This document is a Minimum Salient Characteristics specification for an EMCS Mainframe Upgrade (Contract Project #1142758) outlining detailed hardware and software requirements. The hardware specifications include one hardened PC desktop computer with 32 GB RAM, Quad Port Network Interface Card, RAID 5 stack, multiple SSDs, and a monitor; 15 Niagara 9000 compatible controllers supporting BacNet IP with specific technical requirements; and one uninterruptible power supply unit. Software requirements encompass Niagara 4 Supervisor version 4.14 or newer, Microsoft Windows 2022 Server License, Microsoft SQL 2022 Server License, Niagara Unlimited Devices License - Enterprise Package, and 3-year service maintenance agreements for controllers and Niagara systems. All hardware and software purchases must comply with the Trade Agreements Act (TAA), and the controllers must be without Wi-Fi capability.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MINIMUM SALIENT CHARACTERISTICS

FOR

EMCS MAINFRAME UPGRADE

CP#1142758

All hardware and software purchases must comply with Trade Agreements Act (TAA).

Hardware:

1. Hardened PC Desktop Computer (1 Each)

32 GB RAM

Quad Port Network Interface Card Raid 5 Stack Arrangement 3 x 1TB SSD 3 x Additional 1TB SSD Keyboard & Mouse Monitor with minimum 1920x1080 Resolution

2. Niagara 9000 Compatible Controllers (15 Each) Must support Bac Net IP Individual controllers must support a minimum of 10 devices & 500 points Must be compatible with Niagara 4 supervisor version 4.14 or newer Without Wi-Fi capability

3. Uninterruptible Power Supply Unit (1 Each) Minimum 450 Watts Software:

1. (Brand Name) Niagara 4 Supervisor version 4.14 or newer

2. Microsoft Windows 2022 Server License or newer

3. Microsoft SQL 2022 Server License or newer

4. Niagara Unlimited Devices License - Enterprise Package

5. 3-year Service Maintenance Agreement for all 15 each controllers

6. 3-year Service Maintenance Agreement for Unlimited Niagara