Attachment 2 - Drawings NIAGARA FALLS AIR RESERVE STATION USAF-Repair TACAN Electrical Feed NY.pdf
PDF 7 MB Posted
- Attached to
- Repair TACAN Electrical Feed
- Solicitation number
- FA6670-20-B-0002
About this file
This is a notice for a federal construction contract solicitation for repair of a TACAN electrical feed at Niagara Falls Air Reserve Station. The project involves replacing an underground primary electrical feeder line connecting a TACAN, ILS, and fire training areas to the base electrical system, including replacement of pad mounted transformers, switching equipment, and related components. The estimated value is between $500,000 and $1,000,000. The solicitation is set aside 100% for HUBZone small businesses. Electronic submissions will not be accepted. Bid, payment and performance bonds are required. Liquidated damages will be identified in the contract. The site visit date is provided, and all questions must be submitted in writing by 31 August 2020. Only the full solicitation will be available electronically on SAM.gov; no paper copies will be provided. Interested vendors may register contact information on FBO.gov. Offerors must be registered in SAM and WAWF. The notice does not obligate funds or the government for any costs.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E C P
E C P
E C P
E C P E C P
MON. 2
PAPI
S U R V E Y D I S K V - 4 - 9 1
D I S K W / C R O S S
D I S K
TENNIS
COURTS
TRANSFORMER BANK
TACAN
ANTENNA
I L S
I L S A N T E N N A S
PAPI
W I N D C O N E A S S E M B L Y
ABANDONED FIRE TRAINING
FACILITY
FIRE TRAINING FACILITY
VACCANT FAA BLDGS.
FAA RTR SITE
CONTROL TOWER
W I N D S O C K E Q U I P M E N T
CONC. C
ULV. T
OP
C-119C -4
A I R P O R T
A R P R M 1
A R P R M 2
BLE WE TT A VE .
JO
H
N S
O N
S T
R E
E T
E N
T A
V E
N U
E
T U
S C
A R
O R
A R
O A
D
KRUG AVENUE
UTZ IG D RI VE
K
IR
K B
R
ID
G E
D R
IV
E
WA GN E R D R I V E
HU LB Y S TR EE T
KI R SC H DR I V E
A V
F U
E L
S C
IR
C
L E
R U
B
IN
W A
Y
MERRE L L LAN E
C O
O P
E R
C U
R V
E
C O
S E
G L
IA
S
T
PORTER ROAD
TUSCAR
ORA R
OAD
LOCK P OR T R OA D
PORTER ROAD
NIAGARA FALLS BOULEVARD
LOCK P OR T R OA D
304306308
M
M
M
M
M
61 6459
57- 1
51 51- 1
5050- 1
44- 1
43- 3 43- 143
43- 2
43- 4
14 614 5- 1
14 5
14 4
14 314 2
14 1
14 0
14 2- 1
13 9
13 8
13 7
13 6
13 5
13 4
13 3
13 2
13 2- 1
13 1- 1
13 1
13 2- 2
13 2- 3
13 2- 4 13 2- 513 2- 6
40393837
14 4- 1 14 3- 1
13 2- 7 13 2- 813 2- 9
13 0- 2
13 0- 1
13 012 7
12 8
12 9
12 6
34- 1
31 32
0-1
0-2
0-3
13- 2
13- 3
13- 1
15- 1
17- 1
20- 1
12 5
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
C-130 H
-30
C -130
H -30
SCALE:
B2
VIEW NAME
1/8" = 1'-0"
A4
EARTH
EARTH GRAVEL
CONCRETE
REGULAR
DETAIL TITLE
BUILDING SECTION
WALL SECTION
EXTERIOR / INTERIOR
ELEVATION
INTERIOR MULTI-VIEW
ELEVATION
MATERIALS
REFERENCE
DETAIL SECTION
AE402
C4
AE201
A1
AE305
SIM
A1
AE305
SIM
A1
AE305
SIM
AE505
C3
SIM
A3
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
KEYNOTE
REVISION NUMBER
ELEVATION INDICATION
COLUMN GRID
IDENTIFICATION
NORTH ARROW
?A1
1t EQUIPMENT TAG
D
NTRUE
NORTH
MATCHLINE
SCOPE OF WORK BOUNDARY
MH MH MH MH
MH MH MH
MH
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
P L A N N I N G
N
EW
S
NIAGARA FALLS AIR RESERVE STATION
LIST OF DRAWINGS DRAWING SYMBOLS
PARTIAL BASE PLAN
AIRFIELD OPERATIONS
(716) 236-2358
EMERGENCY NUMBER (ON BASE 911)
(716) 236-2117
AIR BASE FIRE DEPARTMENT
(716) 236-2086
CONTACT PHONE NUMBERS AT NFARS
AIR TRAFFIC CONTROL TOWER
AIRFIELD MANAGEMENT
(716) 236-2175
(716) 236-2358 (alt)
GRID COORDINATES: NAD 83
STATE PLANE NEW YORK WEST 3103
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO. SCALE: AS INDICATED
6/9/2020 5:26:15 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt
USAF-Repair TACAN Electrical Feed NY
9 June 2020
GI001
9 June 2020
USAF-Repair TACAN Electrical Feed NY
COVER SHEET
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CONTRACT NO . FA667018F0023
PROJECT NO.RVKQ190734
GENERAL
GI001 COVER SHEET
CIVIL
CS100 OVERALL SITE PLAN
CS101 SITE PLAN - EAST
CS102 SITE PLAN - WEST
CS103 CONSTRUCTION SAFETY AND PHASING PLAN
CS501 CIVIL DETAILS
ELECTRICAL
E-001 ELECTRICAL SYMBOLS
ES101 ELECTRICAL SITE PLAN
ES401 ELECTRICAL ENLARGED PLANS
ES501 ELECTRICAL DETAILS
ES601 ELECTRICAL RISER DIAGRAM
TOTAL SHEET COUNT: 11
06/09/2020
TAXIWAY - B
VASI VASI
TAXIWAY - A
TA
XI
W
AY
A1
ILS
TA
XI
W
AY
A
ILS ANTENNAS
TAXIWAY - E
BLEWETT AVE.
TU
SC
AR
OR
A
RO
AD
TA
XI
W
AY
A
KIRSCH DRIVE
AV
FU
EL
S
CI
RC
LE
RU
BI
N W
AY
WINDCONE ASSEMBLY
ABANDONED FIRE TRAINING FACILITY
FIRE TRAINING FACILITY
SURVEY DISK
V-4-91
DISK W/CROSS
DISK
7566'
3687'
4387' TORA
5438' 2844'
3544' TORA 6281'
1559'
2259' TORA
TAXIWAY - A
A-10 A-8 A-5
A-9 A-6A-7
TRANSFORMER
BANK
TACAN
ANTENNA
C C
C
C
C
C
E E
E
E
EEEE
T
SW
REFER TO SHEET CS101
REFER TO SHEET CS102
TB-2
TB-1
TB-3
TB-4
TB-5
NIGRA01-003
NIGRA01-002
NIGRA01-005
NIGRA01-001NIGRA01-004
APPROXIMATE AREA OF DRAINAGE
SWALE (CONTRACTOR TO FIELD VERIFY)
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO.SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
9 JUNE 2020
USAF-Repair TACAN Electrical Feed NY
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CS100
OVERALL SITE PLAN
1. CONTRACTOR IS TO ADHERE TO INSPECTION REQUIREMENTS OF SPECIFICATION SECTION 01 57 20.00 10 (EVERY 7 CALENDAR DAYS AND WITHIN 24 HOURS OF THE END OF A STORM EVENT OF 0.5 INCHES OR
GREATER.
2. INSTALL AND ESTABLISH EROSION CONTROL BMPS AT THE BEGINNING OF CONSTRUCTION AND MAINTAIN IN WORKING ORDER FOR THE DURATION OF LAND DISTURBING ACTIVITIES. REPAIR DAMAGES
CAUSED BY SOIL EROSION AND CONSTRUCTION EQUIPMENT AT OR BEFORE THE END OF EACH
WORKING DAY. PROVIDE ADDITIONAL BMPS TO SUPPLEMENT THE ORIGINAL DESIGN IF NEEDED TO PREVENT SEDIMENT FROM LEAVING THE LIMITS OF CONSTRUCTION DUE TO UNFORESEEN CONDITIONS.
3. CONDUCT LAND DISTURBING ACTIVITIES SO AS TO MINIMIZE THE SIZE AND DURATION OF THE WORK AREA EXPOSED AT ONE TIME. STABILIZE AND/OR TEMPORARILY SEED DISTURBED AREAS OF THE SITE AS SOON AS PRACTICAL FOLLOWING THE COMPLETION OR SUSPENSION OF CONSTRUCTION ACTIVITY.
4. BMPS SHOWN ON PLAN ARE PROVIDED AS A MINIMUM LEVEL OF PROTECTION AGAINST EROSION AND SEDIMENT LOSS. CONTRACTOR SHALL ADD, ADJUST, AND MAINTAIN BMPS AS NEEDED TO PROTECT
OFFSITE AREA FROM EXCESS EROSION AND SEDIMENT RUNOFF FROM THE SITE.
5. FOLLOWING THE CONCLUSION OF LAND DISTURBING ACTIVITIES AND FINAL STABILIZATION OF THE SITE, CONTRACTOR SHALL REMOVE THE TEMPORARY EROSION AND SEDIMENT CONTROL BMPS CLEAN OUT
ANY REMAINING SEDIMENT FROM STORM DRAINAGE CONVEYANCES AND STRUCTURES.
6. TOTAL AREA TO BE DISTURBED BY CONSTRUCTION = 0.67 ACRES
7. FOLLOWING THE COMPLETION OF FINAL GRADING ACTIVITIES, INSTALL PERMANENT SEEDING IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS (SECTION 32 92 19 SEEDING).
8. EISA SECTION 438 IS NOT APPLICABLE TO THIS PROJECT
EROSION & SEDIMENT CONTROL NOTES
1. THE SCOPE OF WORK SHOWN ON THE CIVIL PLANS SHALL BE PERFORMED IN ACCORDANCE WITH THE
REQUIREMENTS OF THE DETAILED PROJECT SPECIFICATIONS AND APPLICABLE OSHA REGULATIONS.
2. THE DESIGN SHOWN IS BASED ON THE ENGINEER'S UNDERSTANDING OF THE EXISTING SITE CONDITIONS WITHIN THE PROJECT BOUNDARY. EXISTING INFORMATION SHOWN ON THE CIVIL PLANS IS BASED UPON RECORD PLAN
AND GIS INFORMATION PROVIDED BY NIAGARA FALLS AIR RESERVE STATION.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING SITE CONDITIONS, INCLUDING THE LOCATION OF UNDERGROUND UTILITIES, PRIOR TO CONSTRUCTION. NOTIFY ENGINEER OF ANY DISCREPANCIES AFFECTING THE SCOPE OF
WORK.
4. PROTECT PROPERTY CORNERS AND BENCHMARKS WITHIN THE PROJECT BOUNDARY TO THE EXTENT PRACTICABLE. RELOCATE BENCHMARKS AS NECESSARY WITH A TOLERANCE OF 0.010 VERTICAL FEET.
5. THE CONTRACTOR IS SPECIFICALLY CAUTIONED THAT THE LOCATION OF EXISTING UTILITIES SHOWN ON THIS PLAN HAVE BEEN DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR CONVENIENCE
ONLY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THEIR ACCURACY.
6. PRIOR TO THE START OF LAND DISTURBING ACTIVITIES, THE CONTRACTOR SHALL CONTACT THE LOCAL UTILITY MARKING AUTHORITY (ONE CALL SERVICE) AND COORDINATE WITH THE RESPECTIVE UTILITY COMPANIES PRIOR TO THE REMOVAL AND/OR RELOCATION OF THE AFFECTED UTILITIES. THE CONTRACTOR SHALL COORDINATE WITH THE UTILITY COMPANY ANY FEES WHICH ARE TO BE PAID TO THE UTILITY COMPANY FOR THEIR SERVICES.
7. INSTALL EROSION AND SEDIMENTATION CONTROL MEASURES PRIOR TO THE START OF LAND DISTURBING
ACTIVITIES.
8. UNLESS OTHERWISE NOTED, THE CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS REQUIRED BY LOCAL, STATE AND FEDERAL AGENCIES PRIOR TO CONSTRUCTION AND BE RESPONSIBLE FOR ANY ASSOCIATED FEES.
9. ELECTRICAL ELEMENTS SHOWN ON THE CIVIL PLANS ARE FOR REFERENCE ONLY. REFER TO THE APPROPRIATE
DRAWINGS FOR CONSTRUCTION DETAILS OF THESE ITEMS.
10. DEBRIS AND REFUSE RESULTING FROM CONSTRUCTION OPERATIONS SHALL BE HAULED OFF-SITE AND
DISPOSED OF PROPERLY AT THE CONTRACTOR'S EXPENSE.
11. GENERAL NOTES THAT REFERENCE THE OWNER REFER TO THE CONTRACTING OFFICER ON THIS PROJECT.
12. PRIOR TO OBTAINING A DIG PERMIT, THE CONTRACTOR IS RESPONSIBLE FOR LOCATING AND MARKING ALL UTILITIES IN THE WORK AREA, INCLUDING THE OWNER'S UTILITIES. THE CONTRACTOR SHALL USE STANDARD UTILITY LOCATING METHODS AND EQUIPMENT INCLUDING LOCATORS AND GROUND PENETRATING RADAR AS
NEEDED.
13. CONSTRUCTION PERSONNEL WHO OPERATE VEHICLES WITHIN THE AIRFIELD WILL BE REQUIRED TO OBTAIN AIRFIELD DRIVERS TRAINING OR BE ACCOMPANIED BY AN ESCORT. CONTRACTOR SHALL COORDINATE TRAINING
AND ESCORTS THROUGH AIRFIELD MANAGEMENT (716)-236-2398.
14. WETLAND INFORMATION SHOWN ON THESE DOCUMENTS IS FROM A 2017 DELINEATION PROVIDED BY 914 CES.
15. SWALE SHOULD NOT BE DISTURBED (INCLUDING TRAFFIC FROM HEAVY EQUIPMENT) AND IF NECESSARY IT WILL
NEED TO BE RESTORED IN KIND.
GENERAL NOTES
100'
SCALE: 1"=200'-0"
0 100' 200'
N
LEGEND EXISTING PROPOSED
BUILDING
WETLAND AREA
FLOODPLAIN
SILT FENCE
SECURITY FENCE
STORM SEWER
SANITARY SEWER
DOMESTIC WATER MAIN
COMMUNICATIONS
POWER
NATURAL GAS
SOIL BORING LOCATION NIGRA01-000 TB-0
E
T
SW
ELECTRIC MANHOLE
ELECTRICAL SWITCH
TRANSFORMER
1. SOIL MATERIAL EXCAVATED FOR INSTALLATION OF THE PROPOSED ELECTRICAL DUCT BANK MUST BE PLACED BACK INTO THE TRENCH FROM WHERE IT WAS INITIALLY REMOVED AND MAY NOT BE STOCKPILED ON SITE.
2. EXCAVATED SOIL THAT IS EXCESS OF WHAT CAN BE DIRECTLY REPLACED INTO THE TRENCH (DUE TO THE ADDED VOLUME OF THE DUCT BANK) SHALL BE SPREAD OVER THE TOP OF TRENCH AND STABILIZED IN ACCORDANCE WITH THE PROJECT REQUIREMENTS ONLY WHERE THE EXCAVATION IS NOT LOCATED WITHIN A
FLOODPLAIN AS IDENTIFIED ON THE PROJECT PLANS.
3. CONTRACTOR RESPONSIBLE FOR THE POLLUTION PREVENTION AND CONTROL OF LITTER, CONSTRUCTION CHEMICALS, AND CONSTRUCTION DEBRIS FROM BECOMING A POLLUTANT SOURCE IN STORMWATER.
ENVIRONMENTAL NOTES
· CONTRACTING OFFICER:
ANDREW CHURCH (914 MSG/PK)
(716) 236-2216
· AIRFIELD MANAGER:
GERRY GILCHRIST
(716) 236-2358
· BASE ENVIRONMENTAL:
KIMBERLY POWELL
(716) 236-3126
· CIVIL ENGINEERING:
ANDREW SALISBURY
(716) 236-3122
POINTS OF CONTACT
TA
XI
W
AY
A
A-10 A-9
C C
C
C
E E
E
E
EE
DIRECTIONAL BORE CONDUIT
BENEATH WETLAND/DITCH
SEE DETAIL C1/CS501
SOURCE CONNECTION POINT
REFER TO SHEET EP101
DIRECTIONAL BORE CONDUIT
BENEATH WETLAND/DITCH
SEE DETAIL C1/CS501
PERIMETER FENCE
PERIMETER FENCE
AIRFIELD FENCE
EXISTING COMM LINE
ABANDON EXISTING TACAN
POWER LINES IN PLACE
NEW ELECTRICAL DUCT BANK
REFER TO SHEET ES101
EXISTING WETLAND/REGULATED
DITCH AREA - DO NOT DISTURBEXISTING WETLAND/REGULATED
DITCH AREA - DO NOT DISTURB
INSTALL SILT FENCE ON
DOWNSLOPE SIDE OF EXCAVATION
SEE DETAIL E1/CS501
INSTALL SILT FENCE ON
DOWNSLOPE SIDE OF EXCAVATION
SEE DETAIL E1/CS501
EXISTING MANHOLE WITH
TERMINATION TO
TEMPORARY TACAN FEEDER
EXISTING ABOVEGROUND POWER FEEDER USED AS A TEMPORARY REPAIR FOR THE
TACAN ELECTRICAL FEEDER. THE CONDUIT, CONDUCTORS, AND SUPPORT FOR THIS
TEMPORARY FEEDER SHALL BE REMOVED AS PART OF THE CONSTRUCTION OF THIS
PROJECT, AFTER THE NEW PERMANENT FEEDER IS FULLY OPERATIONAL.
LIMITS OF DISTURBANCE
ELECTRICAL MANHOLE (TYPICAL)
REFER TO SHEET ES101
STAGING/LAYDOWN AREA
~5400 SQ FT.
CONCRETE WASHOUT
SEE DETAIL E9/CS501
APPROXIMATE AREA OF DRAINAGE
SWALE (CONTRACTOR TO FIELD VERIFY)
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO.SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
9 JUNE 2020
USAF-Repair TACAN Electrical Feed NY
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CS101
SITE PLAN - EAST
30'
SCALE: 1"=60'-0"
0 30' 60'
N
LEGEND EXISTING PROPOSED
BUILDING
WETLAND AREA
FLOODPLAIN
SILT FENCE
SECURITY FENCE
STORM SEWER
SANITARY SEWER
DOMESTIC WATER MAIN
COMMUNICATIONS
UNDERGROUND ELECTRICAL
NATURAL GAS
SOIL BORING LOCATION NIGRA01-000 TB-0
E
T
SW
ELECTRIC MANHOLE
ELECTRICAL SWITCH
TRANSFORMER
LIMITS OF DISTURBANCE
DRAINAGE SWALE
TAXIWAY - A
TA
XI
W
AY
A1
WINDCONE ASSEMBLY
TRANSFORMER
BANK
TACAN
ANTENNA
C
C
EEE
T
SW
NEW ELECTRICAL DUCT BANK
REFER TO SHEET ES101
PERIMETER FENCE
TACAN EQUIPMENT BUILDING CONNECTION
REFER TO SHEET EP101
REMOVE & REPLACE EXISTING ACCESS
DRIVEWAYS IN KIND TO ACCOMMODATE
INSTALLATION OF NEW DUCT BANK
INSTALL SILT FENCE ON
DOWNSLOPE SIDE OF EXCAVATION
SEE DETAIL E1/CS501
TRANSFORMER PAD
SEE DETAIL E3/CS501
LIMITS OF DISTURBANCE
APPROXIMATE AREA OF DRAINAGE
SWALE (CONTRACTOR TO FIELD VERIFY)
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO.SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
9 JUNE 2020
USAF-Repair TACAN Electrical Feed NY
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CS102
SITE PLAN - WEST
30'
SCALE: 1"=60'-0"
0 30' 60'
N
LEGEND EXISTING PROPOSED
BUILDING
WETLAND AREA
FLOODPLAIN
SILT FENCE
SECURITY FENCE
STORM SEWER
SANITARY SEWER
DOMESTIC WATER MAIN
COMMUNICATIONS
UNDERGROUND ELECTRICAL
NATURAL GAS
SOIL BORING LOCATION NIGRA01-000 TB-0
E
T
SW
ELECTRIC MANHOLE
ELECTRICAL SWITCH
TRANSFORMER
LIMITS OF DISTURBANCE
DRAINAGE SWALE
VASI VASI
LOCKPORT ROAD
TAXIWAY - A
TA
XI
W
AY
A1
TA
XI
W
AY
A
BLEWETT AVE.
JO
HN
SO
N
ST
RE
ET
EN
T
AV
EN
UE
TU
SC
AR
OR
A
RO
AD
LOCKPORT ROAD
TAXIWAY - A
TA
XI
W
AY
A
WAGNER DRIVE
KIRSCH DRIVE
AV
FU
EL
S
CI
RC
LE
RU
BI
N W
AY
MERRELL LANE
CO
OP
ER
C
UR
VE
TRANSMISSOMETER
WINDCONE ASSEMBLY
ABANDONED FIRE TRAINING FACILITY
7566'
3687'
4387' TORA
5438'
1559'
2259' TORA
TAXIWAY - A
A-3 A-1
A-10 A-8 A-5 A-4
A-9
A-2A-6A-7
TENNIS
COURTS
TRANSFORMER
BANK
TACAN
ANTENNA
C C
C
C
C
C
E E
E
E
EEEE
T
SW
HAUL ROUTE
ENTER BASE
FROM MAIN GATE
ON ENTRANCE AVE
TAXIWAY BARRICADE
ALL WORK WITHIN THE TAXIWAY OBJECT FREE AREA SHALL
ONLY BE DONE DURING TAXIWAY CLOSURES. CONTRACTOR
SHALL COORDINATE PHASING AND CLOSURES WITH THE
AIR FORCE RESERVE OPERATIONS
TAXIWAY BARRICADE
TAXIWAY BARRICADETAXIWAY BARRICADE
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO.SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
9 JUNE 2020
USAF-Repair TACAN Electrical Feed NY
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CS103
CONSTRUCTION SAFETY AND PHASING PLAN
100'
SCALE: 1"=200'-0"
0 100' 200'
N
NIGRA01-000 TB-0
E
T
SW
1. PHASE 1 - ESTABLISH BARRIERS ALONG PROJECT AREA AND MARK OUT HAUL ROUTE
2. PHASE 2 - POWER LINE WILL BE TRENCHED IN STARTING FROM THE WEST MOVING EASTWARD
ALONG THE HAUL ROUTE.. COMPLETE TURF ESTABLISHMENT AS THE POWER LINE IN
TRENCHED IN.
3. PRIOR TO BEGINNING CONSTRUCTION, THERE WILL BE A PRE-CONSTRUCTION MEETING FOR
REVIEWING PHASING SCHEDULE AND APPROVING CRITICAL SUBMITTALS.
PHASING NOTESLEGEND EXISTING PROPOSED
BUILDING
WETLAND AREA
FLOODPLAIN
SILT FENCE
SECURITY FENCE
STORM SEWER
SANITARY SEWER
DOMESTIC WATER MAIN
COMMUNICATIONS
POWER
NATURAL GAS
SOIL BORING LOCATION
ELECTRIC MANHOLE
ELECTRICAL SWITCH
TRANSFORMER
HAUL ROUTE
BARRICADE
1. TAXIWAY A WILL BE CLOSED FROM THE WEST EDGE OF THE MAIN RAMP TO THE APPROACH FOR
RWY 10L. TAXIWAYS A1 AND A2 WILL BE CLOSED.
2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND PLACING ALL BARRIERS AND REMOVING
BARRIERS AT THE CONCLUSION OF THE PROJECT.
3. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING AIRFIELD PAVEMENTS WITHIN THE WORK AREA
TO PREVENT ANY ACCUMULATION OF DIRT OR FOREIGN OBJECT DEBRIS. CONTRACTOR SHALL
SWEEP AND CLEAN AIRFIELD PAVEMENTS WITHIN THE WORK AREA WITH A SELF-PROPELLED
VACUUM PICKUP SWEEPER AS NEEDED AND AT A MINIMUM AT THE END OF EVERY WORKDAY.
4. WORK HOURS ARE 0700 TO 1600 MONDAY THROUGH FRIDAY. WORK IS NOT ALLOWED ON
WEEKENDS OR GOVERNMENT HOLIDAYS UNLESS REQUESTED IN WRITING AND APPROVED BY 914
CE AT MINIMUM 14 CALENDAR DAYS IN ADVANCE.
5. ALL PERSONNEL DRIVING ON THE AIRFIELD WILL BE REQUIRED TO ATTEND A TRAINING SESSION
WITH AIRFIELD MANAGEMENT PERSONNEL PRIOR TO OBTAINING ACCESS.
6. NO WORK WILL BE ALLOWED JUNE 14-21, 2021 DUE TO A SCHEDULED AIR SHOW. ALL BARRIERS AND
CONTRACTOR EQUIPMENT MUST BE REMOVED PRIOR TO JUNE 14, 2021 TO ALLOW FULL
OPERATION OF THE RUNWAYS, APRONS, AND TAXIWAYS DURING THIS PERIOD. WORK AREAS AND PAVEMENTS SHALL BE CLEANED AND REMOVED OF ANY FOREIGN OBJECT DEBRIS. NO ELECTRICAL
OUTAGES ARE ALLOWED DURING THIS PERIOD. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ANY ADDITIONAL MOBILIZATIONS/DEMOBILIZATIONS NECESSARY TO ACCOMMODATE THIS WORK
EXCLUSION PERIOD.
SPECIAL NOTES
NO SCALE
TAXIWAY BARRICADED2
· CONTRACTING OFFICER:
ANDREW CHURCH (914 MSG/PK)
(716) 236-2216
· AIRFIELD MANAGER:
GERRY GILCHRIST
(716) 236-2358
· BASE ENVIRONMENTAL:
KIMBERLY POWELL
(716) 236-3126
· CIVIL ENGINEERING:
ANDREW SALISBURY
(716) 236-3122
POINTS OF CONTACT
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO.SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
9 JUNE 2020
USAF-Repair TACAN Electrical Feed NY
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
CS501
CIVIL DETAILS
TRENCH
(BACKFILLED)
WOVEN WIRE
SUPPORT
(IF USED)
WOOD FENCE POSTS
(MAX. 8' SPACING)
RECOMMENDED TOE-IN
METHOD
NOTES:
1. WOOD POSTS WHICH SUPPORT THE SILT FENCE SHALL BE INSTALLED ON A SLIGHT
ANGLE TOWARD THE ANTICIPATED RUNOFF SOURCE.
2. SILT FENCE SHALL BE TRENCHED IN WITH A SPADE OR MECHANICAL TRENCHER SO
THAT THE DOWNSLOPE FACE OF THE TRENCH IS FLAT AND PERPENDICULAR TO THE
LINE OF FLOW.
3. THE TRENCH SHOULD BE A MINIMUM OF 6" DEEP AND 3"-4" WIDE TO ALLOW FOR THE
SILT FENCE TO BE PLACED IN THE GROUND AND BACKFILLED.
4. SILT FENCE SHOULD BE SECURELY FASTENED TO EACH WOOD SUPPORT POST OR TO
WOVEN WIRE WHICH IS IN TURN ATTACHED TO THE WOOD FENCE POSTS.
5. INSPECTION SHALL BE FREQUENT AND REPAIR OR REPLACEMENT SHALL BE MADE
PROMPTLY AS NEEDED.
6. SILT FENCE SHALL BE REMOVED WHEN IT HAS SERVED ITS USEFULNESS SO AS NOT TO
BLOCK OF IMPEDE STORM FLOW OR DRAINAGE.
7. SEDIMENT TRAPPED BY THIS PRACTICE SHALL BE UNIFORMLY DISTRIBUTED ON THE
SOURCE AREA PRIOR TO TOPSOILING.
FLOW
SILT
FENCE
SCALE:
SILT FENCE
NO SCALE
2"8"
4"
CONCRETE ELECTRICAL PAD,
MINIMUM 8" THICK
NOTE:
COORDINATE OPENINGS IN TRANSFORMER
PAD WITH ELECTRICAL CONTRACTOR.
SCALE:
CONCRETE ELECTRICAL TRANSFORMER PAD
NO SCALE
HMAC SURFACE COURSE
MINIMUM 2" DEPTH
PLACE TO 1" ABOVE
EXIST. PVMT GRADE
6" TRENCH WIDTH6" 6"6"
ITL APPROVED BACKFILL
MATERIAL COMPACTED PER
SPECIFICATIONS.
HMAC BASE COURSE
TO DEPTH OF
EXISTING PVMT
MINIMUM 3" DEPTH
TACK COAT ON ALL
EXPOSED EDGES
AND SURFACES
EXIST. ASPHALT
PAVEMENT
FULL-DEPTH BITUMINOUS PAVEMENT REPAIR
PRIMARY POWER DUCTBANK
ENTRANCE PIT
BORING LENGTH
MAINTAIN MINIMUM
OF 3' DEPTH AT
PAVED ACCESS
ROADS
TYPICAL DIRECTIONAL BORING DETAIL
RECEIVING PIT
DIRECTIONALLY
BORED DUCT BANK
UTILITY CROSSING
2'
MI
N.
PAVED ACCESS
ROAD
3'
WETLAND
3'
MAINTAIN MINIMUM
OF 3' DEPTH AT
WETLAND CROSSINGS
2'
MI
N.
UTILITY CROSSING
E3 E6E1
C1
CONCRETE WASHOUT
NO SCALEE9
SET TOP OF PAD 4" ABOVE
ADJACENT GRADE
GROUND
ELEVATION
WELL-COMPACTED GRAVEL
BASE, MINIMUM 6" THICK
REINFORCEMENT 6"x6" - W2.9/W2.9
MESH, PLACED UNIFORMLY 4"
BELOW TOP OF SLAB
8' X 8' MIN OR AS
REQUIRED TO
CONTAIN WASTE
CONCRETE
2'-0" MIN
BERM AROUND PERIMETER
GROUND SURFACE
12" MIN
12" MIN
COMPACTED EMBANKMENT
MATERIAL (TYP.)
3:1 OR FLATTER
SIDE SLOPES
NOTES:
1. CONCRETE WASHOUT AREA SHALL BE INSTALLED PRIOR TO ANY CONCRETE PLACEMENT ON SITE.
2. CONCRETE WASHOUT AREA SHALL BE LINED WITH MINIMUM 10 MIL THICK PLASTIC LINER.
3. VEHICLE TRACKING CONTROL IS REQUIRED IF ACCESS TO CONCRETE WASHOUT AREA IS OFF
PAVEMENT.
4. THE CONCRETE WASHOUT AREA SHALL BE REPAIRED AND ENLARGED OR CLEANED OUT AS
NECESSARY TO MAINTAIN CAPACITY FOR WASTED CONCRETE.
5. AT THE END OF CONSTRUCTION, ALL CONCRETE SHALL BE REMOVED FROM THE SITE AND
DISPOSED OF AT AN ACCEPTED WASTE SITE.
6. WHEN THE CONCRETE WASHOUT AREA IS REMOVED, THE DISTURBED AREA SHALL BE SEEDED
AND MULCHED OR OTHERWISE STABILIZED IN A MANNER ACCEPTABLE TO THE INSTALLATION.
DESCRIPTIONSYMBOL
CIRCUIT BREAKER
MOTOR STARTER, # INDICATES NEMA STARTER SIZE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
DRAWOUT CIRCUIT BREAKER
FUSE
GROUND CONNECTION
GENERATOR
KIRK KEY INTERLOCK
LIGHTNING ARRESTOR
MAGENTIC MOTOR STARTER
METER (AS SPECIFIED)
SWITCH
TRANSFER SWITCH, AUTOMATIC UON
TRANSFORMER
ATS BYPASS
SOLID-STATE MULTI-FUNCTION METER
AMMETER AND PHASE SELECTOR SWITCH
VOLTMETER AND PHASE SELECTOR SWITCH
PANELBOARD
PREWIRED CONTROL PANEL
SURGE PROTECTIVE DEVICE
DISCONNECT SWITCH
CT
PT
G
G F P GROUND FAULT PROTECTOR
K
M
3 CT
AAS
VVS
X-X
TRANSIENT VOLTAGE SURGE SUPPRESSION
PWCP
SPD
TVSS
ONE-LINE DIAGRAM
DESCRIPTIONSYMBOL
POWER DISTRIBUTION
CONDUIT DOWNWARD
CONDUIT UPWARD
CONDUIT CONTINUATION
SURFACE MOUNTED BRANCH PANELBOARD
FLUSH MOUNTED BRANCH PANELBOARD
DISTRIBUTION PANEL OR SWITCHBOARD
SWITCHGEAR OR SWITCHBOARD
MOTOR CONTROL CENTER
ELECTRICAL CABINET OR SPECIAL PURPOSE ENCLOSURE
PULL BOX
MANHOLE
HANDHOLE
AUTOMATIC TRANSFER SWITCH
SURGE PROTECTION DEVICE
PB
MH
HH
ATS
SPD
VARIABLE FREQUENCY DEVICEVFD
MOTOR
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
INDIVIDUAL MOLDED CASE CIRCUIT BREAKER IN ENCLOSURE
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH
J
J
J
JUNCTION BOX, WALL MOUNTED
JUNCTION BOX, FLUSH MOUNTED ON CEILING
JUNCTION BOX, FLUSH MOUNTED IN FLOOR
CONDUIT END CAP
ELECTRICAL SYMBOL LEGEND NOTES
1. ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED ON PLANS.
MOUNTING HEIGHT A.F.F. TO CENTER LINE OF DEVICE
DESCRIPTIONSYMBOL
SUBSCRIPTS
MOUNT DEVICE 6' ABOVE COUNTER OR 36" A.F.F. AT
WORKSTATIONS
DEDICATED
EMERGENCY
EXPLOSION PROOF, CLASS GROUP AND DIVISION AS NOTED
UNIT IS CONNECTED TO FIRE ALARM SYSTEM
GROUND FAULT CIRCUIT INTERRUPTER
HOSPITAL GRADE
ISOLATED GROUND
44"
AC
D
E
EX
FA
GF
H
IG
UNSWITCHED NIGHT LIGHT
RAINTIGHT NEMA TYPE 3R OR EQUIVALENT
SURGE PROTECTED TYPE RECEPTACLE
TAMPER-RESISTANT
TELEVISION
CONNECTED TO UPS SYSTEM
WEATHERPROOF NEMA TYPE 3 OR EQUIVALENT
NL
RT
SP
T
TV
U
WP
PAN, TILT, ZOOM TYPE CAMERAPTZ
R RELAY
RECESSED FLOOR DUCT, TYPE/SIZE AS INDICATED ON PLANS
POLE MOUNTED TRANSFORMER
3 PHASE POLE MOUNTED TRANSFORMERS
CONDUIT EXPOSED OR CONCEALED, REFER TO PLANS
A AMPERES
AC ALTERNATING CURRENT
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERES INTERRUPTING CAPACITY
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BKBD BACKBOARD
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CLG CEILING
CKT CIRCUIT
COMM COMMUNICATION
CORR CORRIDOR
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU CONDENSING UNIT
CU COPPER
DISC DISCONNECT
DIST DISTRIBUTION
DWG DRAWING
EA EACH
EF EXHAUST FAN
EGB EQUIPMENT GROUND BAR
ELEC ELECTRICAL
EMH ELECTRICAL MANHOLE
EMT ELECTRICAL METALLIC TUBING
EQ EQUAL
EQUIP. EQUIPMENT
EWH ELECTRIC WATER HEATER
EUH ELECTRIC UNIT HEATER
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FT FEET
G GROUND
GEN GENERATOR
GF GROUND FAULT CIRCUIT INTERRUPTER
G.F.C.I. GOVT. FURNISHED, CONTRACTOR INSTALLED
G.F.G.I. GOVT. FURNISHED, GOVT. INSTALLED
GND GROUND
GRD GROUNDED
GOVT. GOVERNMENT
GRS GALVANIZED RIGID STEEL CONDUIT
HP HORSEPOWER
HVAC HEATING, VENTILATION,
AIR CONDITIONING
HWP HOT WATER PUMP
HZ HERTZ
IN INCHES
J-BOX JUNCTION BOX
kcmil or KCM THOUSAND CIRCULAR MILS
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LA LIGHTNING ARRESTOR
LPI LIGHTNING PROTECTION INSTITUTE
LTG LIGHTING
LV LOW VOLTAGE
M METER
MTBB MAIN TELEPHONE BACK BOARD
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MTD MOUNTED
MTS MANUAL TRANSFER SWITCH
N NEUTRAL
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NF NON-FUSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OCPD OVER-CURRENT PROTECTION DEVICE
ELECTRICAL ABBREVIATIONS
P POLE (1P = 1 POLE, 2P = 2 POLE, ETC.)
P PUMP
PA PUBLIC ADDRESS
PB PULL BOX
PB PUSHBUTTON
PH PHASE
PIV POST INDICATOR VALVE
PNL PANEL
PP POWER POLE
PSI POUNDS PER SQUARE INCH
PT POTENTIAL TRANSFORMER
PTZ PAN-TILT-ZOOM
PVC POLYVINYL-CHLORIDE
PWR POWER
RC REMOTE CONTROL
RCVR RECEIVER
REC RECEPTACLES CIRCUIT
REQD REQUIRED
REV REVISION
RF RETURN FAN
RGS RIGID GALVANIZED STEEL
RM ROOM
RMU RACK MOUNTING UNITS
RPM REVOLUTIONS PER MINUTE
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SCH SCHEDULE
SEC SECURITY
SF SQUARE FEET
SF SUPPLY FAN
SFL SUB FEED LUGS
SN SOLID NEUTRAL
SP SINGLE POLE
SP SUMP PUMP
SPD SURGE PROTECTION DEVICE
SPEC SPECIFICATION
SPKR SPEAKER
SST STAINLESS STEEL
ST SHUNT TRIP
ST SINGLE THROW
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
TBB TELEPHONE BACK BOARD
TCC TELECOMMUNICATIONS CABINET
TEL TELEPHONE
TELE TELEPHONE
TEMP TEMPERATURE
TFL THRU FEED LUGS
TL TWIST-LOCK
TR TAMPER RESISTANT
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UE UNDERGROUND ELECTRICAL
UFC UNITED FACILITIES CRITERIA
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UT UNDERGROUND TELECOMMUNICATIONS
UON UNLESS OTHERWISE NOTED
UV ULTRAVIOLET
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VA VOLT AMPERES
VAR VOLT AMPERES REACTIVE
VD VOLTAGE DROP
VDT VIDEO DISPLAY TERMINAL
VFD VARIABLE FREQUENCY DRIVE
W WATTS
W WIDE
W WIRES
WH WATER HEATER
WP WEATHERPROOF
W/ WITH
W/O WITHOUT
XFMR TRANSFORMER
XMTR TRANSMITTER
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO. SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
6/9/2020 5:26:09 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt
E-001
9 June 2020
USAF-Repair TACAN Electrical Feed NY
ELECTRICAL SYMBOLS
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
ECP
MON. 2
SURVEY DISK
V-4-91
DISK W/CROSS
DISK
TRANSFORMER BANK
TACAN
ANTENNA
ILS
ILS ANTENNAS
WINDCONE ASSEMBLY
ABANDONED FIRE TRAINING
FACILITY
FIRE TRAINING FACILITY
M
M
M
M
LBS
LBS
LBS
ES401
A1
ES401
D1
EXISTING UNDERGROUND POWER DUCTBANKS AND DIRECT
BURIED CONDUCTORS SERVING WEST-END AIRFIELD LOADS
TO REMAIN FOR CONTINUED OPERATION. (TYP)
EXISTING ABOVEGROUND POWER FEEDER USED AS A
TEMPORARY REPAIR FOR THE TACAN ELECTRICAL
FEEDER. THE CONDUIT, CONDUCTORS, AND SUPPORT
FOR THIS TEMPORARY FEEDER SHALL BE REMOVED AS
PART OF THE CONSTRUCTION OF THIS PROJECT, AFTER
THE NEW PERMANENT FEEDER IS FULLY OPERATIONAL.
EXISTING HANDHOLE WITH
TERMINATION TO TEMPORARY
TACAN FEEDER
NEW ELECTRICAL DUCTBANK ROUTE, REFER TO
CIVIL PLANS FOR ADDITIONAL DETAILS (TYP).
E5
ES501
NEW TYPE 3 MANHOLE
SEE E1/ES501 (TYP)
NEW TYPE 3 MANHOLE
SEE E1/ES501 (TYP)
EXISTING TRANSFORMER
SERVING ILS BUILDING
TO REMAIN
MH MH MH MH
MH
MH
MH
MH
EXISTING TRANSFORMER
SERVING FIRE TRAINING
FACILITY TO REMAIN
SW-WEST
T-TACAN
T-AFL
SW-MON 2
T-ILS
T-FT
EXISTING TRANSFORMER
SERVING AIR FIELD LIGHTING
LOADS TO REMAIN
T-WEST
T-MON 2
SW-TACAN
DIRECTIONAL BORE CONDUIT -
REFER TO CIVIL PLANS (TYP)
1. SITE PLAN IS SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO CIVIL PLANS FOR
FURTHER DETAILS AND LOCATIONS FOR DIRECTIONAL BORING (DB).
2. A DB PLAN SHALL BE SUBMITTED TO THE AIR FORCE FOR REVIEW AND APPROVAL A
MINIMUM OF 30-DAYS PRIOR TO ANY SITE WORK.
SITE PLAN GENERAL NOTES:
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO. SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
6/9/2020 5:26:10 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt
ES101
9 June 2020
USAF-Repair TACAN Electrical Feed NY
ELECTRICAL SITE PLAN
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
SCALE: 1" = 200'-0"
C1
ELECTRICAL SITE PLAN
SCALE : 1" = 200'-0"
0 200' 400'
N
TRANSFORMER BANK
TACAN
ANTENNA
M
LBS
MON. 2
M
LBS
NEW PRIMARY SWITCH
'SW-WEST'
NEW PAD MOUNTED
TRANSFORMER 'T-TACAN'
EXISTING TRANSFORMER 'T-AFL'
SERVING AIR FIELD LIGHTING
LOADS TO REMAIN
NEW SECONDARY SERVICE
CONDUIT AND CONDUCTORS
EXISTING OPEN-AIR FENCED
IN SWITCHYARD 'SW-TACAN'
TO REMAIN
NEW ELECTRICAL DUCTBANK ROUTE, REFER TO
CIVIL PLANS FOR ADDITIONAL DETAILS (TYP)
NEW PAD MOUNTED
TRANSFORMER 'T-WEST'
NEW SERVICE DISCONNECT
TO REPLACE EXISTING
NEW UTILITY METER
EXISTING PRIMARY SWITCH 'SW-MON 2'
TO REMAIN
EXISTING PAD MOUNTED TRANSFORMER 'T-MON 2'
AND PRIMARY FEEDER TO BE REMOVED
EXISTING PAD MOUNTED TRANSFORMER
TO REMAIN
NEW ELECTRICAL DUCTBANK
ROUTE, REFER TO CIVIL PLANS
FOR ADDITIONAL DETAILS (TYP)
STUB OUT AND CAP (2) 5-INCH CONDUITS BEYOND THE DRIVEWAY EDGE
A MINIMUM OF 25-FOOT FOR FUTURE EXTENSION. PROVIDE CONCRETE
ENCASEMENT FOR THE ENTIRE RUN TO WITHIN 1-FOOT OF THE END OF
THE CONDUITS AS NECESSARY FOR FUTURE CONDUIT TIE-IN. PROVIDE
ABOVE GRADE MARKING TO INDICATE LOCATION OF END OF CONDUITS.
KEY NOTES
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO. SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
6/9/2020 5:26:11 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt
ES401
9 June 2020
USAF-Repair TACAN Electrical Feed NY
ELECTRICAL ENLARGED PLANS
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
SCALE: 1" = 20'-0"
A1
ENLARGED PLAN - TACAN ANTENNA AREA
SCALE: 1" = 20'-0"
D1
ENLARGED PLAN - MAIN POWER SOURCE AREA
SCALE : 1" = 20'-0"
0 20' 40'10'
N
N
SECONDARY COMPARTMENT
CONCRETE PAD
GRADE
LOW VOLTAGE CABLE TERMINATIONS
SECONDARY CIRCUIT
2'-0"
MIN
#4/0 BARE COPPER GROUND LOOP
ENCIRCLING ENTIRE CONCRETE PAD.
MIN 18" BELOW FINISHED GRADE.
GROUND ROD, TYP OF
4, ONE AT EACH
CORNER OF PAD.
GROUND PAD (TYP OF 2)
#4/0 BARE
(600V)
PRIMARY CIRCUIT
LOAD BREAK
CONNECTOR
PRIMARY NEUTRAL
BUSHING INSERT
(3) 2-POSITION LOAD
BREAK OIL SWITCH
OIL-IMMERSED CURRENT-
LIMITING FUSES
PRIMARY COMPARTMENT
SURGE ARRESTERS
(6) TRANSFORMER
BUSHING WELLS
X0
BAYONET OIL-IMMERSED
EXPULSION FUSES
CABLE WELL
STUB OUT AND CAP 2-5"C
TO 5' FROM EDGE OF PAD
PROVIDE SUPPLEMENTAL GROUNDING ELECTRODE PER NFPA 70: NATIONAL ELECTRICAL CODE (NEC) AND BOND ALL AVAILABLE GROUNDING ELECTRODES IN THE BUILDING OR STRUCTURE TO FORM THE GROUNDING ELECTRODE SYSTEM PER NEC. THIS SUPPLEMENTAL ELECTRODE SHALL INCLUDE EITHER A 10'-0" x 3/4" COPPER CLAD GROUND ROD FOR AN EXTERIOR MAIN SERVICE ENTRANCE DISCONNECT, OR A MINIMUM OF 20 FEET OF 1/2" OR LARGER CONCRETE ENCASED REBAR FOR AN INTERIOR MAIN SERVICE DISCONNECT. IF THE REBAR BEING USED IN THE FOOTING IS SMALLER THAN 1/2", THEN USE 20' OF BARE SOLID #4 AWG COPPER CONDUCTOR OR 20' GROUND ROD AND BOND TO THE REBAR WITH STEEL TIE WRAPS. IN REMODEL PROJECTS THAT WILL NOT HAVE NEW FOOTINGS INSTALLED, THIS SUPPLEMENTAL ELECTRODE SHALL BE IN THE FORM OF A 10'-0" x 3/4" COPPER CLAD GROUND
ROD INSTALLED PER CURRENT NEC REQUIREMENTS.
ALL METAL CONDUITS ENCLOSING ANY SERVICE CONDUCTORS SHALL BE FITTED WITH A "BONDING BUSHING". SIZE THE JUMPER PER NEC.
ALL METAL CONDUITS ENCLOSING ANY GROUNDING ELECTRODE CONDUCTOR SHALL BE FITTED WITH A "BONDING BUSHING" AT EACH END. SIZE THE JUMPER PER NEC.
IF STRUCTURAL STEEL MEMBER IS AVAILABLE, BOND IT TO THE SERVICE USING A UL LISTED IRREVERSIBLE CLAMP OR WELDED LUG.
CONNECTIONS TO THE METAL WATER PIPE SHALL BE LOCATED WITHIN THE FIRST 5 FEET OF POINT OF ENTRANCE OF THE INTERIOR METAL WATER PIPE, IF AVAILABLE ON THE PREMISES.
ALL BRANCH CIRCUIT AND FEEDER CONDUITS ARE TO HAVE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR REGARDLESS OF THE CONDUIT MATERIAL.
WHEN THE SERVICE CONSISTS OF MULTIPLE DISCONNECTING MEANS IN SEPARATE ENCLOSURES, CONNECT A TAP CONDUCTOR FROM THE MAIN GROUNDING ELECTRODE CONDUCTOR TO EACH DISCONNECTING MEANS. SIZE THIS TAP BASED ON THE LARGEST SERVICE CONDUCTOR IN THAT SERVICE DISCONNECT ENCLOSURE.
CT CABINET OR OTHER
SERVICE ENCLOSURE
SERVICE
DISCONNECTING MEANS
TYPICAL SUB-PANEL
GROUNDING
ELECTRODE
CONDUCTORS.
GROUND
ROD.
CONCRETE ENCASED
ELECTRODE.
METAL FRAME OF
BUILDING.
METAL UNDERGROUND
WATER PIPE.
GROUNDING
ELECTRODE
BONDING
JUMPERS.
MAIN
BONDING
JUMPER.
GROUNDING
EQUIPMENT
CONDUCTORS.
EQUIPMENT GROUND AND
NEUTRAL CONDUCTOR TO
TYPICAL BRANCH CIRCUIT.
NONMETALLIC
PROTECTIVE SLEEVE.
2" MIN.
BONDED
TERMINAL
BLOCK.
BONDED
EQUIPMENT
GROUND BUS.
BONDED
NEUTRAL
BUS.
NEUTRAL BUS
(NOT BONDED).
GRADE
M
IN
IM
U
M
2' -0
1'
-2
GRADE
EARTH
YELLOW
WARNING
TAPE
CONCRETE WITH STEEL REBAR
REINFORCEMENT
1' -0
2'-0"
5"C (TYP)
SPARE
12" X 12" X 8"
DEEP SUMP
7/8" ø PULLING-IN IRON
DUCT ENTRANCE - LOCATION TO
BE AS INDICATED
PLAN
A
B8"
A A
GRADE
GROUND ROD & CLAMP
DUCT ENTRANCE
MANHOLE FRAME & COVER - SEE FED. SPEC. A-A-60005
FIG. 1, SIZE 30A AND FIG. 11, SIZE 30, RESPECTIVELY.
MANHOLE/COVER SHALL BE SUITABLE FOR H20 HIGHWAY
LOADING IN ACCORDANCE WITH UFC 3-550-01.
BRICK COLLAR LINED UP WITH CEMENT MORTAR
8"
8"
B
SECTION A-A
C
8"
8"
8"
8"
LAP REINF. 24" (TYP.)
6" MIN.
NOTES:
MANHOLE AND COVERS SHALL BE DESIGNED
FOR MAXIMUM WHEEL LOAD IN ACCORDANCE
WITH AASHTO HS20-44.
MINIMUM CONCRETE COMPRESSIVE STRENGTH
SHALL BE 3000 PSI.
WATERSTOP AT ALL
CONSTRUCTION JOINTS. (TYP.)
MANHOLE DIMENSIONS
TYPE
3 8'-0"
A
8'-0"
B C (CLEAR HT.)
6'-6"
7/8" ø PULLING-IN IRON
SLOPE 1:40 TO SUMP
#5 REINF. AT 6" EW TOP,
SIDES & BOTTOM
1.
2.
WALL OF
MANHOLE
TYPICAL CABLE RACK TYPICAL DUCTBANK ENTRANCE
DUCTBANK
INSIDE FACE OF
MANHOLE
45°
3"
DETAIL OF PULLING-IN IRON
7" MIN (TYP)
8 3/8"
7/8"Ø
9"
CAST IN PLACE
3"
1 1/2" (MIN)
CONCRETE WALL
LOCKWASHER
FILLET WELD
2 1/2"Ø WASHER
6 1/2" X 2 1/2" X 3/16" PLATE
ALTERNATE METHOD
CL
1"Ø U-BOLT
W/ 2 1/2" RAD
1"Ø NUT
1 1/4"Ø
SLEEVE
13/16"
3/16" 4"
NOTE
ALL METAL PARTS SHALL BE
HOT DIP GALVANIZED
1. CONCRETE MUST BE 3000 P.S.I. @ MINIMUM 28 DAYS.
2. DUCTBANKS MUST HAVE A MINIMUM OF 3 INCHES CLEAR CONCRETE COVER ON ALL SIDES.
3. #4 STEEL REBAR CLOSED TIES, SPACED TO MAINTAIN HORIZONTAL BAR ALIGNMENT.
4. #4 STEEL REBAR AT CORNERS CONTINUOUS.
5. PVC CONDUIT SPACERS MUST BE USED AT 6'-0" ON CENTER TO SUPPORT CONDUIT BUNDLES.
TYPICAL DUCTBANK FABRICATION NOTES:
1. DUCTBANK ROUTES SHOWN ON ES101 ARE APPROXIMATE. ADJUSTMENTS SHOULD BE
MADE AS NECESSARY FOR COORDINATION WITH EXISTING SITE UTILITIES. REFER TO
CIVIL PLANS FOR FURTHER DETAILS.
2. ALL MEDIUM VOLTAGE PRIMARY POWER CABLING SHALL BE ROUTED IN A CONCRETE
ENCASED DUCTBANK.
DUCTBANK NOTES:
CONCRETE PAD
GRADE
PRIMARY CIRCUIT
2'-0"
MIN
#4/0 BARE COPPER GROUND LOOP
ENCIRCLING ENTIRE CONCRETE PAD.
MIN 18" BELOW FINISHED GRADE.
GROUND ROD, TYP
OF 4, ONE AT EACH
CORNER OF PAD.
GROUND BUS (TYP OF 2)
#4/0 BARE
(600V)
PRIMARY CIRCUIT
PRIMARY NEUTRAL
BUSHING INSERT
BUSHING WELLS
CABLE WELL
STUB OUT AND CAP 2-5"C
TO 5' FROM EDGE OF PAD
SWITCHED WAY COMPARTMENT
(TYPICAL FOR OPPOSITE SIDE)
FUSED WAY COMPARTMENT
(TYPICAL FOR OPPOSITE SIDE)
TO FUSED WAY ON OPPOSITE SIDE
TO SWITCHED WAY ON OPPOSITE SIDE
REV DATE DESCRIPTION INITIAL
AFRC-914th AW
AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG
DATE:
AIR FORCE RESERVE
NIAGARA FALLS AIR RESERVE STATION
NEW YORK
Removal of this caveat is prohibited. This material is
For Official Use Only.
LIMITED DISTRIBUTION
Distribution authorized to DoD, IAW
10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW
48 C.F.R. §252.245-7000
Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.
Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.
DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.
OF THEDEPARTMENT AIR FORCE
TAB NO. SCALE: AS INDICATED
A
B
C
D
E
F
G
2 3 4 5 6 7 8 9
6/9/2020 5:26:12 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt
ES501
9 June 2020
USAF-Repair TACAN Electrical Feed NY
ELECTRICAL DETAILS
LAD Project No: 092-10066-001
FINAL DESIGN SUBMITTAL
SCALE: NTS
A1
PAD-MOUNTED TRANSFORMER DETAIL
SCALE: 1/8" = 1'-0"
A5
GROUNDING ELECTRODE SYSTEM - MAIN SERVICE - PER NFPA 70
SCALE: NTS
E5
PRIMARY POWER DUCTBANK
SCALE: NTS
E1
MANHOLE DETAIL - TYPE 3
SCALE: NTS
E3
MANHOLE DETAIL - TYPICAL COMPONENTS
SCALE: 1/8" = 1'-0"
C1
PAD-MOUNTED PRIMARY SWITCHGEAR DETAIL
NEW WORK.
EXISTING ELEMENTS TO REMAIN.
EXISTING ELEMENTS TO BE REMOVED OR RELOCATED AS
INDICATED.
208/120V 225A
MCB
1NLA
AMPERAGE SHOWN INDICATES RATED OVERCURRENT
PROTECTION (CIRCUIT BREAKER FEED) TO PANEL (TYP.)
MLO = MAIN LUG ONLY
MCB = MAIN CIRCUIT BREAKER
225A,3P
ARROW INDICATES "FED FROM" DEVICE. OVERCURRENT
PROTECTION DEVICE BREAKER SIZE AND POLES ARE INDICATED
NEXT TO THE ARROW.
RISER DIAGRAM LEGEND:
EXISTING 13.2kV PRIMARY SWITCHGEAR. CONNECT NEW 13.2kV FEEDER TO THE
SAME LOCATION MADE AVAILABLE AFTER REMOVAL OF EXISTING FEEDER.
COORDINATE CHANGE OVER OF FEEDER TO MINIMIZE DOWNTIME.
PROVIDE NEW 13.2kV PRIMARY AIR-INSULATED SWITCHGEAR WITH TWO (2) LOAD
INTERRUPTING SWITCHED WAYS AND TWO (2) FUSED SWITCHED WAYS. PROVIDE E-
RATED MEDIUM VOLTAGE FUSES, MINIMUM SIZE AS INDICATED. SWITCHGEAR SHALL
BE MOUNTED ON NEW CONCRETE PAD.
PROVIDE NEW TRANSFORMER AS INDICATED, MOUNTED ON NEW CONCRETE PAD.
PROVIDE CONCRETE PAD. REFER TO CIVIL DRAWINGS AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
EXISTING OPEN-AIR FUSED CUT-OUT SWITCHES AND RACKING TO REMAIN FOR
CONTINUED OPERATION. PROVIDE NEW 4.8kV SECONDARY FEEDER FROM
TRANSFORMER 'T-WEST' CONNECTED TO THE SAME LOCATION MADE AVAILABLE
AFTER REMOVAL OF EXISTING FEEDER FOR MAINTAINING SERVICE TO WEST-END
LOADS. COORDINATE CHANGE OVER OF FEEDER TO MINIMIZE DOWNTIME.
PROVIDE NEW UTILITY METER AS SPECIFIED AND NEW SERVICE DISCONNECT AS
INDICATED. MOUNT METER ON EXTERIOR OF BUILDING AND REPLACE EXISTING
DISCONNECT WITH A NEW ONE AS INDICATED. CONNECT EXISTING TACAN BUILDING
LOAD TO NEW SERVICE DISCONNECT.
PROVIDE GROUNDING OF DISCONNECT AS INDICATED BY DETAIL A5/ES501.
PROVIDE GROUNDING OF TRANSFORMER AS INDICATED BY DETAIL A1/ES501 AND AS
SPECIFIED.
PROVIDE GROUNDING OF PRIMARY SWITCHGEAR AS INDICATED BY DETAIL C1/ES501
AND AS SPECIFIED.
EXISTING 13.2kV PRIMARY SWITCHGEAR TO REMAIN FOR CONTINUED USE.
EXISTING TRANSFORMER AND 13.2kV FEEDER TO BE REMOVED. TRANSFORMER TO
BE TURNED OVER TO GOVERNMENT. REMOVAL MUST BE COORDINATED WITH THE
INSTALLATION OF NEW 13.2kV FEEDER AND EQUIPMENT TO MINIMIZE DOWNTIME OF
WEST-END LOADS.
EXISTING 4.8kV FEEDER THAT HAS BEEN TEMPORARILY REPAIRED WITH AN
ABOVEGROUND FEEDER. ALL EXISTING UNDERGROUND AND ABOVEGROUND
CONDUCTORS SHALL BE REMOVED AFTER THE NEW 13.2kV FEEDER AND EQUIPMENT
ARE MADE OPERATIONAL. ANY DIRECT-BURIED CABLING CAN BE ABANDONED IN
PLACE. ANY EXISTING UNDERGROUND DUCTBANKS CAN BE ABANDONED IN PLACE,
AFTER REMOVAL OF CONDUCTORS. REMOVE ALL ABOVEGROUND CONDUIT AND
OTHER STRUCTURES ASSOCIATED WITH REMOVAL OF THIS FEEDER.
EXISTING UNDERGROUND 4.8kV FEEDERS SERVING WEST-END AIRFIELD LOADS TO
REMAIN FOR CONTINUED OPERATION.
EXISTING OPEN AIR FUSED CUT-OUT SWITCHES AND RACKING TO REMAIN FOR
CONTINUED OPERATION. MAINTAIN EXISTING CONNECTIONS TO WEST-END LOADS.
EXISTING TACAN TRANSFORMER CONSISTS OF THREE (3) SINGLE-PHASE, POLE TYPE
TRANSFORMERS INSTALLED ON A CONCRETE PAD. THE TRANSFORMERS AND 4.8kV
PRIMARY CONNECTIONS SHALL BE REMOVED. CONCRETE PAD TO REMAIN.
REMOVAL MUST BE COORDINATED WITH THE INSTALLATION OF NEW 13.2kV FEEDER
AND EQUIPMENT TO MINIMIZE DOWNTIME OF WEST-END LOADS.
EXISTING SECONDARY FEEDER AND SERVICE DISCONNECT SHALL BE REMOVED.
EXISTING TRANSFORMER TO REMAIN.
EXISTING SECONDARY FEEDERS, SERVICE DISCONNECTS, AND METERS TO REMAIN.
D1
D2
D3
D4
D5
D6
D7
D8
D9
NEW RISER DIAGRAM KEY NOTES:DEMO RISER DIAGRAM KEY NOTES:
GRADE
T-ILS(1-PH) T-FT(3-PH) T-AFL(1-PH) T-TACAN T-MON 2
SW-MON 2
13.2 KV TO 4.8 KV
M
240/120V 100A
MLO
P-ILS
208/120V 100A
MCB
P-FTP
240/120V 100A
MLO
P-AFL
M
M
D3
D5 D6
D9
D7D8D8D8
TACAN BLDG 732
FIRE TRAINING
(FT) BLDG
FAA INSTRUMENT
LANDING SYSTEM
(ILS) BLDG FENCED IN SWITCHYARD
D2
D4
D1
D9D9
SW-TACAN
GRADE
T-TACAN
SW-MON 2SW-WEST
45 KVA, 3-PHASE,
13.2KV-DELTA TO
208Y/120V-GRD Y
3#2/0 AWG ALUMINUM (15kV) TYPE MV-105 SHIELDED
CONDUCTORS WITH EPR INSULATION & 1#2/0 AWG COPPER
(600V RATED) INSULATED NEUTRAL IN 5"C AND 1-5"C SPARE
WITH PULL ROPE; PROVIDE CONCRETE ENCASED DUCTBANK
OR DIRECTIONAL BORING (DB) AS INDICATED.
TACAN BLDG 732
NEW 100A/3P/F100/NEMA 4X
SERVICE DISCONNECT
4#2 AWG, 1#6G
IN 1-1/2"C
M
FENCED IN SWITCHYARD
T-WEST
150KVA, 3-PHASE,
13.2 KV-DELTA TO
4.8 KV-DELTA
STUB OUT AND CAP (2) 5-INCH
CONDUITS WITH CONCRETE
ENCASEMENT (SEE ES401 FOR
ADDITIONAL INFORMATION)
MAINTAIN EXISTING
FEEDERS TO WEST-
END AIRFIELD LOADS
8 7 9 8
SW-TACAN10E
3E
4#2 AWG, 1#6G
IN 1-1/2"C
(DIRECT-BURIED)
1. IN CONNECTION WITH THE ELECTRICAL ALTERATIONS SHOWN, THERE WILL BE
CERTAIN REMOVALS AND RELOCATIONS OF THE EXISTING ELECTRICAL WORK
NECESSARY FOR THE SATISFACTORY PERFORMANCE OF THE GENERAL
WORK. CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE EXISTING
AREAS AFFECTED. IF DIFFICULTIES ARISE DURING THE DEMOLITION WORK
THAT ARE BEYOND THE CONTRACT DOCUMENTS AND REQUIRES ADDITIONAL
WORK, THE CONTRACTOR SHALL COORDINATE THIS WITH THE GOVERNMENT
AND RESOLVE THE ISSUE(S) PRIOR TO CONTINUING DEMOLITION OF THE
AFFECTED AREA(S).
2. ALL ELECTRICAL ITEMS THAT ARE TO BE DEMOLISHED SHALL BE REMOVED IN
THEIR ENTIRETY, UNLESS OTHERWISE NOTED OR REQUIRED BY OTHER
CONDITIONS IN THESE DOCUMENTS. THE CONTRACTOR SHALL CUT BACK AND
PLUG BOTH ENDS OF CONCEALED CONDUITS MADE OBSOLETE BY THIS
ALTERATION. EXPOSED CONDUITS, WIREWAYS, PULL BOXES, HANGERS, ETC.,
MADE OBSOLETE BY THE ALTERATION WORK SHALL BE REMOVED, UNLESS
OTHERWISE NOTED. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL
BE REMOVED IN THEIR ENTIRETY. CONDUCTORS SHALL BE COMPLETELY
REMOVED FROM THE ITEM TO BE DEMOLISHED BACK TO THE SOURCE
OVERCURRENT DEVICE. EXISTING CONDUCTORS SHALL NOT BE REUSED
UNLESS OTHERWISE NOTED. REFER ALL QUESTIONS TO THE CONTRACTING
OFFICER'S REPRESENTATIVE (COR) PRIOR TO BID FOR CLARIFICATION.
3. CONFIRM WITH THE GOVERNMENT ANY ELECTRICAL EQUIPMENT ITEMS THAT
THEY WISH TO SALVAGE FOR THIS PROJECT.