIMIT,

(E) 120 GAL PROPANE TANK HAS THE CAPACITY RUN TIME FOR 39-HOURS )

PDF ATTACHMENT

7 FUEL TANK LOCATION AND SET BACKS

LOCATED OUTDOORS, ADJACENT TO BUILDINGS AND

PROTECTED BY BOLLARDS

8 GENERATOR/TANK PAD DETAILS & LOAD CALCULATIONS SEE ON DWG E0.4, E3.3, AND PDF ATTACHMENTS

9 SECONDARY CONTAINMENT

GENERATOR IS SUPPLIED TO ABOVE GROUND PROPANE TANK, THERE ARE NO

SECONDARY SPILL CONTAINMENTS.

E3.3, PDF ATTACHMENTS

10 PIPING TYPE, FITTING AND METHOD OF JOINING

PIPING TYPE, FITTING, AND METHOD OF JOINING N.A., PRE-INSTALLED & PACKAGED BY

GENERATOR MANUFACTURER

PDF ATTACHMENT

11 VEHICLE IMPACT PROTECTION PROTECTED BY BUILDINGS AND BOLLARDS E0.5, E2.1

12 GROSS AREA OF THE NEW IMPROVEMENTS 275 SQ/FT

OPTIONAL STANDBY GENERATOR

LOCATED OUTDOORS, ADJACENT BUILDINGS

E0.5, E2.1, E3.3, PDF ATTACHMENT

E0.5, E2.1

E0.5, E2.1, E3.3

E0.5

E0.4, E3.3, PDF ATTACHMENT

TRIAGE LIST AND SIGNAGE REQUIREMENTS - GENERATOR

E0.5, E2.1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .1

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

FUSE W/ DISCONNECT SWITCH

M MOTOR

GROUNDING

MOTOR

GROUNDING

TRANSFORMER

CIRCUIT BREAKER

F

T OR

BRANCH CIRCUIT DESTINATION (PANEL NAME-CIRCUIT NUMBER)

HOMERUN INDICATES PROVIDING CONDUIT AND CONDUCTORS

MINIMUM CONDUIT SIZE: 3/4"

MINIMUM CONDUCTOR SIZE: #12AWG

PROVIDE 3/4"C-2#12+1#12G WHERE NO CONDUIT/WIRE SIZE IS STATED.

PROVIDE DEDICATED NEUTRAL FOR ALL BRANCH CIRCUIT WIRING.

CONTRACTOR RESPONSIBLE FOR DE-RATING CONDUIT WITH MORE

THAN SIX CURRENT CARRYING CONDUCTORS PER CEC 310.

#12 AWG FOR CIRCUITS UP TO 100'

#10 AWG FOR CIRCUITS FROM 100' TO 200'

#8 AWG FOR CIRCUIT GREATER THAN 200'

P4-10

J

SHEET WHERE DETAIL IS DRAWN

DETAIL NO.

NEW WORK KEY NOTE

DEMOLITION KEY NOTE

RJ45 ETHERNET PORT - WALL MOUNTED

120V 20A - DUPLEX - WALL MOUNTED - RECEPTACLE

120V 20A - QUADPLEX - WALL MOUNTED - RECEPTACLE

JUNCTION BOX OR PULL BOX

(208Y/120V OR 240Y/120V) 3Ø, 4W OR (240/120V) 1Ø, 3W PANELBOARD

480Y/277V, 3Ø, 4W PANELBOARD

SWITCHBOARD, DISTRIBUTION BOARD OR MOTOR CONTROL CENTER

AUTOMATIC TRANSFER SWITCH (A.T.S.)

E

L

N

GENERATOR G

ELECTRICAL LEGENDS ABBREVIATIONSTYPICAL PLAN LEGEND

NEGLIGIBLENEGL

DEMOLISH

EXISTING(E)

CB CIRCUIT BREAKER

EA. EACH

COPPERCU

G, GND GROUND

MCB MAIN CIRCUIT BREAKER

AMP./A AMPERE

FIN FINISHED

CIRCUITCKT

LOW VOLTAGE

AMPERE INTERRUPTING

CAPACITY

AIC

ABOVE FINISHED FLOORAFF

BKR BREAKER

WEATHER PROOFWP

SWITCHBOARDSWB

TYP. TYPICAL

UG UNDERGROUND

SWITCHSW

PULL BOXPB

SLD SINGLE LINE DIAGRAM

POLEP

PANELBOARDPNL

(R) RELOCATED

SUB SUBSTATION

NEW(N)

TD TIME DELAY

UNLESS OTHERWISE

NOTED

UON

TRANSFORMERXFMR,

TRANSF.

VD VOLTAGE DROP

(D)

NTS NOT TO SCALE

LV

EM. EMERGENCY

AUTHORITY HAVING

JURISDICTION

AHJ

OS OCCUPANCY SENSOR

PHOTOCELL SENSORPC

PLC

GENERAL CONTRACTORGC

GFCI

GEC

DRAWINGDWG

EGC

L LENGTH

VFD VARIABLE FREQUENCY DRIVE

SCE SOUTHERN CALIFORNIA EDISON

EQUIPMENT GROUNDING

CONDUCTOR

GROUNDING ELECTRODE

CONDUCTOR

GROUND FAULT CURRENT

INTERRUPTER

PROGRAMMABLE LOGICAL

CONTROLLER

THRU THROUGH

MIN. MINIMUM

MFR MANUFACTURER

EQUIP EQUIPMENT

THIS SYMBOLOGY TO BE USED BY ELECTRICAL AND LAYOUT FOR ALL FLOOR PLANS,

EQUIPMENT, DEVICES, UTILITIES, ETC..., SHOWN ON DRAWINGS.

LIGHT, DASHED THIN LINES INDICATE EXISTING

UNDERGROUND CONDUITS AND CONDUCTORS.

LIGHT, CONTINUOUS THIN LINES INDICATE EXISTING OR

EXISTING ABOVE GROUND CONDUITS AND

CONDUCTORS.

MEDIUM, SHORT DASHED LINES INDICATE DEMOLITION

OR REMOVAL.

HEAVY, DASHED THICK LINES INDICATE NEW

UNDERGROUND CONDUITS AND CONDUCTORS.

HEAVY, CONTINUOUS THICK LINES INDICATE NEW OR

NEW ABOVE GROUND CONDUITS AND CONDUCTORS.

HEAVY, LINES WITH "G" TEXTS INDICATE NEW

UNDERGROUND BARE COPPER CONDUCTOR.

LIGHT LINE WITH "OH" TEXTS INDICATE EXISTING

OVERHEAD CONDUIT AND CONDUCTORS.

HEAVY, LINES WITH "GAS" TEXTS INDICATE NEW

UNDERGROUND GAS PIPE.

G G

FUSE

M MULTIFUNCTION POWER METER

E0.1

ELECTRICAL COVER

SHEET

SA ON ON

INTEGRATED ATS AND PANELBOARD (240/120V) 1Ø, 3W

OH OH

GASGAS

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .2

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

1. GENERAL:

A. THE PROVISIONS OF THE GENERAL CONDITIONS ARE PART OF THIS SECTION AS THOUGH FULLY SET

FORTH HEREIN. BEFORE SUBMITTING THE BID, THE BIDDER SHALL VISIT THE SITE AND DETERMINE ANY EXISTING CONDITIONS WHICH MAY AFFECT THE COST OF WORK UNDER THIS SECTION; AND SHALL

INCLUDE IN THE BID ALLOWANCE FOR SUCH COST.

B. THE ELECTRICAL GENERAL NOTES ARE PROVIDED ONLY TO EMPHASIZE PORTIONS OF WORK OR

INFORMATION REQUIRED FOR THE SCOPE OF WORK. CONTRACTOR TO REFER TO ALL OTHER

INFORMATION INCLUDED IN THE COMPLETE DRAWINGS PACKAGE FOR ALL DISCIPLINES IN THE

PROJECT, PROJECT MANUALS AND SPECIFICATIONS AS WELL AS ALL OTHER DOCUMENTS AND

INFORMATION PROVIDED OR REFERENCED IN CONTRACT DOCUMENTS.

2. WORK INCLUDED:

PROVIDE MATERIALS AND PERFORM LABOR REQUIRED TO EXECUTE THIS WORK AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS NECESSARY TO COMPLETE THE CONTRACT, INCLUDING, BUT NOT LIMITED

TO, THESE MAJOR ITEMS:

A. MAINTAIN ALL EXISTING ELECTRICAL WORK WITHIN THE CONSTRUCTION AREA REQUIRED TO

CONTINUE EXISTING ELECTRICAL SYSTEMS OPERATION BEYOND THE CONSTRUCTION AREA.

B. PROVIDE "AS-BUILT" DRAWINGS SHOWING CHANGES FROM THE CONTRACT DOCUMENTS.

C. TEST THE COMPLETED WORK. CORRECT ANY DEFECTS TO THE SATISFACTION OF PROJECT

REPRESENTATIVE.

3. DRAWINGS:

A. ALL DRAWINGS IN THE PACKAGE ARE INCLUDED IN THE SCOPE OF WORK. DRAWINGS FROM EVERY

TRADE SHOULD BE CAREFULLY REVIEWED AND COORDINATED WITH THE ELECTRICAL DRAWINGS TO ESTABLISH AN UNDERSTANDING OF THE PROJECT AS A WHOLE. WHERE THERE ARE ITEMS SHOWN ON DRAWINGS OF OTHER TRADES THAT REQUIRE ELECTRICAL PROVISIONS, SUCH PROVISIONS SHALL BE

DETERMINED BY THE CONTRACTOR AND THE COST SHALL BE INCLUDED IN THE BID.

B. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE LOCATIONS OF EQUIPMENT, DEVICES AND OTHER LOADS AS WELL AS THE CIRCUIT ARRANGEMENT OR THE REQUIRED CONDUIT AND WIRING, ALTHOUGH NOT NECESSARILY INDICATING THE ACTUAL RUNS OF CONDUIT THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS COORDINATION WITH THE WORK OF OTHER TRADES AND THE STAGES AVAILABLE WILL PERMIT. ANY DISCREPANCIES, CONFLICTS OR QUESTIONABLE

POINTS SHALL BE IMMEDIATELY REPORTED TO PROJECT MANAGER.

C. IF RELOCATION OR ADJUSTMENT OF ANY PORTION OF WORK IS REQUIRED, IT SHALL BE MADE BY THE CONTRACTOR WITHOUT EXTRA COST, PROVIDED THE NEW LOCATION IS NOT MORE THAN FIVE FEET

FROM THE LOCATION SHOWN ON THE DRAWINGS.

D. ALL ITEMS NOT SPECIFICALLY MENTIONED IN THE SPECIFICATIONS OR NOTED ON THE DRAWINGS, BUT

WHICH ARE OBVIOUSLY NECESSARY TO MAKE A COMPLETE WORKING INSTALLATION SHALL BE

INCLUDED.

4. SPECIFICATIONS:

A. A SEPARATE SPECIFICATION PACKAGE IS PROVIDED IN ADDITION TO THE DRAWINGS. THE

SPECIFICATIONS ARE PART OF THE CONTRACT SCOPE. ALL SECTIONS OF THE SPECIFICATION

PACKAGE SHALL BE CAREFULLY REVIEWED BY THE CONTRACTOR. NOT ALL ELECTRICAL WORK IS

NECESSARILY STATED IN THE ELECTRICAL SECTIONS, THEREFORE IT IS NECESSARY TO CAREFULLY

REVIEW ALL SECTIONS TO DETERMINE ELECTRICAL PROVISIONS THAT ARE REQUIRED.

B. ALL REQUIREMENTS STATED IN THE SPECIFICATIONS PACKAGE SHALL APPLY TO THE PROJECT, WHETHER OR NOT SHOWN ON THE DRAWINGS. COORDINATE ALL INFORMATION SHOWN ON DRAWINGS

AND SPECIFICATION PRIOR TO BID AND REPORT ANY DISCREPANCY, CONFLICT OR QUESTIONS

IMMEDIATELY TO THE PROJECT MANAGER. WHERE A CONFLICT EXISTS BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MORE STRINGENT, SAFE AND/OR COSTLY OF THE ITEMS SHALL BE USED AS

BASIS FOR THE BID AND INCLUDED IN WORK.

5. DELEGATED DESIGN DRAWINGS, PRODUCT DATA AND SPECIFICATIONS:

DELEGATED DESIGN SHALL INCLUDE DRAWINGS, SPECIFICATIONS AND SPECIFIC PRODUCT DATA /

CUT-SHEETS FOR PRODUCTS THAT ARE USED. SUBMIT TO PROJECT MANAGER FOR APPROVAL.

6. SHOP DRAWINGS:

SUBMIT TO PROJECT MANAGER FOR APPROVAL. SHOP DRAWING SHOWING COMPLETE DETAILS AND DIMENSIONS FOR ALL ELECTRICAL POWER, LIGHTING AND CONTROL EQUIPMENT AND DEVICES SHALL BE PROVIDED. REFER TO SPECIFICATIONS FOR DETAILED INFORMATION ON SHOP DRAWING REQUIREMENTS.

7. ORDINANCE REQUIREMENTS:

THE ELECTRICAL WORK SHALL COMPLY WITH THE REQUIREMENTS OF ALL APPLICABLE LOCAL AND STATE CODES AND ALL OTHER LEGAL REQUIREMENTS. IN CASE OF CONFLICTS BETWEEN CODE REQUIREMENTS, THE MOST RESTRICTIVE SHALL APPLY; EXCEPT WHERE THE REQUIREMENTS OF THE CONTRACT

DOCUMENTS EXCEED CODE REQUIREMENTS, IN WHICH CASE THE CONTRACT DOCUMENTS SHALL GOVERN.

8. PERMITS AND INSPECTIONS:

A. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES AND FEES REQUIRED FOR THE

EXECUTION OF HIS WORK, AND SHALL ARRANGE FOR AND PAY FOR ALL REQUIRED TESTS AND

INSPECTIONS, AND SHALL GIVE ALL NOTICES REQUIRED BY ANY AND ALL LAWS, RULES, REGULATIONS, AND ORDINANCES WHICH PERTAIN TO THE CONTRACTOR'S WORK.

B. CONTRACTOR SHALL PERFORM THE FOLLOWING LISTED ABOVE FOR AUTHORITY HAVING JURISDICTION

AND IMPERIAL COUNTY APCD.

C. OBTAIN A PERMIT AND REGISTRATION FOR BACKUP GENERATOR. MEET ALL REQUIRED COMPLIANCE WITH STATE AND FEDERAL EMISSION LIMITS, AND SPECIFIC OPERATIONAL AND TESTING PROTOCOLS.

9. TESTING AND COMMISSIONING:

A. CONTRACTOR SHALL CONDUCT SUCH TESTING AND COMMISSIONING OF ANY PORTION OF

INSTALLATIONS AS MAY BE NECESSARY TO ENSURE FULL COMPLIANCE WITH PLANS AND

SPECIFICATIONS. COST OF TESTING AND COMMISSIONING SHALL BE BORNE BY CONTRACTOR AND

CONTRACTOR SHALL PROVIDE ALL THE INSTRUMENTS, EQUIPMENT, LABOR AND MATERIALS TO

COMPLETE TESTS.

B. TESTING AND COMMISSIONING SHALL BE DONE IN A COMPREHENSIVE MANNER APPLIED TO THE ENTIRE SYSTEM AS A WHOLE. FOR EXAMPLE, THE ELECTRICAL, MECHANICAL AND PLUMBING SYSTEM

AS WELL AS THEIR INTERCONNECTION AND FUNCTIONALITY WITH THE CONTROL AND

COMMUNICATIONS SYSTEM SHALL BE TESTED AND COMMISSIONED IN THEIR ENTIRETY TO

DEMONSTRATE A COMPLETE AND FUNCTIONAL SYSTEM.

C. SHOULD THESE TESTS DEVELOP ANY DEFECT IN MATERIALS OR POOR WORKMANSHIP OR VARIANCE

WITH REQUIREMENTS OF SPECIFICATIONS, THEN CONTRACTOR SHALL MAKE ANY CHANGES

NECESSARY AND REMEDY ANY DEFECTS AT THE CONTRACTOR'S OWN EXPENSE.

D. WHERE ANY FAILURE OR UNSATISFACTORY RESULTS FROM THE TESTING AND COMMISSIONING

PROCESS ARE RECORDED OR OBSERVED, THE CONTRACTOR SHALL PROVIDE ALL LABOR AND

MATERIAL AS NECESSARY TO RESOLVE THE ISSUE IN SUCH A WAY THAT TESTING AND COMMISSIONING IS COMPLETED SUCCESSFULLY. TESTING AND COMMISSIONING OF THE SYSTEM AS A WHOLE SHALL BE REPEATED IN SUCH CASES UNTIL ALL ISSUES HAVE BEEN RESOLVED, SATISFACTORY RESULTS ARE ACHIEVED AND RECORDED AND SYSTEM FUNCTIONALITY IS ITS ENTIRETY IS DEMONSTRATED AND

PROVEN.

10. WARRANTY / GUARANTEE:

EQUIPMENT AND ACCESSORIES INSTALLED UNDER THIS SECTION SHALL CARRY THE MANUFACTURER'S WARRANTY AND/OR GUARANTEE FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE EQUIPMENT. THE CONTRACTOR SHALL GUARANTEE IN WRITING, IN A FORM ACCEPTABLE TO THE PROJECT MANAGER, THE ENTIRE ELECTRICAL INSTALLATION AGAINST DEFECTIVE MATERIALS AND/OR IMPROPER WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. DURING THE PERIOD COVERED BY THE GUARANTEE CONTRACTOR SHALL MAKE NECESSARY REPLACEMENTS AND REPAIR AT NO COST TO THE CITY. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS ON WARRANTY/GUARANTEE FOR SPECIFIC EQUIPMENT, DEVICES AND

SYSTEMS.

11. COOPERATION WITH OTHERS:

THE CONTRACTOR SHALL CONSULT AND COOPERATE FULLY WITH ALL OTHER CONTRACTORS AND

SUB-CONTRACTORS FURNISHING LABOR, MATERIALS OR SERVICES, SO THAT THE WORK AS A WHOLE, SHALL BE EXECUTED IN THE MOST EFFICIENT MANNER, AND WITHOUT CONFLICT OR DELAY.

12. MATERIAL:

ALL MATERIALS AND EQUIPMENT USED IN THE WORK SHALL BE NEW (UNLESS OTHERWISE NOTED OR SCHEDULED), AND SUITED TO THE INTENDED USE, AND SHALL BE LISTED BY THE UNDERWRITERS

LABORATORIES INC. AND SHALL MEET THEIR REQUIREMENTS AND BEAR THEIR LABEL WHENEVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY.

ALL MATERIALS AND EQUIPMENT SHALL BE OF THE MAKES AND TYPES SPECIFIED, AND NO SUBSTITUTIONS WILL BE ALLOWED UNLESS APPROVED IN WRITING. THE PROJECT MANAGER RESERVES THE RIGHT TO REJECT ANY MATERIAL OR EQUIPMENT, EITHER BEFORE OR AFTER INSTALLATION, WHICH, IN THE PROJECT MANAGER'S OPINION IS NOT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS OR INTENDED USE.

13. CONDUIT INSTALLATION:

A. USE RIGID METAL CONDUIT FOR ALL EXPOSED EXTERIOR WORK.

B. ALL UNDERGROUND CONDUIT SHALL BE PVC SCHEDULE 40. ALL TRANSITIONS FROM UNDERGROUND

TO ABOVE GROUND, EXPOSED CONDUIT SHALL UTILIZE RIGID METAL ELBOWS AND FITTINGS.

C. PENETRATE AND SEAL ACCESS TO MANHOLES, WELL, VAULTS, ETC. AS REQUIRED TO ROUTE POWER AND CONTROL CONDUCTORS TO VALVES AND OTHER COMPONENTS. SUCH PENETRATIONS SHALL BE SEALED TO COMPLETE WATERTIGHT CONDITIONS. IN ADDITION, ALL CONDUIT PENETRATIONS TO AND

FROM WELLS AND VAULTS SHALL BE EQUIPPED WITH EXPLOSION-PROOF FITTING, SIMILAR TO

"COOPER INDUSTRIES" TYPE "EYS AND EZS" FITTING. SUCH FITTINGS SHALL BE PROVIDED WITH APPROPRIATE LISTED SEALANT TO PREVENT GASES TRAVELING THROUGH CONDUITS TO AND FROM

WELLS TO VAULTS AND OTHER PARTS OF THE SYSTEM.

D. WHERE UNDERGROUND BORING IS REQUIRED, CONTRACTOR SHALL PROVIDE ALL NECESSARY SITE PREPARATION, EQUIPMENT, STAGING, ETC. TO ROUTE THE CONDUIT AS INDICATED ON PLANS.

E. WHEN ROUTING ANY UNDERGROUND CONDUIT, CAREFULLY COORDINATE WITH UTILITIES SHOWN ON CIVIL SHEETS. CONTRACTOR IS RESPONSIBLE FOR CONDUCTING A COMPLETE SURVEY TO CONFIRM EXISTING UTILITIES SHOWN, VERIFY ALL OTHER EXISTING UTILITIES AND ADJUST WORK TO AVOID

DISRUPTION OF ALL EXISTING UTILITIES IN WORK AREA.

F. THE SCOPE OF THIS PROJECT INCLUDES EXTENSIVE UNDERGROUND TRENCHING AND UNDERGROUND

CONDUIT SYSTEMS.

G. THE EXISTING UNDERGROUND UTILITIES ARE UNKNOWN, HOWEVER IT SHOULD BE ASSUMED THAT THERE ARE MANY EXISTING UNDERGROUND UTILITIES, MANY OF WHICH ARE INSTALLED AT VERY

SHALLOW DEPTHS.

H. THE CONTRACTOR IS RESPONSIBLE FOR USING SCANNING/LOCATING, UTILIZE SMALL TOOLS, AND

PERFORM WORK CAREFULLY AS PART OF THE EXCAVATION AND EARTHWORK EFFORTS.

I. THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY AND ALL EXISTING UTILITIES DAMAGED DURING CONSTRUCTION. EXISTING UTILITIES INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

· ELECTRICAL POWER

· LOW-VOLTAGE (FIBER AND COPPER)

· HOT/COLD WATER LINES

· GAS LINES

· SEWER LINES

14. WIRE AND CABLE:

A. PROVIDE WIRES AND CABLES OF THE SIZE AND TYPE SHOWN ON DRAWINGS AND AS SPECIFIED HEREIN. UNLESS OTHERWISE SPECIFIED ALL WIRE AND CABLE SHALL BE U.L. STANDARD ANNEALED

COPPER WIRE WITH U.S. 600 VOLT INSULATION. THE MINIMUM SIZE WIRE FOR LIGHTING OR POWER

CIRCUITS SHALL BE NO.12 AWG. ALL CONDUCTORS SHALL BE STRANDED. INSULATION OF

CONDUCTORS SHALL BE TYPE THHN/THWN.

B. COLOR CODE NO. 12 THROUGH NO. 8 BRANCH CIRCUIT WIRES. USE BLACK, RED, BLUE & WHITE FOR 120/208V CIRCUITS. USE YELLOW, ORANGE, BROWN & GRAY FOR 277/480V CIRCUITS. USE GREEN WIRES

FOR EQUIPMENT GROUNDS ONLY.

C. WIRES AND CABLES FOR CONTROL AND COMMUNICATIONS FOR SPORTS LIGHTING SYSTEM HAVE NOT BEEN SHOWN ON THE DRAWINGS AS THESE ITEMS ARE A PART OF THE DELEGATED DESIGN SCOPE OF WORK. THE CONTRACTOR IS RESPONSIBLE FOR SELECTING TYPE, SIZE AND QUANTITY OF WIRES AND CABLES AS REQUIRED TO PROVIDE THE COMPLETE SYSTEMS DESCRIBED IN THE DELEGATED DESIGN

SCOPE OF WORK.

15. CONDUCTOR IDENTIFICATION:

A. ALL FEEDERS SHALL BE TAGGED AT EACH POINT WHERE THE CONDUIT RUN IS BROKEN. ALL BRANCH CIRCUIT CONDUCTORS AT PANELBOARDS AND SWITCHBOARDS SHALL BE IDENTIFIED WITH "E-Z" CODE

MARKERS.

B. ALL CONTROL AND COMMUNICATION WIRING SHALL BE TAGGED NEAR THE POINT OF TERMINATION OF THE EQUIPMENT TO WHICH THE WIRING IS CONNECTED. THE TAGS SHALL BE TYPEWRITTEN, UV

RESISTANT AND WATERPROOF.

16. BOXES AND ENCLOSURES:

A. ALL OUTDOOR BOXES AND ENCLOSURES SHALL BE NEMA 3R.

B. ALL BOXES AND ENCLOSURES USED IN VAULTS AND WELLS SHALL BE NEMA 4X STAINLESS STEEL TYPE.

17. WIRING DEVICES:

A. ALL WIRING DEVICES SHALL BE FIRST QUALITY, HEAVY-DUTY "SPECIFICATION" GRADE, AND SHALL BE

OF WHITE COLOR, GFCI TYPE.

B. ALL WIRING DEVICES IN VAULTS AND WELLS SHALL BE HOUSED IN WEATHERPROOF NEMA 4X

STAINLESS STEEL BOX OR ENCLOSURE.

C. COMPLY WITH ALL APPLICABLE GROUNDING REQUIREMENTS SPECIFIED IN NFPA 70 ARTICLE 250 FOR

GROUNDING AND BONDING ALL METAL DEVICES, LIGHTING POLES, AND CONDUIT RACEWAYS.

18. CODE COMPLIANCE:

ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST APPLICABLE FOLLOWING CODES AND

REGULATIONS, AS ADOPTED AND AMENDED BY LOCAL, CITY, COUNTY, MUNICIPAL AND STATE

REGULATIONS:

· 2022 CALIFORNIA BUILDING CODE, VOLUMES I, II, III

· 2022 CALIFORNIA ELECTRICAL CODE

· 2022 CALIFORNIA ENERGY CODE

· 2022 CALIFORNIA FIRE CODE

· 2022 CALIFORNIA MECHANICAL CODE

· 2022 CALIFORNIA PLUMBING CODE

· ALL OTHER CODES AND REGULATIONS AS REQUIRED BY DRAWINGS OF OTHER TRADES OR

INCLUDED IN THE SPECIFICATIONS

19. SAFETY:

A. ALL ELECTRICAL WORK SHALL BE CONDUCTED IN ACCORDANCE WITH CAL/OSHA "LOCK OUT / TAG OUT

" PROCEDURES.

20. TRAINING:

A. AT THE CONCLUSION OF WORK, AFTER ALL POWER AND CONTROL EQUIPMENT HAVE BEEN INSTALLED, ENERGIZED, PROGRAMMED, TESTED/COMMISSIONED AND READY FOR USE, PROVIDE TRAINING FOR

THE CITY STAFF.

B. TRAINING SESSION SHALL BE NO LESS THAN 8 HOURS AND SHALL COVER THE OPERATION AND

MAINTENANCE OF THE LIGHTING CONTROL, COMMUNICATIONS AND MONITORING SYSTEM.

C. TRAINING SHALL BE PERFORMED BY A FACTORY TECHNICIAN OR AUTHORIZED VENDOR OF THE

SPECIFIC PRODUCTS USED IN THE SYSTEM.

ELECTRICAL NOTES CONTRACTOR NOTES

1. THE CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT, TOOLS, TRANSPORTATION, WAREHOUSING, AND ANY OTHER SERVICES REQUIRED TO COMPLETE THE WORK IN A

TIMELY AND EFFICIENT MANNER.

2. INDIVIDUAL ITEMS OF WORK ARE DETAILED IN THE VARIOUS SECTIONS OF THIS SCOPE OF WORK, THE

ATTACHED DRAWINGS, AND THE NOTES AND LEGENDS ON THE DRAWINGS. THE CONTRACTOR IS

RESPONSIBLE TO COMPLETE THE REQUIREMENTS FOUND IN ANY OF THE ABOVE.

3. CONTRACTOR BIDS ARE TO BE BASED UPON COMPLETING THE WORK WITHIN THE AMOUNT BID. ANY

QUESTIONS PERTAINING TO UNKNOWN CONDITIONS, CHANGES IN DESIGN, OMISSIONS IN THE DESIGN OR

SCOPE OF WORK, MATERIALS, AND INSTALLATION TECHNIQUE ARE TO BE DISCUSSED WITH THE PROJECT

MANAGER. THE PROJECT MANAGER WILL GET THE ANSWERS TO QUESTIONS, AS SOON AS POSSIBLE, IF

"ON-THE-SPOT" ANSWERS CAN NOT BE PROVIDED. UNKNOWN CONDITIONS ENCOUNTERED DURING THE

COURSE OF WORK, WHICH MAY DELAY WORK OR ADD COST, WILL BE REPORTED TO THE PROJECT MANAGER

IMMEDIATELY-SO THAT PROPER ARRANGEMENTS CAN BE MADE WITHOUT WORK STOPPAGE.

4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSURE THAT ALL APPLICABLE SAFETY LAWS ARE

STRICTLY ENFORCED AND TO MAINTAIN A SAFE CONSTRUCTION PROJECT.

5. THE CONTRACTOR SHALL REPAIR AND/OR REPAINT ALL AREAS DAMAGED BY DEMOLITION OR CONSTRUCTION, AND FINISH TO MATCH EXISTING ADJACENT SURFACES.

6. THE CONTRACTOR SHALL SUBMIT "AS-BUILT" DRAWINGS TO THE PROJECT MANAGER UPON COMPLETION OF

CONSTRUCTION.

7. DAILY, AND UPON COMPLETION OF WORK, CONTRACTOR SHALL REMOVE DEBRIS, RUBBISH, WASTE, AND

SURPLUS MATERIAL FROM PREMISES.

8. THE CONTRACTOR SHALL PROTECT AND COVER ALL FIXTURES AND EQUIPMENT IN AREAS AFFECTED BY

WORK, AND UPON COMPLETION OF WORK, SHALL THOROUGHLY CLEAN ALL FIXTURES, EQUIPMENT, WALLS, FLOOR, AND HARDWARE.

9. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB CONDITIONS AT THE JOB SITE PRIOR TO THE START

OF CONSTRUCTION.

10. ALL COMMUNICATION CONDUIT SHALL BE INSTALLED IN COMPLIANCE WITH ANSI STANDARDS AND INDUSTRY

BEST PRACTICES.

11. ANY POWER OUTAGES SHALL BE APPROVED BY THE OWNER. A 7-DAY WRITTEN NOTICE SHALL BE GIVEN

PRIOR TO FOR ANY OUTAGE REQUEST.

12. VERIFY EXACT LOCATION OF OUTLET, SWITCHES, EQUIPMENT, ETC WITH THE PROJECT MANAGER & USER

PRIOR TO INSTALLATION. COUNTY RESERVES THE RIGHT TO RELOCATE ANY UNINSTALLED OUTLET IN ANY

DIRECTION.

13. ALL NEW WIRING SHALL BE COPPER WITH "THHN" OR "THWN-2" 600 VOLT INSULATION COLOR CODE ALL

BRANCH CIRCUIT WIRING.

14. UPON COMPLETION OF THE WORK, COOPERATE IN CONDUCTING AN OPERATING TEST TO DEMONSTRATE

THAT ALL EQUIPMENT IS OPERATING IN A SATISFACTORY MANNER.

15. ALL ELECTRICAL WORK SHALL BE GUARANTEED BY THE CONTRACTOR FOR A PERIOD OF ONE YEAR FROM

THE DATE OF ACCEPTANCE OF THE WORK BY THE OWNER.

16. ALL OUTLETS & DEVICE SHALL BE FLUSH WITH WALL, UNLESS OTHERWISE NOTED AS SURFACE MOUNTED.

17. ALL DEVICE COLOR SHALL BE WHITE U.O.N.

18. CONTRACTOR SHALL CORE DRILL, SAW CUT, PATCH TO MATCH ADJACENT SURFACES, AND PAINT ALL

EXPOSED CONDUITS & BOXES TO MATCH ROOM FINISH.

19. THE CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT, TOOLS, TRANSPORTATION, WAREHOUSING, AND ANY OTHER SERVICES REQUIRED TO COMPLETE THE WORK IN A

TIMELY AND EFFICIENT MANNER.

20. INDIVIDUAL ITEMS OF WORK ARE DETAILED IN THE VARIOUS SECTIONS OF THIS SCOPE OF WORK, THE

ATTACHED DRAWINGS, AND THE NOTES AND LEGENDS ON THE DRAWINGS. THE CONTRACTOR IS

RESPONSIBLE TO COMPLETE THE REQUIREMENTS FOUND IN ANY OF THE ABOVE.

21. ALL WORK SHALL BE IN COMPLIANCE WITH THE MOST CURRENT VERSION OF EDITION OF 2022 CALIFORNIA

ELECTRICAL CODE AND ALL LOCAL ORDINANCES AND REQUIREMENTS.

22. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL ALL TEMPORARY BARRIERS TO INSURE

THE SAFETY OF THE WORK UNTIL IT IS IN ITS COMPLETED FORM.

23. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSURE THAT ALL APPLICABLE SAFETY LAWS ARE

STRICTLY ENFORCED AND TO MAINTAIN A SAFE CONSTRUCTION PROJECT.

24. THE CONTRACTOR SHALL UPDATE "AS-BUILT" DRAWINGS DAILY.

1. CONTRACTOR SHALL COORDINATE WITH PROJECT MANAGER, OWNER, FACILITY MAINTENANCE, AND ELECTRICAL ENGINEER TO HOST AN ON-SITE PRE-CONSTRUCTION MEETING TO REVIEW REQUIREMENTS OF PROVIDING AN EFFICIENT SEQUENCE OF CONSTRUCTION AND MAINTAIN FACILITY DAILY OPERATIONS TO

MINIMIZE DOWNTIME/POWER OUTAGE TO FACILITY.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE THEIR OWN TEMPORARY POWER SUPPLY IN PERFORMING THEIR WORK TO AVOID DISRUPTION ON THE CLIENTS FACILITY OPERATIONS DURING

CONSTRUCTION.

3. ONCE ALL PROVISIONS HAVE BEEN MADE, START DEMOLITION OF ALL EQUIPMENT AS SHOWN ON DEMOLITION PLANS. COORDINATE WITH PROJECT MANAGER AND OTHER TRADES FOR INDIVIDUAL TASKS AND RESPONSIBILITIES TO NOT DISRUPTS OR CAUSE CONFLICT/INTERFERENCE DURING CONSTRUCTION.

4. AFTER ALL ASSOCIATED EQUIPMENT WITHIN SCOPE OF WORK HAS BEEN DEMOLISHED, BEGIN TRENCHING

GROUND AND PROVIDING ALL NECESSARY EQUIPMENT.

5. AFTER INSTALLATION OF CONDUITS AND CONDUCTORS WITHIN ALL TRENCHED DUCTBACKS ON SITE.

COORDINATE WITH FIELD INSPECTOR TO INSPECT AND APPROVE UNDERGROUND CONDUITS. AFTER INSPECTION APPROVAL PROPERLY BACKFILL ALL TRENCHES AND REPAIR GROUND SURFACE AREAS TO

MATCH EXISTING CONDITIONS.

6. CONTRACTOR SHALL BE RESPONSIBLE TO CAREFULLY COORDINATE LEAD TIMES WITH CONSTRUCTION TIMELINES. COORDINATE WITH PROJECT MANAGER FOR APPROPRIATE ONSITE STORAGE LOCATIONS FOR

BOTH EQUIPMENT AND TOOLS.

7. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY ALL EXISTING UNDERGROUND UTILITY LINES BY VIA DIG ALERT 811 PRIOR TO EXCAVATING EXISTING ASPHALT DRIVEWAY, DRIVEWAYS, AND SIDE

WALKS TO AVOID INTERFERENCE AND DAMAGE TO EXISTING INFRASTRUCTURES.

1. PROVIDE EXTENSIVE SIGNAGE AT EVERY ELECTRICAL ENCLOSURE TO IDENTIFYING THE POWER SOURCE

AND RATING OF THE CONDUCTORS DUE TO MULTIPLE POWER SOURCES.

2. CONDUIT ROUTING IS SHOWN DIAGRAMMATICALLY UNDERGROUND CONDUIT ROUTING BASED ON SITE

CONDITIONS.

3. GROUNDING SYSTEM IS SHOWN DIAGRAMMATICALLY. PROVIDE ALL NECESSARY COMPONENTS FOR A

COMPLETE GROUNDING SYSTEM TO ALL ELECTRICAL ENCLOSURE AND DEVICES.

4. ALL EXISTING UNDERGROUND UTILITIES INCLUDING BUT NOT LIMITED TO, POWER, COMMUNICATION WATER, SEWER AND GAS LINES, WHETHER SHOWN OR NOT ON THIS PLAN, SHALL REMAIN AND BE PROTECTED IN

PLACE UNLESS OTHERWISE NOTED.

5. FEEDER LENGTHS ARE SHOWN FOR SIZING PURPOSES. CONTRACTOR IS RESPONSIBLE FOR VERIFYING

LENGTHS IN FIELD AND MAKING ADJUSTMENTS ACCORDINGLY.

6. CAREFULLY COORDINATE POWER SHUT-DOWN REQUIREMENTS WITH SITE MANAGEMENT

REPRESENTATIVES AND PROJECT MANAGER.

7. UPDATE ALL PANEL SCHEDULES TO REFLECT FINAL CONDITIONS.

8. ALL CIRCUIT BREAKERS SHALL BE FULLY RATED AND SHALL HAVE THE CAPABILITY TO BE LOCKABLE FOR

SAFETY MAINTENANCE PURPOSES.

9. ALL (E) EQUIPMENT IS TO REMAIN AND BE PROTECTED IN PLACE UNLESS NOTED. ALL (E) UNDERGROUND AND ABOVEGROUND FEEDERS WHETHER SHOWN OR NOT ON THIS PLAN SHALL REMAIN AND BE PROTECTED

IN PLACE UNLESS OTHERWISE NOTED.

10. ALL SPARE CONDUITS SHALL BE CAPPED OFF AND LABELED FOR FUTURE USE.

11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING LENGTHS IN FIELD AND MAKING ADJUSTMENTS ACCORDINGLY. CONDUIT ROUTINGS ARE DIAGRAMMATICALLY REPRESENTING A PROPOSED LOCATION OF TRENCH. IF THERE ARE OBSTRUCTIONS IN PATH, USE FACTORY 22.5°, 45°, AND 90° BENDS AS NEEDED TO

OFFSET OBJECTS IN PATH. DO NOT EXCEED MORE THAN 360° BENDS.

12. ALL PANELS, DISCONNECTS, TRANSFORMER, CONTROL PANELS, EQUIPMENT/DEVICES, AND INSTRUMENTS SHALL BE FIELD MARKED WITH LOCATION OF PRIMARY SOURCE, VOLTAGE CLASS, AND CIRCUITS #.

GENERAL NOTES

SEQUENCE OF CONSTRUCTION

E0.2

ELECTRICAL NOTES

SA ON ON

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .3

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

ELECTRICAL SINGLE LINE DIAGRAM

E0.3

NO SCALE

(E) UTILITY POWER POLE

MOUNTED TRANSFORMER

(E) UNDERGROUND

CONDUIT AND FEEDERS

(E) IID

SERVICE

(E)

PROVIDE 20kW/25kVA OPTIONAL STANDBY PROPANE GENERATOR

RATED 240/120V, 1PH, 3W. PROVIDE AN F217-2 SOUND ATTENUATED

LEVEL II ALUMINUM ENCLOSURE.

PROVIDE POWER SUPPLY TO GENERATOR CONTROLLER (20A, 120V,

1P, 2W). GENERATOR MANUFACTURER SHALL DELIVER ON SITE

COMPLETE WITH WIRING TO BLOCK/ENGINE HEATER, BATTERY

CHARGER, ETC.

GENERATOR MANUFACTURER SHALL PROVIDE EMERGENCY LOCKOUT

SWITCH AND SHALL BE DELIVERED ON SITE COMPLETE WITH WIRING

TO SWITCH. EMERGENCY SHUT DOWN OF PRIME MOVER SHALL BE

CAPABLE OF BEING LOCKED IN THE OPEN POSITION.

PROVIDE CONCRETE ENCASED GROUNDING ELECTRODE

CONDUCTOR (UFER). REFER TO DETAILS #/E3.# AND #/E3.#4.

PROVIDE AN INTEGRATED ATS/PANELBOARD RATED 100A, 240/120V,

1PH, 3W, 10KAIC, NEMA 3R, 16 CIRCUIT, WITH CIRCUIT BREAKERS

SIZED AS SHOWN ON PANEL SCHEDULES. AUTOMATIC TRANSFER

SWITCH (ATS) SHALL BE NEUTRAL SWITCHED WITH OPEN TRANSITION.

PROVIDE CIRCUIT BREAKER SIZED AS SHOWN ON SINGLE LINE

DIAGRAM AND PANEL SCHEDULE.

PROVIDE CONDUITS FROM PANELBOARD "D" TO NEW ATS. EXTEND (E)

CONDUCTORS TO (N) LOCATION. TERMINATE CONDUCTORS TO THERE

(E) BREAKER SIZES.

PROVIDE CONTROL WIRING PER EQUIPMENT MANUFACTURER

RECOMMENDATION.

BOND ALL SYSTEM GROUNDING ELECTRODES PRESENT AT EACH

BUILDING OR STRUCTURE. PROVIDE BONDING JUMPERS TO ALL

GROUNDING ELECTRODES IN ACCORDANCE WITH CEC 250.53(C) AND

250.66. REFER TO DETAIL #/E#.#.

PROVIDE A MINIMUM OF (2) TWO 3/4"Ø x 10' COPPER CLAD GROUND

RODS SPACED A MINIMUM OF 6" APART, WITH A GROUNDING TEST

INSPECTION WELL. REFER TO DETAILS #/E3.# AND #/E3.#.

NEW WORK KEYNOTES:

DISCONNECT AND DEMOLISH EQUIPMENT.

DISCONNECT AND DEMOLISH CONDUCTORS AND CONDUITS.

DISCONNECT (E) BRANCH CIRCUIT CONDUCTORS FROM GENERATOR.

PROTECT IN PLACE (E) BRANCH CIRCUIT CONDUCTORS WITHIN

PANELBOARD "D". CONDUCTORS ARE TO BE RE-USED AND EXTENDED

TO NEW EQUIPMENT. SEE NEW WORK.

DEMOLITION KEYNOTES:

1. ALL EXISTING EQUIPMENT IS TO REMAIN AND BE PROTECTED IN PLACE

UNLESS NOTES OTHERWISE.

2. ALL NEW CIRCUIT BREAKERS SHALL BE FULLY RATED AND HAVE THE

CAPABILITY TO BE LOCKABLE FOR SAFETY MAINTENANCE PURPOSES.

3. ABOVE GROUND PROPANE PIPES SHALL REMAIN AND BE PROTECTED

IN PLACE.

4. CONTRACTOR IS RESPONSIBLE FOR VERIFYING LENGTHS IN FIELD AND

MAKING ADJUSTMENTS ACCORDINGLY.

5. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH

GENERATOR MANUFACTURER TO CONFIRM EACH GENERATOR'S

SHORE POWER AUXILARY REQUIREMENTS AND MODIFY SIZE AND TYPE

OF CIRCUIT BREAKER, CONDUIT, CONDUCTORS, AND OUTLET BOX

ACCORDINGLY.

GENERAL NOTES:

(E

II

D M

E T E R

D

Y B -2

M

(E)

(E S E R

V

IC

E M

E T E R

E D

S E C

T

"M S A /1

V Ø

W

K

A

IC

C

U B

U S N

E M

A

R

(E)

(E M

A

IN

D

IS

C O

N N E C

T S

E C

T "M

S

A /1

V Ø

W

K

A

IC

C

U B

U S N

E M

A

R

(E)

400AS

400AF

3P

E0.3

ELECTRICAL SINGLE

LINE DIAGRAMS

SA ON ON

(E G

U T T E R

B O

X

(E)

(E) (E)

(E) PANEL "B"

125A, 240/120V, 3Ø, 4W, 10 KAIC,

20 CIRCUIT,

NEMA 3R, CU BUS

(E) PANEL "A"

225A, 240/120V, 3Ø, 4W, 10 KAIC,

42 CIRCUIT,

NEMA 3R, CU BUS

(E) 200A 3P

125A 2P

(E) PANEL "D"

125A, 240/120V, 1Ø, 3W, 10 KAIC,

12 CIRCUIT,

NEMA 3R, CU BUS

(E)

100A 2P

(E) PANEL "D1"

125A, 240/120V, 1Ø, 3W, 10 KAIC,

24 CIRCUIT,

NEMA 1, CU BUS

(E)

(D) INTEGRATED

ATS/PANELBOARD

100A, 240/120V, 1Ø, 3W, 10 KAIC,

12 CIRCUIT,

NEMA 1, CU BUS

L

E N

100A 2P

70A 2P

(N) INTEGRATED

ATS/PANELBOARD

"ATS"

100A, 240/120V, 1Ø, 3W, 10 KAIC, 16 CIRCUIT,

NEMA 3R, CU BUS

L

EN

20A 1P

REFER TO FEEDER SCHEDULE KEYNOTES ON SHEET E0.4 FOR

CONDUIT AND CONDUCTOR SIZES.

FEEDER SCHEDULE KEYNOTES:

100A 2P

(LSI)

G

1 (N) GENERATOR

GENERATOR

GROUNDING BAR

70A 2P

(LSI)

G

(D) GENERATOR1

E1 E3

C1 E1E2

8GENERATOR

CONTROLLER

(MBJ)

4 G1

10 G1

9 G1

SHORE POWER

G2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .4

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

(1) 1-1/2"C - 3#1 + 1# 8 GND.

(1) 3/4"C - 2#12 + 1#12 GND.

(1) 1"C - WITH (E) CONDUCTORS. E3

E2

E1 (1) 1#6 CONTINUOUS BARE COPPER.

(1) 1"C - 1#6 CONTINUOUS BARE COPPER.

G1

G2

C1

FEEDER SCHEDULE GENERAL NOTES:

PROVIDE LOW-VOLTAGE COMMUNICATION CONDUCTORS FOR ALL FEEDER KEYNOTES DENOTING . COORDINATE WITH MANUFACTURER OF EACH PRODUCT REQUIRING LOW-VOLTAGE CONDUCTORS TO VERIFY SIZE, QUANTITY, AND INSTALLATION REQUIREMENTS.

C#

- - SUBSCRIPT "#" INDICATES THE QUANTITY OF FEEDER SCHEDULE KEYNOTES.

KEYNOTE SYMBOL CLARIFICATION

DESCRIPTIONSYMBOL

(#)- - OR

PANEL SCHEDULE

(1) 1"C - WITH CONTROL SIGNAL WIRING PER EQUIPMENT

MANUFACTURER RECOMMENDATION.

E0.4

ELECTRICAL

SCHEDULES

SA ON ON

FEEDER SCHEDULE

FEEDER SCHEDULE KEYNOTES:GENERAL NOTES:

1. PANEL SCHEDULES AND LOAD CALCULATIONS ARE PROVIDED BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF DESIGN. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING AVAILABLE SPACES, AND MAKING ADJUSTMENTS AS REQUIRED TO PROVIDE THE NEW BRANCH CIRCUITS SHOWN IN THE

SCHEDULES.

2. UPDATE ALL SCHEDULES TO REFLECT FINAL CONDITIONS. CONTRACTOR SHALL PROVIDE EXACT QUANTITIES AND SIZES OF BREAKERS TO MATCH (D)

ATS/PANELBOARD. RECONNECT (E) CONDUCTORS TO THERE ORIGINAL BREAKER SIZES.

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

F

C A D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .5

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

0 40 FEET 20

1/32" = 1'-0"

10 60

ELECTRICAL OVERALL SITE PLAN

SCALE: NE0.5

FRONTAGE ROAD

I-8 EAST KUMEYAAY HIGHWAY I-8 EAST KUMEYAAY HIGHWAY

I-8 WEST KUMEYAAY HIGHWAY

I-8 W

EST KUMEYAAY HIGHWAY

E0.5

ELECTRICAL

OVERALL SITE PLAN

SA ON ON

SEE SHEET E1.1 - ELECTRICAL DEMOLITION PLAN

SEE SHEET E2.1 - ELECTRICAL NEW WORK PLAN

CONTRACTOR

PARKING

(E) INSPECTION BOOTH

/1

13'-9"(E) 120 GAL PROPANE TANK

(E) BOLLARDS

(E) LAB BLDG.

(E) VEHICLE AND TRUCK INSPECTION CANOPY

(E) INSPECTION OFFICE

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

OHOH OH OH OH OH OH OH OH OH OH OH OH OH OH OH

C A D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .1

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

DEMOLITION KEYNOTES:

1 DISCONNECT AND DEMOLISH EQUIPMENT.

DISCONNECT AND DEMOLISH CONDUCTORS AND CONDUITS.

DISCONNECT (E) BRANCH CIRCUIT CONDUCTORS FROM

GENERATOR. PROTECT IN PLACE (E) BRANCH CIRCUIT

CONDUCTORS WITHIN PANELBOARD "D". CONDUCTORS ARE TO BE

RE-USED AND EXTENDED TO NEW EQUIPMENT. SEE NEW WORK.

DISCONNECT AND DEMOLISH FLEXIBLE PROPANE GAS LINE FROM

GENERATOR. PROTECT IN PLACE (E) PROPANE PIPE STUB UP, TO

BE RE-USED IN NEW WORK.

SAW CUT (E) ASPHALT PAVEMENT IN PREPARATION FOR NEW

CONCRETE EQUIPMENT PAD. PRIOR TO EXCAVATION, VERIFY IF

ANY (E) UNDERGROUND UTILITY AND PROPANE PIPING ARE

PRESENT. PROVIDE ALL REQUIRED PIPING, FITTINGS, AND SITE

PREPARATIONS TO RELOCATE THESE PIPES AS NEEDED TO

INSTALL NEW CONCRETE PAD. REFER TO DETAIL 1/E3.4.

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE SEQUENCE OF CONSTRUCTION TO

MINIMIZE DOWNTIME/POWER OUTAGE. CAREFULLY COORDINATE

SEQUENCE OF CONSTRUCTION WITH OWNER AS REQUIRED TO

COMPLETE THE WORK IN A TIMELY AND EFFICIENT MANNER.

CAREFULLY COORDINATE POWER SHUT-DOWN REQUIREMENTS WITH

FACILITY REPRESENTATIVES.

2. ALL (E) UNDERGROUND FEEDERS WHETHER SHOWN OR NOT ON

THIS PLAN SHALL REMAIN AND BE PROTECTED IN PLACE U.O.N.

3. CAREFULLY COORDINATE WORK WITH (E) UTILITIES. PERFORM ALL

REQUIRED SITE INVESTIGATION TO AVOID INTERFERENCE WITH

OTHER UTILITIES DURING CONSTRUCTION.

4. REPAIR ALL (E) SURFACES WHERE DAMAGE HAS OCCURRED DURING

(D) OF MATERIAL.

ELECTRICAL DEMOLITION PLAN

SCALE: NE1.1

0 6 12 INCHES 2 24

3/4" = 1'-0"

E1.1

ELECTRICAL

DEMOLITION PLAN

SA ON ON

3 4

(E) PANEL "D1"

(E) PANEL "D"

(E) LAB BLDG.

(E) INSPECTION OFFICE

MODULAR PLATFORM RAMP

(E) ASPHALT PAVEMENT

(E) ASPHALT PAVEMENT

(E) INSPECTION OFFICE MODULAR STAIRCASE

(E) ASPHALT PAVEMENT

(E) ASPHALT PAVEMENT

(E) INSPECTION OFFICE

(E) VEHICLE AND TRUCK INSPECTION CANOPY

(E) HVAC UNIT

(E) OVERHEAD CONDUITS AND CONDUCTORS

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

OHOH OH OH OH OH OH OH OH OH OH OH OH OH OH OH

A D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .1

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

NEW WORK KEYNOTES:

1 PROVIDE 20kW/25kVA OPTIONAL STANDBY PROPANE GENERATOR.

PROVIDE EMERGENCY LOCKOUT SWITCH.

PROVIDE EQUIPMENT HOUSE KEEPING POUR IN PLACE CONCRETE

PAD. REFER TO DETAILS 3/E3.1, 3/E3.2 AND 1/E3.4.

PROVIDE A SURFACE MOUNTED INTEGRATED ATS/PANELBOARD.

PROVIDE CONCRETE ENCASED ELECTRODE (UFER) SIZED AS SHOWN

ON SINGLE LINE DIAGRAM. REFER TO DETAILS 1/E3.1.

STUB UP GENERATOR FEEDER CONDUITS AND TERMINATE

CONDUCTORS AT GENERATOR CIRCUIT BREAKER TERMINALS.

STUB UP COMMUNICATION CONDUITS AND TERMINATE AT

GENERATOR CONTROLLER SECTION.

STUB UP SHORE POWER CONDUITS AND TERMINATE AT GENERATOR

ACCESSORIES DISTRIBUTION BAR.

PROVIDE CONDUITS FROM PANELBOARD "D" TO NEW INTEGRATED

ATS/PANELBOARD. EXTEND (E) CONDUCTORS TO (N) LOCATION.

TERMINATE CONDUCTORS TO THERE (E) BREAKER SIZES.

PROVIDE CONNECTION OF PROPANE LINE PIPING TO GENERATOR

FUEL INLETS. PROVIDE ALL NECESSARY MATERIAL FOR

CONNECTION AND SUPPORT OF (N) PIPES. COORDINATE WITH

EQUIPMENT MANUFACTURER FOR INSTALLATION SPECIFICATIONS,

AND CONNECTIONS.

PROVIDE NEW BOLLARD, 4"Ø CONCRETE FILLED. REFER TO DETAIL

4/E3.2.

PROVIDE UNDERGROUND CONDUITS AND TRENCH, SIZED AS SHOWN

ON FEEDER SCHEDULE. CONTRACTOR SHALL BE RESPONSIBLE FOR

PERFORMING ALL REQUIRED SITE INVESTIGATIONS AND

PREPARATIONS AS SHOWN ON DETAIL 1/E3.2.

PROVIDE EXOTHERMIC WELDING CONNECTIONS. REFER TO DETAIL

2/E3.1.

PROVIDE A MINIMUM OF (2) TWO 3/4"Ø x 10' COPPER CLAD GROUND

RODS SPACED A MINIMUM OF 6" APART. REFER TO DETAIL 4/E3.1.

PROVIDE GROUNDING TEST INSPECTION WELL. REFER TO DETAIL

4/E3.1.

PROVIDE ALL REQUIRED SUPPORT SYSTEMS, SUCH AS BRACKETS,

CLAMPS, BOLTS, GUY WIRES, PIPES, FITTINGS, COUPLINGS AND

EXPANSION FITTINGS NEEDED TO SUPPORT AND EXTEND EXHAUST

PIPE AT AN ELEVATION THAT EXCEEDS THE (E) VEHICLE AND TRUCK

INSPECTION CANOPY. OVERALL HEIGHT ELEVATION OF EXHAUST

PIPE SHALL BE FIELD VERIFIED BASED ON SELECTED EQUIPMENT

AND PER FIELD CONDITIONS. REFER TO DETAIL 1/E3.3.

GENERAL NOTES:

1. PROVIDE ALL NECESSARY EQUIPMENT TO PROPERLY TRANSPORT

(N) GENERATOR WITHOUT CAUSING DAMAGE TO GENERATOR OR

BUILDINGS. REPAIR ANY DAMAGES CAUSED DURING

TRANSPORTATION AND INSTALLATION.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING AND

COORDINATING WITH ALL EQUIPMENT MANUFACTURERS TO

IDENTIFY EXACT LOCATION OF CONDUIT TERMINATION

LOCATIONS PRIOR TO POURING EQUIPMENT CONCRETE PAD

FOUNDATIONS.

3. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT

MANUFACTURER TO OBTAIN SHOP DRAWINGS FOR COMPLETE

PACKAGE AND ADJUST CONDUIT STUB-UP LOCATIONS AS NEEDED

PRIOR TO STARTING WORK.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL

REQUIRED MATERIAL AND HARDWARE TO SECURELY FASTEN ALL

ENCLOSURES, EQUIPMENT, AND CONDUITS.

5. ALL NEW EQUIPMENT SHALL BE CAPABLE OF WITHSTANDING THE

MAXIMUM AMBIENT TEMPERATURE OF 125°F.

E2.1

ELECTRICAL NEW

WORK PLAN

SA ON ON

ELECTRICAL NEW WORK PLAN

SCALE: NE2.1

0 6 12 INCHES 2 24

3/4" = 1'-0"

REFER TO FEEDER SCHEDULE KEYNOTES ON SHEET E0.4 FOR

CONDUIT AND CONDUCTOR SIZES.

FEEDER SCHEDULE KEYNOTES:

(E) PANEL "D1"

(E) PANEL "D"

E1 E3

C1

E1

E2

3'-10"

(E) LAB BLDG.

(E) INSPECTION OFFICE

MODULAR PLATFORM RAMP

(E) ASPHALT PAVEMENT

(E) ASPHALT PAVEMENT

(E) INSPECTION OFFICE MODULAR STAIRCASE

(E) ASPHALT PAVEMENT

(E) ASPHALT PAVEMENT

(E) INSPECTION OFFICE

(E) VEHICLE AND TRUCK

INSPECTION CANOPY

(E) HVAC UNIT

(E) OVERHEAD CONDUITS

AND CONDUCTORS

MECHANICAL CONNECTION

TO GROUNDING BUS BAR

G1

G1

3'-10" 3'-10" 6'-10"1

/8

/1

/8

/4 " 3

1'-5" 4'-4" 4'-4" 8'-3"

6'-0"

/1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/21/26

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

D

F ile

L \2

-1

G e n e ra to r R e p la c e m e n t, C

D F A W in te rh a v e n \C

A D

\2 E .1

.d w g

P lo t D a te

N o v

:2 tt e d b y O rl a n d o N a je ra

V1

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s R e a l E s ta te S e rv ic e s D iv is io n

JCCA#: 25690-1

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

INSPECTION STATION

WINTERHAVEN FOOD AND AGRICULTURAL

GENERATOR

REPLACEMENT

3510 I-8, WINTERHAVEN, CALIFORNIA 92283

03-E00486 25-S-3919-C-DR

AS SHOWN

000000000013525

DATE SIGNED: 11/18/2025

EXOTHERMIC WELDING TYPICAL DETAIL

E3.1

NO SCALE

E3.1

ELECTRICAL

GROUNDING DETAILS

SA ON ON

E3.1

NO SCALE

REINFORCEMENT BAR DETAILS

E3.1

NO SCALE

GENERATOR GROUNDING UFER DETAIL

E3.1

NO SCALE

1. INSTALL 25' MIN. OF (1) STRANDED B.C. CONDUCTOR SIZED AS SHOWN ON SINGLE LINE DIAGRAM, 20' MIN.

ENCASED WITHIN CONCRETE, MAINTAIN 2" MINIMUM SPACING FROM EDGES EXCEPT WHEN (E) CONCRETE

THROUGH SLEEVE.

2. SECURE B.C. CONDUCTOR TO…