Attachment 2 - Salient Characteristics.pdf

PDF 871 KB Posted

Attached to
Transformers Federal contract opportunity
Solicitation number
FA460825QC067
Issued by
Department of the Air Force Global Strike Command

About this file

Attachment 2 is a detailed specification document outlining salient characteristics for transformers to be procured by the Department of the Air Force Global Strike Command. The document specifies 20 key design requirements for transformers, including electrical specifications such as 12,470V Delta primary voltage, 95 kV BIL, copper windings, 30 kV BIL secondary voltage, and specific configuration details like tap settings, bushing types, and cooling class. Notable exceptions are noted for 150 kVA and 750 kVA transformer models, including allowable fluid types and bushing configurations.

Additional technical specifications cover frequency (60 Hz), temperature rise (65C), conductor material (Al/Al), tank material (mild steel), and physical attributes like liquid level gauge, dial thermometer, pressure vacuum gauge, and Schrader valve. The transformers must be painted Barksdale Brown with a black polymer undercoat and be UL Listed. This specification document is part of solicitation FA460825QC067, which is a small business set-aside for transformer procurement, with quotes due by 06 May 2025 at 1:30 PM CDT.

View the file

Other files for this federal contract opportunity

Other files attached to Transformers, newest first.
File Type Posted
Amendment 02 - QA.pdf PDF
Amendment 01 - QA.pdf PDF
Attachment 1 - Provisions and Clauses.pdf PDF
Attachment 3 - Equipment List.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics for Requested Transformers

The following minimum requirements pertain to all transformers.

Part 1 – Design

1.1 DESIGN REQUIREMENTS

1. All transformers are 12,470V Delta, 95 kV BIL primary.

2. All transformers must have copper windings

3. All transformers are 30 kV BIL secondary.

4. Taps: 2 above, 2 below @ 2.5%

5. HV bushings: (6) 15kV 200A Wells & Inserts (dead front loop feed)

6. LV bushings: (4) 4 hole spades

a. Exception is the 750 kVA: (4) 6 hole spades

7. Fluid: Mineral Oil

a. Exception is the 150 kVA: FR3 is allowable.

8. Frequency: 60 Hz

9. Temperature Rise: 65C

10. Cooling Class: ONAN

a. Exception is the 150 kVA: KNAN

11. Conductor: Al / Al

12. Tank Material: Mild Steel

13. Cabinet depth: standard

14. Liquid Level Guage

15. Dial type thermometer

16. Pressure Vacuum Guage

17. Schrader Valve

18. Pressure Relief Valve

19. Paint: Barksdale Brown (Federal FS 20117) w/ Black Polymer

Undercoat

20. UL Listed

FA460825QC067

Attachment 2