Attachment 2 - Drawings Work Area and Door Install Comb.pdf
PDF 2 MB Posted
- Attached to
- Repair SCIF BLDG 150 Federal contract opportunity
- Solicitation number
- W50S8Q-23-B-0004
- Issued by
- Department of the Army National Guard
About this file
This document includes drawings and specifications for a security installation project at Building 150. The project involves demolishing an existing vault door and frame and installing a new hollow metal door and frame. Additional work includes installing a new maglock, request to exit button, card reader, emergency power off button, white noise speakers, and PIR sensor to secure an area within the building. All security control panels, junction boxes and devices must communicate with the base defense operations center and security room. The contractor will be required to use Advantor for the security aspects of the work. The contractor will provide labor, materials and equipment to complete the job according to the drawings and statement of work, running no less than 3/4" conduit and installing 4x4 junction boxes. The contractor must also supply power circuits and perform testing with the government to ensure proper system operation before providing training.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers1419_W50S8Q23B0004.pdf | ||
| RFI_W50S8Q23B0004_SCIFDoor.pdf | ||
| W50S8Q-23-B-0004 Repair SCIF Door.pdf | ||
| Attachment 4 - RFI Format.docx | DOCX document | |
| Attachment 1 - SOW Bldg.150 ISRG door WAAR232004.docx | DOCX document | |
| Attachment 3 - Material Submittals ISRG Complete.xlsx | XLSX spreadsheet | |
| Attachment 5 - DBIDs -Base Entry Request.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ML
O
TRAVEL
95'-0"
BLDG EXIT
1/100 B
0.2" 68"340
EXIT
1/100 B
0.2" 34"170
FE
FE
TRAVEL
126'-0"
BLDG EXIT
1/100 B
0.2" 34"170
UP
EXISTING
COMBAT
OPERATIONS
EXISTING
OPEN
OFFICE
EXISTING
ENTRY
SECURITY
OFFICE
VEST
OFFICE
OFFICE
129 OFFICE
OPEN
OFFICE
EXISTING
MAIN
WAREHOUSE
SERVER/
COMM ROOM
EXISTING
FLAMMABLES
LIFE SAFETY PLAN
SCALE: 1/8"=1'-0"
NORTH
LEGEND
DENOTES EXIT
ROUTE
TRAVEL
DISTANCE
START
POINT
EGRESS ELEMENT
USE AND OCCUPANCY
CLASSIFICATION
OCCUPANT LOAD
SERVED
REQUIRED ELEMENT
WIDTH
ACTUAL EGRESS WIDTH
PROVIDED
DENOTES
FLOOR OR
BUILDING EXIT
S.F. PER OCCUPANT
SURFACE MOUNTED
FIRE EXTINGUISHER
FE
CEILING MOUNTED EXIT
SIGN
EXIT
1/100 B
0.2" 46"230
SHEET
REFERENCE
NUMBER
D
ES
IG
N
E D
B Y
: A
JD
D W
N B
Y:
A
JD
R
EV
IE
W
E D
B Y
: C
LK
D
AT
E:
D
ES
IG
N
F
IL
E N
O
D R
AW
IN
G C
O D
E:
FI
LE
N
AM
E:
P
LO
T
D A
TE
P
LO
T
SC
AL
E:
R
EV
P ar kw ay
L an e, S ui te
N or cr os s, G
A
Ph on e
8.
6.
Fa x
8.
6.
W eb : w w w
.p on dc o.
co m
R
EV
D
ES
C
R
IP
TI
O
N P
R
EP
B Y
D
AT
E A
PR
VD
D R
A W
IN
G
R
EV
IS
IO
N S
FI
N
AL
S
U
BM
IT
TA
L
A
LT
ER
B
U
IL
D
IN
G
O
H
IO
N
AT
IO
N
AL
G
U
AR
D S
PR
IN
G
FI
E
LD
M
AP
, S P
R
IN
G
FI
EL
D
, O H
IO
/1
7/
C
D
B
A
Id ea
C en te r B ou le va rd
D ay to n, O H
Ph on e
7.
1.
Fa x
7.
1.
W eb
: w w w .w oo lp er t.c om
FI
N
AL
S U
BM
IT
TA
L
-2
0-
S U
B M
IT
TE
D B
Y:
G
H C
SHEET OF 46
FOR OFFICIAL USE ONLY
TRAVEL
294'-0"
EXIT SCHEDULE
AREA
OCCUPANTS
(1/100)
NUMBER OF
EXITS
PROVIDED
EGRESS WIDTH REQUIRED EGRESS WIDTH PROVIDED
STAIRS
(0.3)
OCCUPANTS
SERVED
OTHER
(0.2)
OCCUPANTS
SERVED
TOTAL EGRESS
WIDTH
REQUIRED
TOTAL
OCCUPANTS
SERVED
STAIRS
(0.3)
OCCUPANTS
SERVED
OTHER
(0.2)
OCCUPANTS
SERVED
TOTAL EGRESS
WIDTH
PROVIDED
TOTAL
OCCUPANTS
SERVED
5,400 SF 54 2 N/A N/A 10.8" 54 10.8" 181 N/A N/A 102" 510 102" 510
DIRECTIONAL CEILING
MOUNTED EXIT SIGN
WALL MOUNTED EXIT
SIGN
APPLICABLE CODES & STANDARDS:
EXISTING BUILDING USE AND OCCUPANCY CLASSIFICATION (IBC 302.1):
MIXED USE B, S-1, H-2
EXISTING BUILDING CONSTRUCTION CLASSIFICATION (IBC 602.2):
TYPE II-B CONSTRUCTION
BUILDING ELEMENTS ARE REQUIRED TO BE FIRE RESISTANT RATED AS FOLLOWS:
FIRE SUPPRESSION SYSTEM (UFC 3-600-01 CH. 4 & 6):
PORTABLE FIRE EXTINGUISHERS (NFPA 10):
FIRE CLASSIFICATION AND TRAVEL DISTANCE:
75' TRAVEL DISTANCE - TYPE ABC
LIGHT HAZARD (LOW): 1-2A TYPE ABC PER 3000 SF, 75' MAXIMUM TRAVEL DISTANCE
ORDINARY HAZARD (MODERATE):
EXTRA (HIGH) HAZARD: 1-4A TYPE ABC PER 1000 SF, 75' MAXIMUM TRAVEL DISTANCE
FIRE & SMOKE DAMPERS (NFPA 90A):
FIRE AND SMOKE DAMPERS ARE NOT REQUIRED
DETECTION ALARM & COMMUNICATION (UFC 3-600-01 CH. 5 & NFPA 100 3.4 (CH 12-42):
AUTOMATIC FIRE ALARM SYSTEM COMPLETE WITH SOUNDERS, STROBES, PULL STATIONS
AND RADIO TRANSMITTER
INTERIOR FINISHES CLASSIFICATION (NFPA 101 CH 10.2):
EXITS: CLASS A PER ASTM E84
EXIT ACCESS CORRIDORS: CLASS A PER ASTM E84
OTHER SPACES: CLASS A OR B PER ASTM E84
MEANS OF EGRESS:
OCCUPANT LOAD (NFPA 101 TABLE 7.3.1): B - BUSINESS AREAS - 100 GROSS
EGRESS CAPACITY (NFPA 101 7.3.3.1): DOORS = 0.2" PER OCCUPANT SERVED
NUMBER OF MEANS OF EGRESS (NFPA101 7.4.1): 2 PER NFPA 101 7.4.1
DEAD END LIMITS: 50' PER NFPA 101 39.2.5.2
COMMON PATH OF TRAVEL: 100' PER NFPA 101 39.2.5.3.1
TRAVEL DISTANCE TO EXITS: 300' PER NFPA 101 39.2.6.3
DISCHARGE FROM EXITS (NFPA 101 7.7.2): PLAN COMPLIES
ILLUMINATION OF MEANS OF EGRESS (NFPA 101 7.8): 1FC MINIMUM REQUIRED
EMERGENCY LIGHTING (NFPA 101 7.9 - 7.10): BATTERY BACKUP LIGHTS ARE PROVIDED
ACCESSIBILITY REQUIREMENTS:
BUILDING IS ACCESSIBLE PER UFC 3-600-01 CH. 1
BUILDING IS ACCESSIBLE PER UFAS
BUILDING IS ACCESSIBLE PER ADAAG
A COMPLETE AUTOMATIC SPRINKLER SYSTEM WILL BE PROVIDED -
DESIGN PER NFPA 13 AND UFC 3-600-01.
- UNITED FACILITIES CRITERIA (UFC): 1-200-01 - GENERAL BUILDING REQUIREMENTS,
NOVEMBER 27, 2007
- IC TECH SPEC FOR ICD / ICS 705 - OCTOBER 31, 2011
- UNITED FACILITIES CRITERIA (UFC): 3-600-01 - FIRE PROTECTION ENGINEERING FOR
FACILITIES, SEPTEMBER 26, 2006 INCLUDING CHANGE 1 JULY 14, 2009
- UNITED FACILITIES CRITERIA (UFC): 4-010-01 - DoD MINIMUM ANTITERRORISM
STANDARDS FOR BUILDINGS, OCTOBER 8, 2003
- ANG ETL 01-1-1 - AIR NATIONAL GUARD DESIGN POLICY, MARCH 2004
- INTERNATIONAL BUILDING CODE 2006 - FOR FIRE RESISTANCE REQUIREMENTS,
ALLOWABLE FLOOR AREA, BUILDING HEIGHTS AND BUILDING SEPARATION
DISTANCE REQUIREMENTS, EXCEPT AS MODIFIED BY UFC 3-600-01
- NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101-LIFE SAFETY CODE 2009
EDITION, FOR BUILDING EGRESS AND LIFE SAFETY - FOR CONFLICTS BETWEEN
IBC AND NFPA 101, CONFORM TO NFPA 101 AND APPLICABLE CRITERIA UFC
3-600-01
- UNIFORM FEDERAL ACCESSIBILITY STANDARDS (UFAS), AUGUST 1984 AND THE
AMERICANS WITH DISABILITIES ACT (ADAAG) AS AMENDED THROUGH JANUARY
1998.
1-2A TYPE ABC PER 1500 SF, 75' MAXIMUM TRAVEL DISTANCE
CODE SUMMARY
A-003
LI
FE
S
AF
ET
Y
PL
AN
16'0 8'4'
SCALE: 1/8" = 1'-0"
CONTRACTOR Main Work Area
1410612050M Polygon
1410612050M Line
1410612050M Rectangle
1410612050M Text Box Notes 1.) CONTRACTOR shall provide all labor, material, and equipment to complete job as indicated in this Statement of work and Drawings.
2.)The CONTRACTOR shall demo out existing steel vault door and properly dispose off base.
3.)The CONTRACTOR shall demo out existing threshold and properly dispose off base.
4.) The CONTRACTOR shall install new single hollow metal door and frame and install in current door opening in room #130
5.) IF CONTRACTOR shall use CMU to fill the rough opening to fit no less than a 36” hollow metal door and frame, if needed.
6.) The CONTRACTOR shall be required to paint any CMU the gets damaged or added on too. The contractor shall match existing CMU paint as close as possible.
7.)The CONTRACTOR shall paint the door and door frame Base Facility Standard. The contractor shall properly prep door and door frame for paint to make sure it gets proper adhesion.
8.)The CONTRACTOR shall install rubber gaskets around door frame to ensure that no noise can leak out through edges of door.
9.)The CONTRACTOR shall install heavy duty door closure and hardware.
10.)The CONTRACTOR shall install a combination lock that meets Federal Specifications FF-L-2740. (For Example Kaba-Mas X-09) The CONTRACTOR shall install panic hardware on secure side of door and a L shaped handle combination that includes a mortise lock cylinder on non-secured side that can be keyed to building
11.)The CONTRACTOR shall be required to install new metal threshold under door.
1410612050M Line
1410612050M Text Box Existing vault door and frame to be demolished and replaced with new hollow metal door and frame.
ML
O
TRAVEL
95'-0"
BLDG EXIT
1/100 B
0.2" 68"340
EXIT
1/100 B
0.2" 34"170
FE
FE
TRAVEL
126'-0"
BLDG EXIT
1/100 B
0.2" 34"170
UP
EXISTING
COMBAT
OPERATIONS
EXISTING
OPEN
OFFICE
EXISTING
ENTRY
SECURITY
OFFICE
VEST
OFFICE
OFFICE
129 OFFICE
OPEN
OFFICE
EXISTING
MAIN
WAREHOUSE
SERVER/
COMM ROOM
EXISTING
FLAMMABLES
LIFE SAFETY PLAN
SCALE: 1/8"=1'-0"
NORTH
LEGEND
DENOTES EXIT
ROUTE
TRAVEL
DISTANCE
START
POINT
EGRESS ELEMENT
USE AND OCCUPANCY
CLASSIFICATION
OCCUPANT LOAD
SERVED
REQUIRED ELEMENT
WIDTH
ACTUAL EGRESS WIDTH
PROVIDED
DENOTES
FLOOR OR
BUILDING EXIT
S.F. PER OCCUPANT
SURFACE MOUNTED
FIRE EXTINGUISHER
FE
CEILING MOUNTED EXIT
SIGN
EXIT
1/100 B
0.2" 46"230
SHEET
REFERENCE
NUMBER
D
ES
IG
N
E D
B Y
: A
JD
D W
N B
Y:
A
JD
R
EV
IE
W
E D
B Y
: C
LK
D
AT
E:
D
ES
IG
N
F
IL
E N
O
D R
AW
IN
G C
O D
E:
FI
LE
N
AM
E:
P
LO
T
D A
TE
P
LO
T
SC
AL
E:
R
EV
P ar kw ay
L an e, S ui te
N or cr os s, G
A
Ph on e
8.
6.
Fa x
8.
6.
W eb : w w w
.p on dc o.
co m
R
EV
D
ES
C
R
IP
TI
O
N P
R
EP
B Y
D
AT
E A
PR
VD
D R
A W
IN
G
R
EV
IS
IO
N S
FI
N
AL
S
U
BM
IT
TA
L
A
LT
ER
B
U
IL
D
IN
G
O
H
IO
N
AT
IO
N
AL
G
U
AR
D S
PR
IN
G
FI
E
LD
M
AP
, S P
R
IN
G
FI
EL
D
, O H
IO
/1
7/
C
D
B
A
54321
Id ea
C en te r B ou le va rd
D ay to n, O H
Ph on e
7.
1.
Fa x
7.
1.
W eb
: w w w .w oo lp er t.c om
FI
N
AL
S U
BM
IT
TA
L
-2
0-
S U
B M
IT
TE
D B
Y:
G
H C
SHEET OF 46
FOR OFFICIAL USE ONLY
TRAVEL
294'-0"
EXIT SCHEDULE
AREA
OCCUPANTS
(1/100)
NUMBER OF
EXITS
PROVIDED
EGRESS WIDTH REQUIRED EGRESS WIDTH PROVIDED
STAIRS
(0.3)
OCCUPANTS
SERVED
OTHER
(0.2)
OCCUPANTS
SERVED
TOTAL EGRESS
WIDTH
REQUIRED
TOTAL
OCCUPANTS
SERVED
STAIRS
(0.3)
OCCUPANTS
SERVED
OTHER
(0.2)
OCCUPANTS
SERVED
TOTAL EGRESS
WIDTH
PROVIDED
TOTAL
OCCUPANTS
SERVED
5,400 SF 54 2 N/A N/A 10.8" 54 10.8" 181 N/A N/A 102" 510 102" 510
DIRECTIONAL CEILING
MOUNTED EXIT SIGN
WALL MOUNTED EXIT
SIGN
APPLICABLE CODES & STANDARDS:
EXISTING BUILDING USE AND OCCUPANCY CLASSIFICATION (IBC 302.1):
MIXED USE B, S-1, H-2
EXISTING BUILDING CONSTRUCTION CLASSIFICATION (IBC 602.2):
TYPE II-B CONSTRUCTION
BUILDING ELEMENTS ARE REQUIRED TO BE FIRE RESISTANT RATED AS FOLLOWS:
FIRE SUPPRESSION SYSTEM (UFC 3-600-01 CH. 4 & 6):
PORTABLE FIRE EXTINGUISHERS (NFPA 10):
FIRE CLASSIFICATION AND TRAVEL DISTANCE:
75' TRAVEL DISTANCE - TYPE ABC
LIGHT HAZARD (LOW): 1-2A TYPE ABC PER 3000 SF, 75' MAXIMUM TRAVEL DISTANCE
ORDINARY HAZARD (MODERATE):
EXTRA (HIGH) HAZARD: 1-4A TYPE ABC PER 1000 SF, 75' MAXIMUM TRAVEL DISTANCE
FIRE & SMOKE DAMPERS (NFPA 90A):
FIRE AND SMOKE DAMPERS ARE NOT REQUIRED
DETECTION ALARM & COMMUNICATION (UFC 3-600-01 CH. 5 & NFPA 100 3.4 (CH 12-42):
AUTOMATIC FIRE ALARM SYSTEM COMPLETE WITH SOUNDERS, STROBES, PULL STATIONS
AND RADIO TRANSMITTER
INTERIOR FINISHES CLASSIFICATION (NFPA 101 CH 10.2):
EXITS: CLASS A PER ASTM E84
EXIT ACCESS CORRIDORS: CLASS A PER ASTM E84
OTHER SPACES: CLASS A OR B PER ASTM E84
MEANS OF EGRESS:
OCCUPANT LOAD (NFPA 101 TABLE 7.3.1): B - BUSINESS AREAS - 100 GROSS
EGRESS CAPACITY (NFPA 101 7.3.3.1): DOORS = 0.2" PER OCCUPANT SERVED
NUMBER OF MEANS OF EGRESS (NFPA101 7.4.1): 2 PER NFPA 101 7.4.1
DEAD END LIMITS: 50' PER NFPA 101 39.2.5.2
COMMON PATH OF TRAVEL: 100' PER NFPA 101 39.2.5.3.1
TRAVEL DISTANCE TO EXITS: 300' PER NFPA 101 39.2.6.3
DISCHARGE FROM EXITS (NFPA 101 7.7.2): PLAN COMPLIES
ILLUMINATION OF MEANS OF EGRESS (NFPA 101 7.8): 1FC MINIMUM REQUIRED
EMERGENCY LIGHTING (NFPA 101 7.9 - 7.10): BATTERY BACKUP LIGHTS ARE PROVIDED
ACCESSIBILITY REQUIREMENTS:
BUILDING IS ACCESSIBLE PER UFC 3-600-01 CH. 1
BUILDING IS ACCESSIBLE PER UFAS
BUILDING IS ACCESSIBLE PER ADAAG
A COMPLETE AUTOMATIC SPRINKLER SYSTEM WILL BE PROVIDED -
DESIGN PER NFPA 13 AND UFC 3-600-01.
- UNITED FACILITIES CRITERIA (UFC): 1-200-01 - GENERAL BUILDING REQUIREMENTS,
NOVEMBER 27, 2007
- IC TECH SPEC FOR ICD / ICS 705 - OCTOBER 31, 2011
- UNITED FACILITIES CRITERIA (UFC): 3-600-01 - FIRE PROTECTION ENGINEERING FOR
FACILITIES, SEPTEMBER 26, 2006 INCLUDING CHANGE 1 JULY 14, 2009
- UNITED FACILITIES CRITERIA (UFC): 4-010-01 - DoD MINIMUM ANTITERRORISM
STANDARDS FOR BUILDINGS, OCTOBER 8, 2003
- ANG ETL 01-1-1 - AIR NATIONAL GUARD DESIGN POLICY, MARCH 2004
- INTERNATIONAL BUILDING CODE 2006 - FOR FIRE RESISTANCE REQUIREMENTS,
ALLOWABLE FLOOR AREA, BUILDING HEIGHTS AND BUILDING SEPARATION
DISTANCE REQUIREMENTS, EXCEPT AS MODIFIED BY UFC 3-600-01
- NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101-LIFE SAFETY CODE 2009
EDITION, FOR BUILDING EGRESS AND LIFE SAFETY - FOR CONFLICTS BETWEEN
IBC AND NFPA 101, CONFORM TO NFPA 101 AND APPLICABLE CRITERIA UFC
3-600-01
- UNIFORM FEDERAL ACCESSIBILITY STANDARDS (UFAS), AUGUST 1984 AND THE
AMERICANS WITH DISABILITIES ACT (ADAAG) AS AMENDED THROUGH JANUARY
1998.
1-2A TYPE ABC PER 1500 SF, 75' MAXIMUM TRAVEL DISTANCE
CODE SUMMARY
A-003
LI
FE
S
AF
ET
Y
PL
AN
16'0 8'4'
SCALE: 1/8" = 1'-0"
Secured Area
1410612050M Rectangle
1410612050M Rectangle
1410612050M Rectangle
1410612050M Oval
1410612050M Oval
1410612050M Rectangle
1410612050M Rectangle
1410612050M Rectangle
1410612050M Oval
1410612050M Oval
1410612050M Oval
1410612050M Text Box Legend
CR /CARD READER WITH PIN PAD
RTEB / REQUEST TO EXIT BUTTON
PIR / CEILING MOUNT PIR SENSOR 360 DEGREE
HSS / HIGH SECURITY SWITCH
SCP / SECURITY CONTROL PANEL
ML / MAGNETIC LOCK / MAG-LOCK
WNS / WHITE NOISE SPEAKERS
EPO / EMERGENCY POWER OFF BUTTON
1410612050M Rectangle
1410612050M Oval
1410612050M Oval
1410612050M Rectangle
1410612050M Rectangle
1410612050M Rectangle
1410612050M Rectangle
1410612050M Line
1410612050M Line
1410612050M Rectangle
1410612050M Line
1410612050M Line
1410612050M Oval
1410612050M Text Box Notes
ALL Contractors bidding this job shall be required to use Advantor for the security side of this work.
1.) The CONTRACTOR shall field verify all measurements prior to execution.
2.)The CONTRACTOR shall provide all labor, material, and equipment to complete job as indicated in this Statement of work and Drawings.
3.) The CONTRACTOR shall install new mag-lock, HSS,RTEB,CR,EPO, WNS and PIR. All shall be submitted and approved by COR .
3.) The CONTRACTOR shall install control panel in protected area. Verify exact location with in secured area with Government.
4.) The CONTRACTOR shall be required to install no less than 3/4" conduit or flex for this job.
5.) The CONTRACTOR shall be required to install nothing less than a 4x4 junction box with cover.
6.) The CONTRACTOR shall supply a 120V circuit for security controls.
7.) All Security Control Panels and junction boxes that contain splices or terminations shall have a tamper switch installed.
8.) All junction Boxes for security wiring and communication shall have tamper resistant security screws.
9.) The CONTRACTOR shall install white noise speakers above ceiling in locations shown.
10) The CONTRACTOR shall supply dedicate circuit to white noise speakers.
11.) The CONTRACTOR shall insure all communications and security devices communicate with BDOC at Bldg 131 as well as security room with in Bldg 150.
12.) The CONTRACTOR shall perform final test on system with Government present to insure it is working properly.
13.) The CONTRACTOR shall provide training on new security system with Security Forces and Customer.
1410612050M Line
1410612050M Text Box Existing security Control panels
| 10 - 150 Drawing#1 Work Area and Door Install.pdf |
| 10 - 150 Security Install Drawing#1.pdf |
File details come from the government source that posted it. Updated .