Attachment 2 - Drawings.pdf
PDF 13 MB Posted
- Attached to
- Safety Shower Modifications and Installations Federal contract opportunity
- Solicitation number
- 1232SA26Q0170
About this file
This document is a complete set of design drawings for an Emergency Eyewash facility upgrade project at the National Center for Cool and Cold-Water Aquaculture (NCCCWA) in Kearneysville, West Virginia, commissioned by the U.S. Department of Agriculture Agricultural Research Service. The design contract number is 12305B21D0013 with design order number 12305B24F0112, prepared by Johnson-McAdams Architects/Engineers and dated July 1, 2025.
The project encompasses plumbing and electrical work across three primary buildings: the Main Building, Broodstock Building, and Hazmat Building. Plumbing work includes installation of thermostatic mixing valves (TMV-1 basis of design: Guardian G6040), safety shower/eyewash stations (basis of design: Guardian G1950), electric water heaters (basis of design: Hubbell ER50-6-SLRS for Hazmat; Rheem PRO+E50 T2 RH92 CL for Broodstock), and hot water circulation pumps (basis of design: Taco 006E3). All indoor domestic water piping requires minimum 1/2-inch flexible elastomeric insulation with K-value of 0.23 BTU-IN/HR-SQ-FT-°F. Electrical work includes new load centers, circuit breaker panels, and connections to support the mechanical equipment. The contractor must coordinate all work with ongoing facility operations, maintain watertight building envelopes, field-verify existing conditions before fabrication, and comply with all applicable electrical codes (NEC 2020), mechanical codes, and Buy American Act requirements. Special protocols govern personnel movement between the Broodstock Building, Hatchery Building, and Quarantine Labs E and F to protect research stocks, with restrictions on footbath and hand sanitizer procedures clearly documented in general notes.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFIs.pdf | ||
| SF30 - Amendment 01.pdf | ||
| Site Visit Sign In Sheets.pdf | ||
| As Built Drawing.pdf | ||
| Revised Drawings - P-101 and P-102.pdf | ||
| Attachment 3 - Specifications.pdf | ||
| Attachment 1 - Solicitation Terms and Conditions.pdf | ||
| Attachment 4 - Wage Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\T -1
.d w g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
T-101
TITLE SHEET
INDEX OF DRAWINGS
SHEET NO. DRAWING NO. TITLE
T-101 1 OF 17 TITLE SHEET
C-101 2 OF 17 SITE PLAN
P-001 3 OF 17 PLUMBING NOTES, LEGEND AND ABBREVIATIONS
PD101 4 OF 17 MAIN BUILDING DOMESTIC WATER DEMOLITION PLAN
PD102 5 OF 17 BROODSTOCK BUILDING DOMESTIC WATER DEMOLITION PLAN
PD103 6 OF 17 HAZMAT BUILDING DOMESTIC WATER DEMOLITION PLAN
P-101 7 OF 17 MAIN BUILDING DOMESTIC WATER PLAN
P-102 8 OF 17 MAIN BUILDING DOMESTIC WATER PLAN
P-103 9 OF 17 BROODSTOCK BUILDING DOMESTIC WATER PLAN
P-104 10 OF 17 HAZMAT BUILDING DOMESTIC WATER PLAN
P-501 11 OF 17 PLUMBING DETAILS
P-601 12 OF 17 PLUMBING EQUIPMENT SCHEDULES
E-001 13 OF 17 ELECTRICAL NOTES AND LEGEND
E-002 14 OF 17 ELECTRICAL NOTES AND LEGEND
ED101 15 OF 17 ELECTRICAL DEMOLITION PLANS
E-101 16 OF 17 HAZMAT BUILDING POWER PLAN
E-102 17 OF 17 BROODSTOCK BUILDING POWER PLAN
LOCATION MAPVICINITY MAP NO SCALE NO SCALE
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
EMERGENCY EYEWASH NCCCWA
DESIGN CONTRACT NO: 12305B21D0013
DESIGN ORDER NO: 12305B24F0112
NATIONAL CENTER FOR COOL AND COLD-WATER AQUACULTURE (NCCCWA)
KEARNEYSVILLE, WV
GENERAL NOTES:
THE BUILDINGS WILL REMAIN OCCUPIED DURING CONSTRUCTION. DOWNTIME DURING INSTALLATION MUST BE MINIMIZED.
INSTALLATION MUST BE COORDINATED WITH THE SITE OPERATION SCHEDULE.
DUE TO THE NATURE OF RESEARCH CONDUCTED AT THE NCCCWA, IT IS IMPERATIVE TO CONSIDER THE MOVEMENT OF PERSONNEL AND EQUIPMENT TO PROTECT STOCKS IN THE BROODSTOCK BUILDING, HATCHERY BUILDING AND QUARANTINE LABS E AND F. EQUIPMENT MUST NEVER GO BACK INTO THE BROODSTOCK BUILDING AFTER HAVING ENTERED THE HATCHERY BUILDING OR QUARANTINE LABS E AND F. PERSONNEL AND EQUIPMENT MUST NEVER ENTER THE MAIN HATCHERY BUILDING
AFTER ENTERING QUARANTINE LABS E OR F.
ALL PERSONS ENTERING THE BROODSTOCK FACILITY WILL WALK THROUGH A FOOTBATH AND USE A HAND SANITIZER UPON ENTRY. UPON ENTERING THE CHANGING ROOM AREA, ALL SHOES MUST BE CHANGED. APPROPRIATE RAINGEAR OR OTHER PROTECTIVE WEAR SHOULD BE CHANGED INTO AT THIS POINT AS WELL. ALL PERSONS MUST STEP IN THE 2-INCH-DEEP FOOTBATH BEFORE LEAVING THE CHANGING ROOM AREA. ANYONE WHO HAS BEEN IN QUARANTINED ROOMS E OR F MAY NOT
ENTER THE BROODSTOCK FACILITY IN THE SAME DAY.
ALL PERSONS ENTERING THE MAIN HATCHERY FROM ANY DOOR MUST USE HAND SANITIZERS AND CHANGE INTO BOOTS OR
SHOE COVERS BEFORE ENTERING AND EXITING THE HATCHERY.
ALL PERSONS ENTERING QUARANTINED FISH ROOMS MUST USE HAND SANITIZER, FOOT BATH AND CHANGE FOOTWEAR OR USE SHOE COVERS BEFORE ENTERING AND BEFORE EXITING THE ROOM IN THE DESIGNATED CHANGING AREA.
ENTRY INTO THE FISH HEALTH LABS (07, 08, 17, AND 18) WILL BE RESTRICTED TO NECESSARY PERSONNEL. PERSONNEL WHO HAVE BEEN WORKING IN THE FISH HEALTH LAB WILL NOT ENTER THE MAIN HATCHERY BUILDING OR BROODSTOCK BUILDING THE SAME DAY. ANY WORK THAT NEEDS TO BE PERFORMED IN THE FISH HEALTH LABS WILL BE DONE AFTER WORK IN OTHER
LABORATORIES IS COMPLETED.
MAIN BUILDING AND HAZARDOUS MATERIALS STORAGE BUILDING
NATIONAL CENTER FOR COOL AND COLD-WATER AQUACULTURE (NCCCWA)
11861 LEETOWN RD.
KEARNEYSVILLE, WV
PROJECT LOCATION
LE
ET
OW
N
RO
AD
PROJECT LOCATION
KEARNEYSVILLE
CHARLESTON
JND
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\C iv il\ C
-1
.d w g J ul
1,
- 9 :0
6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
SCALE: 1" =
050 50
50'
25AREA SITE PLAN1
SCALE: 1" = 50'C-101
MAIN BUILDING
BROODSTOCK BUILDING
NORTH
LE
ETOWN ROAD
HAZMAT BUILDING
HATCHERY ROAD
SCALE: 1" =
020 2010
20'
HAZMAT SITE PLAN2
SCALE: 1" = 20'C-101
NORTH
HAZMAT BUILDING
C-101
SITE PLAN
AEJ
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\T
LO
VE
L~
1\ Ap pD at a\ Lo ca l\T em p\
Ac Pu bl is h_
6\
P-
1.
dw g J ul
1,
- 9 :0
6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
P-001
PLUMBING NOTES, LEGEND AND ABBREVIATIONS
JND
PLUMBING LEGEND
DOMESTIC COLD WATER
PLUMBING ABBREVIATIONS
1. CONTRACTOR MUST COVER ALL FISH TANKS DURING ALL CONSTRUCTION WORK.
2. PRIOR TO INSTALLING ANY SAFETY SHOWERS, CONTRACTOR MUST VERIFY THAT NO ELECTRICAL OUTLETS NOT PROTECTED BY GROUND
FAULT INTERRUPTION (GFI) ARE WITHIN 10 FEET OF THE SAFETY SHOWER LOCATION. GFI PROTECTED OUTLETS MAY BE LOCATED WITHIN
10 FEET OF THE SAFETY SHOWER LOCATIONS.
3. REMOVE RUBBISH AND DEBRIS FROM THE PROJECT SITE; DO NOT ALLOW ACCUMULATIONS INSIDE OR OUTSIDE THE BUILDING. REMOVE
DUST, DIRT, AND DEBRIS FROM WORK AREAS DAILY.
4. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS MUST BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT
PURCHASE.
5. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR WILL PROVIDE A COMPLETE AND FUNCTIONAL PLUMBING SYSTEM AS INDICATED WITH ALL NECESSARY
EQUIPMENT, APPURTENANCES AND CONTROLS AS INDICATED.
6. REMOVE AND CAP CONNECTING UTILITIES (WATER, DRAINAGE, POWER, GAS, ETCETERA) AS INDICATED OR NECESSARY FOR FUTURE
RECONNECTION.
7. THE CONTRACTOR MUST EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO PERFORM PLUMBING AND
PLUMBING DEMOLITION WORK.
8. THE CONTRACTOR MUST USE APPROPRIATE TOOLS AND MUST NOT IMPART EXCESSIVE VIBRATIONS TO THE EXISTING STRUCTURE OR
OTHER BUILDING COMPONENTS.
9. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. THE
CONTRACTOR WILL PROVIDE COORDINATION DRAWINGS OF TRADES.
10. ALL NEW & DEMOLISHED PIPING PENETRATIONS TO ANY BUILDING ENVELOPE MUST BE FULLY SEALED WATER TIGHT.
11. THE CONTRACTOR MUST FIELD VERIFY EXACT LOCATIONS AND POINTS OF CONNECTIONS TO THE EXISTING UTILITIES (DOMESTIC WATER
& SANITARY SEWER, NATURAL GAS, ETCETERA).
12. REFER TO SPECIFICATIONS, SHEET NOTES, DETAILS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS PERTAINING TO THE PLUMBING
WORK.
13. ALL WORK (MATERIALS, EQUIPMENT, DEVICES, COMPONENTS, SYSTEMS, SUPPORTS, ETCETERA) MUST COMPLY WITH THE
REQUIREMENTS OF ALL CODES, CODE AMENDMENTS, AND ORDINANCES AS USED, ADOPTED AND/OR ENFORCED BY THE LOCAL JURISDICTION, COUNTY AND STATE IN WHICH THE PROJECT IS LOCATED. WHERE INSPECTIONS ARE REQUIRED BY COR, WORK MUST NOT BE CONCEALED UNTIL INSPECTIONS AND TESTS ARE COMPLETED AND ACCEPTED. REFER TO SPECIFICATIONS FOR APPLICABLE CODES.
14. SCHEDULES, NOTES OR SPECIFICATIONS MAY REFERENCE "BASIS OF DESIGN" INFORMATION REGARDING A SPECIFIC MANUFACTURER OR MODEL NUMBER. SUCH INFORMATION IS PROVIDED SO AS TO ESTABLISH A STANDARD OF PERFORMANCE, QUALITY, FEATURES AND OPTIONS (SEE SCHEDULES AND SPECIFICATIONS). THE INTENT IS NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS MUST BE ACCEPTABLE PROVIDED SUCH EQUIPMENT EQUALS OR EXCEEDS THE BASIS OF DESIGN EQUIPMENT IN PERFORMANCE, QUALITY, FEATURES AND OPTIONS WHETHER SPECIFIED, SCHEDULED OR NOTED.
15. ALL EQUIPMENT FURNISHED FOR THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT".
16. ALL WORK MUST BE FABRICATED AND/OR ERECTED USING THE CONTRACTOR'S FIELD MEASUREMENTS FOR PROPER COORDINATION
WITH WORK OF OTHER TRADES.
17. ALL CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS OF
THE WORK. THEY ARE NOT INTENDED TO SPECIFY OR SHOW EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING, OR COMPONENT. DO
NOT SCALE DRAWINGS.
18. INFORMATION AND COMPONENTS SHOWN ON DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE VERSA, MUST BE PROVIDED
AS IF EXPRESSLY REQUIRED BY BOTH.
19. EXCEPT WHERE INDICATED OTHERWISE, THE NOTATION OR DESCRIPTION OF ANY ITEM IN THE CONTRACT DOCUMENTS CARRIES WITH IT THE INSTRUCTION TO FURNISH AND INSTALL THE ITEM, WHETHER OR NOT THIS INSTRUCTION IS EXPLICITLY STATED.
20. ALL WORK MUST BE INSTALLED SO AS MAINTAIN ANY "UL" ASSEMBLY RATINGS, FIRE RATINGS OR SMOKE BARRIER CAPABILITIES OF WALLS, PARTITIONS, FLOORS AND ROOF. SEAL AROUND AND PLACE UL RATED FIRE-STOP MATERIAL AT ANY PENETRATION OR DISTURBANCE OF SUCH ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND THE CONTRACTOR.
21. COORDINATE PLACEMENT OF ALL WORK WITH OTHER TRADES. DO NOT LOCATE, POSITION OR INSTALL ANY WORK IN SUCH A WAY THAT SYSTEM COMPONENTS OR ACCESS DOORS WILL BE INACCESSIBLE, UNUSABLE OR UN-MAINTAINABLE AFTER CONSTRUCTION IS
COMPLETED. COMPLY WITH MANUFACTURER'S MINIMUM RECOMMENDED SERVICE CLEARANCES.
22. UNLESS OTHERWISE INDICATED, ALL WORK MUST BE SUPPORTED FROM STRUCTURE ABOVE, FROM WALLS, FROM COLUMNS, OR FROM THE FLOOR. DO NOT USE THE INSTALLED WORK OF OTHER TRADES, OR WORK RELATED TO ANY SUPPORT SYSTEMS FOR SUPPORT FOR
OTHER TRADES.
23. PROVIDE PIPE TRANSITIONS AT FIXTURE CONNECTIONS WHERE PIPE SIZES INDICATED DIFFER FROM THE FIXTURE CONNECTION SIZE.
24. DOMESTIC WATER PIPING MUST MATCH EXISTING CONSTRUCTION.
25. PRIOR TO ANY CONSTRUCTION, FIELD VERIFY LOCATIONS OF ELECTRICAL SOURCES. LOCATE SAFETY SHOWERS A MINIMUM OF 6 FEET
AWAY FROM ANY ELECTRICAL SOURCES NOT PROTECTED BY A GROUND FAULT INTERRUPTER. PROVIDE PROPOSED LOCATIONS OF ALL
ADDED SAFETY SHOWERS TO THE GOVERNMENT FOR APPROVAL.
° DEGREES
Ø DIAMETER
AFF ABOVE FINISHED FLOOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
BTU BRITISH THERMAL UNIT
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RECIRCULATION
DTW DOMESTIC TEPID WATER
EWH ELECTRIC WATER HEATER
F FARENHEIGHT
GPM GALLONS PER MINUTE
HWCP HOT WATER CIRCULATION PUMP
IPC INTERNATIONAL PLUMBING CODE
kW KILLOWATT
MAX MAXIMUM
MIN MINIMUM
P PLUMBING
PDI PLUMBING AND DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
SSEW SAFETY SHOWER EYE WASH
TYP TYPICAL
U/G UNDERGROUND
NOTE:
UNDERLINED FIXTURE AND EQUIPMENT MARKS (SUCH AS WC) ARE
NOT ABBREVIATIONS. REFER TO THE PLUMBING SCHEDULE SHEETS,
P601 - P699 FOR FIXTURE AND EQUIPMENT DESCRIPTIONS.
1. CONTRACTOR MUST COVER ALL FISH TANKS DURING ALL DEMOLITION WORK.
2. THE DEMOLITION PLAN AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE. ITEMS TO BE REMOVED ARE DENOTED BY KEYED NOTES.
3. DEMOLITION MUST INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS IDENTIFIED. THE CONTRACTOR MUST COORDINATE ALL REQUIRED
RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION WORK
REQUIRED.
4. IN THE EVENT THE CONTRACTOR ENCOUNTERS MATERIAL REASONABLY BELIEVED TO BE ASBESTOS OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR MUST IMMEDIATELY REPORT THE CONDITION TO THE
CONTRACTING OFFICER IN WRITING.
5. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL CONSTRUCTION ASSISTANCE DEVICES
SUCH AS SCAFFOLDING AND BARRIERS.
6. THE BUILDING ENVELOPE MUST REMAIN WATERTIGHT THROUGHOUT THE CONSTRUCTION PROCESS.
GENERAL PLUMBING NOTES:
PLUMBING DEMOLITION NOTES:
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRCULATION
DOMESTIC TEPID WATER (TO SAFETY SHOWERS)
PLUMBING DEMOLITION LEGEND
HATCHING INDICATED ITEMS TO BE
DISMANTLED AND REMOVED
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\
PD
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
PD101
MAIN BUILDING DOMESTIC WATER
DEMOLITION PLAN
KEYED NOTES
1. DISCONNECT EXISTING DOMESTIC COLD WATER
FROM SAFETY SHOWER. PIPE TO BE CAPPED.
2. DISCONNECT EXISTING DOMESTIC COLD WATER
FROM SAFETY SHOWER AND PREPARE PIPING FOR
INSTALLATION OF THERMOSTATIC MIXING VALVE.
3. DISCONNECT EXISTING DOMESTIC COLD WATER
FROM SAFETY SHOWER AND REMOVE PIPING BACK
TO TEE.
4. EXISTING DOMESTIC WATER PIPING TO EXTERIOR
WALL HYDRANT TO REMAIN.
5. EXISTING COLD WATER PIPING TO SAFETY SHOWER
TO REMAIN. (TO BE CONNECTED TO THERMOSTATIC
MIXING VALVE.)
6. DISCONNECT EXISTING DOMESTIC COLD WATER
PIPING AT TEE AND PREPARE PIPING FOR
INSTALLATION OF THERMOSTATIC MIXING VALVE.
GRAPHIC SCALE
KEY PLAN
SCALE:
MAIN BUILDING DOMESTIC WATER DEMOLITION PLAN
3/32" = 1'-0"
PD101
ROOM
07/08
ROOM
ROOM
17/18
ROOM
ROOM
ROOM
44/45
ROOM
ROOM
ROOM
31/32
ROOM
2 2
EXISTING DOMESTIC COLD WATER PIPING
JND
GENERAL NOTES
1. ALL EXISTING SAFETY SHOWERS ARE TO REMAIN IN
PLACE.
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\
PD
2.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
SCALE:
BROODSTOCK BUILDING DOMESTIC WATER DEMOLITION PLAN
3/16" = 1'-0"
PD102
GRAPHIC SCALE
PD102
BROODSTOCK BUILDING DOMESTIC WATER
DEMOLITION PLAN
NORTH
1. DISMANTLE AND REMOVE EXISTING WATER HEATER.
EXISTING COLD AND HOT WATER PIPING TO REMAIN
FOR CONNECTION TO NEW WATER HEATER.
JND
KEYED NOTES#
EXISTING UNDERGROUND
DOMESTIC WATER PIPING
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\
PD
3.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
SCALE:
HAZMAT BUILDING DOMESTIC WATER DEMOLITION PLAN
1/2" = 1'-0"
PD103
GRAPHIC SCALE
PD103
HAZMAT BUILDING DOMESTIC WATER
DEMOLITION PLAN
PLAN
NORTH
JND
1. DISCONNECT EXISTING DOMESTIC COLD WATER
PIPING FROM SAFETY SHOWER AND PREPARE PIPING
FOR INSTALLATION OF WATER HEATER.
KEYED NOTES#
GENERAL NOTES
1. THE HAZMAT BUILDING MAY CONTAIN FLAMMABLE OR
EXPLOSIVE MATERIALS. FOLLOW SITE AND
REGULATORY SAFETY STANDARDS FOR WORKING IN
HAZARDOUS AREAS.
1 1
1 1
2 1
EXISTING DOMESTIC
HOT WATER PIPING
EXISTING DOMESTIC
COLD WATER PIPING
EXISTING DOMESTIC
HOT WATER PIPING
EXISTING DOMESTIC
COLD WATER PIPING
TMV-1
TMV-1
TMV-1
ROOM
07/08
ROOM
ROOM
17/18
ROOM
ROOM
ROOM
44/45
ROOM
ROOM
ROOM
31/32
ROOM
2 2 4
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
P-101
MAIN BUILDING DOMESTIC WATER PLAN
KEYED NOTES
1. EXISTING SAFETY SHOWER.
2. PROVIDE THERMOSTATIC MIXING VALVE AND 1-1/4"
MINIMUM TEPID WATER PIPING TO EXISTING SAFETY
SHOWER.
3. PROVIDE 1" MINIMUM DOMESTIC HOT AND COLD
WATER PIPING TO THERMOSTATIC MIXING VALVE.
4. EXISTING DOMESTIC WATER PIPING TO EXTERIOR
WALL HYDRANT TO REMAIN.
5. CONNECT EXISTING DOMESTIC WATER PIPING TO
THERMOSTATIC MIXING VALVE AS SHOWN.
6. PROVIDE 1" MINIMUM DOMESTIC HOT WATER PIPING
TO THERMOSTATIC MIXING VALVE.
GRAPHIC SCALE
KEY PLAN
SCALE:
MAIN BUILDING DOMESTIC WATER PLAN
3/32" = 1'-0"
P-101
PLAN
NORTH
JND
GENERAL NOTES
1. INSULATE ALL INDOOR DOMESTIC WATER PIPING
WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC
CELLULAR INSULATION WITH A THERMAL
CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.
TMV-1SSEW-1
TMV-1 SSEW-1
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
2.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
P-102
MAIN BUILDING DOMESTIC WATER PLAN
GRAPHIC SCALE
KEY PLAN
SCALE:
MAIN BUILDING DOMESTIC WATER PLAN
3/32" = 1'-0"
P-102
PLAN
NORTH
TANK ROOM
E
TANK ROOM
F
TANK ROOM
G
TANK ROOM
B
1. PROVIDE SAFETY SHOWER, THERMOSTATIC MIXING
VALVE, 1" MINIMUM DOMESTIC HOT AND COLD WATER
PIPING TO THERMOSTATIC MIXING VALVE AND 1-1/4"
MINIMUM TEPID WATER PIPING TO SAFETY SHOWER.
2. PROVIDE (2) 10" x 7" PLASTIC SIGNS NEAR OVERHEAD
DOOR. INSTALL ON BOTH SIDES OF WALL. SIGN
VERBIAGE: "NOTICE DOOR MUST REMAIN OPEN
DURING OCCUPANCY". REFER TO DETAIL 5/P-501.
3. PROVIDE 1" MINIMUM DOMESTIC HOT AND COLD
WATER PIPING TO THERMOSTATIC MIXING VALVE.
JND
KEYED NOTES#
GENERAL NOTES
1. INSULATE ALL INDOOR DOMESTIC WATER PIPING
WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC
CELLULAR INSULATION WITH A THERMAL
CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.
TANK ROOM
C
TANK ROOM
A
TANK ROOM
D
1" DOMESTIC
HOT AND COLD
TMV-1
SSEW-1
HWCP-1
3/4" DOMESTIC HOT
WATER RECIRCULATION
EWH-2
1-1/4" TEPID
WATER TO TMV-1
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
3.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
SCALE:
BROODSTOCK BUILDING DOMESTIC WATER PLAN
3/16" = 1'-0"
P-103
GRAPHIC SCALE
P-103
BROODSTOCK BUILDING DOMESTIC WATER PLAN
NORTH
1. PROVIDE SAFETY SHOWER, THERMOSTATIC MIXING
VALVE, 1" MINIMUM DOMESTIC HOT AND COLD WATER
PIPING TO THERMOSTATIC MIXING VALVE AND 1-1/4"
MINIMUM TEPID WATER PIPING TO SAFETY SHOWER.
2. PROVIDE HOT WATER CIRCULATION PUMP AND 3/4"
RECIRCULATION PIPING TO EXISTING WATER HEATER.
CONNECT POWER CORD OF CIRCULATING PUMP TO
ELECTRICAL RECEPTACLE AT LOCATION OF EXISTING
WATER HEATER. REFER TO ELECTRICAL.
3. REMOVE EXISTING WATER HEATER AND PROVIDE
WATER HEATER, EWH-2, IN LOCATION OF EXISTING
WATER HEATER. ENSURE ALL EXISTING PIPING
REMAINS IN PLACE.
JND
KEYED NOTES#
GENERAL NOTES
1. INSULATE ALL INDOOR DOMESTIC WATER PIPING
WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC
CELLULAR INSULATION WITH A THERMAL
CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.
2. THE PIPING SHOWN ON PLAN IS TO BE PROVIDED IN
ADDITION TO THE EXISTING PIPING THAT FEEDS THE
EXISTING STAINLESS STEEL SINK AND THE EXISTING
RESTROOM.
EXISTING
SAFETY SHOWER
EXISTING UNDERGROUND
DOMESTIC WATER PIPING
TMV-1
1-1/4" DOMESTIC
TEPID WATER
3/4" DOMESTIC
HOT WATER
1" DOMESTIC
COLD WATER
EWH-1
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
4.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
SCALE:
HAZMAT BUILDING DOMESTIC WATER PLAN
1/2" = 1'-0"
P-104
1. PROVIDE EXPLOSION RESISTANT ELECTRIC TANK
TYPE WATER HEATER, THERMOSTATIC MIXING VALVE
AND INTERCONNECTING PIPING TO EXISTING SAFETY
SHOWER.
GRAPHIC SCALE
P-104
HAZMAT BUILDING DOMESTIC WATER PLAN
PLAN
NORTH
JND
KEYED NOTES#
GENERAL NOTES
1. INSULATE ALL INDOOR DOMESTIC WATER PIPING
WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC
CELLULAR INSULATION WITH A THERMAL
CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.
INSULATE ALL OUTDOOR DOMESTIC WATER PIPING
WITH MINIMUM 1" THICK FLEXIBLE ELASTOMERIC
CELLULAR INSULATION WITH A THERMAL
CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.
PROVIDE OUTDOOR PIPING WITH A PVC JACKET.
2. THE HAZMAT BUILDING MAY CONTAIN FLAMMABLE OR
EXPLOSIVE MATERIALS. FOLLOW SITE AND
REGULATORY SAFETY STANDARDS FOR WORKING IN
HAZARDOUS AREAS.
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
P-501
PLUMBING DETAILS
SAFETY SHOWER/EMERGENCY EYEWASH DETAIL - SSEW-11
SCALE: NOT TO SCALEP-501
84"
37 1/2"
PULL ROD
FLOOR FLANGE
SHOWER HEAD
STAY-OPEN BALL
VALVE
1" STAY-OPEN BALL VALVE
1-1/4" NPT FEMALE INLET
H
M
CHOT WATER
INLET
LOCKNUT
TEMPERATURE
GAUGE
1-1/4" TEPID
WATER OUTLET
UNION (TYPICAL)
TEMPERATURE
ADJUSTING STEM
FULL PORT
BALL VALVE
(TYPICAL)
SET OUTLET TEMPERATURE
BETWEEN 60 AND 100°F
COLD WATER
INLET
AQUASTAT FOR CONTROL OF PUMP
PRESSURE GAUGE
GAUGE COCK
CHECK VALVE
TEPID WATER PIPING FROM
THERMOSTATIC MIXING VALVE
1-1/4" NPT
FEMALE INLET
(PLUGGED)
GALVANIZED STEEL
PIPE AND FITTINGS
EYE WASH
SPRAY HEADS
STAINLESS STEEL
BOWL
FLAG HANDLE FOR EYE
WASH ACTUATION
1-1/4" NPT
FEMALE OUTLET
IN-LINE CIRCULATING PUMP
MARK: HWCP (SEE
PLUMBING EQUIP
SCHEDULE)
CIRCUIT SETTER
W P/T PORTS
REFER TO PLANS
FOR PIPE SIZES
BALL VALVE REFER TO
SPECIFICATIONS
DOMESTIC HOT WATER CIRCULATION PUMP - HWCP-13
SCALE: NOT TO SCALEP-501
ISOLATION VALVE
(TYPICAL)
HOT WATER
SUPPLY
COLD WATER
SUPPLY
TEMPERATURE AND
PRESSURE RELIEF VALVE.
PIPE TO FLOOR DRAIN.
DRAIN VALVE WITH 3/4"
HOSE THREADS
JND
THERMOSTATIC MIXING VALVE DETAIL - TMV-12
SCALE: NOT TO SCALEP-501
ELECTRIC WATER HEATER DETAIL - EWH-1 & EWH-24
SCALE: NOT TO SCALEP-501
SIGNAGE DETAIL5
SCALE: NOT TO SCALEP-501
7"
10"
PROVIDE 10" x 7" PLASTIC SIGN
EQUAL TO COMPLIANCESIGNS.COM
SKU: ONE-35542.
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\M ec h\ P-
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
P-601
PLUMBING EQUIPMENT SCHEDULES
JND
PLUMBING EQUIPMENT SCHEDULE
MARK DESCRIPTION BASIS OF DESIGN ELECTRICAL
SSEW-1 SAFETY SHOWER/EYE WASH, COMBINATION EYE/FACE WASH AND SHOWER SAFETY
STATION. 11 1/2" STAINLESS STEEL EYE WASH BOWL. 1/2" STAY OPEN FACE WASH
BALL VALVE. 1" STAY OPEN SHOWER VALVE WITH PULL HANDLE. 1-1/4 NPT FEMALE
INLET. UNIT SHALL MEET OR EXCEED ANSI Z358.1 - 2014, AND COME WITH A FULL
2-YEAR WARRANTY.
GURDIAN G1950 NONE
TMV-1 THERMOSTATIC MIXING VALVE, 50 GPM FLOW CAPACITY AT 30 PSIG SUPPLY
PRESSURE, PROVIDE WITH COLD WATER BYPASS FUNCTIONALITY, 1" NPT INLETS
AND 1-1/4" NPT OUTLETS, ANSI/ASSE 1071 CERTIFIED.
GURDIAN G6040 NONE
EWH-1 EXPLOSION RESISTANT WATER HEATER, ELECTRIC, 50 GALLON, 5000 WATT HEATING
ELEMENT, UL AND CSA LISTED HOUSING RATED FOR OPERATION IN CLASS I,
DIVISION 1 & 2.
HUBBELL ER50-6-SLRS 240/1 VOLT
5000 WATT
24 AMP
EWH-2 ELECTRIC WATER HEATER, 50 GALLON, DUAL NON-SIMULTANEOUS 4500 WATT
HEATING ELEMENTS
RHEEM PRO+E50 T2 RH92 CL 240/1 VOLT
4500 WATT
21 AMP
HWCP-1 HOT WATER CIRCULATION PUMP, COMPRESSION FITTINGS, 24 HOUR
PROGRAMMABLE TIMER, 120 VAC, 25 WATTS, PROVIDE WITH 10' POWER CORD
TACO 006E3 120 VOLT
25 WATT
0.2 AMP
NOTE:
BASIS OF DESIGN INFORMATION REGARDING A SPECIFIC MANUFACTURER OR MODEL NUMBER IS PROVIDED SO AS TO ESTABLISH A STANDARD OF PERFORMANCE, QUALITY, FEATURES AND OPTIONS. THE INTENT IS NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS MUST BE ACCEPTABLE PROVIDED SUCH EQUIPMENT EQUALS OR EXCEEDS THE BASIS OF DESIGN EQUIPMENT IN PERFORMANCE, QUALITY, FEATURES
AND OPTIONS WHETHER SPECIFIED, SCHEDULED OR NOTED.
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR MUST COVER ALL FISH TANKS DURING ALL CONSTRUCTION AND DEMOLITION WORK.
2. THE WORK MUST CONFORM WITH ALL REQUIREMENTS OF:
· NFPA 70, NATIONAL ELECTRICAL CODE (NEC) (2020)
· NFPA 101, LIFE SAFETY CODE (2018)
· NFPA 780, STANDARDS FOR INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2020)
· IEEE C2, NATIONAL ELECTRICAL SAFETY CODE (NESC) (2017)
· ASHRAE 90.1, ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS (2013)
*CRITERIA AND STANDARDS LISTED ALSO INCLUDE SPECIFIED STANDARDS AND RELATED SECTIONS AS PART OF THE DESIGN.
2. MINIMUM RACEWAY SIZE MUST BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL FOR FEEDERS
AND 20% FOR BRANCH CIRCUITS IAW CNIFR REQUIREMENTS.
3. THE ELECTRICAL CONTRACTOR MUST CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND MUST BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN
LOCATIONS OF ELECTRICAL CONNECTIONS.
4. ALL FEEDERS AND BRANCH CIRCUITS MUST INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
5. EXISTING ELECTRICAL WORK (NOT SHOWN) MUST REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER MUST BE RESTORED TO WORKING CONDITION. THE RESTORATION MUST INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED MUST BE INCLUDED IN THE CONTRACT AND NO EXTRA
COMPENSATION WILL BE GRANTED.
6. NEW WORK MUST BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK MUST BE CHECKED AGAINST EXISTING
WORK
7. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
8. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
9. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
10. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
11. CONTRACTOR MUST FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND
DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
12. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT MUST BE BLACK, 1/4" IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN WITH A PERMANENT MARKER.
ELECTRICAL ABBREVIATIONS:
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
BMGB
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CMS
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
ECB
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
HWRP
HWSP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
BUILDING MASTER GROUNDING BUSBAR
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
COMBINATION MOTOR STARTER
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR STANDARD
DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY SYSTEM
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
HWUH
HZ
IAW
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PBB
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RBB
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SBB
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TEBC
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
WPIU
XFMR
Z
HOT WATER UNIT HEATER
HERTZ
IN ACCORDANCE WITH
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
PRIMARY BONDING BUSBAR
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RACK BONDING BUSBAR
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SECONDARY BONDING BUSBAR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
WEATHERPROOF IN USE
TRANSFORMER
IMPEDANCE
E-001
ELECTRICAL NOTES AND LEGEND
WS
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\E le c\ D
W G
S\ E-
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
JGM
LA-1
LA-1
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" MUST BE GROUND FAULT CIRCUIT
INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" MUST BE GFI AND WEATHERPROOF.
4.
DEVICES NOTED AS "DL" MUST BE RATED FOR DAMP LOCATION.5.
DEVICES NOTED AS "NL" MUST BE NIGHT LIGHTS. PROVIDE
UNSWITCHED POWER TO FIXTURE.
6.
DEVICES NOTED AS "WG" MUST BE PROVIDED AND INSTALLED WITH
A WIRE GUARD.
7.
DEVICES NOTED AS "TR" MUST BE TAMPER RESISTANT.8.
PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
DUPLEX GFI RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
CONDUIT AND WIRING RECEPTACLESLEGEND GENERAL NOTES
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR
CEILING. TIC MARKS INDICATE NUMBER OF
CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR
IS NOT SHOWN, BUT MUST BE PROVIDED. SIZE THE
EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES
THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE
MARKINGS TO THE LEFT SIGNIFY THAT THREE
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR
FLOOR. TIC MARKS INDICATE NUMBER OF CONDUCTORS.
THE EQUIPMENT GROUNDING CONDUCTOR IS NOT
SHOWN, BUT MUST BE PROVIDED. SIZE THE EQUIPMENT
GROUNDING CONDUCTOR AND THE CONDUIT PER THE
NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS TO
THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF
THE CONDUCTORS THAT MUST BE RUN IN THE CONDUIT.
THE ABSENCE OF TEXT SIGNIFIES THAT THE
CONDUCTORS SHOULD BE #12 AWG.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES
EXPOSED SURFACE-MOUNTED RACEWAY (SEE
SPECIFICATIONS).
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL
PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN
A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.
LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR
CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS
FOR CONDUCTOR REQUIREMENTS.
DEVICES NOTED AS "WPIU" MUST BE GFI AND WEATHERPROOF IN USE.
9.
LONG TIC MARK IDENTIFIES CONDUCTOR. SHORT TICK MARK
IDENTIFIES NEUTRAL. HOOKED TIC MARK IDENTIFIES GROUND.
E-002
ELECTRICAL NOTES AND LEGEND
WS
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\E le c\ D
W G
S\ E-
2.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
CON_CENTERCON_TYPE
CON_WIDTH
CON_LENGTH
KEYED NOTES
GRAPHIC SCALE
1. DEMO EXISTING WATER HEATER. PRESERVE
CIRCUIT/CONDUIT FOR REUSE. REFER TO KEYED
NOTE 1 ON E-102.
2. DISMANTLE AND REMOVE EXISTING LOAD CENTER.
DISCONNECT EXISTING WIRING AND CONDUIT.
EXISTING WIRING AND CONDUIT TO REMAIN FOR
CONNECTION TO NEW LOAD CENTER.
SCALE:
HAZMAT BUILDING ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
ED101
PLAN
NORTH
ED101
ELECTRICAL DEMOLITION PLANS
WS
SCALE:
BROODSTOCK BUILDING ELECTRICAL DEMOLITION PLAN
3/16" = 1'-0"
ED101
NORTH
GENERAL NOTES
1. THE HAZMAT BUILDING MAY CONTAIN FLAMMABLE OR
EXPLOSIVE MATERIALS. FOLLOW SITE AND
REGULATORY SAFETY STANDARDS FOR WORKING IN
HAZARDOUS AREAS.
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\E le c\ D
W G
S\
ED
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
LC
EWH-1
4.5KVA,240/120V2P3W
LC-11,13
3/4"C,2#10,#10N,#10G
NOTE
NEUTRAL
BUS AMPS
VOLTS AIC
MAIN BKR
LUGSFED FROM
MOUNTING
ROOM
BCIRCUIT DESCRIPTION
LOAD KVA
CKT
CIRCUIT DESCRIPTION
CKT
BKR#
CKTCKT
BKR A B
LOAD KVA
A
STANDARD
22,000
240/120V 2P 3W
"EX" PREFIX DENOTES EXISTING - INTERCEPT AND EXTEND CIRCUITS TO NEW PANEL. LOADS SHOWN ARE ADDITIONAL ONLY.
SURFACE
LC
UTILITY 100%
00 20/220/1 21 3 420/1 |0 0
00 20/120/1 65 7 820/1 20/10 0
00 20/220/1 109 11 1230/2 |2.25 0
02.25 20/1 | 1413 15 1620/1 20/10 0
00 20/120/1 1817 19 2020/1 20/10 0
00 20/120/1 2221 23 2420/1 20/10 0
00 20/120/1 2625 27 2820/1 20/10 0
00 20/120/1 3029
TOTAL CONNECTED KVA BY PHASE 2.252.25
CONN KVA CALC KVACALC KVA
HEATING 4.5 4.5 (100%) TOTAL LOAD 4.5
BALANCED LOAD 18.8 A
EX-LIGHTS
EX-T-STAT HEATER
EX-GEN CHARGER
EX-HEAT TAPE
EX-EXISTING
EWH-1 & HEATER
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
EX-AIC
EX-RECEP
EX-DAY TANK
EX-GEN HEATER
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
1. REPLACE EXISTING LOAD CENTER WITH NEW LOAD
CENTER AS SHOWN IN THE PANEL SCHEDULE. RE-USE
EXISTING FEEDER. INTERCEPT AND EXTEND EXISTING
CIRCUITS TO NEW PANEL. CONNECT NEW CIRCUIT AS
SHOWN IN PANEL SCHEDULE.
2. ELECTRICAL CONNECTION FOR WATER HEATER. UTILIZE
APPROPRIATE EXPLOSION PROOF CONDUIT AND
TERMINATIONS TO WATER HEATER.
3. SPACE IS CLASSIFIED CLASS 1 DIV 2. PROVIDE
EQUIPMENT AND DEVICES LISTED FOR USE. INSTALL
UTILIZING CLASS 1 DIV 2 WIRING METHODS PER NFPA 70.
1. UNLESS OTHERWISE NOTED, INSTALL DUPLEX
RECEPTACLES AT 18" A.F.F.
SCALE:
HAZMAT BLDG. POWER PLAN
1/4" = 1'-0"
E-101
PLAN
NORTH
E-101
HAZMAT BUILDING POWER PLAN
WS
EQUIPMENT CONNECTION SCHEDULE
CALL OUT DESCRIPTION CIRCUIT VOLTS AMPS BREAKER HP KVA WIRE SIZE DISCONNECT WIRE LENGTH NOTE
EWH-1
WATER HEATER. SEE
MECHANICAL FOR MORE
DETAILS PRIOR TO
ROUGH-IN
LC: 11,13 240/120V 2P 3W 18.75000 30 4.50000 #10 NON FUSED 8'-6"
3 4" CONDUIT
NEMA 7/9
EWH-2
WATER HEATER. SEE
MECHANICAL FOR MORE
DETAILS PRIOR TO
ROUGH-IN
RP-2: 65,67 240/120V 2P 3W 18.75000 30 5.00000 #10 NON FUSED 3 4" CONDUIT
HWCP-1
HOT WATER CIRCULATION
PUMP. SEE MECHANICAL
FOR MORE DETAILS PRIOR
TO ROUGH-IN
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\E le c\ D
W G
S\ E-
1.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
NOTE
NEUTRAL
BUS AMPS
VOLTS AIC
MAIN BKR
LUGSFED FROM
MOUNTING
ROOM
BCIRCUIT DESCRIPTION
LOAD KVA
CKT
CIRCUIT DESCRIPTION
CKT
BKR#
CKTCKT
BKR A B
LOAD KVA
A
TOTAL CONNECTED KVA BY PHASE
CONN KVA CALC KVACALC KVA
HEATING 0 0 (100%) TOTAL LOAD 0
BALANCED LOAD 0
MOD'S
RECEPT PENDANT CARD
RECEPT PENDANT CARD
OUTSIDE GFI BY HHJ
BROWN
BLUE
OFFICE FRIDGE
OFFICE MICROWAVE
OFFICE REC FREEZER
OFFICE LTS
EWH-2
SPARE
SPARE
FEED SYSTEM
208 OUTLET
208 OUTLET
SWITCH 1 BROWN
EGG PANEL
SPARE OVERHEAD BOX YELLOW
DOUBLE POLE 30 AMP
2FT POLLY AUX LIGHTING
SPACE
SPACE
OFFICE HEAT
STANDARD
22,000
240/120V 2P 3W
"EX" PREFIX DENOTES EXISTING - INTERCEPT AND EXTEND CIRCUITS TO NEW PANEL. LOADS SHOWN ARE ADDITIONAL ONLY.
SURFACE
RP2
UTILITY 100%
00 20/120/1 4443 45 4620/1 0 0
00 50/220/1 4847 49 5020/1 0 0
00 20/120/1 5251 53 5420/2 0 0
00 125/2 | 5655 57 5820/1 0 0
00 20/120/1 6059 61 6220/1 30/20 0
0020/1 6463 65 6630/2 20/10 0
00 20/16867 69 7020/1 20/10 0
00 20/220/1 7271
SPARE
SPARE
YELLOW HEATER
ORANGE HEATER
RED HEATER
BLUE HEATER
BATH HEAT
LARGE FAN
HATCH FAN 1
HATCH FAN 2
73 7420/1 0 0 00 20/220/1 7675
77 7820/1 0 0 00 20/120/1 8079
81 8220/1 20/10 0 00 20/120/1 8483
BLACK
20/1 FEED SYSTEM
20/1 SWITCH 2 BLUE
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
1. CONNECT NEW GFI RECEPTACLE TO EXISTING
CIRCUIT RP1:39. PLUG HWCP-1 INTO RECEPTACLE.
1. UNLESS OTHERWISE NOTED, INSTALL DUPLEX
RECEPTACLES AT 18" A.F.F.
E-102
BROODSTOCK BUILDING POWER PLAN
WS
SCALE:
BROODSTOCK BUILDING ELECTRICAL POWER PLAN
3/16" = 1'-0"
E-102
NORTH
RP2: 25,27
3/4"C,2#10,#10N,#10G
EPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\5
4- M
U
SD
A Em er ge nc y
Sh ow er
M ix in g
Va lv es
Ke ar ne ys vi lle
W V\
W or ki ng F ol de r\E le c\ D
W G
S\ E-
2.
dw g
J ul
1,
- 9
:0 6a m
COR
TEL
5424-M
C. MORRIS
A. ANDERSON
. 7/1/25
Agricultural
Service Research
USDA ARS NORTHEAST AREA
10300 BALTIMORE AVENUE
BELTSVILLE, MD 20705
EMERGENCY EYEWASH NCCCWA
11861 LEETOWN ROAD
KEARNEYSVILLE, WV
| Sheets and Views |
| T-101 |
| C-101 |
| P-001 |
| PD101 |
| PD102 |
| PD103 |
| P-101 |
| P-102 |
| P-103 |
| P-104 |
| P-501 |
| P-601 |
| E-001 |
| E-002 |
| ED101 |
| E-101 |
| E-102 |
File details come from the government source that posted it. Updated .