This document package includes construction drawings and specifications for the Building 62 Renovation project for the Department of Health and Human Services Food and Drug Administration. The drawings show details for roof repairs including replacement of roof drains, installation of new roofing membrane, flashing details, and parapet wall details. Reference drawings are also provided. The related federal contract opportunity is solicitation number 75F40122R00086 for the Building 62 Renovation project. A site visit is scheduled as outlined in Section L-11 of the solicitation documents. Responses to the solicitation are due on the date specified. The contract will be awarded by the FDA Office of Acquisition and Grant Services.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEMBRANE BASE SHEET (fully adhere)
FLASHING SYSTEM (extend a minimum 8" beyond outermost edge of drain)
MEMBRANE BASE SHEET (fully adhere, lap a minimum of 4" beyond Flashing)
MEMBRANE CAP SHEET
STRAINER & CLAMPING RING
EXISTING ROOF DECK
MASTIC (set all roof layers above Flashing in mastic 6" around drain perimeter)
APPROVED COVERBOARD
MEMBRANE BASE SHEET
(fully adhere to roof surfaces)
FLASHING SYSTEM
(fully adhere - wipe w/ approved solvent before lapping subsequent sheets)
MEMBRANE BASE SHEET(fully adhere)
MASTIC (shaded area)
MEMBRANE CAP SHEET (fully adhere)
CLAMPING RING
OVERHEAD VIEW
4"
CAUTION: FOLLOW ALL PRACTICES PERTAINING TO NRCA CERTA GUIDELINES WHEN TORCHING METHODS ARE EMPLOYED. THIS INCLUDES PERFORMING A FIRE WATCH FOLLOWING ANY TORCH APPLICATIONS.
ALWAYS HAVE APPROVED FIRE-EXTINGUISHING EQUIPMENT NEARBY.
NOTE: BASIS OF DESIGN = SIPLAST. SEE SPECIFICATION FOR OTHER ACCEPTABLE MANUFACTURERS.
NEW STRAINER
CAUTION: SIPLAST RECOMMENDS THAT ALL PRACTICES PERTAINING TO NRCA CERTA GUIDELINES BE FOLLOWED WHEN TORCHING METHODS ARE EMPLOYED. THIS INCLUDES PERFORMING A FIRE WATCH FOLLOWING
ANY TORCH APPLICATIONS. ALWAYS HAVE APPROVED FIRE-EXTINGUISHING EQUIPMENT NEARBY.
EXISTING ROOF DECK
PARADIENE 20
(dry on cant, fully adhere to roof surfaces)
PARADIENE 20 SA
(fully adhere to primed substrate and underlying Paradiene 20)
PARADIENE 30 FR (fully adhere, prepare granule surfaces)
VERAL, PARAFOR 50 TG, PARAFOR 30 TG, OR PARADIENE 40 FR TG
(torch to prepared surfaces and fasten 9" o.c.)
WALL (prime masonry surfaces)
CONTINUOUS SEALANT
NON - COMBUSTIBLE CANT
APPROVED COVERBOARD
PARADIENE 20 SA
(fully adhere to vertical and horizontal surfaces as shown)
NOTES:
1. PREPARE GRANULE SURFACES UNDER FLASHING BY TORCH PREPARATION.
2. WHERE PRIMER IS INDICATED TO MAINTAIN PROPER ADHESION, TA-119 PRIMER IS REQUIRED FOR ALL PARADIENE 20 SA FLASHING REINFORCING AND STRIPPING PLY APPLICATIONS. USE PA-1125 OR PA-917 LS PRIMER FOR ALL OTHER PARADIENE 20 SERIES PRODUCTS THAT ARE NOT SELF-ADHESIVE SHEETS. CONTACT SIPLAST FOR SPECIFIC REQUIREMENTS.
3. THE METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
4. A NAILER AND TREATED WOOD CANT MAY BE REQUIRED FOR COMPLIANCE WITH SPECIFIC BUILDING CODES OR APPROVALS.
5. DISSIMILAR METAL TYPES SUBJECT TO ELECTROLYTIC REACTION SHOULD BE PHYSICALLY SEPARATED.
6. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
M
IN
IM
U
M
3" 1"
PARAPET - WALL SUPPORTED DECK with TORCH-APPLIED FLASHING
PARADIENE 20/30 FR - NVS SUBSTRATE
CONTINUOUS TERMINATION BAR PARALLEL TO ROOF
SURFACE. PROVIDE WATERTIGHT ANCHORS AT 12" O.C.
RIGID INSULATION
EXIST. ROOF DECK
WOOD CURB
VERIFY EXISTING CONDITIONS
COUNTER FLASHING
NON - COMBUSTIBLE CANT
MEMBRANE BASE SHEET (fully adhere to vertical and horizontal surfaces as shown)
MEMBRANE BASE SHEET (dry on cant, fully adhere to roof surfaces)
MEMBRANE BASE SHEET
(mechanically attach to wood curb with approved fasteners, fully adhere to underlying base sheet)
MEMBRANE CAP SHEET
(fully adhere)
ALUM. FLASHING SHEET EQUAL TO
VERAL (torch to prepared surfaces and fasten 9" o.c.)
BASE SHEET FLASHING STRIP
NOTES:
1.PREPARE GRANULE SURFACES UNDER FLASHING BY TORCH PREPARATION.
2.WHERE PRIMER IS INDICATED TO MAINTAIN PROPER ADHESION, TA-119 PRIMER IS REQUIRED FOR ALL PARADIENE 20 SA FLASHING REINFORCING AND STRIPPING PLY
APPLICATIONS. USE PA-1125 OR PA-917 LS.
3.THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.
4.DISSIMILAR METAL TYPES SUBJECT TO ELECTROLYTIC REACTION SHOULD BE PHYSICALLY SEPARATED.
5.REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
3" 3"
1"
NOTE: BASIS OF DESIGN = SIPLAST. SEE SPECIFICATION FOR OTHER ACCEPTABLE MANUFACTURERS.
CAUTION: FOLLOW ALL PRACTICES PERTAINING TO NRCA CERTA GUIDELINES WHEN TORCHING METHODS ARE EMPLOYED. THIS INCLUDES PERFORMING A FIRE WATCH FOLLOWING ANY TORCH APPLICATIONS. ALWAYS HAVE APPROVED FIRE-EXTINGUISHING EQUIPMENT NEARBY.
NOTE: TURN ROOF LAYERS UP
AND OVER CURB - TYPICAL
APPROVED
COVERBOARD
THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
PRIMER FOR ALL OTHER PARADIENE 20 SERIES PRODUCTS THAT ARE NOT SELF-ADHESIVE SHEETS. CONTACT SIPLAST FOR SPECIFIC REQUIREMENTS.
EXISTING
OPENING
AND CURB
NEW WOOD FRAMING AS REQ'D
PREFINISHED METAL CAP OVER
3/4" PLYWOOD TOP
REPLACE CURBS IF DETERIORATED -
TYPICAL ALL CURBS AND PERIMETER
BLOCKING AT EDGE OF ROOF.
ROOF SYSTEM SEALANT
TREATED 2x_ WOOD CONTINUOUS
PREFINISHED METAL ROOF
EDGE FLASHING (DRIP EDGE)
NEW ROOFING SYSTEM
ROOF EDGE FASTENERS
REINSTALL GUTTER
Copyright
Date
Title
Sheet No.
901 West Third Street Little Rock, Arkansas 72201 501.374.5300
Seal
Job No.
www.WERarch.com
SRQPNMLKJHGFEDCBA
A B C D E F G H J K L M N P Q R S
ARCHITECT
WER Architects/Planners
/1
/2
:0
:1
A
M
C U s e rs
\a s a n d e rs o n
\D o c u m e n ts \F
D A
ID
I2
.0
-F
D A
B u ild in g
C o n s t D o c s v a s a n d e rs o n
W E
.r v t
FDA Jefferson
Laboratories
BLDG. 62
RENOVATIONS
3900 NCTR Road, HFT_324
Jefferson, AR 72079
MEPFP ENGINEERS
Energy Engineering Consultants, Inc 10 Corporate Hill Dr Little Rock, AR 72205 501-244-0511
A8.06
ROOF DETAILS
03/24/22
FDAIDI21.01
OWNER
FDA
Jefferson Laboratories
OAGS - Field Operations Branch 3900 NCTR Road Jefferson, AR 72079
P ro je c t
N a m e
ISSUE FOR CONSTRUCTION
3" = 1'-0" M14
EXISTING ROOF DRAIN TO BE REFLASHED
1 : 5 M10
Roof-To-Wall Flashing - 2030
1 1/2" = 1'-0" M4
EQUIPMENT CURB AT ABANDONED EQUIPMENT
1 1/2" = 1'-0" F14
GUTTER DETAIL
No. Issue Date
Copyright
Date
Title
Sheet No.
901 West Third Street Little Rock, Arkansas 72201 501.374.5300
Seal
Job No.
www.WERarch.com
SRQPNMLKJHGFEDCBA
A B C D E F G H J K L M N P Q R S
ARCHITECT
WER Architects/Planners
/1
/2
:0
:2
A
M
C U s e rs
\a s a n d e rs o n
\D o c u m e n ts \F
D A
ID
I2
.0
-F
D A
B u ild in g
C o n s t D o c s v a s a n d e rs o n
W E
.r v t
FDA Jefferson
Laboratories
BLDG. 62
RENOVATIONS
3900 NCTR Road, HFT_324
Jefferson, AR 72079
MEPFP ENGINEERS
Energy Engineering Consultants, Inc 10 Corporate Hill Dr Little Rock, AR 72205 501-244-0511
A9.00
REFERENCE
DRAWINGS
03/24/22
FDAIDI21.01
OWNER
FDA
Jefferson Laboratories
OAGS - Field Operations Branch 3900 NCTR Road Jefferson, AR 72079
P ro je c t
N a m e
ISSUE FOR CONSTRUCTION
1" = 1'-0"
REFERENCE DRAWING1
THIS DRAWING IS FOR REFERENCE ONLY, NOT PART OF WORK SCOPE
Copyright
Date
Title
Sheet No.
901 West Third Street Little Rock, Arkansas 72201 501.374.5300
Seal
Job No.
www.WERarch.com
SRQPNMLKJHGFEDCBA
A B C D E F G H J K L M N P Q R S
ARCHITECT
WER Architects/Planners
/1
/2
:0
:2
A
M
C U s e rs
\a s a n d e rs o n
\D o c u m e n ts \F
D A
ID
I2
.0
-F
D A
B u ild in g
C o n s t D o c s v a s a n d e rs o n
W E
.r v t
FDA Jefferson
Laboratories
BLDG. 62
RENOVATIONS
3900 NCTR Road, HFT_324
Jefferson, AR 72079
MEPFP ENGINEERS
Energy Engineering Consultants, Inc 10 Corporate Hill Dr Little Rock, AR 72205 501-244-0511
A9.01
REFERENCE
DRAWINGS
03/24/22
FDAIDI21.01
OWNER
FDA
Jefferson Laboratories
OAGS - Field Operations Branch 3900 NCTR Road Jefferson, AR 72079
P ro je c t
N a m e
ISSUE FOR CONSTRUCTION
1" = 1'-0"
REFERENCE DRAWING2
THIS DRAWING IS FOR REFERENCE ONLY, NOT PART OF WORK SCOPE