Amendment 3 Attachment 3 Section 280746-CAT 6.pdf

PDF 50 KB Posted

Attached to
Building 62 Renovation Federal contract opportunity
Solicitation number
75F40122R00086
Issued by
Department of Health and Human Services Food and Drug Administration Office of Acquisition and Grant Services

About this file

This document outlines specifications for a Category 6 computer network system installation at the FDA Jefferson Laboratories Building 62. The specifications cover conduit, boxes, cables, outlets, connections, patch panels, and testing requirements. Cable must be four-pair, Category 6 and plenum rated. Outlets require two-port cover plates. Patch panels must allow for 25% spare capacity. The contractor must be a full-time telecommunications contractor and guarantee work for one year. Cables must be labeled and tested to TIA/EIA 568 standards with attenuation and crosstalk testing. The contractor must be a certified installer to provide a 15-year warranty. Conduit and cable supports are specified. The solicitation number is 75F40122R00086 from the Department of Health and Human Services Food and Drug Administration for the Building 62 Renovation project, with site visit details in Section L-11.

View the file

Other files for this federal contract opportunity

Other files attached to Building 62 Renovation, newest first.
File Type Posted
Amendment 5.pdf PDF
Amendment 5 Attachment 2 Substitution Request form.pdf PDF
Amendment 5 Attachment 1 revised Sol Doc bldg 62 renovation.docx DOCX document
Amendment 5 Attachment 3 as-builts 1962 Pilot Line Facilities - 03-01-62.pdf PDF
amendment 4.pdf PDF
Amendment 3 Attachment 1 Campus 1991-1992 - Street Lighting System - 11-24-92.pdf PDF
Amendment 3 Attachment 2 Table of Contents_10.03.2022.pdf PDF
amendment 3.pdf PDF
amendment 2.pdf PDF
Amendment 2 Attachment 1 revised Sol Doc bldg 62 renovation.pdf PDF
Amendment 2 Attachment 2 updated Attachment J-3 Wage Decision.pdf PDF
Amendment 2 Attachment 3 09 6700-RESINOUS AGGREGATE FLOORING 09.30.2022.pdf PDF
Amendment 1.pdf PDF
Amendment 1 Attachment 1 updated Specifications.pdf PDF
Amendment 1 Attachment 2 A1.02 22.09.12 UPDATE.pdf PDF
Amendment 1 Attachment 3 Site Light cutsheet.pdf PDF
Amendment 1 Attachment 4 Adaptor cutsheet.pdf PDF
Attachment 1 Project Manual Bldg 62 Renovation.pdf PDF
Attachment 2 C Drawings Bldg 62 Renovation.pdf PDF
Attachment 2 F Drawings Bldg 62 Renovation.pdf PDF
Attachment 3 Wage Determination.pdf PDF
Sol Doc 75F40122R00086 bldg 62 renovation.pdf PDF
Attachment 2 A Drawings Bldg 62 Renovation.pdf PDF
Attachment 2 B Drawings Bldg 62 Renovation.pdf PDF
Attachment 5 Sample Client Authorization Letter.docx DOCX document
Attachment 6 Past Performance Evaluation Questionnaire.docx DOCX document
Attachment 2 G Drawings Bldg 62 Renovation.pdf PDF
Attachment 4 - Form FDA 3398.pdf PDF
Attachment 2 D Drawings Bldg 62 Renovation.pdf PDF
Attachment 2 E Drawings Bldg 62 Renovation.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FDAIDI21.01 COMPUTER NETWORK SYSTEM - CATEGORY 6

FDA Jefferson Laboratories 28 0746 - 1 09/27/2022 Building 62 100% Final Design Submission

SECTION 280746

COMPUTER NETWORK SYSTEM - CATEGORY 6

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Complete computer network system, including but not limited to:

1. Conduit

2. Boxes

4. Cables.

5. Outlets.

6. Connections.

7. Patch panels.

8. Testing.

1.2 RELATED SECTIONS

1.3 SUBMITTALS

A. Submit under provisions of Division 1.

1.4 PROJECT RECORD DOCUMENTS

A. Submit record documents under provisions of Division 1.

1.5 GENERAL

A. This Contractor shall be a full time telecommunications contractor.

B. This Contractor shall furnish a compatible computer horizontal cabling network system as described in these specifications and indicated on the drawings.

C. All Category 6 cable shall be installed, tested and certified. Reports showing testing of all cable shall be submitted upon completion of installation. Reports shall be used as proof that all cables have been tested to Category 6 standards.

PART 2 - PRODUCTS

2.1 EQUIPMENT

FDA Jefferson Laboratories 28 0746 - 2 09/27/2022 Building 62 100% Final Design Submission

A. Cables shall be four pair, Category 6, 550MHz, 24 AWG, unshielded twisted pair, plenum rated, Jacket color shall be blue. CommCables or approved equal.

B. Category 6, RJ-45 jack modules, TIA/EIA-568, Leviton or approved equal. Color shall be selected during submittal review.

C. Two-port flush-mounted cover plates with slopped jacks mount. Two jacks per cover plate unless noted on drawings. Color shall be selected during submittal review. Insert tag for voice and insert tag for data. Leviton or approved equal.

D. Category 6 patch panels with 24 port RJ45 jacks and 110 wire terminations. Quantity shall allow for 25% spare port capacity over drops indicated on plans. Leviton or approved equal.

E. Analog telephone blocks, Type-110 style.

F. Patch cables shall be Category 6, 550MHz and shall be 6 foot in length.

CommCables or approved equal.

G. Patch panels shall be 48-port.

H. All cables shall be terminated and tested.

PART 3 - EXECUTION

3.1 Provide factory bends for all elbows on conduit. Do not install more than two (2) 90 degree bends without installing a pullbox. For conduit runs longer than 100'-0", install a pullbox. Where routing is above an accessible ceiling, conduit may be stubbed out from the wall box and turned horizontal above the ceiling and terminated with plastic bushing to protect emerging cable.

3.2 Contractor shall guarantee labor and materials for one year from date of acceptance.

3.3 No LB condulets shall be allowed.

3.4 If pull boxes are installed, they must be large enough to maintain a minimum bending radius for cables.

3.5 A complete set of "contractor revised" drawings of installation shall be provided upon completion of project.

3.6 Backboxes shall be mounted at 18 inches above the finished floor unless noted otherwise on the drawings.

3.7 Category 6 cables shall be wired, terminated and tested to TIA/EIA 568 specifications.

3.8 All computer cables must be labeled at both ends with "Building No." - " Room No." -

FDA Jefferson Laboratories 28 0746 - 3 09/27/2022 Building 62 100% Final Design Submission

"No. of Outlet". If room has more than one outlet, outlets shall be numbered sequentially when going around the room clockwise from the main entrance to the room.

Coordinate cabling identification with Owner's representative.

3.9 All Category 6 wiring, connectors, and jacks must be installed by contractors who are certified installers such that the completed wiring is certified for 15 year warranty for Category 6 compliance. All cabling installed shall comply with TIA/EIA-568 Standards.

3.10 All horizontal cable runs from wiring closet to outlet locations shall be supported with J-hooks recommended for use with Category 6 cables. Bridle rings and tie wraps are prohibited. J-hook fasteners shall be placed at 5 foot intervals and supported from the building structure. Cables shall not be supported on ceiling support wires. Cables shall not be tightly bundled and shall have visible sag between supports. Supports shall have not sharp edges.

3.11 Installer shall maintain the minimum distance from sources of electromagnetic interference: 6 inches from power circuits; 1 foot from fluorescent and HID lamps; and 4 feet from transformers, meters and variable frequency drives.

3.12 Each cable run shall be tested from patch panel to workstation outlets in accordance with TIA/EIA TSB67, transmission performance specifications for field testing of unshielded twisted-pair cabling systems, including attenuation, near end crosstalk, wire mapping, and cable length.

3.13 Submit certification of the proper operation of the computer network system.

3.14 Provide 1-year warranty of all materials and labor provided under this Section.

3.15 All raceway elbows shall be long radius elbows.

3.16 Install conduit where cables, not in conduit, pass through floors. Extend conduit at least 6 inches above top of floor.

3.17 Copper grounding buss bar (minimum 12 holes) shall be installed in metal data rack frame. One #6 AWG ground conductor shall be connected to buss and routed to nearest power panel and terminated at the panel ground buss bar.

3.18 Non-plenum rated cables, not in conduit, shall not be installed in supply or return air plenums.

3.19 Not used.

3.20 Cables shall be continuous, without splicing, from patch panels to outlets.

3.21 Do not peel back cable sheath more than necessary to separate conductors.

3.22 Do not score copper conductors when peeling back conductor insulation. Scored conductors shall be replaced.

FDA Jefferson Laboratories 28 0746 - 4 09/27/2022 Building 62 100% Final Design Submission

3.23 Do not bend cables with a radius less than five times the cable’s diameter. Cables bent with a radius less than this shall be replaced.

3.24 Kinked, torn, or twisted cable sheaths are unacceptable and will be replaced.

3.25 Install cables to avoid water, high humidity, chemicals, cold temperature bending, pair spreading, pair wrapping, and different lengths of pairs in same cable.

3.26 Do not bundle more than 216 four-pair cables or 36 twenty-five pair cables.

3.27 Conduits shall not have 90 degree bends within 100 feet of each other.

3.28 Make sure conduits are properly terminated, reamed and brushed before installation of cable(s).

3.29 At patch panels, tie wrap cable bundles.

3.30 At patch panel terminations:

A. Push pairs down in the cable slot against the block but not against the index strips.

B. Keep pairs twisted up to termination.

C. Pull cables tight around turns.

D. Install cables in cable managers.

3.31 Do not criss-cross pairs or allow them to become interwoven.

3.32 Verify proper conductor location at each termination before energizing.

3.33 Follow color code labels.

3.34 Cable sheaths shall be held in place by strain relief fittings.

END OF SECTION