Attachment 2 Greenhouse Ventilation.pdf

PDF 117 KB Posted

Attached to
Renovate Greenhouse Ventilation Federal contract opportunity
Solicitation number
12805B21Q0349
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Greenhouse Ventilation, newest first.
File Type Posted
Attachment 4 Rev 1 Scope of Work (SOW).pdf PDF
Amendment 0001.pdf PDF
Attachment 1 Greenhouse Dimensions Existing.pdf PDF
Attachment 4 Scope of Work (SOW).pdf PDF
Attachment 6 ARS-371.pdf PDF
Solicitation 12805B21Q0349.pdf PDF
Attachment 7 ARS-372.pdf PDF
Attachment 3 Infrared_Heaters_Specs.pdf PDF
Attachment 5 Wage Determination TX20210235.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 2

• Ridge Vent one manual gear box in center of building.

• Ventilation fans and cooling pads controlled by Wadworth controller (not funcitioning)

Existing Greenhouse ventilation arrangement.

Cooling pad with exterior louver

Exhaust fan

Supply fan Modine heater

Ridge louver

• Remove end wall exhaust fans and patch openings.

• Divide ridge louver into two manually operated sections.

• Replace end wall supply fan with exhaust fan interlocked with shuttered gooseneck exhaust port.

• Install new exhaust fans on side wall and interlock with shutters on opposite wall.

• Install infrared solaronic tube heater.

• Install cooling pad system.

• Install control system and sensor as required.

New Final Ventilation System Arrangement.

Exhaust fan

Infrared heater

Ridge louver

Gooseneck vent

Shutters

Cooling pad

Top exhaust fan

Top exhaust fan Recirc fan (8)

Controls Operation

• Top ridge vent for each greenhouse section controlled via manual gear and chain.

Cooling

• Recirc fans on normally.

• 1st stage: Top exhaust fan come on. Recirc fans turn off.

• 2nd stage: One Side exhaust fans and one-half of shutters open (every other one)

• 3rd stage: Other Side exhaust fans and one-half of shutters open (every other one).

• 4th stage: Cooling pad turn on.

• System ramps down due to temperature setpoints.

Heating

• Recirc fans on normally.

• Infrared heaters turn on.

Notes:

• Two independent controls systems, one for each half of the greenhouse.

• All relays and contacts to be duty rated for equipment controlling.

• System to automatically switch between heating and cooling modes as necessary.

File details come from the government source that posted it. Updated .