Revised Drawings - P-101 and P-102.pdf

PDF 1 MB Posted

Attached to
Safety Shower Modifications and Installations Federal contract opportunity
Solicitation number
1232SA26Q0170
Issued by
Department of Agriculture Agricultural Research Service

About this file

This document is a set of architectural construction drawings for the Main Building Domestic Water Plan at the USDA Agricultural Research Service (ARS) Northeast Area facility located in Kearneysville, West Virginia (NCCCWA, 11861 Leetown Road).

The drawings specify the installation of domestic hot and cold water piping systems with thermostatic mixing valves (TMV-1, SSEW-1) throughout the main building and tank rooms. Key requirements include: providing 1-inch minimum diameter domestic hot and cold water piping to thermostatic mixing valves; installing 1.25-inch minimum diameter tepid water piping from mixing valves to existing safety showers; connecting existing domestic water piping to exterior wall hydrants; providing domestic hot water recirculation piping from headers to thermostatic mixing valves; and insulating all indoor domestic water piping with minimum 0.5-inch thick flexible elastomeric cellular insulation with a thermal conductivity K-value of 0.23 BTU-IN/HR-SQ-FT-°F. The drawings cover multiple areas including Rooms 21, 31/32, 33, 43, and 44/45 in the main building, as well as Tank Rooms A, B, C, and G. The project was designed by Johnson-McAdams Architects/Engineers and revised per Pre-Bid RFI 01 as of March 6, 2026. The drawings were prepared by C. Morris and A. Anderson with a project date of July 1, 2025.

View the file

Other files for this federal contract opportunity

Other files attached to Safety Shower Modifications and Installations, newest first.
File Type Posted
SF30 - Amendment 01.pdf PDF
Site Visit Sign In Sheets.pdf PDF
As Built Drawing.pdf PDF
RFIs.pdf PDF
Attachment 2 - Drawings.pdf PDF
Attachment 1 - Solicitation Terms and Conditions.pdf PDF
Attachment 4 - Wage Determination.pdf PDF
Attachment 3 - Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 1

1 1

2 1

EXISTING DOMESTIC

HOT WATER PIPING

EXISTING DOMESTIC

COLD WATER PIPING

EXISTING DOMESTIC

HOT WATER PIPING

EXISTING DOMESTIC

COLD WATER PIPING

TMV-1

TMV-1

TMV-1

ROOM

07/08

ROOM

ROOM

17/18

ROOM

ROOM

ROOM

44/45

ROOM

ROOM

ROOM

31/32

ROOM

2 2 42

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

J:

\C ol lie rv ille

\2

Pr oj ec ts \5

4-

M U

SD

A

Em er ge nc y Sh ow er

M ix in g Va lv es

Ke ar ne ys vi lle W

V\

S ub m itt al s\

R ec or d

D w g\ C

AD

\P

-1

.d w g M ar

9,

- 3 :5

9p m

COR

TEL

5424-M

C. MORRIS

A. ANDERSON

. 7/1/25

Agricultural

Service Research

USDA ARS NORTHEAST AREA

10300 BALTIMORE AVENUE

BELTSVILLE, MD 20705

EMERGENCY EYEWASH NCCCWA

11861 LEETOWN ROAD

KEARNEYSVILLE, WV

JGM

P-101

MAIN BUILDING DOMESTIC WATER PLAN

KEYED NOTES

1. EXISTING SAFETY SHOWER.

2. PROVIDE THERMOSTATIC MIXING VALVE AND 1-1/4"

MINIMUM TEPID WATER PIPING TO EXISTING SAFETY

SHOWER.

3. PROVIDE 1" MINIMUM DOMESTIC HOT AND COLD

WATER PIPING TO THERMOSTATIC MIXING VALVE.

4. EXISTING DOMESTIC WATER PIPING TO EXTERIOR

WALL HYDRANT TO REMAIN.

5. CONNECT EXISTING DOMESTIC WATER PIPING TO

THERMOSTATIC MIXING VALVE AS SHOWN.

6. PROVIDE 1" MINIMUM DOMESTIC HOT WATER PIPING

TO THERMOSTATIC MIXING VALVE.

GRAPHIC SCALE

KEY PLAN

SCALE:

MAIN BUILDING DOMESTIC WATER PLAN

3/32" = 1'-0"

P-101

PLAN

NORTH

JND

GENERAL NOTES

1. INSULATE ALL INDOOR DOMESTIC WATER PIPING

WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC

CELLULAR INSULATION WITH A THERMAL

CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.

A 3-6-26 TEL REVISED PER PRE-BID RFI 01

A

TMV-1SSEW-1

TMV-1 SSEW-1

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

J:

\C ol lie rv ille

\2

Pr oj ec ts \5

4-

M U

SD

A

Em er ge nc y Sh ow er

M ix in g Va lv es

Ke ar ne ys vi lle W

V\

S ub m itt al s\

R ec or d

D w g\ C

AD

\P

-1

.d w g M ar

9,

- 3 :5

9p m

COR

TEL

5424-M

C. MORRIS

A. ANDERSON

. 7/1/25

Agricultural

Service Research

USDA ARS NORTHEAST AREA

10300 BALTIMORE AVENUE

BELTSVILLE, MD 20705

EMERGENCY EYEWASH NCCCWA

11861 LEETOWN ROAD

KEARNEYSVILLE, WV

JGM

P-102

MAIN BUILDING DOMESTIC WATER PLAN

GRAPHIC SCALE

KEY PLAN

SCALE:

MAIN BUILDING DOMESTIC WATER PLAN

3/32" = 1'-0"

P-102

PLAN

NORTH

TANK ROOM

E

TANK ROOM

F

TANK ROOM

G

TANK ROOM

B

1. PROVIDE SAFETY SHOWER, THERMOSTATIC MIXING

VALVE, 1" MINIMUM DOMESTIC HOT AND COLD WATER

PIPING TO THERMOSTATIC MIXING VALVE AND 1-1/4"

MINIMUM TEPID WATER PIPING TO SAFETY SHOWER.

2. PROVIDE (2) 10" x 7" PLASTIC SIGNS NEAR OVERHEAD

DOOR. INSTALL ON BOTH SIDES OF WALL. SIGN

VERBIAGE: "NOTICE DOOR MUST REMAIN OPEN

DURING OCCUPANCY". REFER TO DETAIL 5/P-501.

3. PROVIDE 1" MINIMUM DOMESTIC HOT AND COLD

WATER PIPING TO THERMOSTATIC MIXING VALVE.

4. PROVIDE 1" MINIMUM DOMESTIC HOT WATER

RECIRCULATION PIPING FROM HEADER TO

THERMOSTATIC MIXING VALVE.

JND

KEYED NOTES#

GENERAL NOTES

1. INSULATE ALL INDOOR DOMESTIC WATER PIPING

WITH MINIMUM 1/2" THICK FLEXIBLE ELASTOMERIC

CELLULAR INSULATION WITH A THERMAL

CONDUCTIVITY K-VALUE OF 0.23 BTU-IN/HR-SQ-FT-°F.

TANK ROOM

C

TANK ROOM

A

TANK ROOM

D

A 3-6-26 TEL REVISED PER PRE-BID RFI 01