Attachment 2 - Drawings NIAGARA FALLS AIR RESERVE STATION USAF-Repair TACAN Electrical Feed NY.pdf

PDF 7 MB Posted

Attached to
Repair TACAN Electrical Feed
Solicitation number
FA6670-20-B-0002
Issued by

About this file

This is a notice for a federal construction contract solicitation for repair of a TACAN electrical feed at Niagara Falls Air Reserve Station. The project involves replacing an underground primary electrical feeder line connecting a TACAN, ILS, and fire training areas to the base electrical system, including replacement of pad mounted transformers, switching equipment, and related components. The estimated value is between $500,000 and $1,000,000. The solicitation is set aside 100% for HUBZone small businesses. Electronic submissions will not be accepted. Bid, payment and performance bonds are required. Liquidated damages will be identified in the contract. The site visit date is provided, and all questions must be submitted in writing by 31 August 2020. Only the full solicitation will be available electronically on SAM.gov; no paper copies will be provided. Interested vendors may register contact information on FBO.gov. Offerors must be registered in SAM and WAWF. The notice does not obligate funds or the government for any costs.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E C P

E C P

E C P

E C P E C P

MON. 2

PAPI

S U R V E Y D I S K V - 4 - 9 1

D I S K W / C R O S S

D I S K

TENNIS

COURTS

TRANSFORMER BANK

TACAN

ANTENNA

I L S

I L S A N T E N N A S

PAPI

W I N D C O N E A S S E M B L Y

ABANDONED FIRE TRAINING

FACILITY

FIRE TRAINING FACILITY

VACCANT FAA BLDGS.

FAA RTR SITE

CONTROL TOWER

W I N D S O C K E Q U I P M E N T

CONC. C

ULV. T

OP

C-119C -4

A I R P O R T

A R P R M 1

A R P R M 2

BLE WE TT A VE .

JO

H

N S

O N

S T

R E

E T

E N

T A

V E

N U

E

T U

S C

A R

O R

A R

O A

D

KRUG AVENUE

UTZ IG D RI VE

K

IR

K B

R

ID

G E

D R

IV

E

WA GN E R D R I V E

HU LB Y S TR EE T

KI R SC H DR I V E

A V

F U

E L

S C

IR

C

L E

R U

B

IN

W A

Y

MERRE L L LAN E

C O

O P

E R

C U

R V

E

C O

S E

G L

IA

S

T

PORTER ROAD

TUSCAR

ORA R

OAD

LOCK P OR T R OA D

PORTER ROAD

NIAGARA FALLS BOULEVARD

LOCK P OR T R OA D

304306308

M

M

M

M

M

61 6459

57- 1

51 51- 1

5050- 1

44- 1

43- 3 43- 143

43- 2

43- 4

14 614 5- 1

14 5

14 4

14 314 2

14 1

14 0

14 2- 1

13 9

13 8

13 7

13 6

13 5

13 4

13 3

13 2

13 2- 1

13 1- 1

13 1

13 2- 2

13 2- 3

13 2- 4 13 2- 513 2- 6

40393837

14 4- 1 14 3- 1

13 2- 7 13 2- 813 2- 9

13 0- 2

13 0- 1

13 012 7

12 8

12 9

12 6

34- 1

31 32

0-1

0-2

0-3

13- 2

13- 3

13- 1

15- 1

17- 1

20- 1

12 5

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

LBS

C-130 H

-30

C -130

H -30

SCALE:

B2

VIEW NAME

1/8" = 1'-0"

A4

EARTH

EARTH GRAVEL

CONCRETE

REGULAR

DETAIL TITLE

BUILDING SECTION

WALL SECTION

EXTERIOR / INTERIOR

ELEVATION

INTERIOR MULTI-VIEW

ELEVATION

MATERIALS

REFERENCE

DETAIL SECTION

AE402

C4

AE201

A1

AE305

SIM

A1

AE305

SIM

A1

AE305

SIM

AE505

C3

SIM

A3

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

KEYNOTE

REVISION NUMBER

ELEVATION INDICATION

COLUMN GRID

IDENTIFICATION

NORTH ARROW

?A1

1t EQUIPMENT TAG

D

NTRUE

NORTH

MATCHLINE

SCOPE OF WORK BOUNDARY

MH MH MH MH

MH MH MH

MH

A R C H I T E C T U R E

E N G I N E E R I N G

I N T E R I O R S

P L A N N I N G

N

EW

S

NIAGARA FALLS AIR RESERVE STATION

LIST OF DRAWINGS DRAWING SYMBOLS

PARTIAL BASE PLAN

AIRFIELD OPERATIONS

(716) 236-2358

EMERGENCY NUMBER (ON BASE 911)

(716) 236-2117

AIR BASE FIRE DEPARTMENT

(716) 236-2086

CONTACT PHONE NUMBERS AT NFARS

AIR TRAFFIC CONTROL TOWER

AIRFIELD MANAGEMENT

(716) 236-2175

(716) 236-2358 (alt)

GRID COORDINATES: NAD 83

STATE PLANE NEW YORK WEST 3103

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO. SCALE: AS INDICATED

6/9/2020 5:26:15 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt

USAF-Repair TACAN Electrical Feed NY

9 June 2020

GI001

9 June 2020

USAF-Repair TACAN Electrical Feed NY

COVER SHEET

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CONTRACT NO . FA667018F0023

PROJECT NO.RVKQ190734

GENERAL

GI001 COVER SHEET

CIVIL

CS100 OVERALL SITE PLAN

CS101 SITE PLAN - EAST

CS102 SITE PLAN - WEST

CS103 CONSTRUCTION SAFETY AND PHASING PLAN

CS501 CIVIL DETAILS

ELECTRICAL

E-001 ELECTRICAL SYMBOLS

ES101 ELECTRICAL SITE PLAN

ES401 ELECTRICAL ENLARGED PLANS

ES501 ELECTRICAL DETAILS

ES601 ELECTRICAL RISER DIAGRAM

TOTAL SHEET COUNT: 11

06/09/2020

TAXIWAY - B

VASI VASI

TAXIWAY - A

TA

XI

W

AY

A1

ILS

TA

XI

W

AY

A

ILS ANTENNAS

TAXIWAY - E

BLEWETT AVE.

TU

SC

AR

OR

A

RO

AD

TA

XI

W

AY

A

KIRSCH DRIVE

AV

FU

EL

S

CI

RC

LE

RU

BI

N W

AY

WINDCONE ASSEMBLY

ABANDONED FIRE TRAINING FACILITY

FIRE TRAINING FACILITY

SURVEY DISK

V-4-91

DISK W/CROSS

DISK

7566'

3687'

4387' TORA

5438' 2844'

3544' TORA 6281'

1559'

2259' TORA

TAXIWAY - A

A-10 A-8 A-5

A-9 A-6A-7

TRANSFORMER

BANK

TACAN

ANTENNA

C C

C

C

C

C

E E

E

E

EEEE

T

SW

REFER TO SHEET CS101

REFER TO SHEET CS102

TB-2

TB-1

TB-3

TB-4

TB-5

NIGRA01-003

NIGRA01-002

NIGRA01-005

NIGRA01-001NIGRA01-004

APPROXIMATE AREA OF DRAINAGE

SWALE (CONTRACTOR TO FIELD VERIFY)

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO.SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

9 JUNE 2020

USAF-Repair TACAN Electrical Feed NY

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CS100

OVERALL SITE PLAN

1. CONTRACTOR IS TO ADHERE TO INSPECTION REQUIREMENTS OF SPECIFICATION SECTION 01 57 20.00 10 (EVERY 7 CALENDAR DAYS AND WITHIN 24 HOURS OF THE END OF A STORM EVENT OF 0.5 INCHES OR

GREATER.

2. INSTALL AND ESTABLISH EROSION CONTROL BMPS AT THE BEGINNING OF CONSTRUCTION AND MAINTAIN IN WORKING ORDER FOR THE DURATION OF LAND DISTURBING ACTIVITIES. REPAIR DAMAGES

CAUSED BY SOIL EROSION AND CONSTRUCTION EQUIPMENT AT OR BEFORE THE END OF EACH

WORKING DAY. PROVIDE ADDITIONAL BMPS TO SUPPLEMENT THE ORIGINAL DESIGN IF NEEDED TO PREVENT SEDIMENT FROM LEAVING THE LIMITS OF CONSTRUCTION DUE TO UNFORESEEN CONDITIONS.

3. CONDUCT LAND DISTURBING ACTIVITIES SO AS TO MINIMIZE THE SIZE AND DURATION OF THE WORK AREA EXPOSED AT ONE TIME. STABILIZE AND/OR TEMPORARILY SEED DISTURBED AREAS OF THE SITE AS SOON AS PRACTICAL FOLLOWING THE COMPLETION OR SUSPENSION OF CONSTRUCTION ACTIVITY.

4. BMPS SHOWN ON PLAN ARE PROVIDED AS A MINIMUM LEVEL OF PROTECTION AGAINST EROSION AND SEDIMENT LOSS. CONTRACTOR SHALL ADD, ADJUST, AND MAINTAIN BMPS AS NEEDED TO PROTECT

OFFSITE AREA FROM EXCESS EROSION AND SEDIMENT RUNOFF FROM THE SITE.

5. FOLLOWING THE CONCLUSION OF LAND DISTURBING ACTIVITIES AND FINAL STABILIZATION OF THE SITE, CONTRACTOR SHALL REMOVE THE TEMPORARY EROSION AND SEDIMENT CONTROL BMPS CLEAN OUT

ANY REMAINING SEDIMENT FROM STORM DRAINAGE CONVEYANCES AND STRUCTURES.

6. TOTAL AREA TO BE DISTURBED BY CONSTRUCTION = 0.67 ACRES

7. FOLLOWING THE COMPLETION OF FINAL GRADING ACTIVITIES, INSTALL PERMANENT SEEDING IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS (SECTION 32 92 19 SEEDING).

8. EISA SECTION 438 IS NOT APPLICABLE TO THIS PROJECT

EROSION & SEDIMENT CONTROL NOTES

1. THE SCOPE OF WORK SHOWN ON THE CIVIL PLANS SHALL BE PERFORMED IN ACCORDANCE WITH THE

REQUIREMENTS OF THE DETAILED PROJECT SPECIFICATIONS AND APPLICABLE OSHA REGULATIONS.

2. THE DESIGN SHOWN IS BASED ON THE ENGINEER'S UNDERSTANDING OF THE EXISTING SITE CONDITIONS WITHIN THE PROJECT BOUNDARY. EXISTING INFORMATION SHOWN ON THE CIVIL PLANS IS BASED UPON RECORD PLAN

AND GIS INFORMATION PROVIDED BY NIAGARA FALLS AIR RESERVE STATION.

3. CONTRACTOR SHALL FIELD VERIFY EXISTING SITE CONDITIONS, INCLUDING THE LOCATION OF UNDERGROUND UTILITIES, PRIOR TO CONSTRUCTION. NOTIFY ENGINEER OF ANY DISCREPANCIES AFFECTING THE SCOPE OF

WORK.

4. PROTECT PROPERTY CORNERS AND BENCHMARKS WITHIN THE PROJECT BOUNDARY TO THE EXTENT PRACTICABLE. RELOCATE BENCHMARKS AS NECESSARY WITH A TOLERANCE OF 0.010 VERTICAL FEET.

5. THE CONTRACTOR IS SPECIFICALLY CAUTIONED THAT THE LOCATION OF EXISTING UTILITIES SHOWN ON THIS PLAN HAVE BEEN DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR CONVENIENCE

ONLY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THEIR ACCURACY.

6. PRIOR TO THE START OF LAND DISTURBING ACTIVITIES, THE CONTRACTOR SHALL CONTACT THE LOCAL UTILITY MARKING AUTHORITY (ONE CALL SERVICE) AND COORDINATE WITH THE RESPECTIVE UTILITY COMPANIES PRIOR TO THE REMOVAL AND/OR RELOCATION OF THE AFFECTED UTILITIES. THE CONTRACTOR SHALL COORDINATE WITH THE UTILITY COMPANY ANY FEES WHICH ARE TO BE PAID TO THE UTILITY COMPANY FOR THEIR SERVICES.

7. INSTALL EROSION AND SEDIMENTATION CONTROL MEASURES PRIOR TO THE START OF LAND DISTURBING

ACTIVITIES.

8. UNLESS OTHERWISE NOTED, THE CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS REQUIRED BY LOCAL, STATE AND FEDERAL AGENCIES PRIOR TO CONSTRUCTION AND BE RESPONSIBLE FOR ANY ASSOCIATED FEES.

9. ELECTRICAL ELEMENTS SHOWN ON THE CIVIL PLANS ARE FOR REFERENCE ONLY. REFER TO THE APPROPRIATE

DRAWINGS FOR CONSTRUCTION DETAILS OF THESE ITEMS.

10. DEBRIS AND REFUSE RESULTING FROM CONSTRUCTION OPERATIONS SHALL BE HAULED OFF-SITE AND

DISPOSED OF PROPERLY AT THE CONTRACTOR'S EXPENSE.

11. GENERAL NOTES THAT REFERENCE THE OWNER REFER TO THE CONTRACTING OFFICER ON THIS PROJECT.

12. PRIOR TO OBTAINING A DIG PERMIT, THE CONTRACTOR IS RESPONSIBLE FOR LOCATING AND MARKING ALL UTILITIES IN THE WORK AREA, INCLUDING THE OWNER'S UTILITIES. THE CONTRACTOR SHALL USE STANDARD UTILITY LOCATING METHODS AND EQUIPMENT INCLUDING LOCATORS AND GROUND PENETRATING RADAR AS

NEEDED.

13. CONSTRUCTION PERSONNEL WHO OPERATE VEHICLES WITHIN THE AIRFIELD WILL BE REQUIRED TO OBTAIN AIRFIELD DRIVERS TRAINING OR BE ACCOMPANIED BY AN ESCORT. CONTRACTOR SHALL COORDINATE TRAINING

AND ESCORTS THROUGH AIRFIELD MANAGEMENT (716)-236-2398.

14. WETLAND INFORMATION SHOWN ON THESE DOCUMENTS IS FROM A 2017 DELINEATION PROVIDED BY 914 CES.

15. SWALE SHOULD NOT BE DISTURBED (INCLUDING TRAFFIC FROM HEAVY EQUIPMENT) AND IF NECESSARY IT WILL

NEED TO BE RESTORED IN KIND.

GENERAL NOTES

100'

SCALE: 1"=200'-0"

0 100' 200'

N

LEGEND EXISTING PROPOSED

BUILDING

WETLAND AREA

FLOODPLAIN

SILT FENCE

SECURITY FENCE

STORM SEWER

SANITARY SEWER

DOMESTIC WATER MAIN

COMMUNICATIONS

POWER

NATURAL GAS

SOIL BORING LOCATION NIGRA01-000 TB-0

E

T

SW

ELECTRIC MANHOLE

ELECTRICAL SWITCH

TRANSFORMER

1. SOIL MATERIAL EXCAVATED FOR INSTALLATION OF THE PROPOSED ELECTRICAL DUCT BANK MUST BE PLACED BACK INTO THE TRENCH FROM WHERE IT WAS INITIALLY REMOVED AND MAY NOT BE STOCKPILED ON SITE.

2. EXCAVATED SOIL THAT IS EXCESS OF WHAT CAN BE DIRECTLY REPLACED INTO THE TRENCH (DUE TO THE ADDED VOLUME OF THE DUCT BANK) SHALL BE SPREAD OVER THE TOP OF TRENCH AND STABILIZED IN ACCORDANCE WITH THE PROJECT REQUIREMENTS ONLY WHERE THE EXCAVATION IS NOT LOCATED WITHIN A

FLOODPLAIN AS IDENTIFIED ON THE PROJECT PLANS.

3. CONTRACTOR RESPONSIBLE FOR THE POLLUTION PREVENTION AND CONTROL OF LITTER, CONSTRUCTION CHEMICALS, AND CONSTRUCTION DEBRIS FROM BECOMING A POLLUTANT SOURCE IN STORMWATER.

ENVIRONMENTAL NOTES

· CONTRACTING OFFICER:

ANDREW CHURCH (914 MSG/PK)

(716) 236-2216

· AIRFIELD MANAGER:

GERRY GILCHRIST

(716) 236-2358

· BASE ENVIRONMENTAL:

KIMBERLY POWELL

(716) 236-3126

· CIVIL ENGINEERING:

ANDREW SALISBURY

(716) 236-3122

POINTS OF CONTACT

TA

XI

W

AY

A

A-10 A-9

C C

C

C

E E

E

E

EE

DIRECTIONAL BORE CONDUIT

BENEATH WETLAND/DITCH

SEE DETAIL C1/CS501

SOURCE CONNECTION POINT

REFER TO SHEET EP101

DIRECTIONAL BORE CONDUIT

BENEATH WETLAND/DITCH

SEE DETAIL C1/CS501

PERIMETER FENCE

PERIMETER FENCE

AIRFIELD FENCE

EXISTING COMM LINE

ABANDON EXISTING TACAN

POWER LINES IN PLACE

NEW ELECTRICAL DUCT BANK

REFER TO SHEET ES101

EXISTING WETLAND/REGULATED

DITCH AREA - DO NOT DISTURBEXISTING WETLAND/REGULATED

DITCH AREA - DO NOT DISTURB

INSTALL SILT FENCE ON

DOWNSLOPE SIDE OF EXCAVATION

SEE DETAIL E1/CS501

INSTALL SILT FENCE ON

DOWNSLOPE SIDE OF EXCAVATION

SEE DETAIL E1/CS501

EXISTING MANHOLE WITH

TERMINATION TO

TEMPORARY TACAN FEEDER

EXISTING ABOVEGROUND POWER FEEDER USED AS A TEMPORARY REPAIR FOR THE

TACAN ELECTRICAL FEEDER. THE CONDUIT, CONDUCTORS, AND SUPPORT FOR THIS

TEMPORARY FEEDER SHALL BE REMOVED AS PART OF THE CONSTRUCTION OF THIS

PROJECT, AFTER THE NEW PERMANENT FEEDER IS FULLY OPERATIONAL.

LIMITS OF DISTURBANCE

ELECTRICAL MANHOLE (TYPICAL)

REFER TO SHEET ES101

STAGING/LAYDOWN AREA

~5400 SQ FT.

CONCRETE WASHOUT

SEE DETAIL E9/CS501

APPROXIMATE AREA OF DRAINAGE

SWALE (CONTRACTOR TO FIELD VERIFY)

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO.SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

9 JUNE 2020

USAF-Repair TACAN Electrical Feed NY

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CS101

SITE PLAN - EAST

30'

SCALE: 1"=60'-0"

0 30' 60'

N

LEGEND EXISTING PROPOSED

BUILDING

WETLAND AREA

FLOODPLAIN

SILT FENCE

SECURITY FENCE

STORM SEWER

SANITARY SEWER

DOMESTIC WATER MAIN

COMMUNICATIONS

UNDERGROUND ELECTRICAL

NATURAL GAS

SOIL BORING LOCATION NIGRA01-000 TB-0

E

T

SW

ELECTRIC MANHOLE

ELECTRICAL SWITCH

TRANSFORMER

LIMITS OF DISTURBANCE

DRAINAGE SWALE

TAXIWAY - A

TA

XI

W

AY

A1

WINDCONE ASSEMBLY

TRANSFORMER

BANK

TACAN

ANTENNA

C

C

EEE

T

SW

NEW ELECTRICAL DUCT BANK

REFER TO SHEET ES101

PERIMETER FENCE

TACAN EQUIPMENT BUILDING CONNECTION

REFER TO SHEET EP101

REMOVE & REPLACE EXISTING ACCESS

DRIVEWAYS IN KIND TO ACCOMMODATE

INSTALLATION OF NEW DUCT BANK

INSTALL SILT FENCE ON

DOWNSLOPE SIDE OF EXCAVATION

SEE DETAIL E1/CS501

TRANSFORMER PAD

SEE DETAIL E3/CS501

LIMITS OF DISTURBANCE

APPROXIMATE AREA OF DRAINAGE

SWALE (CONTRACTOR TO FIELD VERIFY)

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO.SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

9 JUNE 2020

USAF-Repair TACAN Electrical Feed NY

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CS102

SITE PLAN - WEST

30'

SCALE: 1"=60'-0"

0 30' 60'

N

LEGEND EXISTING PROPOSED

BUILDING

WETLAND AREA

FLOODPLAIN

SILT FENCE

SECURITY FENCE

STORM SEWER

SANITARY SEWER

DOMESTIC WATER MAIN

COMMUNICATIONS

UNDERGROUND ELECTRICAL

NATURAL GAS

SOIL BORING LOCATION NIGRA01-000 TB-0

E

T

SW

ELECTRIC MANHOLE

ELECTRICAL SWITCH

TRANSFORMER

LIMITS OF DISTURBANCE

DRAINAGE SWALE

VASI VASI

LOCKPORT ROAD

TAXIWAY - A

TA

XI

W

AY

A1

TA

XI

W

AY

A

BLEWETT AVE.

JO

HN

SO

N

ST

RE

ET

EN

T

AV

EN

UE

TU

SC

AR

OR

A

RO

AD

LOCKPORT ROAD

TAXIWAY - A

TA

XI

W

AY

A

WAGNER DRIVE

KIRSCH DRIVE

AV

FU

EL

S

CI

RC

LE

RU

BI

N W

AY

MERRELL LANE

CO

OP

ER

C

UR

VE

TRANSMISSOMETER

WINDCONE ASSEMBLY

ABANDONED FIRE TRAINING FACILITY

7566'

3687'

4387' TORA

5438'

1559'

2259' TORA

TAXIWAY - A

A-3 A-1

A-10 A-8 A-5 A-4

A-9

A-2A-6A-7

TENNIS

COURTS

TRANSFORMER

BANK

TACAN

ANTENNA

C C

C

C

C

C

E E

E

E

EEEE

T

SW

HAUL ROUTE

ENTER BASE

FROM MAIN GATE

ON ENTRANCE AVE

TAXIWAY BARRICADE

ALL WORK WITHIN THE TAXIWAY OBJECT FREE AREA SHALL

ONLY BE DONE DURING TAXIWAY CLOSURES. CONTRACTOR

SHALL COORDINATE PHASING AND CLOSURES WITH THE

AIR FORCE RESERVE OPERATIONS

TAXIWAY BARRICADE

TAXIWAY BARRICADETAXIWAY BARRICADE

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO.SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

9 JUNE 2020

USAF-Repair TACAN Electrical Feed NY

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CS103

CONSTRUCTION SAFETY AND PHASING PLAN

100'

SCALE: 1"=200'-0"

0 100' 200'

N

NIGRA01-000 TB-0

E

T

SW

1. PHASE 1 - ESTABLISH BARRIERS ALONG PROJECT AREA AND MARK OUT HAUL ROUTE

2. PHASE 2 - POWER LINE WILL BE TRENCHED IN STARTING FROM THE WEST MOVING EASTWARD

ALONG THE HAUL ROUTE.. COMPLETE TURF ESTABLISHMENT AS THE POWER LINE IN

TRENCHED IN.

3. PRIOR TO BEGINNING CONSTRUCTION, THERE WILL BE A PRE-CONSTRUCTION MEETING FOR

REVIEWING PHASING SCHEDULE AND APPROVING CRITICAL SUBMITTALS.

PHASING NOTESLEGEND EXISTING PROPOSED

BUILDING

WETLAND AREA

FLOODPLAIN

SILT FENCE

SECURITY FENCE

STORM SEWER

SANITARY SEWER

DOMESTIC WATER MAIN

COMMUNICATIONS

POWER

NATURAL GAS

SOIL BORING LOCATION

ELECTRIC MANHOLE

ELECTRICAL SWITCH

TRANSFORMER

HAUL ROUTE

BARRICADE

1. TAXIWAY A WILL BE CLOSED FROM THE WEST EDGE OF THE MAIN RAMP TO THE APPROACH FOR

RWY 10L. TAXIWAYS A1 AND A2 WILL BE CLOSED.

2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND PLACING ALL BARRIERS AND REMOVING

BARRIERS AT THE CONCLUSION OF THE PROJECT.

3. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING AIRFIELD PAVEMENTS WITHIN THE WORK AREA

TO PREVENT ANY ACCUMULATION OF DIRT OR FOREIGN OBJECT DEBRIS. CONTRACTOR SHALL

SWEEP AND CLEAN AIRFIELD PAVEMENTS WITHIN THE WORK AREA WITH A SELF-PROPELLED

VACUUM PICKUP SWEEPER AS NEEDED AND AT A MINIMUM AT THE END OF EVERY WORKDAY.

4. WORK HOURS ARE 0700 TO 1600 MONDAY THROUGH FRIDAY. WORK IS NOT ALLOWED ON

WEEKENDS OR GOVERNMENT HOLIDAYS UNLESS REQUESTED IN WRITING AND APPROVED BY 914

CE AT MINIMUM 14 CALENDAR DAYS IN ADVANCE.

5. ALL PERSONNEL DRIVING ON THE AIRFIELD WILL BE REQUIRED TO ATTEND A TRAINING SESSION

WITH AIRFIELD MANAGEMENT PERSONNEL PRIOR TO OBTAINING ACCESS.

6. NO WORK WILL BE ALLOWED JUNE 14-21, 2021 DUE TO A SCHEDULED AIR SHOW. ALL BARRIERS AND

CONTRACTOR EQUIPMENT MUST BE REMOVED PRIOR TO JUNE 14, 2021 TO ALLOW FULL

OPERATION OF THE RUNWAYS, APRONS, AND TAXIWAYS DURING THIS PERIOD. WORK AREAS AND PAVEMENTS SHALL BE CLEANED AND REMOVED OF ANY FOREIGN OBJECT DEBRIS. NO ELECTRICAL

OUTAGES ARE ALLOWED DURING THIS PERIOD. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

ANY ADDITIONAL MOBILIZATIONS/DEMOBILIZATIONS NECESSARY TO ACCOMMODATE THIS WORK

EXCLUSION PERIOD.

SPECIAL NOTES

NO SCALE

TAXIWAY BARRICADED2

· CONTRACTING OFFICER:

ANDREW CHURCH (914 MSG/PK)

(716) 236-2216

· AIRFIELD MANAGER:

GERRY GILCHRIST

(716) 236-2358

· BASE ENVIRONMENTAL:

KIMBERLY POWELL

(716) 236-3126

· CIVIL ENGINEERING:

ANDREW SALISBURY

(716) 236-3122

POINTS OF CONTACT

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO.SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

9 JUNE 2020

USAF-Repair TACAN Electrical Feed NY

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

CS501

CIVIL DETAILS

TRENCH

(BACKFILLED)

WOVEN WIRE

SUPPORT

(IF USED)

WOOD FENCE POSTS

(MAX. 8' SPACING)

RECOMMENDED TOE-IN

METHOD

NOTES:

1. WOOD POSTS WHICH SUPPORT THE SILT FENCE SHALL BE INSTALLED ON A SLIGHT

ANGLE TOWARD THE ANTICIPATED RUNOFF SOURCE.

2. SILT FENCE SHALL BE TRENCHED IN WITH A SPADE OR MECHANICAL TRENCHER SO

THAT THE DOWNSLOPE FACE OF THE TRENCH IS FLAT AND PERPENDICULAR TO THE

LINE OF FLOW.

3. THE TRENCH SHOULD BE A MINIMUM OF 6" DEEP AND 3"-4" WIDE TO ALLOW FOR THE

SILT FENCE TO BE PLACED IN THE GROUND AND BACKFILLED.

4. SILT FENCE SHOULD BE SECURELY FASTENED TO EACH WOOD SUPPORT POST OR TO

WOVEN WIRE WHICH IS IN TURN ATTACHED TO THE WOOD FENCE POSTS.

5. INSPECTION SHALL BE FREQUENT AND REPAIR OR REPLACEMENT SHALL BE MADE

PROMPTLY AS NEEDED.

6. SILT FENCE SHALL BE REMOVED WHEN IT HAS SERVED ITS USEFULNESS SO AS NOT TO

BLOCK OF IMPEDE STORM FLOW OR DRAINAGE.

7. SEDIMENT TRAPPED BY THIS PRACTICE SHALL BE UNIFORMLY DISTRIBUTED ON THE

SOURCE AREA PRIOR TO TOPSOILING.

FLOW

SILT

FENCE

SCALE:

SILT FENCE

NO SCALE

2"8"

4"

CONCRETE ELECTRICAL PAD,

MINIMUM 8" THICK

NOTE:

COORDINATE OPENINGS IN TRANSFORMER

PAD WITH ELECTRICAL CONTRACTOR.

SCALE:

CONCRETE ELECTRICAL TRANSFORMER PAD

NO SCALE

HMAC SURFACE COURSE

MINIMUM 2" DEPTH

PLACE TO 1" ABOVE

EXIST. PVMT GRADE

6" TRENCH WIDTH6" 6"6"

ITL APPROVED BACKFILL

MATERIAL COMPACTED PER

SPECIFICATIONS.

HMAC BASE COURSE

TO DEPTH OF

EXISTING PVMT

MINIMUM 3" DEPTH

TACK COAT ON ALL

EXPOSED EDGES

AND SURFACES

EXIST. ASPHALT

PAVEMENT

FULL-DEPTH BITUMINOUS PAVEMENT REPAIR

PRIMARY POWER DUCTBANK

ENTRANCE PIT

BORING LENGTH

MAINTAIN MINIMUM

OF 3' DEPTH AT

PAVED ACCESS

ROADS

TYPICAL DIRECTIONAL BORING DETAIL

RECEIVING PIT

DIRECTIONALLY

BORED DUCT BANK

UTILITY CROSSING

2'

MI

N.

PAVED ACCESS

ROAD

3'

WETLAND

3'

MAINTAIN MINIMUM

OF 3' DEPTH AT

WETLAND CROSSINGS

2'

MI

N.

UTILITY CROSSING

E3 E6E1

C1

CONCRETE WASHOUT

NO SCALEE9

SET TOP OF PAD 4" ABOVE

ADJACENT GRADE

GROUND

ELEVATION

WELL-COMPACTED GRAVEL

BASE, MINIMUM 6" THICK

REINFORCEMENT 6"x6" - W2.9/W2.9

MESH, PLACED UNIFORMLY 4"

BELOW TOP OF SLAB

8' X 8' MIN OR AS

REQUIRED TO

CONTAIN WASTE

CONCRETE

2'-0" MIN

BERM AROUND PERIMETER

GROUND SURFACE

12" MIN

12" MIN

COMPACTED EMBANKMENT

MATERIAL (TYP.)

3:1 OR FLATTER

SIDE SLOPES

NOTES:

1. CONCRETE WASHOUT AREA SHALL BE INSTALLED PRIOR TO ANY CONCRETE PLACEMENT ON SITE.

2. CONCRETE WASHOUT AREA SHALL BE LINED WITH MINIMUM 10 MIL THICK PLASTIC LINER.

3. VEHICLE TRACKING CONTROL IS REQUIRED IF ACCESS TO CONCRETE WASHOUT AREA IS OFF

PAVEMENT.

4. THE CONCRETE WASHOUT AREA SHALL BE REPAIRED AND ENLARGED OR CLEANED OUT AS

NECESSARY TO MAINTAIN CAPACITY FOR WASTED CONCRETE.

5. AT THE END OF CONSTRUCTION, ALL CONCRETE SHALL BE REMOVED FROM THE SITE AND

DISPOSED OF AT AN ACCEPTED WASTE SITE.

6. WHEN THE CONCRETE WASHOUT AREA IS REMOVED, THE DISTURBED AREA SHALL BE SEEDED

AND MULCHED OR OTHERWISE STABILIZED IN A MANNER ACCEPTABLE TO THE INSTALLATION.

DESCRIPTIONSYMBOL

CIRCUIT BREAKER

MOTOR STARTER, # INDICATES NEMA STARTER SIZE

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

DRAWOUT CIRCUIT BREAKER

FUSE

GROUND CONNECTION

GENERATOR

KIRK KEY INTERLOCK

LIGHTNING ARRESTOR

MAGENTIC MOTOR STARTER

METER (AS SPECIFIED)

SWITCH

TRANSFER SWITCH, AUTOMATIC UON

TRANSFORMER

ATS BYPASS

SOLID-STATE MULTI-FUNCTION METER

AMMETER AND PHASE SELECTOR SWITCH

VOLTMETER AND PHASE SELECTOR SWITCH

PANELBOARD

PREWIRED CONTROL PANEL

SURGE PROTECTIVE DEVICE

DISCONNECT SWITCH

CT

PT

G

G F P GROUND FAULT PROTECTOR

K

M

3 CT

AAS

VVS

X-X

TRANSIENT VOLTAGE SURGE SUPPRESSION

PWCP

SPD

TVSS

ONE-LINE DIAGRAM

DESCRIPTIONSYMBOL

POWER DISTRIBUTION

CONDUIT DOWNWARD

CONDUIT UPWARD

CONDUIT CONTINUATION

SURFACE MOUNTED BRANCH PANELBOARD

FLUSH MOUNTED BRANCH PANELBOARD

DISTRIBUTION PANEL OR SWITCHBOARD

SWITCHGEAR OR SWITCHBOARD

MOTOR CONTROL CENTER

ELECTRICAL CABINET OR SPECIAL PURPOSE ENCLOSURE

PULL BOX

MANHOLE

HANDHOLE

AUTOMATIC TRANSFER SWITCH

SURGE PROTECTION DEVICE

PB

MH

HH

ATS

SPD

VARIABLE FREQUENCY DEVICEVFD

MOTOR

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

INDIVIDUAL MOLDED CASE CIRCUIT BREAKER IN ENCLOSURE

MAGNETIC MOTOR STARTER

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH

J

J

J

JUNCTION BOX, WALL MOUNTED

JUNCTION BOX, FLUSH MOUNTED ON CEILING

JUNCTION BOX, FLUSH MOUNTED IN FLOOR

CONDUIT END CAP

ELECTRICAL SYMBOL LEGEND NOTES

1. ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED ON PLANS.

MOUNTING HEIGHT A.F.F. TO CENTER LINE OF DEVICE

DESCRIPTIONSYMBOL

SUBSCRIPTS

MOUNT DEVICE 6' ABOVE COUNTER OR 36" A.F.F. AT

WORKSTATIONS

DEDICATED

EMERGENCY

EXPLOSION PROOF, CLASS GROUP AND DIVISION AS NOTED

UNIT IS CONNECTED TO FIRE ALARM SYSTEM

GROUND FAULT CIRCUIT INTERRUPTER

HOSPITAL GRADE

ISOLATED GROUND

44"

AC

D

E

EX

FA

GF

H

IG

UNSWITCHED NIGHT LIGHT

RAINTIGHT NEMA TYPE 3R OR EQUIVALENT

SURGE PROTECTED TYPE RECEPTACLE

TAMPER-RESISTANT

TELEVISION

CONNECTED TO UPS SYSTEM

WEATHERPROOF NEMA TYPE 3 OR EQUIVALENT

NL

RT

SP

T

TV

U

WP

PAN, TILT, ZOOM TYPE CAMERAPTZ

R RELAY

RECESSED FLOOR DUCT, TYPE/SIZE AS INDICATED ON PLANS

POLE MOUNTED TRANSFORMER

3 PHASE POLE MOUNTED TRANSFORMERS

CONDUIT EXPOSED OR CONCEALED, REFER TO PLANS

A AMPERES

AC ALTERNATING CURRENT

AC ABOVE COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERES INTERRUPTING CAPACITY

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BKBD BACKBOARD

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CLG CEILING

CKT CIRCUIT

COMM COMMUNICATION

CORR CORRIDOR

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU CONDENSING UNIT

CU COPPER

DISC DISCONNECT

DIST DISTRIBUTION

DWG DRAWING

EA EACH

EF EXHAUST FAN

EGB EQUIPMENT GROUND BAR

ELEC ELECTRICAL

EMH ELECTRICAL MANHOLE

EMT ELECTRICAL METALLIC TUBING

EQ EQUAL

EQUIP. EQUIPMENT

EWH ELECTRIC WATER HEATER

EUH ELECTRIC UNIT HEATER

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FT FEET

G GROUND

GEN GENERATOR

GF GROUND FAULT CIRCUIT INTERRUPTER

G.F.C.I. GOVT. FURNISHED, CONTRACTOR INSTALLED

G.F.G.I. GOVT. FURNISHED, GOVT. INSTALLED

GND GROUND

GRD GROUNDED

GOVT. GOVERNMENT

GRS GALVANIZED RIGID STEEL CONDUIT

HP HORSEPOWER

HVAC HEATING, VENTILATION,

AIR CONDITIONING

HWP HOT WATER PUMP

HZ HERTZ

IN INCHES

J-BOX JUNCTION BOX

kcmil or KCM THOUSAND CIRCULAR MILS

KV KILOVOLTS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LA LIGHTNING ARRESTOR

LPI LIGHTNING PROTECTION INSTITUTE

LTG LIGHTING

LV LOW VOLTAGE

M METER

MTBB MAIN TELEPHONE BACK BOARD

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MTD MOUNTED

MTS MANUAL TRANSFER SWITCH

N NEUTRAL

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NF NON-FUSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OCPD OVER-CURRENT PROTECTION DEVICE

ELECTRICAL ABBREVIATIONS

P POLE (1P = 1 POLE, 2P = 2 POLE, ETC.)

P PUMP

PA PUBLIC ADDRESS

PB PULL BOX

PB PUSHBUTTON

PH PHASE

PIV POST INDICATOR VALVE

PNL PANEL

PP POWER POLE

PSI POUNDS PER SQUARE INCH

PT POTENTIAL TRANSFORMER

PTZ PAN-TILT-ZOOM

PVC POLYVINYL-CHLORIDE

PWR POWER

RC REMOTE CONTROL

RCVR RECEIVER

REC RECEPTACLES CIRCUIT

REQD REQUIRED

REV REVISION

RF RETURN FAN

RGS RIGID GALVANIZED STEEL

RM ROOM

RMU RACK MOUNTING UNITS

RPM REVOLUTIONS PER MINUTE

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SCH SCHEDULE

SEC SECURITY

SF SQUARE FEET

SF SUPPLY FAN

SFL SUB FEED LUGS

SN SOLID NEUTRAL

SP SINGLE POLE

SP SUMP PUMP

SPD SURGE PROTECTION DEVICE

SPEC SPECIFICATION

SPKR SPEAKER

SST STAINLESS STEEL

ST SHUNT TRIP

ST SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

TBB TELEPHONE BACK BOARD

TCC TELECOMMUNICATIONS CABINET

TEL TELEPHONE

TELE TELEPHONE

TEMP TEMPERATURE

TFL THRU FEED LUGS

TL TWIST-LOCK

TR TAMPER RESISTANT

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

TYP TYPICAL

UE UNDERGROUND ELECTRICAL

UFC UNITED FACILITIES CRITERIA

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UT UNDERGROUND TELECOMMUNICATIONS

UON UNLESS OTHERWISE NOTED

UV ULTRAVIOLET

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

V VOLTS

VA VOLT AMPERES

VAR VOLT AMPERES REACTIVE

VD VOLTAGE DROP

VDT VIDEO DISPLAY TERMINAL

VFD VARIABLE FREQUENCY DRIVE

W WATTS

W WIDE

W WIRES

WH WATER HEATER

WP WEATHERPROOF

W/ WITH

W/O WITHOUT

XFMR TRANSFORMER

XMTR TRANSMITTER

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO. SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

6/9/2020 5:26:09 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt

E-001

9 June 2020

USAF-Repair TACAN Electrical Feed NY

ELECTRICAL SYMBOLS

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

ECP

MON. 2

SURVEY DISK

V-4-91

DISK W/CROSS

DISK

TRANSFORMER BANK

TACAN

ANTENNA

ILS

ILS ANTENNAS

WINDCONE ASSEMBLY

ABANDONED FIRE TRAINING

FACILITY

FIRE TRAINING FACILITY

M

M

M

M

LBS

LBS

LBS

ES401

A1

ES401

D1

EXISTING UNDERGROUND POWER DUCTBANKS AND DIRECT

BURIED CONDUCTORS SERVING WEST-END AIRFIELD LOADS

TO REMAIN FOR CONTINUED OPERATION. (TYP)

EXISTING ABOVEGROUND POWER FEEDER USED AS A

TEMPORARY REPAIR FOR THE TACAN ELECTRICAL

FEEDER. THE CONDUIT, CONDUCTORS, AND SUPPORT

FOR THIS TEMPORARY FEEDER SHALL BE REMOVED AS

PART OF THE CONSTRUCTION OF THIS PROJECT, AFTER

THE NEW PERMANENT FEEDER IS FULLY OPERATIONAL.

EXISTING HANDHOLE WITH

TERMINATION TO TEMPORARY

TACAN FEEDER

NEW ELECTRICAL DUCTBANK ROUTE, REFER TO

CIVIL PLANS FOR ADDITIONAL DETAILS (TYP).

E5

ES501

NEW TYPE 3 MANHOLE

SEE E1/ES501 (TYP)

NEW TYPE 3 MANHOLE

SEE E1/ES501 (TYP)

EXISTING TRANSFORMER

SERVING ILS BUILDING

TO REMAIN

MH MH MH MH

MH

MH

MH

MH

EXISTING TRANSFORMER

SERVING FIRE TRAINING

FACILITY TO REMAIN

SW-WEST

T-TACAN

T-AFL

SW-MON 2

T-ILS

T-FT

EXISTING TRANSFORMER

SERVING AIR FIELD LIGHTING

LOADS TO REMAIN

T-WEST

T-MON 2

SW-TACAN

DIRECTIONAL BORE CONDUIT -

REFER TO CIVIL PLANS (TYP)

1. SITE PLAN IS SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO CIVIL PLANS FOR

FURTHER DETAILS AND LOCATIONS FOR DIRECTIONAL BORING (DB).

2. A DB PLAN SHALL BE SUBMITTED TO THE AIR FORCE FOR REVIEW AND APPROVAL A

MINIMUM OF 30-DAYS PRIOR TO ANY SITE WORK.

SITE PLAN GENERAL NOTES:

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO. SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

6/9/2020 5:26:10 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt

ES101

9 June 2020

USAF-Repair TACAN Electrical Feed NY

ELECTRICAL SITE PLAN

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

SCALE: 1" = 200'-0"

C1

ELECTRICAL SITE PLAN

SCALE : 1" = 200'-0"

0 200' 400'

N

TRANSFORMER BANK

TACAN

ANTENNA

M

LBS

MON. 2

M

LBS

NEW PRIMARY SWITCH

'SW-WEST'

NEW PAD MOUNTED

TRANSFORMER 'T-TACAN'

EXISTING TRANSFORMER 'T-AFL'

SERVING AIR FIELD LIGHTING

LOADS TO REMAIN

NEW SECONDARY SERVICE

CONDUIT AND CONDUCTORS

EXISTING OPEN-AIR FENCED

IN SWITCHYARD 'SW-TACAN'

TO REMAIN

NEW ELECTRICAL DUCTBANK ROUTE, REFER TO

CIVIL PLANS FOR ADDITIONAL DETAILS (TYP)

NEW PAD MOUNTED

TRANSFORMER 'T-WEST'

NEW SERVICE DISCONNECT

TO REPLACE EXISTING

NEW UTILITY METER

EXISTING PRIMARY SWITCH 'SW-MON 2'

TO REMAIN

EXISTING PAD MOUNTED TRANSFORMER 'T-MON 2'

AND PRIMARY FEEDER TO BE REMOVED

EXISTING PAD MOUNTED TRANSFORMER

TO REMAIN

NEW ELECTRICAL DUCTBANK

ROUTE, REFER TO CIVIL PLANS

FOR ADDITIONAL DETAILS (TYP)

STUB OUT AND CAP (2) 5-INCH CONDUITS BEYOND THE DRIVEWAY EDGE

A MINIMUM OF 25-FOOT FOR FUTURE EXTENSION. PROVIDE CONCRETE

ENCASEMENT FOR THE ENTIRE RUN TO WITHIN 1-FOOT OF THE END OF

THE CONDUITS AS NECESSARY FOR FUTURE CONDUIT TIE-IN. PROVIDE

ABOVE GRADE MARKING TO INDICATE LOCATION OF END OF CONDUITS.

KEY NOTES

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO. SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

6/9/2020 5:26:11 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt

ES401

9 June 2020

USAF-Repair TACAN Electrical Feed NY

ELECTRICAL ENLARGED PLANS

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

SCALE: 1" = 20'-0"

A1

ENLARGED PLAN - TACAN ANTENNA AREA

SCALE: 1" = 20'-0"

D1

ENLARGED PLAN - MAIN POWER SOURCE AREA

SCALE : 1" = 20'-0"

0 20' 40'10'

N

N

SECONDARY COMPARTMENT

CONCRETE PAD

GRADE

LOW VOLTAGE CABLE TERMINATIONS

SECONDARY CIRCUIT

2'-0"

MIN

#4/0 BARE COPPER GROUND LOOP

ENCIRCLING ENTIRE CONCRETE PAD.

MIN 18" BELOW FINISHED GRADE.

GROUND ROD, TYP OF

4, ONE AT EACH

CORNER OF PAD.

GROUND PAD (TYP OF 2)

#4/0 BARE

(600V)

PRIMARY CIRCUIT

LOAD BREAK

CONNECTOR

PRIMARY NEUTRAL

BUSHING INSERT

(3) 2-POSITION LOAD

BREAK OIL SWITCH

OIL-IMMERSED CURRENT-

LIMITING FUSES

PRIMARY COMPARTMENT

SURGE ARRESTERS

(6) TRANSFORMER

BUSHING WELLS

X0

BAYONET OIL-IMMERSED

EXPULSION FUSES

CABLE WELL

STUB OUT AND CAP 2-5"C

TO 5' FROM EDGE OF PAD

PROVIDE SUPPLEMENTAL GROUNDING ELECTRODE PER NFPA 70: NATIONAL ELECTRICAL CODE (NEC) AND BOND ALL AVAILABLE GROUNDING ELECTRODES IN THE BUILDING OR STRUCTURE TO FORM THE GROUNDING ELECTRODE SYSTEM PER NEC. THIS SUPPLEMENTAL ELECTRODE SHALL INCLUDE EITHER A 10'-0" x 3/4" COPPER CLAD GROUND ROD FOR AN EXTERIOR MAIN SERVICE ENTRANCE DISCONNECT, OR A MINIMUM OF 20 FEET OF 1/2" OR LARGER CONCRETE ENCASED REBAR FOR AN INTERIOR MAIN SERVICE DISCONNECT. IF THE REBAR BEING USED IN THE FOOTING IS SMALLER THAN 1/2", THEN USE 20' OF BARE SOLID #4 AWG COPPER CONDUCTOR OR 20' GROUND ROD AND BOND TO THE REBAR WITH STEEL TIE WRAPS. IN REMODEL PROJECTS THAT WILL NOT HAVE NEW FOOTINGS INSTALLED, THIS SUPPLEMENTAL ELECTRODE SHALL BE IN THE FORM OF A 10'-0" x 3/4" COPPER CLAD GROUND

ROD INSTALLED PER CURRENT NEC REQUIREMENTS.

ALL METAL CONDUITS ENCLOSING ANY SERVICE CONDUCTORS SHALL BE FITTED WITH A "BONDING BUSHING". SIZE THE JUMPER PER NEC.

ALL METAL CONDUITS ENCLOSING ANY GROUNDING ELECTRODE CONDUCTOR SHALL BE FITTED WITH A "BONDING BUSHING" AT EACH END. SIZE THE JUMPER PER NEC.

IF STRUCTURAL STEEL MEMBER IS AVAILABLE, BOND IT TO THE SERVICE USING A UL LISTED IRREVERSIBLE CLAMP OR WELDED LUG.

CONNECTIONS TO THE METAL WATER PIPE SHALL BE LOCATED WITHIN THE FIRST 5 FEET OF POINT OF ENTRANCE OF THE INTERIOR METAL WATER PIPE, IF AVAILABLE ON THE PREMISES.

ALL BRANCH CIRCUIT AND FEEDER CONDUITS ARE TO HAVE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR REGARDLESS OF THE CONDUIT MATERIAL.

WHEN THE SERVICE CONSISTS OF MULTIPLE DISCONNECTING MEANS IN SEPARATE ENCLOSURES, CONNECT A TAP CONDUCTOR FROM THE MAIN GROUNDING ELECTRODE CONDUCTOR TO EACH DISCONNECTING MEANS. SIZE THIS TAP BASED ON THE LARGEST SERVICE CONDUCTOR IN THAT SERVICE DISCONNECT ENCLOSURE.

CT CABINET OR OTHER

SERVICE ENCLOSURE

SERVICE

DISCONNECTING MEANS

TYPICAL SUB-PANEL

GROUNDING

ELECTRODE

CONDUCTORS.

GROUND

ROD.

CONCRETE ENCASED

ELECTRODE.

METAL FRAME OF

BUILDING.

METAL UNDERGROUND

WATER PIPE.

GROUNDING

ELECTRODE

BONDING

JUMPERS.

MAIN

BONDING

JUMPER.

GROUNDING

EQUIPMENT

CONDUCTORS.

EQUIPMENT GROUND AND

NEUTRAL CONDUCTOR TO

TYPICAL BRANCH CIRCUIT.

NONMETALLIC

PROTECTIVE SLEEVE.

2" MIN.

BONDED

TERMINAL

BLOCK.

BONDED

EQUIPMENT

GROUND BUS.

BONDED

NEUTRAL

BUS.

NEUTRAL BUS

(NOT BONDED).

GRADE

M

IN

IM

U

M

2' -0

1'

-2

GRADE

EARTH

YELLOW

WARNING

TAPE

CONCRETE WITH STEEL REBAR

REINFORCEMENT

1' -0

2'-0"

5"C (TYP)

SPARE

12" X 12" X 8"

DEEP SUMP

7/8" ø PULLING-IN IRON

DUCT ENTRANCE - LOCATION TO

BE AS INDICATED

PLAN

A

B8"

A A

GRADE

GROUND ROD & CLAMP

DUCT ENTRANCE

MANHOLE FRAME & COVER - SEE FED. SPEC. A-A-60005

FIG. 1, SIZE 30A AND FIG. 11, SIZE 30, RESPECTIVELY.

MANHOLE/COVER SHALL BE SUITABLE FOR H20 HIGHWAY

LOADING IN ACCORDANCE WITH UFC 3-550-01.

BRICK COLLAR LINED UP WITH CEMENT MORTAR

8"

8"

B

SECTION A-A

C

8"

8"

8"

8"

LAP REINF. 24" (TYP.)

6" MIN.

NOTES:

MANHOLE AND COVERS SHALL BE DESIGNED

FOR MAXIMUM WHEEL LOAD IN ACCORDANCE

WITH AASHTO HS20-44.

MINIMUM CONCRETE COMPRESSIVE STRENGTH

SHALL BE 3000 PSI.

WATERSTOP AT ALL

CONSTRUCTION JOINTS. (TYP.)

MANHOLE DIMENSIONS

TYPE

3 8'-0"

A

8'-0"

B C (CLEAR HT.)

6'-6"

7/8" ø PULLING-IN IRON

SLOPE 1:40 TO SUMP

#5 REINF. AT 6" EW TOP,

SIDES & BOTTOM

1.

2.

WALL OF

MANHOLE

TYPICAL CABLE RACK TYPICAL DUCTBANK ENTRANCE

DUCTBANK

INSIDE FACE OF

MANHOLE

45°

3"

DETAIL OF PULLING-IN IRON

7" MIN (TYP)

8 3/8"

7/8"Ø

9"

CAST IN PLACE

3"

1 1/2" (MIN)

CONCRETE WALL

LOCKWASHER

FILLET WELD

2 1/2"Ø WASHER

6 1/2" X 2 1/2" X 3/16" PLATE

ALTERNATE METHOD

CL

1"Ø U-BOLT

W/ 2 1/2" RAD

1"Ø NUT

1 1/4"Ø

SLEEVE

13/16"

3/16" 4"

NOTE

ALL METAL PARTS SHALL BE

HOT DIP GALVANIZED

1. CONCRETE MUST BE 3000 P.S.I. @ MINIMUM 28 DAYS.

2. DUCTBANKS MUST HAVE A MINIMUM OF 3 INCHES CLEAR CONCRETE COVER ON ALL SIDES.

3. #4 STEEL REBAR CLOSED TIES, SPACED TO MAINTAIN HORIZONTAL BAR ALIGNMENT.

4. #4 STEEL REBAR AT CORNERS CONTINUOUS.

5. PVC CONDUIT SPACERS MUST BE USED AT 6'-0" ON CENTER TO SUPPORT CONDUIT BUNDLES.

TYPICAL DUCTBANK FABRICATION NOTES:

1. DUCTBANK ROUTES SHOWN ON ES101 ARE APPROXIMATE. ADJUSTMENTS SHOULD BE

MADE AS NECESSARY FOR COORDINATION WITH EXISTING SITE UTILITIES. REFER TO

CIVIL PLANS FOR FURTHER DETAILS.

2. ALL MEDIUM VOLTAGE PRIMARY POWER CABLING SHALL BE ROUTED IN A CONCRETE

ENCASED DUCTBANK.

DUCTBANK NOTES:

CONCRETE PAD

GRADE

PRIMARY CIRCUIT

2'-0"

MIN

#4/0 BARE COPPER GROUND LOOP

ENCIRCLING ENTIRE CONCRETE PAD.

MIN 18" BELOW FINISHED GRADE.

GROUND ROD, TYP

OF 4, ONE AT EACH

CORNER OF PAD.

GROUND BUS (TYP OF 2)

#4/0 BARE

(600V)

PRIMARY CIRCUIT

PRIMARY NEUTRAL

BUSHING INSERT

BUSHING WELLS

CABLE WELL

STUB OUT AND CAP 2-5"C

TO 5' FROM EDGE OF PAD

SWITCHED WAY COMPARTMENT

(TYPICAL FOR OPPOSITE SIDE)

FUSED WAY COMPARTMENT

(TYPICAL FOR OPPOSITE SIDE)

TO FUSED WAY ON OPPOSITE SIDE

TO SWITCHED WAY ON OPPOSITE SIDE

REV DATE DESCRIPTION INITIAL

AFRC-914th AW

AFI 32-7062, AIR FORCE COMPREHENSIVE PLNG

DATE:

AIR FORCE RESERVE

NIAGARA FALLS AIR RESERVE STATION

NEW YORK

Removal of this caveat is prohibited. This material is

For Official Use Only.

LIMITED DISTRIBUTION

Distribution authorized to DoD, IAW

10 U.S.C. § 130 & 455. Release Authorized to U.S. DoD contractors IAW

48 C.F.R. §252.245-7000

Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database maybe reflected in the data supplied. The end user must be aware of the data conditions and ultimately bear responsibility and the appropriate use of the information with respect to possible errors, original map scale, collection methodology, currency of data, and other conditions specific to certain data.

Unauthorized reproduction, distribution, publication, or exhibition of this material is STRICTLY PROHIBITED. Refer other requests to 914 MSG/CEC. Destroy as "For Official Use Only". 914 MSG/CEC shall not be liable for any errors, omissions, or damages that result from noncompliance of this message.

DIRECTORATE OF ENGINEERING & SERVICES DCS/LEE-WASHINGTON, D.C.

OF THEDEPARTMENT AIR FORCE

TAB NO. SCALE: AS INDICATED

A

B

C

D

E

F

G

2 3 4 5 6 7 8 9

6/9/2020 5:26:12 PM C:\Users\vnpatel\Documents\Autodesk\Revit 2019 Projects\TACAN_vnpatel.rvt

ES501

9 June 2020

USAF-Repair TACAN Electrical Feed NY

ELECTRICAL DETAILS

LAD Project No: 092-10066-001

FINAL DESIGN SUBMITTAL

SCALE: NTS

A1

PAD-MOUNTED TRANSFORMER DETAIL

SCALE: 1/8" = 1'-0"

A5

GROUNDING ELECTRODE SYSTEM - MAIN SERVICE - PER NFPA 70

SCALE: NTS

E5

PRIMARY POWER DUCTBANK

SCALE: NTS

E1

MANHOLE DETAIL - TYPE 3

SCALE: NTS

E3

MANHOLE DETAIL - TYPICAL COMPONENTS

SCALE: 1/8" = 1'-0"

C1

PAD-MOUNTED PRIMARY SWITCHGEAR DETAIL

NEW WORK.

EXISTING ELEMENTS TO REMAIN.

EXISTING ELEMENTS TO BE REMOVED OR RELOCATED AS

INDICATED.

208/120V 225A

MCB

1NLA

AMPERAGE SHOWN INDICATES RATED OVERCURRENT

PROTECTION (CIRCUIT BREAKER FEED) TO PANEL (TYP.)

MLO = MAIN LUG ONLY

MCB = MAIN CIRCUIT BREAKER

225A,3P

ARROW INDICATES "FED FROM" DEVICE. OVERCURRENT

PROTECTION DEVICE BREAKER SIZE AND POLES ARE INDICATED

NEXT TO THE ARROW.

RISER DIAGRAM LEGEND:

EXISTING 13.2kV PRIMARY SWITCHGEAR. CONNECT NEW 13.2kV FEEDER TO THE

SAME LOCATION MADE AVAILABLE AFTER REMOVAL OF EXISTING FEEDER.

COORDINATE CHANGE OVER OF FEEDER TO MINIMIZE DOWNTIME.

PROVIDE NEW 13.2kV PRIMARY AIR-INSULATED SWITCHGEAR WITH TWO (2) LOAD

INTERRUPTING SWITCHED WAYS AND TWO (2) FUSED SWITCHED WAYS. PROVIDE E-

RATED MEDIUM VOLTAGE FUSES, MINIMUM SIZE AS INDICATED. SWITCHGEAR SHALL

BE MOUNTED ON NEW CONCRETE PAD.

PROVIDE NEW TRANSFORMER AS INDICATED, MOUNTED ON NEW CONCRETE PAD.

PROVIDE CONCRETE PAD. REFER TO CIVIL DRAWINGS AND SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

EXISTING OPEN-AIR FUSED CUT-OUT SWITCHES AND RACKING TO REMAIN FOR

CONTINUED OPERATION. PROVIDE NEW 4.8kV SECONDARY FEEDER FROM

TRANSFORMER 'T-WEST' CONNECTED TO THE SAME LOCATION MADE AVAILABLE

AFTER REMOVAL OF EXISTING FEEDER FOR MAINTAINING SERVICE TO WEST-END

LOADS. COORDINATE CHANGE OVER OF FEEDER TO MINIMIZE DOWNTIME.

PROVIDE NEW UTILITY METER AS SPECIFIED AND NEW SERVICE DISCONNECT AS

INDICATED. MOUNT METER ON EXTERIOR OF BUILDING AND REPLACE EXISTING

DISCONNECT WITH A NEW ONE AS INDICATED. CONNECT EXISTING TACAN BUILDING

LOAD TO NEW SERVICE DISCONNECT.

PROVIDE GROUNDING OF DISCONNECT AS INDICATED BY DETAIL A5/ES501.

PROVIDE GROUNDING OF TRANSFORMER AS INDICATED BY DETAIL A1/ES501 AND AS

SPECIFIED.

PROVIDE GROUNDING OF PRIMARY SWITCHGEAR AS INDICATED BY DETAIL C1/ES501

AND AS SPECIFIED.

EXISTING 13.2kV PRIMARY SWITCHGEAR TO REMAIN FOR CONTINUED USE.

EXISTING TRANSFORMER AND 13.2kV FEEDER TO BE REMOVED. TRANSFORMER TO

BE TURNED OVER TO GOVERNMENT. REMOVAL MUST BE COORDINATED WITH THE

INSTALLATION OF NEW 13.2kV FEEDER AND EQUIPMENT TO MINIMIZE DOWNTIME OF

WEST-END LOADS.

EXISTING 4.8kV FEEDER THAT HAS BEEN TEMPORARILY REPAIRED WITH AN

ABOVEGROUND FEEDER. ALL EXISTING UNDERGROUND AND ABOVEGROUND

CONDUCTORS SHALL BE REMOVED AFTER THE NEW 13.2kV FEEDER AND EQUIPMENT

ARE MADE OPERATIONAL. ANY DIRECT-BURIED CABLING CAN BE ABANDONED IN

PLACE. ANY EXISTING UNDERGROUND DUCTBANKS CAN BE ABANDONED IN PLACE,

AFTER REMOVAL OF CONDUCTORS. REMOVE ALL ABOVEGROUND CONDUIT AND

OTHER STRUCTURES ASSOCIATED WITH REMOVAL OF THIS FEEDER.

EXISTING UNDERGROUND 4.8kV FEEDERS SERVING WEST-END AIRFIELD LOADS TO

REMAIN FOR CONTINUED OPERATION.

EXISTING OPEN AIR FUSED CUT-OUT SWITCHES AND RACKING TO REMAIN FOR

CONTINUED OPERATION. MAINTAIN EXISTING CONNECTIONS TO WEST-END LOADS.

EXISTING TACAN TRANSFORMER CONSISTS OF THREE (3) SINGLE-PHASE, POLE TYPE

TRANSFORMERS INSTALLED ON A CONCRETE PAD. THE TRANSFORMERS AND 4.8kV

PRIMARY CONNECTIONS SHALL BE REMOVED. CONCRETE PAD TO REMAIN.

REMOVAL MUST BE COORDINATED WITH THE INSTALLATION OF NEW 13.2kV FEEDER

AND EQUIPMENT TO MINIMIZE DOWNTIME OF WEST-END LOADS.

EXISTING SECONDARY FEEDER AND SERVICE DISCONNECT SHALL BE REMOVED.

EXISTING TRANSFORMER TO REMAIN.

EXISTING SECONDARY FEEDERS, SERVICE DISCONNECTS, AND METERS TO REMAIN.

D1

D2

D3

D4

D5

D6

D7

D8

D9

NEW RISER DIAGRAM KEY NOTES:DEMO RISER DIAGRAM KEY NOTES:

GRADE

T-ILS(1-PH) T-FT(3-PH) T-AFL(1-PH) T-TACAN T-MON 2

SW-MON 2

13.2 KV TO 4.8 KV

M

240/120V 100A

MLO

P-ILS

208/120V 100A

MCB

P-FTP

240/120V 100A

MLO

P-AFL

M

M

D3

D5 D6

D9

D7D8D8D8

TACAN BLDG 732

FIRE TRAINING

(FT) BLDG

FAA INSTRUMENT

LANDING SYSTEM

(ILS) BLDG FENCED IN SWITCHYARD

D2

D4

D1

D9D9

SW-TACAN

GRADE

T-TACAN

SW-MON 2SW-WEST

45 KVA, 3-PHASE,

13.2KV-DELTA TO

208Y/120V-GRD Y

3#2/0 AWG ALUMINUM (15kV) TYPE MV-105 SHIELDED

CONDUCTORS WITH EPR INSULATION & 1#2/0 AWG COPPER

(600V RATED) INSULATED NEUTRAL IN 5"C AND 1-5"C SPARE

WITH PULL ROPE; PROVIDE CONCRETE ENCASED DUCTBANK

OR DIRECTIONAL BORING (DB) AS INDICATED.

TACAN BLDG 732

NEW 100A/3P/F100/NEMA 4X

SERVICE DISCONNECT

4#2 AWG, 1#6G

IN 1-1/2"C

M

FENCED IN SWITCHYARD

T-WEST

150KVA, 3-PHASE,

13.2 KV-DELTA TO

4.8 KV-DELTA

STUB OUT AND CAP (2) 5-INCH

CONDUITS WITH CONCRETE

ENCASEMENT (SEE ES401 FOR

ADDITIONAL INFORMATION)

MAINTAIN EXISTING

FEEDERS TO WEST-

END AIRFIELD LOADS

8 7 9 8

SW-TACAN10E

3E

4#2 AWG, 1#6G

IN 1-1/2"C

(DIRECT-BURIED)

1. IN CONNECTION WITH THE ELECTRICAL ALTERATIONS SHOWN, THERE WILL BE

CERTAIN REMOVALS AND RELOCATIONS OF THE EXISTING ELECTRICAL WORK

NECESSARY FOR THE SATISFACTORY PERFORMANCE OF THE GENERAL

WORK. CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE EXISTING

AREAS AFFECTED. IF DIFFICULTIES ARISE DURING THE DEMOLITION WORK

THAT ARE BEYOND THE CONTRACT DOCUMENTS AND REQUIRES ADDITIONAL

WORK, THE CONTRACTOR SHALL COORDINATE THIS WITH THE GOVERNMENT

AND RESOLVE THE ISSUE(S) PRIOR TO CONTINUING DEMOLITION OF THE

AFFECTED AREA(S).

2. ALL ELECTRICAL ITEMS THAT ARE TO BE DEMOLISHED SHALL BE REMOVED IN

THEIR ENTIRETY, UNLESS OTHERWISE NOTED OR REQUIRED BY OTHER

CONDITIONS IN THESE DOCUMENTS. THE CONTRACTOR SHALL CUT BACK AND

PLUG BOTH ENDS OF CONCEALED CONDUITS MADE OBSOLETE BY THIS

ALTERATION. EXPOSED CONDUITS, WIREWAYS, PULL BOXES, HANGERS, ETC.,

MADE OBSOLETE BY THE ALTERATION WORK SHALL BE REMOVED, UNLESS

OTHERWISE NOTED. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL

BE REMOVED IN THEIR ENTIRETY. CONDUCTORS SHALL BE COMPLETELY

REMOVED FROM THE ITEM TO BE DEMOLISHED BACK TO THE SOURCE

OVERCURRENT DEVICE. EXISTING CONDUCTORS SHALL NOT BE REUSED

UNLESS OTHERWISE NOTED. REFER ALL QUESTIONS TO THE CONTRACTING

OFFICER'S REPRESENTATIVE (COR) PRIOR TO BID FOR CLARIFICATION.

3. CONFIRM WITH THE GOVERNMENT ANY ELECTRICAL EQUIPMENT ITEMS THAT

THEY WISH TO SALVAGE FOR THIS PROJECT.