Attachment 2 Statement of Work 1232SA26Q0144.pdf
PDF 176 KB Posted
- Attached to
- Steam Valve Repair - Madison WI
- Solicitation number
- 1232SA26Q0144
About this file
Summary
This is a Statement of Work issued by the US Department of Agriculture (USDA) for the repair, rebuild, and replacement of medium to low pressure steam control reducing valves at the Dairy Forage Research Center in Madison, Wisconsin. The facility, a 3-story research building established in 1978-1979, operates two reducing valves (1/3 and 2/3) that reduce steam pressure to 10 PSI for hot water and heating systems. One valve recently malfunctioned by failing to close completely, allowing pressure to reach 20 PSI and triggering the system's safety relief valve. Given the valves' age of 30+ years, the USDA seeks a qualified contractor to inspect, rebuild, and/or replace these valves as necessary.
The contractor must demonstrate full expertise in medium to low pressure reducing steam valves, including installation, troubleshooting, and repair procedures. Work must be performed sequentially on one valve at a time to maintain uninterrupted steam service to the facility. Required tasks include removing and replacing faulty valves, installing rebuilt or new units, and testing for proper operation. All work must comply with applicable laws and regulations. The contractor shall schedule visits in advance by contacting the Building Maintenance Mechanic at (608) 287-6843 and must provide a detailed service report upon completion. The government will provide facility access at 1925 Linden Drive, Madison, WI 53706, and the service provider will be escorted while on-site with limited parking available. No travel is required, key personnel designation is not applicable, and data rights and Section 508 accessibility standards do not apply.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Department of Agriculture (USDA)
Statement of Work
Steam Pressure Reducing Valve Repair/Rebuild/Replace
January 22, 2026
Contents
Project
General Information
1.0 Scope of Work
2.0 Background
Contractor Requirements
3.0 Technical Requirements / Tasks
4.0 Government Furnished
5.0 Deliverables / Schedule
6.0 Travel
7.0 Contractor’s Key Personnel
8.0 Security Requirements
9.0 Parking
10.0 Data Rights
11.0 Section 508 – Electronic and Information Technology Standards
Attachment
Project
The Director of the USDA ARS -Dairy Forage Research Center seeks a qualified vendor to overhaul and rebuild the
Medium to Low Pressure Steam Control Valves 1/3 and 2/3 valves for the Dairy Forage Research Center located at
1925 Linden Drive, Madison, WI 53706.
General Information
1.0 Scope of Work
The Dairy Forage Research Center seeks a qualified Contractor to conduct repairs on the Medium to Low Pressure Steam
Control Valves 1/3rd and 2/3 rd valves. These reducing valves reduce steam pressure to 10psi. for use by the hot water and heating systems for the DFRC Building. On at least one occasion the valve pressure approached 20 PSI causing the system relief valve to activate. It is believed that these valves are original to the facility requests. Construction was completed towards the end of 1978/79. The facility requests that contractors verify to look at and rebuild or replace the existing reduced valves.
2.0 Background
The USDA Dairy Forage Research Center is a 3-story research facility that studies forage and other aspects of the dairy
Industry. The 2/3rd reducing valve on at least one occasion failed to close all the way and allowed the steam pressure to climb to 20 PSIG causing the safety relief valve to activate causing a loud hammer noise and shocking the system. Our facility workers were able to isolate the 2/3 rd valve and run the system running off the 1/3 rd valve. The facility worked later opened the valve and the system has been working properly. This failure brings to the forefront that these valves are
30 + years old and need to be inspected, rebuilt and or replaced as necessary.
Contractor Requirements
3.0 Technical Requirements / Tasks
Key Requirements:
Contractors must be fully familiar with medium to low pressure reducing steam valves, including all aspects of installation, troubleshooting and repair. Work on valves must be one at a time to allow steam pressure to the facility to remain uninterrupted. All work shall be completed in accordance with all applicable laws and regulations
Vendor shall be capable of performing the following actions:
Overhaul and repair Low pressure steam control valve or replace.
1. Remove and replace faulty low pressure steam control valve
2. Install a rebuilt or new low pressure steam control valve
3. Test for proper operation.
4.0 Government Furnished
The government will provide access to the USDA Dairy Forage Research Facility located at 1925 Linden Drive , Madison
WI 53706 for service.
5.0 Deliverables / Schedule
Visits to the US Dairy Forage Research Center shall be scheduled in advanced by contacting the Building Maintenance
Mechanic at (608) 287-6843
Upon completion of the repairs a detailed service report shall be provided to the Facility outlining what actions occurred
6.0 Travel
• N/A
7.0 Contractor’s Key Personnel
• Not Applicable
8.0 Security Requirements
• Service Provider will be escorted while on the facility
9.0 Parking
• Limited parking is available on Site
10.0 Data Rights
11.0 Section 508 – Electronic and Information Technology Standards
Attachment
• None