Attachment 2 OandM manual.pdf
PDF 11 MB Posted
- Solicitation number
- 19UK5626Q0018
- Issued by
-
Department of State US Embassy London
About this file
This is an Operations and Maintenance Manual for the Liebert CW Precision Cooling Unit (26-400 kW capacity), a chilled water-based computer room air conditioning system available in both upflow and downflow configurations for 50/60Hz operation. The manual provides comprehensive technical documentation for installation, operation, and maintenance of these units, which are designed for business-critical data center cooling applications.
The manual covers pre-installation guidelines including room preparation, location considerations, and clearance requirements; detailed dimensional specifications and shipping weights for all model variants (CW026 through CW400) with both EC motorized fans and centrifugal fan options; equipment handling procedures for unpacking and positioning units using forklifts, piano jacks, or rigging equipment; installation of EC fan assemblies and plenums for upflow configurations; electrical connections and three-phase service requirements with specific diagrams for various model types; piping systems including gravity drains and optional condensate pumps with specified flow rates and pressure requirements; initial startup and commissioning procedures; and comprehensive maintenance schedules covering filters, fan impellers, bearings, humidifiers, condensate systems, and facility fluid maintenance. The documentation emphasizes critical safety warnings regarding electrical hazards, moving parts, top-heavy unit risks, and water damage prevention, and includes detailed troubleshooting tables for blower systems, chilled water circuits, and humidification equipment. Operating conditions specify maximum dew points of 59°F (15°C) and minimum return air temperatures of 68°F (20°C) per ASHRAE recommendations for proper data center equipment reliability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SF 18 - 19UK5626Q0018.docx | DOCX document | |
| PMSC SOW CRAC - 19UK5626Q0018.pdf | ||
| Overseas FAR Clauses Commercial Feb 2026 Deviation.pdf | ||
| Attachement 1 Data Sheet.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Precision Cooling For Business-Critical Continuity™
Liebert® CW™
User Manual–26-400 kW, Upflow and Downflow, 50/60Hz i
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
1.0 LIEBERT CW NOMENCLATURE
2.0 PRE-INSTALLATION GUIDELINES
2.1 Room Preparation
2.2 Location Considerations
2.3 Installing Liebert CW300 and Liebert CW400 Units
2.4 Air Distribution—Downflow Units
2.5 Air Distribution—Upflow Units
2.6 Connections and System Setup
2.7 Operating Conditions
2.7.1 Cooling, Humidification and Dehumidification
2.7.2 Heating
3.0 LIEBERT CW DIMENSIONS AND WEIGHTS
3.1 Dimensions—Downflow Models with EC Fans
3.2 Dimensions—Upflow Models with EC Fans
3.3 Dimensions—Downflow Models With Centrifugal Fans
3.4 Dimensions—Upflow Models With Centrifugal Fans
3.5 Floor Stand Dimensions
3.6 Plenum Dimensions
4.0 EQUIPMENT INSPECTION AND HANDLING
4.1 Packaging Material—All Models
SAFETY INFORMATION
4.2 Unpacking the Unit
4.2.1 Removing the Unit from the Skid With a Forklift
4.2.2 Moving the Unit to the Installation Location with Piano Jacks
4.2.3 Removing Piano Jacks
4.2.4 Removing Liebert CW from Skid Using Rigging
5.0 EC FANS
5.1 Lowering and Removing EC Fans—Downflow Units Only
5.1.1 Lowering the EC Fans into the Floor Stand
5.1.2 EC Fan Block-Off Panel Kit—Optional
5.1.3 Removing EC Fans—Downflow Units Only
5.2 Installing Upflow EC Fan Plenums
5.2.1 Liebert CW Upflow Plenum Assembly Parts
5.2.2 Upflow Plenum and EC Fan Preparation
6.0 ELECTRICAL CONNECTIONS
6.1 Electrical Connections
ii
7.0 PIPING
7.1 Fluid Connections
7.1.1 Condensate Piping—Field-Installed
7.1.2 Humidifier Supply Water—Optional Infrared
7.1.3 Humidifier Supply Water—Optional Steam Generating Humidifier
7.2 Chilled Water Piping
7.2.1 Requirements of Systems Using Water or Glycol
8.0 PIPING SCHEMATICS
9.0 CHECKLIST FOR COMPLETED INSTALLATION
9.1 Moving and Placing Equipment
9.2 Electrical
9.3 Piping
9.4 Other
10.0 INITIAL STARTUP CHECKS AND COMMISSIONING PROCEDURE FOR WARRANTY
INSPECTION
10.1 Information for Warranty Inspection—Remove Power From Unit Disconnect
10.2 Startup Checks With Panels Removed and Main Disconnect Off
10.2.1 Inspect and Record
10.3 Startup
10.4 Additional Considerations for Upflow Units
11.0 TROUBLESHOOTING
12.0 MAINTENANCE
12.1 System Testing
12.1.1 Environmental Control Functions
12.1.2 Electric Panel
12.2 Filters
12.3 Blower Package—Centrifugal Fans
12.3.1 Fan Impellers and Bearings
12.3.2 Belts—Except with EC Fans
12.3.3 Electronic Variable Speed Drive (Inverter)
12.4 Blower Package—EC Fans
12.4.1 Fan Impellers and Bearings
12.4.2 Protective Features
12.5 Humidifier
12.5.1 Infrared Humidifier
12.5.2 Cleaning Humidifier Pan and Float Switch
12.5.3 Changing Humidifier Lamps
12.6 Steam Generating Humidifier
12.7 Condensate Drain and Condensate Pump Systems
12.7.1 Condensate Drain
12.7.2 Condensate Pump
12.8 Facility Fluid and Piping Maintenance
iii
12.9 HVAC Maintenance Checklist
APPENDIX A - INSTALLING LIEBERT CW300 AND LIEBERT CW400
COMPLIANCE WITH EUROPEAN UNION DIRECTIVES. . . . . . . . . . . . . . . . . . . . . . INSIDE BACK COVER
FIGURES
Figure 1 Downflow unit ducting and plenum ducting Figure 2 Upflow ducting configurations with centrifugal fans Figure 3 Plenum ducting arrangement—Upflow models with EC fans Figure 4 Cabinet and floor planning dimensions, downflow models CW026 - CW084 with EC fans Figure 5 Cabinet and floor planning dimensions, CW026, CW038 and CW041, downflow with EC fans, front discharge Figure 6 Cabinet and floor planning dimensions, CW051, CW060, CW076 and CW084, downflow with EC fans, front discharge Figure 7 Cabinet and floor planning dimensions, downflow models CW106 and CW114 with EC fans Figure 8 Cabinet and floor planning dimensions for downflow models CW089, CW106 and CW114 with EC fans Figure 9 Cabinet and floor planning dimensions, CW146 - CW181, downflow with EC fans, front discharge Figure 10 Cabinet and floor planning dimensions for downflow models CW146 and CW181 with
EC fans Figure 11 Dimensions and floor planning data downflow models CW300, CW400 with EC fans and filter plenums Figure 12 Cabinet and floor planning dimensions, upflow models CW026-CW084 with EC fans, front air return Figure 13 Cabinet and floor planning dimensions, upflow models CW026 - CW084 with EC fans, bottom air return Figure 14 Cabinet and floor planning dimensions, upflow models CW106, CW114 with EC fans, front return Figure 15 Cabinet and floor planning dimensions, upflow models CW106, CW114 with EC fans, rear return Figure 16 Cabinet and floor planning dimensions, downflow models CW106 and CW114 with centrifugal fans Figure 17 Cabinet and floor planning dimensions, upflow models CW026-CW084 with centrifugal fans Figure 18 Cabinet and floor planning dimensions upflow models, CW106 and CW114 with centrifugal fans Figure 19 Floor stand and floor planning dimensions, downflow models CW026 - CW041 with EC fans Figure 20 Floor stand and floor planning dimensions, downflow models CW076 and CW084 with
EC fans Figure 21 Floor stand and floor planning dimensions, downflow models CW089, CW106 and
CW114 with EC fans Figure 22 Floor stand and floor planning dimensions, downflow models CW146 and CW181 with
EC fans Figure 23 Floor stand and floor planning dimensions—Downflow CW300 AND CW400 with EC fans Figure 24 Floor stand dimensions, optional steam, hot water reheat and humidifier piping entrances for downflow models CW026 - CW84 with centrifugal fans Figure 25 Floor stand dimensions for downflow models CW106 and CW114 with centrifugal fans Figure 26 Plenum dimension, CW026 - CW084 upflow plenums with EC fans iv
Figure 27 Plenum dimensions for upflow models CW026 - CW084 with centrifugal fans Figure 28 Plenum dimensions for upflow models CW106 and CW114 with centrifugal fans Figure 29 Plenum dimensions CW106, CW114 upflow plenums with EC fans Figure 30 Filter plenum dimensions, downflow models CW146 and CW181 with EC fans Figure 31 Equipment recommended for handling the Liebert CW Figure 32 Removing packaging Figure 33 Remove the unit from the skid Figure 34 Moving the unit to its installation location Figure 35 Locate center of gravity marker and place slings Figure 36 Using rigging to lift Liebert CW off skid—Models CW026-CW181 Figure 37 EC fan lowering procedure Figure 38 EC fan block-off panel kit- add data from DPN002037 need to add operation in up position . . . 44 Figure 39 EC fan lowering and removal procedure Figure 40 Non-grilled plenum—122" (3099mm) unit length Figure 41 Grilled plenum, front discharge—122" (3099mm) unit length Figure 42 Grilled plenum, rear discharge—122" (3099mm) unit length Figure 43 Non-grilled plenum—99" (2515mm) unit length Figure 44 Grilled plenum, front discharge—99" (2515mm) unit length Figure 45 Grilled plenum, rear discharge—99" (2515mm) unit length Figure 46 Non-grilled plenum—50", 74" (1270mm, 1880mm) unit length Figure 47 Grilled plenum, front discharge—50", 74" (1270mm, 1880mm) unit length Figure 48 Grilled plenum, rear discharge—50", 74" (1270mm, 1880mm) unit length Figure 49 EC fan assembly Figure 50 Recommended tools for installing the upflow plenum and EC fan Figure 51 Non-grilled plenum / Grilled plenum-front discharge Figure 52 Grilled plenum-rear discharge Figure 53 Plenum placement on top of Liebert CW unit Figure 54 EC fan assembly alignment for placement on top of Liebert CW unit Figure 55 EC fan assembly placement and attachment on top of Liebert CW unit Figure 56 EC fan wire routing Figure 57 Junction box connection (fan 1 and 2 for units with 2 or 3 fans) Figure 58 Junction box connection (Fan 3 for units with three fans / Fan 1 for single-fan units) Figure 59 Front frame members for non-grilled and grilled rear-discharge plenum Figure 60 Grilled front-discharge plenum grille attachment Figure 61 Non-grilled and grilled rear-discharge plenum front panel attachment Figure 62 Grilled plenum front / rear-discharge top panel attachment Figure 63 Electrical field connections for downflow models CW026 - CW084 Figure 64 Electrical field connections (Ethernet) for downflow models CW026 - CW084 Figure 65 Electrical field connections for downflow models CW089, CW106 and CW114 Figure 66 Electrical field connections (Ethernet) for downflow models CW089, CW106 and CW114 Figure 67 Electrical field connections (high voltage) for upflow models CW026 - CW084 Figure 68 Electrical field connections (low voltage) for upflow models CW026 - CW084 Figure 69 Electrical field connections (Ethernet) for upflow models CW026 - CW084 Figure 70 Electrical field connections (Ethernet) for upflow models CW106 and CW114 Figure 71 Electrical field connections (low voltage) for upflow models CW106 and CW114 Figure 72 Electrical field connections (low voltage Ethernet) upflow models CW106 and CW114 Figure 73 Electrical field connections for downflow models CW146 and CW181 with EC fans Figure 74 Gravity drain for downflow and upflow units Figure 75 Downflow general arrangement, CW026-CW114 Figure 76 Downflow general arrangement, CW181-CW146 v
Figure 77 Primary connection locations, downflow models CW026 - CW041 with EC fans Figure 78 Primary connection locations, downflow models CW051 and CW060 with EC fans Figure 79 Primary connection locations, downflow models CW076 - CW084 with EC fans Figure 80 Primary connection locations, downflow models CW089, CW106 and CW114 with EC fans . . . 91 Figure 81 Primary connection locations, downflow models CW146 and CW181 with EC fans Figure 82 Primary connection locations, downflow units, model CW300 and CW400 with EC fans Figure 83 Piping connections, downflow models CW026 - CW084 with centrifugal fans Figure 84 Piping connections for downflow models CW106 and CW114 with centrifugal fans Figure 85 Upflow general arrangement Figure 86 Piping connections for upflow models CW026 - CW084 Figure 87 Piping connections for upflow models CW106 and CW114 Figure 88 Correct orientation of float switch Figure 89 Infrared humidifier lamps Figure 90 Steam generating humidifier Figure 91 Run/drain switch Figure 92 Steam generating humidifier control board Figure 93 Rear floor stand and rear unit mounted on floor stand Figure 94 Rear floor stand jack Figure 95 Floor stand bolt locations Figure 96 Module bolt locations Figure 97 Fan deck bolt locations Figure 98 Wire harness routing point Figure 99 Wire harness junction box detail
TABLES
Table 1 Shipping dimensions Table 2 Shipping weights Table 3 Liebert CW upflow plenum with EC fan assembly(s) configurations Table 4 Key to Liebert CW Upflow plenum assembly parts Table 5 Liebert CW Upflow EC fan assembly weight Table 6 Maximum harmonic current distortion, IEEE-519-1992 Table 7 Typical TDD for CW106, CW114 and CW146 at 460V Table 8 Typical TDD for CW181 at 460V Table 9 Blower troubleshooting Table 10 Chilled water troubleshooting Table 11 Humidifier—steam generator troubleshooting Table 12 Humidifier—infrared troubleshooting Table 13 Reheat troubleshooting Table 14 Humidifier canister part numbers Table 15 Faults—canister generator humidifier Table 16 Steam generating humidifier capacity Table 17 DIP switch settings for steam generating humidifier Table 18 Liebert CW300 and Liebert CW400 component parts and weights Table 19 Table 2 - Liebert CW300 and Liebert CW400 Assembly Parts vi
1 Liebert® CW™
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert CW. Read this manual thoroughly before attempting to install or operate this unit.
Only properly trained and qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
! WARNING
Arc flash and electric shock hazard. Disconnect all electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
! WARNING
Risk of high-speed moving parts. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit.
Do not operate this unit with any or all cabinet panels removed.
Do not operate upflow units without installing a plenum, ductwork or guard over the blower opening(s) on the top surface of the unit cabinet.
Ductwork must be connected to the blower(s), or a plenum must be installed on the blower deck for protection from rotating blower wheel(s) on upflow units.
! WARNING
Risk of top-heavy unit falling over. Can cause equipment damage, injury or death.
Read all of the following instructions before attempting to move the unit, lift it, remove packaging or prepare the unit for installation.
! CAUTION
Risk of contact with hot surfaces. Can cause injury.
The humidifiers and reheats are extremely hot during unit operation. Allow sufficient time for them to cool before working within the unit cabinet. Use extreme caution and wear protective gloves and arm protection when working on or near hot discharge lines, humidifiers and reheats.
! CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move the unit, lift it, remove packaging or prepare the unit for installation.
Liebert® CW™ 2
NOTICE
Risk of clogged or leaking drain lines. Can cause equipment and building damage.
This unit requires a water drain connection. Drain lines must be inspected regularly and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
Emerson recommends installing leak detection equipment for unit and supply lines.
NOTICE
Risk of a leaking coil due to freezing and/or corrosion. Can cause equipment and serious building damage.
Cooling coils and piping systems that are connected to open cooling towers or other open water/glycol systems are at high risk for freezing and premature corrosion. Fluids in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil corrosion. The water or water/glycol solution must be analyzed by a competent water treatment specialist before startup to establish the inhibitor requirement. The water or water/glycol solution must be analyzed every six months to determine the pattern of inhibitor depletion. The complexity of water-caused problems and their correction makes it important to obtain the advice of a water treatment specialist and follow a regularly scheduled maintenance program.
NOTICE
Risk of overhead interference. Can cause unit and/or building damage.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans to verify clearances prior to moving the unit.
NOTICE
Risk of damage from forklift. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert CW upright, indoors and protected from dampness, freezing temperatures and contact damage.
Liebert CW Nomenclature
3 Liebert® CW™
1.0 LIEBERT CW NOMENCLATURE
CW
CW = Liebert CW Floor Mount Chilled Water Unit
026 D C S A 2 1234 A
Nominal Capacity, kW
D = Downflow U = Upflow
C = Chilled Water
S = Centrifugal Fan with Standard Motor
V = Centrifugal Fan with Variable Speed Drive
1 = EC Motorized Impeller H = EC Motorized Impeller with THD
2 = 2-Way Valve, Standard Pressure 3 = 3-Way Valve, Standard Pressure 1 = 2-Way Valve, High Pressure T = 3-Way Valve, High Pressure
A-Z = Standard configuration
S = SFA
A = 460/3/60 B = 575/3/60 C = 208/3/60 D = 230/3/60 2 = 380/3/60 F = 380/3/50 G = 415/3/50 M = 380-415/3/50
XXXX
Pre-Installation Guidelines
Liebert® CW™ 4
2.0 PRE-INSTALLATION GUIDELINES
2.1 Room Preparation
• Verify that the floor is level, solid and sufficient to support the unit. See Table 2 for unit weights.
• Confirm that the room is properly insulated and has a sealed vapor barrier.
• For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of total air circulated in the room).
• Do not install Liebert CW units in an alcove or at the end of a long, narrow room.
• Install the units as close as possible to the largest heat load.
• Allow at least the minimum recommended clearances for maintenance and service. See
Figures 4 through 30 for dimensions.
• Emerson recommends installing an under-floor water detection system. Contact your local Emer-son representative for information.
2.2 Location Considerations
For a downflow unit, the unit can sit on an accessible, elevated flooring system. It may be necessary to furnish additional pedestal support below the unit to ensure maximum structural support. A separate floor stand for the unit may be used as support, independent of the elevated floor and installed prior to the flooring system.
For downflow and upflow units, provide approximately 34" (864mm) service clearance on the left, right and in front of the unit whenever possible. The minimum space required for service is 18" (457mm) on the left end, 18" (457mm) on the right end and 24" (610mm) in front of the unit. This space is necessary to permit routine maintenance, such as replacing filters and adjusting the fan speed. On downflow units and upflow CW106 and CW114 models, left- and right-end minimum clearances are 0" (0 mm), with the exception of rear return.
Avoid installing units in an alcove or at the extreme end of a room that has a high aspect ratio (long narrow room). Also avoid installing units too close together. This tends to reduce the effectiveness of the air distribution as compared to units located 30-40 feet (9-12m) apart.
2.3 Installing Liebert CW300 and Liebert CW400 Units
Installing Liebert CW300 and Liebert CW400 differ from methods to install other Liebert CW units;
for details, refer to Appendix A - Installing Liebert CW300 and Liebert CW400.
2.4 Air Distribution—Downflow Units
• Verify that the raised floor has been properly sized for the unit’s airflow and the room is free of airflow restrictions.
• Perforated floor tiles in the raised floor should ensure minimal pressure loss.
• The raised floor must provide 7-1/2" (191mm) of clearance.
• Ensure that there is adequate clearance above the unit for service, such as replacing filters.
• Optional plenums are available for downflow unit ducting.
• If installing units with electrically commutated fans (EC fans), there must be 24" minimum clear-ance below the unit to lower the fans. Fans may also remain the in unit if desired.
• A filter plenum is required for Liebert CW146 and CW181 units.
NOTE
The floor stand used with EC units is not symmetrical and its orientation to the Liebert CW is critical to lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
5 Liebert® CW™
Figure 1 Downflow unit ducting and plenum ducting
Provided Service Access Door for filter replacement
Optional Liebert Plenum
Field-Fabricated Ductwork
Field-Fabricated Ductwork
DIRECT UNIT DUCTING
PLENUM DUCTING
Field Service Access for filter replacement (minimum height of 12" [305mm]; minimum distance from unit, 2" [51mm])
Liebert® CW™ 6
2.5 Air Distribution—Upflow Units
Various configurations are available:
• Front return
• Rear return
• Bottom return (not available on CW106 and CW114 models)
For in-room applications with supply and return grilles, several feet of clearance must be maintained at the intake and discharge of the unit. For a bottom return, at least 6-8 inches of unrestricted under-floor height is needed.
Upflow rear-return configurations use a filter box attached to the back of the Liebert CW. Allow 25" (635 mm) on one side of the unit for access to the rear return filter box. Refer to the filter box installation sheet, which can be found inside the rear return filter box package.
For ducted applications, duct flanges are supplied on the blower outlets. Follow the SMACNA-Duct Construction Standard for single-, dual-, or triple-blower systems. Do not run ductwork off the perimeter flange on the top of the unit. This flange is for positioning and attaching the optional air discharge plenum with grille. Attaching a duct to this flange may reduce airflow to inadequate levels.
Figure 2 Upflow ducting configurations with centrifugal fans
! WARNING
Risk of high-speed moving parts. Can cause injury or death. Disconnect all local and remote electric power supplies and make sure blowers and pulleys have stopped rotating before working in the unit.
Do not operate upflow units without installing a plenum, ductwork or guard over the blower opening(s) on the top surface of the unit cabinet.
Ductwork must be connected to the blower(s), or a plenum must be installed on the blower deck for protection from rotating blower wheel(s) on upflow units.
NOTE
Drain traps are qualified to a return duct static of negative 1.5 i.w.g. (-1.5 i.w.g).
DPN001156
Rev. 0* Follow standard practices on all duct work.
Straight section of duct off of unit to be 1.5 to 2.5 times the longest blower dimension.
Typical ducting shown; ducting may run to either side.
7 Liebert® CW™
Figure 3 Plenum ducting arrangement—Upflow models with EC fans
2.6 Connections and System Setup
• Plan the routing of wiring, piping and ductwork to the unit. See Figures 63 through 73 and
Figures 75 through 87 for unit connection locations.
• The unit requires a drain, which must comply with all applicable codes. This drain line may con-tain boiling water. See 7.1.1 - Condensate Piping—Field-Installed for details.
• Three-phase electrical service is required for all models. Electrical service must conform to national and local electrical codes. See the equipment nameplate for details.
• If seismic requirements apply, consult your local Emerson representative for information about a seismic-rated floor stand.
2.7 Operating Conditions
2.7.1 Cooling, Humidification and Dehumidification
The Liebert CW must be operated in a conditioned space within the operating envelope ASHRAE recommends for data centers: Maximum dew point of 59°F (15°C).
Operating outside this envelope can decrease equipment reliability.
Return air to the Liebert CW must be no cooler than the ASHRAE recommendation of 68°F (20°C) DB and 40% RH or minimum WB of 54°F (12.2°C) for proper unit operation.
Operating below this can decrease equipment reliability.
Refer to ASHRAE’s publication, “Thermal Guidelines for Data Processing Environments.”
2.7.2 Heating
The Liebert CW is qualified for heating-only operation at temperatures not exceeding 80°F (27°C).
Follow standard practices in all duct work.
Typical ducting shown may run either direction.
Ducting attached to provided plenum flanges only.
DPN002390
Rev. 0
Liebert CW Dimensions and Weights
Liebert® CW™ 8
3.0 LIEBERT CW DIMENSIONS AND WEIGHTS
Table 1 Shipping dimensions
Model Domestic Packed
in. (mm) Export Packed
in. (mm)
026, 028, 031 55x40x76
(1400x1020x1930) 58x41x82
(1470x1040x2080)
051, 060 77x40x76 (1960x1020x1930)
80x41x82 (2030x1040x2080)
076, 084 102x40x76 (2590x1020x1930)
105x41x82 (2670x1040x2080)
089, 106, 114 125x40x80
(3180x1020x2030) 128x41x82
(3250x1040x2080)
146, 181 125x53x80 (3180x1350x2030)
128x54x82 (3250x1370x2080)
300, 400* 125x53x80 (3180x1350x2030)
128x54x82 (3250x1370x2080)
1. Models CW300 and CW400 ship in two separate sections, each the size shown.
Table 2 Shipping weights
Model
Domestic Packaging
lb. (kg)
Export Packaging
lb. (kg)
026 805 (365) 1030 (467)
038 840 (381) 1065 (483)
041 890 (404) 1115 (506)
051 1135 (515) 1360 (617)
060 1200 (544) 1425 (646)
076 1380 (625) 1630 (739)
084 1480 (671) 1730 (785)
089 1800 (817) 2075 (942)
106 1950 (885) 2225 (1,009)
114 2090 (949) 2365 (1,073)
146 2900 (1,314) 3200 (1,450)
181 2900 (1,314) 3200 (1,450)
300 * 5800 (2,628) 6400 (2,900)
400 * 5800 (2,628) 6400 (2,900)
* Models CW300 and CW400 ship in two separate sections, each weighing half of the amount shown.
9 Liebert® CW™
3.1 Dimensions—Downflow Models with EC Fans
Figure 4 Cabinet and floor planning dimensions, downflow models CW026 - CW084 with EC fans
Model
Dimensions, inches (mm) Net Weight lb (kg)A B C D E F G
H (FC Only) J K
L (EC Only)
M (EC Only)
CW026 50
(1270)
(1168)
(889)
(813)
(1219)
(883)
(203)
(940)
35-5/8 (905)
(787)
(711)
2-7/8 (73)
(345)
CW038
(1270)
(1168)
(889)
(813)
(1219)
(883)
(203)
(940) 35-5/8 (905)
(787)
(711)
2-7/8 (73)
(361)
CW041 50
(1270)
(1168)
(889)
(813)
(1219)
(883)
(203)
(940)
35-5/8 (905)
(787)
(711)
2-7/8 (73)
(388)
CW051 74
(1880)
(1778)
(889)
(813)
(1829)
(883)
(203)
(1549)
35-5/8 (905)
(787)
(1295)
2-7/8 (73)
(494)
CW060
(1880)
(1778)
(889)
(813)
(1829)
(883)
(203)
(1549) 35-5/8 (905)
(787)
(1295)
2-7/8 (73)
(524)
CW076 99
(2515)
(2413)
(889)
(813)
(2464)
(883)
15-1/4 (387)
78-3/4 (2000)
35-5/8 (905)
(787)
60-3/4 (1543)
8-7/8 (225)
(599)
CW084 99
(2515)
(2413)
(889)
(813)
(2464)
(883)
15-1/4 (387)
78-3/4 (2000)
35-5/8 (905)
(787)
60-3/4 (1543)
8-7/8 (225)
(644)
Source: DPN001659, Rev. 1
Projection of Display Bezel 3/4" (19mm)
J
Overall Dimension J
Overall Dimension
C
Unit Cabinet
AOverall Dimension AOverall DimensionUnit and PlenumD
C
Air Return
Opening
Air Return
Opening
B
B K
Air Return Opening
Air Return Opening
2" (50.8mm)2"
(50.8mm)
72" (1829mm)
Shaded areas indicate a recommended clearance of 36" (914mm) for component access and filter removal.
EUnit Base
F
Unit B ase
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
31" (787.4mm)
1" (25.4mm)1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
Pre-Filter Plenum
Projection of Display Bezel 3/4" (19mm)
F Plenum
Overall
2" (50.8mm)
9" (228mm)
72" (1829mm)
MODELS WITH PRE-FILTERS
GG
F
9" (228mm)9" (228mm)
20" (508mm)
20" (508mm)
20" (508mm)
Reheat or Humidifier Piping Opening (Optional Steam & Hot Water Only)
Reheat or Humidifier Piping Opening (Optional Steam & Hot Water Only)
Air Discharge Opening
L
E E
H
M
Floor Level
Floor Level
Standard Piping & Electrical Opening
Standard Piping & Electrical Opening
18" (457mm)
Air Discharge Opening
3" (76.2mm)
3" (76.2mm)
UNIT DIMENSIONAL DATA
DPN001659
Rev. 1
Floor Cutout Dimensions for Units with Centrifugal Fans
Floor Cutout Dimensions for Units with EC Fans
Liebert® CW™ 10
Figure 5 Cabinet and floor planning dimensions, CW026, CW038 and CW041, downflow with EC fans, front discharge
Customer Piping and Wiring Connections Standard bottom connections require unit to be placed on a floor stand at least 9" (229mm) high.
If unit is to be placed directly on the floor, an additional SFA is required to relocate customer connections
Striated area indicates the recommended minimum clearance for component access
36" (914mm)
36" (914mm)
46" (1168mm) Opening
16" (408mm)
29-3/4" (754mm)
Air Discharge Opening
2" (51mm)
FRONT VIEW
48" (1219mm)
3" (76mm)
72" (1829mm)
50" (1270mm)
33" (838mm)
35" (889mm)31"
(787mm) Opening
Return Air Opening
3/4" (19mm) Bezel
TOP VIEW
310807 Pg. 1, Rev. 0
11 Liebert® CW™
Figure 6 Cabinet and floor planning dimensions, CW051, CW060, CW076 and CW084, downflow with EC fans, front discharge
Dimensions inches (mm)
Model A B C D E F G
CW051 72 (1829) 74 (1880) 70 (1778) 2.0 (51) 25.0 (636) 25.3 (643) 30.1 (764)
CW060 72 (1829) 74 (1880) 70 (1778) 2.0 (51) 25.0 (636) 25.3 (643) 30.1 (764)
CW076 97 (2464) 99 (2515) 95 (2413) 8.0 (203) 28.6 (727) 28.8 (730) 41.9 (1064)
CW084 97 (2464) 99 (2515) 95 (2413) 8.0 (203) 28.6 (727) 28.8 (730) 41.9 (1064)
A
B
D
G
Customer Piping and Wiring Connections Standard bottom connections require unit to be placed on a floor stand at least 9" (229mm) high.
If unit is to be placed directly on the floor, an additional SFA is required to relocate customer connections
Striated area indicates the recommended minimum clearance for component access
36" (914mm)
36" (914mm)
C Opening
16" (408mm)
16" (408mm)
FRONT VIEW
3-1/8" (79mm)
72" (1829mm)
33" (838mm)
35" (889mm)31"
(787mm) Opening
Return Air Opening
3/4" (19mm) Bezel
TOP VIEW
310807 Pg. 2, Rev. 0
F Air Discharge
Opening
E Air Discharge
Opening
Liebert® CW™ 12
Figure 7 Cabinet and floor planning dimensions, downflow models CW106 and CW114 with EC fans
Model
Dimensions, inches (mm) Net Weight lb (kg)A B C D E F G H I
CW106 122
(3099)
(2997)
(889)
(787)
(3048)
(838)
35-5/8 (905)
(762)
(864)
(810)
CW114 122
(3099)
(2997)
(889)
(787)
(3048)
(838)
35-5/8 (905)
(762)
(864)
(873)
Source: DPN001660, Rev. 0
UNIT DIMENSIONAL DATA
Projection Of Display Bezel 3/4" (19mm)
Projection Of Display Bezel 3/4" (19mm)
*Note: "Electrical Opening" is also used for drain connection of optional steam generating canister humidifier
AOverall Dimension
G Overall
Dimension
G
Overall
Dimension A
Overall DimensionUnit and Plenum
BAir Return Opening
D
Air Return
Opening
BAir Return Opening
H Air Return
Opening
2" (50.8mm)
2" (50.8mm)
2" (50.8mm)
76" (1930mm)
E Unit Base
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
FLOOR CUTOUT DIMENSIONS
Air Discharge Opening
Pre-Filter Plenum
Standard Piping Opening
77" (1955.8mm)
Shaded area indicates a recommended clearance of 36" (914mm) for component access and filter removal
6" (152.4mm)
16-1/4" (412.75mm)
26" (660.4mm)
24" (609.6mm)
10" (254mm)
28" (711mm)
20" (508mm)
* Electrical Opening
F Unit Base
DPN001660
Rev. 0
9" (228mm)
76" (1930mm)
C
Unit Cabinet
Plenum
Overall
MODELS WITH PRE-FILTERS
C
2" (51mm)
E
*This drawing pertains to CW106 & CW114 with forward-curve blowers only.
13 Liebert® CW™
Figure 8 Cabinet and floor planning dimensions for downflow models CW089, CW106 and CW114 with EC fans
Model Weight lb (kg)
CW089 1925 (873)
CW106 1785 (810)
CW114 1925 (873)
Source: DPN001659, Rev. 1
33" (838mm)
36" (914mm)
35" (889mm)
120" (3048mm)
DPN001614
Rev. 1
Notes: Filters are accessible from front of unit only.
Electrical connections can be made from the bottom of unit.
FRONT VIEW
TOP VIEW
Shaded area indicates the required minimum clearance below the unit to lower the fans. Fans may also remain in unit if desired.
Striated area indicates the recommended minimum clearance for component access.
1-1/2" (38mm)
3/4" (19mm) Bezels
118" (2997mm)
Opening
30-3/4" (781mm) Opening
24" (610mm)
122" (3099mm)
76" (1930mm)
Liebert® CW™ 14
Figure 9 Cabinet and floor planning dimensions, CW146 - CW181, downflow with EC fans, front discharge
A
1-1/2" (38mm)
1-1/2" (38mm)
3-1/8" (78mm)
94" (2386mm)
Total Height
76" (1930mm) Base Unit
18" (457mm) Filter Plenum
4-5/8" (117mm)
45" (1143mm)
37" (940mm)
1" (25mm)
Customer Piping and Wiring Connections Standard bottom connections require unit to be placed on a floor stand at least 9" (229mm) high.
If unit is to be placed on the floor, an opening is provided in front left end panel for piping and high voltage wire routings.
Customer must drill holes in right end panel to route low-voltage connections to standard location (must be routed separate from any high voltage wires).
Striated area indicates the recommended minimum clearance for component access
CW146 or
CW181
Base Unit
117-3/4" (2989mm) Opening
FRONT VIEW
REAR VIEW
45" (1143mm)
9-5/8" (244mm)
122" (3099mm)
120" (3048mm)
42" (1067mm) Opening
48" (1219mm)
3/4" (19mm) Bezel
TOP VIEW
LEFT END
Detail A
Piping Connections
310807 Pg. 4, Rev. 0
18-7/8" (478mm)
3-1/4" (83mm)
36-3/8" (924mm)
36-3/8" (924mm)
68-1/4" (1734mm)
68-1/4" (1734mm)
18-7/8" (478mm)
18-7/8" (478mm)
18-7/8" (478mm)
18-7/8" (478mm)
18-7/8" (478mm)
15" (381mm)
27-5/8" (700mm)
Air Discharge Opening
29-1/2" (749mm)
Air Discharge Opening
30-3/4" (779mm)
Air Discharge Opening
27-5/8" (700mm)
Air Discharge Opening
29-1/2" (749mm)
Air Discharge Opening
30-3/4" (779mm)
Air Discharge Opening
Filter Plenum (shipped separately
1-1/2" (38mm)
3-1/4" (83mm)
Filters are removed through the front of the plenum
15 Liebert® CW™
Figure 10 Cabinet and floor planning dimensions for downflow models CW146 and CW181 with EC fans
Model Weight lb (kg)
CW146 2520 (1143)
CW181 2520 (1143)
Source: DPN001707, Rev. 2
24" (610mm)
48" (1219mm)
3/4" (20mm)
BEZELS
122" (3099mm)
1" (25mm) typical
Liebert
CW146
and CW181
47" (1194mm)
45" (1143mm)
120" (3044mm) 1-1/2"
(38mm)
94" (2388mm)
Total Height
117-11/16" (2989mm) Opening
42" (1067mm) Opening
18" (457mm)
Filter Plenum
45" (1143mm) Plenum
76" (1930mm) Base Unit
Reference DPN001693 for the electrical and plumbing requirements.
Filters are removed through the front of the plenum.
Note: Typical CW166 and CW181 with EC fans unit orientation shown.
Shaded area indicates the required minimum clearance below the unit to lower the fans into the floo r. Fans may also remain in their shipped position.
Striated area indicates the recommended minimum clearance for component access.
Filter Plenum (shipped separately)
CW146 or CW181 base unit
DPN001707
Rev. 2
Liebert® CW™ 16
Figure 11 Dimensions and floor planning data downflow models CW300, CW400 with EC fans and filter plenums
DPN002432
Rev. 0
118" (2997mm) Opening
87" (2210mm) Opening
3/4" (19mm) Bezels
18" (457mm)
94" (2388mm)
76" 1930mm
1-1/2" (38mm)
1" (25mm)
1" (25mm)
91" (2311mm)
45" (1143mm)
92" (2337mm)
Filter Plenum (shipped separately)
122" (3099mm)
120" (3048mm)
36" (914mm)
48" (1219mm) 24" (610mm)
Two Cabinets
Striated area indicates the recommended minimum clearance for component access.
Shaded area indicates the minimum required area below the unit to be unobstructed for the skirted floorstand and fan service clearance.
Filters are removed by removing front panel of the plenum.
Refer to DPN001693 for the electrical and plumbing requirements.
For information on installing CW300 and CW400 units, refer to Appendix A - Installing Liebert CW300 and Liebert
CW400
17 Liebert® CW™
3.2 Dimensions—Upflow Models with EC Fans
Figure 12 Cabinet and floor planning dimensions, upflow models CW026-CW084 with EC fans, front air return
Model
Dimensions, in. (mm) Plenum Height, Supply Air Dimension A
in. (mm)B C
CW026, CW038, CW041 50 (1270) 48 (1219) Grille Discharge 22.75 (578)
CW051, CW060 74 (1880) 72 (1829) Top Discharge 22.75 (578), 30 (762), 36 (914)
CW076, CW084 99 (2515) 97 (2464)
Source: DPN002836, Pg. 1, Rev. 1
B Overall
1" (25mm)
1" (25mm)
35" (889mm) OverallProjection of
Display Bezel 3/4" (19mm)
Duct flanges on plenum top for supply air ducting when solid panel plenum is used
A Plenum
72" (1829mm)
Unit Return Air Grille
Supplied on Units with Front Return
Shaded areas indicate a recommended clearance of 36" (914mm) for component access and filter removal
EC Fan Terminal Box
C Base
33" (838mm)
Base 75-1/4"
(1911mm) 72"
(1829mm)
Left Side Detail View Without Plenum or EC Fans
FRONT AIR RETURN MODEL SHOWN
DPN002386
Pg. 1, Rev. 1
Liebert® CW™ 18
Figure 13 Cabinet and floor planning dimensions, upflow models CW026 - CW084 with EC fans, bottom air return
Chilled Water ModeL
Dimensions, in. (mm) Net Weight lb (kg)
A B VC D E F Unit Only Unit w/Plenum and Fans
CW026 44 (1118) 18 (457) 5 (127) 3 (76) 46 (1168) 48 (1219) 518 (235) 750 (340)
CW038 44 (1118) 18 (457) 5 (127) 3 (76) 46 (1168) 48 (1219) 542 (246) 774 (351)
CW041 44 (1118) 18 (457) 5 (127) 3 (76) 46 (1168) 48 (1219) 589 (267) 821 (372)
CW051 68 (1727) 20 (508) 4 (102) 3 (76) 70 (1778) 72 (1829) 755 (342) 1118 (507)
CW060 68 (1727) 20 (508) 4 (102) 3 (76) 70 (1778) 72 (1829) 827 (375) 1190 (540)
CW076 86 (2184) 18 (457) 5 (127) 6-1/2 (165) 95 (2413) 97 (2464) 1141 (518) 1566 (710)
CW084 86 (2184) 18 (457) 5 (127) 6-1/2 (165) 95 (2413) 97 (2464) 1239 (562) 1664 (755)
Source: DPN002386, Pg. 2, Rev. 1
E
C
A
D
Return Air Opening
1" (25mm)
1-1/8" (29mm)
Return Air Opening Floor Cutout Dimensions Bottom Air Return Model
5-1/2" (140mm)
F
33" (838mm)
22" (559mm)
REAR AIR RETURN MODEL
DPN002386
Pg. 2, Rev. 1
19 Liebert® CW™
Figure 14 Cabinet and floor planning dimensions, upflow models CW106, CW114 with EC fans, front return
122" (3099mm)
Overall
35" (889mm) Overall
1" (25mm)
1" (25mm)
120" (3048mm)
Base
33" (838mm)
Base
Front Air Return Model Shown
Note: Duct flanges on plenum top for supply air ducting when solid panel plenum is used.Projection of
Display Bezel 3/4" (19mm)
A Plenum
76" (1930mm)
Unit
Return Air Grille Supplied on
Units With Front Air Return
Shaded areas indicate a recommended clearance of 36" (914mm) for component access and filter removal
79-1/4" (2013mm)76"
(1930mm)
Left Side Detail View Without Plenum or EC Fans
EC Fan Terminal Box
DPN002387
Pg. 1, Rev. 1
Liebert® CW™ 20
Figure 15 Cabinet and floor planning dimensions, upflow models CW106, CW114 with EC fans, rear return
Model
Net Weight, lb. (kg)
Unit Only Unit with Plenum
And Fans
CW106 1240 (562) 1827 (829)
CW114 1375 (624) 1962 (890)
Source: DPN002387, Pg. 2, Rev. 1
Shaded area indicates a recommended clearance of 25" (635mm) for rear return filter removal on one end of the unit
22" (559mm)
2-1/4" (57mm)
117-1/2" (2984mm)
Return Air Filter Opening
24-1/4" (616mm)
DPN002387
Pg. 2, Rev. 1
21 Liebert® CW™
3.3 Dimensions—Downflow Models With Centrifugal Fans
Figure 16 Cabinet and floor planning dimensions, downflow models CW106 and CW114 with centrifugal fans
Model
Dimensions, inches (mm) Net Weight lb (kg)A B C D E F G H I
CW106
(3099)
(2997)
(889)
(787)
(3048)
(838) 35-5/8 (905)
(762)
(864)
(810)
CW114 122
(3099)
(2997)
(889)
(787)
(3048)
(838)
35-5/8 (905)
(762)
(864)
(873)
Source: DPN001660, Rev. 0
UNIT DIMENSIONAL DATA
Projection Of Display Bezel 3/4" (19mm)
Projection Of Display Bezel 3/4" (19mm)
*Note: "Electrical Opening" is also used for drain connection of optional steam generating canister humidifier
AOverall Dimension
G Overall
Dimension
G
Overall
Dimension A
Overall DimensionUnit and Plenum
BAir Return Opening
D
Air Return
Opening
BAir Return Opening
H Air Return
Opening
2" (50.8mm)
2" (50.8mm)
2" (50.8mm)
76" (1930mm)
E Unit Base
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
FLOOR CUTOUT DIMENSIONS
Air Discharge Opening
Pre-Filter Plenum
Standard Piping Opening
77" (1955.8mm)
Shaded area indicates a recommended clearance of 36" (914mm) for component access and filter removal
6" (152.4mm)
16-1/4" (412.75mm)
26" (660.4mm)
24" (609.6mm)
10" (254mm)
28" (711mm)
20" (508mm)
* Electrical Opening
F Unit Base
DPN001660
Rev. 0
9" (228mm)
76" (1930mm)
C
Unit Cabinet
Plenum
Overall
MODELS WITH PRE-FILTERS
C
2" (51mm)
E
*This drawing pertains to CW106 & CW114 with forward-curve blowers only.
Liebert® CW™ 22
3.4 Dimensions—Upflow Models With Centrifugal Fans
Figure 17 Cabinet and floor planning dimensions, upflow models CW026-CW084 with centrifugal fans
Model # of
Blowers
Dimensions, inches (mm) Net Weight lb (kg)A B C D E F G H J K L M
CW026 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15-7/8 (403)
18-5/8 (473)
2-3/16 (55)
17-3/8
(454) _ 760
(345)
CW038 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15-7/8 (403)
18-5/8 (473)
2-3/16 (55)
17-3/8
(454) _ 795
(361)
CW041 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15-7/8 (403)
18-5/8 (473)
2-3/16 (55)
17-3/8
(454) _ 855
(388)
CW051 2 74
(1880)
(1829)
(1778)
(1727)
(76)
(102)
(508)
15-7/8 (403)
14-5/8 (371)
2-3/16 (55)
20-3/8 (517)
11-1/4 (286)
(494)
CW060 2 74
(1880)
(1829)
(1778)
(1727)
(76)
(102)
(508)
15-7/8 (403)
14-5/8 (371)
2-3/16 (55)
20-3/8 (517)
11-1/4 (286)
(524)
CW076 2 99
(2515)
(2464)
(2413)
(1727)
6-1/2 (165)
(127)
(457)
15-7/8 (403)
18-5/8 (473)
3-1/4 (82)
20-5/8 (524)
12-5/8 (321)
(599)
CW084 2 99
(2515)
(2464)
(2413)
(1727)
6-1/2 (165)
(127)
(457)
15-7/8 (403)
18-5/8 (473)
3-1/4 (82)
20-5/8 (524)
12-5/8 (321)
(644)
Source: DPN001661, Rev. 0
D
B
A
B C
G
F E
H
J J
J
H
K
M
L
K
72" (1829mm)
Projection of Display Bezel 3/4" (19mm)
Unit B ase
1" (25.4mm)
1" (25.4mm)
1" (25.4mm)
Overall Dimension Overall Dimension
35-5/8" (905mm)
35" (889mm)
33"
(838mm)
Unit Base Shaded area indicates a recommended clearance of 36" (914mm) for component access and filter removal. Refer to the user manual for recommended minumum clearance.
Air grille may be supplied on units with front or rear return air.
Duct Flanges on two blowers
Front of Unit
Duct Flanges on 1 blower
Front of Unit
1" (25.4mm) Flang for Plenum Connection
Note: Flanges provided on Blower(s) outlet for supply air ducting.
Air R eturn O pening
A return air grille may be ordered in place of the duct flange. See specification sheet for option supplied.
Air Return Opening
Air Return Opening
33"
(838mm)
1-1/8" (28.6mm)
5-1/2" (139.7mm)
22" (559mm)
Floor Level
Unit Dimensional Data
Floor Cutout Dimensions Models with Bottom Return
Models with Rear Return
DPN001661
Rev. 1
23 Liebert® CW™
Figure 18 Cabinet and floor planning dimensions upflow models, CW106 and CW114 with centrifugal fans
Model Blower Supply Motor hp
Dimensions, inches (mm
A B C D E F
CW106
CW114
15 x 15 Top Front 10-15 27-1/2 (699) 3-1/2 (89) 18-11/16 (475) 16-3/16 (411) 10 (254) 4-1/2 (114)
Top Rear 10-15 27-1/2 (699) 12-5/16 (313) 18-11/16 (475) 16-3/16 (411) 10 (254) 4-1/2 (114)
15 x 11 Top Front
10-15 30 (762) 3-1/2 (89) 14-3/4 (375) 16-3/16 (411) 10 (254) 4-1/2 (114)
20 30 (762) 3-1/2 (89) 14-3/4 (375) 16-3/16 (411) 10 (254) 4-1/2 (114)
Top Rear 10-20 30 (762) 12-5/16 (313) 14-3/4 (375) 16-3/16 (411) 10 (254) 4-1/2 (114)
Unit Dimensions
Air grille supplied on units with front return air only
Shaded areas indicate a recommended clearance of 36" (914mm) for component access and filter removal.
Duct Connections Models With Rear Return
Projection of Display Bezel 3/4" (19mm)
24-1/4" (616mm)
117-1/2" (2985mm)
1" (25mm) flange for decorative plenum alignment Flanges provided on blower outlets for supply air ducting.
2" (51mm)
Shaded area indicates a recommended clearance of 25" (635mm) for rear return filter removal on one end of the unit.
33" Base (838mm)
2" (51mm)
122" Overall (3099mm)
122" Overall (3099mm)
118" (2997mm)
Plenum Flange
76" (1930mm)
Air Return Opening
Filter Access (Both Ends)
22" (559mm)
2-1/4" (57mm) DPN001662
Rev. 2
32" (813mm) Plenum Flange
35" Overall (889mm)
120" Base (3048mm)
1" (25mm)
4" (102mm)
A B
D
CC C
F
E E
Duct Flanges on 3 Blowers
35" (889mm)
Ref.
76" (1930mm) Ref.
Front of Unit Blower Duct Flange Location
Top of Unit Blower Deck
Front or Rear Air Supply
Liebert® CW™ 24
3.5 Floor Stand Dimensions
Figure 19 Floor stand and floor planning dimensions, downflow models CW026 - CW041 with EC fans
Dimension A* Height, in (mm)
24 (610)
30 (762)
36 (914)
42 (1067)
48 (1219)
Source: DPN00209, Rev. 0
DPN002029
REV 0
NOTES:
1) This floor stand should be used when EC fans are will be lowered into a raised floor. The standard Liebert CW floor stand can be used if the fans will remain in their original, raised position.
2) All paneled sides of unit overhang the floor stand by 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its orientation to the Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
4) The jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed.
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “A.”
See Note 4
46-1/2" (1181mm) Support Feet Centers
3/4" (19mm)
3/4" (19mm)
3/4" (19mm) typ
3/4" (19mm)
1" (25mm)
31-1/2" (800mm)
14" (356mm)
48" (1219mm)
Piping access area
49-1/2" (1257mm)
7/8" (23mm)
33" (838mm)
34-1/2" (876mm) Overall Depth
3" (76mm) typ A*
25 Liebert® CW™
Figure 20 Floor stand and floor planning dimensions, downflow models CW076 and CW084 with EC fans
Dimension A* Height, in (mm)
24 (610)
30 (762)
36 (914)
42 (1067)
48 (1219)
Source: DPN002027, Rev. 0
DPN002027
Rev. 0
NOTE:
1) This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert CW floor stand can be used “if” the fans are to remain in their original raised position.
2) All paneled sides of unit overhang floorstand 1” (25mm).
3) The floor stand used with EC units is not symmetrical and its orientation to the Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed.
*Leveling feet are provided with ± 1-1/2” (38mm) adjustment from nominal height “A”.
33" (838mm)
35" (889mm) Overall Depth
A*
1" (25mm) typ
3/4" (19mm)
3/4" (19mm)
3/4" (19mm)
1" (25mm)
98-1/2" (2502mm)
3" (76mm) typ
7/8" (23mm) typ
97" (2464mm)
32" (813mm)
Center Feet
Piping access area
25" (635mm)
31-1/2" (800mm)
47-3/4" (1213mm)
95-1/2" (2426mm) Support Feet Centers
See Note 4
Liebert® CW™ 26
Figure 21 Floor stand and floor planning dimensions, downflow models CW089, CW106 and CW114 with EC fans
NOTES
1. This floor stand should be used when EC fans are intended to be lowered into the floor stand. The standard Liebert CW floor stand can be used “if” the fans are to remain in their original raised position.
2. All paneled sides of unit overhang floorstand 1" (25mm).
3. The floor stand used with EC units is not symmetrical, and its orientation to the Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
4. Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed.
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height “A.”
See Note 4
Piping access area
20-1/4" (514mm)1"
(25mm)
31-1/2" (800mm)
3/4" (19mm)
32" (813mm) Center Feet
3/4" (19mm)
118-1/2" (3010mm) Support Feet Centers
59-1/4" (1505mm)
120" (3048mm)3/4" (19mm)
Typ
1" (25mm)
TYP
33" (838mm)
35" (889mm) Overall Depth
121-1/2" (3086mm) Overall Width
A*
7/8" (22mm)
Typ 3" (76mm) TYP
DPN001629
Rev. 4
Height, in. (mm) A*
24 (610) 30 (762) 36 (914)
42 (1067) 48 (1219)
27 Liebert® CW™
Figure 22 Floor stand and floor planning dimensions, downflow models CW146 and CW181 with EC fans
NOTE:
1. This floor stand should be used when EC fans are intended to be lowered into the floor stand. The standard Liebert CW floor stand can be used if the fans are to remain in their original, raised position.
2. All paneled sides of unit overhang floor stand 1" (25mm).
3. The floor stand used with EC units is not symmetrical, and its orientation to the
Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
4. The jack and jack support are shipped loose and are intended to be placed into position under each fan and used to lower or raise one fan at a time as needed.
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height†“A.”
20-1/4" (514mm)
1" (25mm)
3" (76mm)
7/8" (23mm)
TYP
A*
Height in (mm) A*
24 (610) 30 (762) 36 (914)
42 (1067) 48 (1219)
See Note 4120" (3048mm)
3/4" (19mm)
TYP
121-1/2" (3086mm) Overall Depth 47"
(1194mm) Overall Depth
45" (1143mm)
1" (25mm)
TYP
43-1/2" (1105mm)
3/4" (19mm)
Support Feet Centers
59-1/4" (1505mm)
Piping access area
118-1/2" (3010mm)
3/4" (19mm)
44" (1118mm)
CENTER FEET
DPN001696
Rev. 3
Liebert® CW™ 28
Figure 23 Floor stand and floor planning dimensions—Downflow CW300 AND CW400 with EC fans
A
Detail A
NOTE:
1. This floor stand should be used when EC fans are permitted to be lowered into the floor stand.
2. All paneled sides of unit overhang floor stand 1" (25mm).
3. The floor stand used with EC units is not symmetrical and its orientation to the Liebert CW is critical for lowering the EC fans. Unless the floorstand is installed in the correct position, the blowers will not lower into the floorstand.
4. Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed.
5. Hatched area for piping access.
DPN002433
Rev. 0
See Note 4
See Note 5
43" (1092mm)
3/4" (19mm) 118-1/2" (3010mm)
59-1/4" (1505mm) 3/4"
(19mm)
42-1/4" (1073mm) Center of
Feet
42-1/4" (1073mm) Center of
Feet
4" (102mm)
4" (102mm)
20-1/4" (514mm)
1" (25mm)
1" (25mm)
1" (25mm)
1" (25mm)
43" (1092mm)
46" (1169mm)
92" (2338mm) Overall Depth
90" (2287mm)
A *
120" (3048mm)
122" (3099mm) Overall Width
3" (76mm) typ.
7/8"
(23mm)
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height 36" (914mm).
Height, in. (mm) A*
24 (610) 30 (762) 36 (914)
42 (1067) 48 (1219)
29 Liebert® CW™
Figure 24 Floor stand dimensions, optional steam, hot water reheat and humidifier piping entrances for downflow models CW026 - CW84 with centrifugal fans
Model
Dimensions, inches (mm) Height in. (mm)
Overall Unit Width A B C D E H* Nominal J
CW026, CW038, CW041 50 (1270) 48 (1219) 0 0 36 (914) 8 (203) 9 (229) 6-1/2 (165)
CW051, CW060 74 (1880) 72 (1829) 0 0 60 (1524) 8 (203) 12 (305) 9 (229)
CW076, CW084 99
(2515)
(2464)
48-1/2 (1232)
48-1/2 (1232)
77-3/4 (1975)
15-1/4 (362)
15 (381) 12 (305)
18 (458) 15 (381)
Source: DPN001676, Rev. 0 21 (553) 18 (458)
24 (610) 21 (553)
DPN001676
Rev. 0
B
A C
E
D
J
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height H.
1" (25.4mm)
8" (203mm)
(76.2mm)
Standard piping and electrical entrance location
Optional Steam/Hot Water Reheat or Humidifier Piping Entrance Location
Optional Turning Vane Field-Installed in Fan Discharge Opening For Rear or Front Air Discharge
62" (1574.8mm)
A + 2" (50.8mm) = Overall Width of Unit Air Discharge
Opening
1" (25.4mm)
2" (50.8mm)
16-1/4" (413mm)
Leg support supplied on 18, 21 & 24" high models
Length of Vane = D - 1/8" (3mm)
H ±1-1/2" (38mm) *
33" (838mm)
56-3/4" (1441.5mm)
CROSS-BRACING LOCATION FOR 72" FRAMES ONLY
Liebert® CW™ 30
Figure 25 Floor stand dimensions for downflow models CW106 and CW114 with centrifugal fans
Model
Dimensions, inches (mm) Height, in. (mm)
Overall Unit Width A B C D E F G K
H* Nominal J
CW106
CW114
(3099)
(3048)
(1524)
(1524)
(838)
100-3/4 (2559)
16-1/4 (413)
8-1/4 (210)
(279)
9 (229) 6-1/2 (165)
12 (305) 9 (229)
Source: DPN001677, Rev.