Attachment 2_Drawings.pdf
PDF 23 MB Posted
- Attached to
- XTLF 15-1018 Repair AA and E Storage at F527
- Solicitation number
- FA3029-25-R-0007
About this file
This document is a comprehensive set of architectural and engineering drawings for a construction project at Vance Air Force Base in Enid, Oklahoma. The project, identified as XTLF 15-1018, involves repairing the Security Forces (SFS) Arms, Ammunition, and Explosives (AA&E) Storage in Building 527. The drawings include detailed plans for architectural modifications, structural reinforcements, electrical systems, mechanical systems, and fire alarm installations.
Key technical details include replacing the entry door with a GSA Class 5 door, installing new epoxy floor coating, reinforcing interior walls with steel and plywood layers, adding a new acoustical drop ceiling, and relocating electrical circuits to a new panel outside the room. The renovation aims to comply with UFC 04-026-01 and MIL-HNDBK 1013/1A standards, specifically addressing forced entry resistance requirements for AA&E storage. The project involves removing and reinstalling existing fixtures, replacing window fasteners with tamper-resistant versions, and installing a dehumidifier with specific mounting and condensate drainage requirements. The drawings are dated September 15, 2023, with multiple discipline-specific sheets covering architectural, structural, mechanical, electrical, and fire alarm system modifications.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NAME:
PROJECT INFORMATION
PROJECT NUMBER:
Project Location:
Project Status: ISSUE DATE:
REFERENCES:
UNITED STATES AIR FORCE
AIR EDUCATION TRAINING COMMAND
ENID OKLAHOMA
140 CHANNEL ST.
VANCE AFB, OK 73705
P: (580) 213-7787
CA# 8716 EXPIRES: 30 JUNE 2024
EXECUTION OF WORK
DESCRIBED WITHIN THIS
PROJECT PLANS AND
SPECIFICATIONS SHALL
OCCUR IAW 48CFR SUBPART
25.2 BUY AMERICAN -
CONSTRUCTION MATERIALS.
IRP REMEDIATION PROGRAM (IRP)
THERE IS KNOWN CONTAMINATION IN
THE PROJECT AREA. SPECIAL
REQUIREMENTS ARE NEEDED.
THERE IS NO KNOWN CONTAMINATION IN
THE PROJECT AREA.
IRP - REMEDIATION PROJECT MANAGER DATE
LEAD BASED PAINT (LBP)
THERE IS NO KNOWN LBP MATERIALS IN THE
PROJECT
THIS FACILITY CONTAINS LBP MATERIALS;
HOWEVER, NOT IN THE AREA OF CONSTRUCTION.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE ABANDON IN PLACE FOR THIS PROJECT.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED BY ACM/LBP REMOVAL
CONTRACTOR.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED BY THE GOVERNMENT.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED IAW THIS PROJECT PLANS AND
SPECIFICATIONS.
BASE ENVIRONMENTAL ENGINEER DATE
ASBESTOS CONTAINING MATERIAL (ACM) INITIAL APPLICABLE
CONDITION
THERE IS NO KNOWN ACM MATERIALS IN THE
PROJECT
THIS FACILITY CONTAINS ACM MATERIALS;
HOWEVER, NOT IN THE AREA OF CONSTRUCTION.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED BY ACM/LBP REMOVAL
CONTRACTOR.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED BY THE GOVERNMENT.
THIS FACILITY CONTAINS LBP MATERIALS THAT
WILL BE REMOVED IAW THIS PROJECT PLANS AND
SPECIFICATIONS.
USER / FACILITY
MANAGER
71ST S5X - ATPM
AFFS/CEN
CHIEF ENGINEER
71 ISS/CE
PROJECT NUMBER: PROJECT NAME:
PROJECT ACCEPTANCE SIGNATURES
BASE ENVIRONMENTAL ENGINEER DATE
INITIAL APPLICABLE
CONDITION
INITIAL APPLICABLE
CONDITION
VANCE AFB, ENID OK
ORGANIZATION ORGANIZATION
REPRESENTATIVE
SIGNATURE DATE
XTLFXTLF15-1018 15-1018 REPAIR SFS AA&E STORAGE, B527
15-1018 REPAIR SFS AA&E STORAGE, B527
XTLF15-1018
09/15/2023FOR CONSTRUCTION
Christopher Wheeler
Christopher Taylor, PE
James Kite
Maj. Zachary Jarvis
SHEET INDEX
Sheet Number Sheet Name
G-001 COVER
G-002 HAUL ROUTE, ABBREVIATIONS, AND COMMON SYMBOLOGY
A-101 FLOOR PLAN, DETAILS, AND DECONSTRUCTION NOTES
S-101 STRUCTURAL RCP, STRUCTURAL WALL SECTIONS, AND STRUCTURAL NOTES
FA-101 FIRE ALARM - PLAN
M-101 MECHANICAL PLAN
ED-101 ELECTRICAL DECONSTRUCTION PLANS AND DETAILS
E-101 ELECTRICAL POWER AND LIGHTING PLANS
E-601 ELECTRICAL PLANS - RISER AND SCHEDULE
E-602 ELECTRICAL PLANS - RISER AND SCHEDULE
18 Sept 2023
18 Sept 23
21 Sep 23
21 Sep 23
2Oct2023
3 Oct 23
IRP SIGNATURE NOT REQUIRED. ALL WORK DESCRIBED
HEREIN IS INTERIOR TO EXISTING FACILITY.
NA
NA
PRIMARY SITE ACCESS
ROUTE
SECONDARY BASE ENTRY AND
ALL VEHICLE EXIT ROUTE
POV BASE ENTRY ONLY
(RESTRICTED HOURS)
PROJECT LOCATION
SECONDARY HAUL ROUTE TO BE USED ONLY
WHEN PRIMARY GATE IS CLOSED
POV ONLY LANE
PROJECT LOCATION, BUILDING 527
BUILDING 288, CIVIL ENGINEERING INCLUDING
CONSTRUCTION MANAGEMENT
BUILDING 500, GOVERNMENT CONTRACTING
BUILDING 72, VISITOR'S CENTER. USE FOR PASS
APPROVAL PRIOR TO BEGINNING WORK
BUILDING 75, COMMERCIAL VEHICLE INSPECTION
9 CONTRACTOR STAGING AREA
PRIMARY HAUL ROUTE
ARCHITECTURAL DRAFTING CONVENTIONS
Room name
150 SF
View Name
SCALE: 1/8" = 1'-0"
G012
DETAIL VIEW NUMBER
SHEET ON WHICH DETAIL
APPEARS
VIEW NUMBER
NUMBER
DESIGNATION
LETTER/NUMBER
DESIGNATION
A-101
DIRECTION OF VIEW FOR ELEVATION
SHEET ON WHICH ELEVATION APPEARS
ELEVATION VIEW NUMBER
HEIGHT
DESIGNATION
10'-0"
NUMBER
DESIGNATION
HEIGHT DESIGNATION
LETTER/NUMBER
DESIGNATION
NAME DESIGNATION
ROOM NAME/NUMBER SYMBOL
PARTITION TYPE SYMBOL
SPOT/CEILING ELEVATION SYMBOL
DOOR SYMBOL
ELEVATION SYMBOL
GRID SYMBOL
VIEW TITLE
EXTERIOR ELEVATION MARKER
INTERIOR ELEVATION MARKER
BUILDING / WALL SECTION MARKER
DETAIL MARKER
A-101
SIM
8' 4' 0 8'
SCALE: 1/8" = 1'-0"
LEVEL 30
24'-0"
MATCHLINE SYMBOL
1 / A-121
1 / A-122
LETTER/NUMBER
DESIGNATION OF
FLOOR PLAN(S)
DIRECTION OF ELEVATION VIEW
ELEVATION VIEW NUMBER
SHEET ON WHICH ELEVATION APPEARS
A101
SIM SIMILAR (IF APPLICABLE)
CENTERLINE SYMBOL =
DIRECTION OF SECTION VIEW
SECTION VIEW NUMBER
SHEET ON WHICH SECTION APPEARS
A101
SIM SIMILAR (IF APPLICABLE)
GRAPHIC SCALE SYMBOL
NORTH ARROW
SIMILAR (IF APPLICABLE)
PLAN NORTH
ARROW DIRECTION
EXISTING NEW
MILLWORK ELEVATION MARKER
DIRECTION OF ELEVATION VIEW
ELEVATION VIEW NUMBER / SHEET NUMBER1 / A-101
N
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
G-002
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
H A
U L
R O
U
TE
, A B
B R
E V
IA
TI
O N
S , A
N D
C O
M M
O N
S Y
M B
O
LO
G Y
B. DECOCQ
09/15/2023
XTLF15-1018
BCD
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
GENERAL NOTES
1. APPROVED HAUL AND ACCESS ROUTES ARE NOTED ON
THE PLAN. THE CONTRACTOR SHALL ONLY USE ACCESS
ROUTES THAT HAVE BEEN PREVIOUSLY APPROVED BY
CONSTRUCTION MANAGEMENT.
2. CONSTRUCTION MANAGER'S OFFICE IS LOCATED ON THE
FIRST FLOOR, NORTH-WEST CORNER OF BLDG 288.
3. GOVERNMENT CONTRACTINGIS LOCATED ON THE SECOND
FLOOR, NORTH -WEST CORNER OF BLDG 500.
4. LOCAL PURCHASE IS LOCATED ON THE FIRST FLOOR,
SOUTH-WEST CORNER OF BLDG 200.
LEGEND
KEY NOTES
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
1" = 400'-0"1 Map
F527
A
@ AT
A AMPERES
A/C AIR CONDITIONING
AA&E ARMS, AMMUNITION and
EXPLOSIVES
AB ANCHOR BOLT
ABI ADDITIVE BID ITEM
ACT ACOUSTICAL CEILING TILE
ADJ ADJACENT, ADJUSTABLE
ADV ADVANTOR SYSTEM
AFF ABOVE FINISH FLOOR
AFL ATHLETIC FLOORING
AGGR AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM, AL ALUMINUM
AP ACRYLIC PANEL
APPROX APPROXIMATE
APVD APPROVED
ARCH ARCHITECT, ARCHITECTURAL
ATTEN ATTENUATOR, ATTENUATION
AWP ACOUSTIC WALL PANEL
B
BB BASE BID
BD BOARD
BITUM BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BOD BASIS OF DESIGN
BOT, BTM BOTTOM
BRG BEARING
BRK BRICK
BSMT BASEMENT
C
C TO C CENTER TO CENTER
CAB CABINET
CBB CEMENTITIOUS BACKER BOARD
CC CONTRACTOR CONNECT
CF CONTRACTOR FURNISHED
CFM COLD-FORMED METAL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CI CONTRACTOR INSTALLED
CJ CONSTRUCTION CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CPT CARPET
CR CONTRACTOR ROUGH-IN
CT CERAMIC TILE
D
DB DOUBLE
DEG DEGREES
DEMO DEMOLITION, DEMOLISH
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DN, DWN DOWN
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DTL DETAIL
DWG DRAWING
DWP DECORATIVE WALL PANEL
DWR DRAWER
E
EA EACH
EF EXHAUST FAN
EIFS EXTERIOR INSULATION & FINISH
SYSTEM
ELEC ELECTRICAL
ELEV ELEVATION
EPC EPOXY COATING
EQ EQUAL
EQPT EQUIPMENT
ES EMERGENCY SHOWER
EW EYE WASH
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXP JT,
EJ
EXPANSION JOINT
EXT EXTERIOR
F
F FAHRENHEIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FHS FIRE HOSE STATION
FIN FINISHED
FLR FLOOR
FPRF FIREPROOF
FRP FIBER-REINFORCED PLASTIC
FT FOOT, FEET
FTG FOOTING
FURR FURRED, FURRING
FWC FABRIC WALL COVERING
G
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GF-GI GOVERNMENT
FURNISHED-GOVERNMENT
INSTALLED
GFCI GROUND-FAULT CURRENT
INTERRUPTER
GL GLASS, GLAZING
GRT GROUT
GT GLASS TILE
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HB HOSE BIB
HC HANDICAPPED
HC HOLLOW CORE
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HMB HORIZONTAL METAL BLINDS
HORIZ HORIZONTAL
HPL HIGH PRESURE LAMINATE
HT HEIGHT
HTR HEATER
HVAC HEATING, VENTILATING, AND
AIR CONDITIONING
Hz HERTZ
I
ID INSIDE DIAMETER
IN INCH
INSUL INSULATION
INT INTERIOR
J
JST JOIST
JT JOINT
L
LAM LAMINATE
LAV LAVATORY
LB POUND
LBL LABEL
LED LIGHT EMITTING DIODE
LF LINEAL FEET
LN LINOLEUM
LVR LOUVER
LVT LUXURY VINYL TILE
LWT LIGHTWEIGHT
M mA MILLIAMP
MACH MACHINE
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MBR MEMBER
MC MEDICINE CABINET
MC METAL CLAD
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURE, MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MK MARK
ML METAL LOCKER
MLDG MOLDING
MO MASONRY OPENING
MSNRY MASONRY
MSP METAL SPLASH PAN
MT METAL THRESHOLD
MTD MOUNTED
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WEATHERPROOFING
N
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPRN NEOPRENE
NTS NOT TO SCALE
O
OA OVERALL, OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
OZ OUNCE
P
PART PARTIAL
PL PLATE, PLASTIC
PLAS PLASTIC
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL, PANELBOARD
PREFAB PREFABRICATED
PREFIN PREFINISHED
PRJ PROJECTION
PROP PROPERTY
PSI POUNDS PER SQ IN
PT PAINT
PTD PAINTED
PTDD PAPER TOWEL DISPENSER /
DISPOSAL
PTN PARTITION
PVC POLYVINYL CHLORIDE
Q
QT QUARRY TILE
QZ QUARTZ MATERIAL
R
RA RETURN AIR
RAF RAISED ACCESS FLOORING
RB RUBBER BASE
RD ROAD, ROOF DRAIN
RECT RECTANGULAR
REF, RE REFER, REFERENCE
REINF REINFORCE, REINFORCED
REP REPRESENTATIVE
REQD REQUIRED
RFG ROOFING
RFL RUBBER FLOORING
RH ROBE HOOK
RH RELATIVE HUMIDITY
RM ROOM
RND ROUND
RS ROLLER SHADES
RST RUBBER STAIR TREADS
S
S SIGNAGE
SB SPLASH BLOCK
SBP SACRIFICIAL BARRIER PANEL
SC SEALED CONCRETE
SCHED SCHEDULE
SCN STAINED CONCRETE
SD SOAP DISPENSER
SECT SECTION
SEQ SEQUENCE
SHT SHEET
SIM SIMILAR
SJ STUCCO JOINT, SAWN JOINT
SMC SUSPENDED METAL CEILING
SND SANITARY NAPKIN DISPENSER
SPD SURGE PROTECTION DEVICE
SPECS CONTRACT SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STAIN
STD STANDARD
STL STEEL
STN NATURAL STONE
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SWC SUSPENDED WOOD CEILING
T
T TREAD
TAB TESTING ADJUSTING AND
BALANCING
TC TOWEL DISPENSER
TFMR TRANSFORMER
THK THICK
THRU THROUGH
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TP TOILET PARTITION
TS FLOORING TRANSITION
TT TILE TRIM
TTD TOILET TISSUE DISPENSER
TYP TYPICAL
TZ TERRAZZO
U
UGND UNDERGROUND
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
VAC VOLTS, ALTERNATING CURRENT
VB VINYL BASE, VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VF VINYL FLOORING
VP VENT PIPE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W/ WITH (COMB. FORM)
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WIDTH, WINDOW DIMENSION, WOOD
WDW WINDOW
WF WOOD FLOORING
WH WATER HEATER
WM WALK-OFF MAT
WP WATERPROOF
WR WASTE RECEPTACLE
WS WEATHERSTRIPPING
WT WINDOW TILE
ABBREVIATIONS
N
A-101
A-101
A-101
NEW GSA CLASS 5 DOOR,
NEW EPOXY FLOOR COATING
A-101
3' - 0" 12' - 4"
WEAPONS STORAGE LOCKER, GF-GI,
REPAIR ALL EXISTING FLOOR
PENETRATIONS PRIOR TO APPLYING
NEW FLOOR FINISH SYSTEM
20' - 10"
A-1018
S im
LOCATION
PHOTO
PANEL BOARD
CLEARANCE
1' - 8"
0' - 3"
REMOVE AND
REINSTALL
EXISTING BULLET
CATCH DEVICE.
REINSTALL IN
SAME LOCATION
AS PREVIOUS.
MECH ROOM
ELECT. ROOM
AA&E
NEW ACOUSTICAL
DROP CEILING, 24" X
24"
EXISTING CMU
WALL
NEW GSA CLASS 5
DOOR FRAME
SBP
HEAVY DUTY CORNER
TRIM, MATCH METAL
GAGE OF TRIM PIECE
6/A101
30# FELT, WRAP AT EDGE
OF ROUGH OPENING
0' - 3"
SBP
J-CHANNEL AT EDGE,
SECURE TO HAT
CHANNEL, (TYP. ALL
SIDES)
EXISTING ISSUE
WINDOW FRAME
EXISTING
CMU
7/8" HAT CHANNEL
IMPACT RESISTANT
GWB
30# FELT
V E
R
IF
Y
NOTE THIS VIEW:
1. REMOVE EXISTING ENTRY DOOR
2. PREPARE JAMB AT HINGE SIDE TO
RECEIVE NEW MOUNT.
3. SAW- CUT CMU WALL AT LATCH SIDE
TO MEET REQUIRED ROUGH OPENING
WIDTH FOR NEW GSA DOOR
A-1012
DROP CEILING
8' - 0"
4" COVE BASE
7/8" HAT CHANNEL, 24"
O.C., ADHERE TO SBP WITH
SELF DRILLING SCREWS,
12" O.C., STAGGERED
IMPACT
RESISTANT GWB
SUSPENDED CEILING
WALL ANGLE
CEILING TILE
SBP @ WALL, RE: 2/S-101 FOR
CONNECTION DETAILS
SBP @ CEILING, RE: 2/S-101
FOR CONNECTION DETAILS
1/2" GAP BETWEEN BOTTOM
OF WALL PANELS AND
EXISTING CONCRETE FLOOR
ADHERE 30# FELT TO
SURFACE OF CMU WALL,
RUN FROM FLOOR TO 6"
ABOVE SBP AT CEILING
SECURE UNISTRUT 24" O.C.
E.W. TO SBP AT CEILING
WITH SELF DRILLING 3/4"
SCREWS, 12" O.C.
UNISTRUT HANGAR
"T", SECURE
CEILING GRID SYSTEM
SURFACE MOUNTED
RECEPTACLE
HANGAR WIRE
SHELF ANGLE AT PERIMETER
(TYP.), RE: S-1O1
METAL INSIDE X CORNER
MOULDING
IMPACT RESISTANT GWB
7/8" HAT CHANNEL , RUN
HORIZONTAL, 24" O.C.
S B
P
SBP
ADHERE 30# FELT TO
EXISTING CMU WALL, (TYP.)
1. REMOVE EXISTING VCT FLOORING AND WALL BASE FROM PROJECT AREA, PREPARE EXISTING CONCRETE FLOOR TO RECEIVE
NEW EPOXY COATING.
2. REMOVE EXISTING DROP CEILING, INCLUDING ALL EXISTING HANGARS, TRACK AND EDGE TRACK FASTENERS. REFERE TO
MECHANICAL AND ELECTRICAL SHOTS FOR CEILING MOUNTED FIXTURES AND EQUIPMENT
3. USER TO RELOCATE ALL FURNITURE AND EQUIPMENT PRIOR TO CONTRACTOR WORK BEGINS.
DECONSTRUCTION NOTES; REFERENCE
KEY PLAN FOR PROJECT AREA:
EXISTING INTERIOR PARTITION
SCH. 10 STEEL SLEEVE, SIZED
1.5X'S THE DIA. OF THE PASS-THRU
PIPE. ENDS OF SLEEVE SHALL BE
FLUSH W/ EACH SURFACE OF THE
WALL.
PACK W/ MIN. 4 PCF MINERAL
WOOL BATT INSULATION. RECESS
FROM BOTH SIDES TO
ACCOMMODATE FILL MATERIAL.
ESCUTCHEON PLACE IN SEALANT
FLUSH AGAINST WALL
MIN. 1-1/4" UL LISTED SEALANT,
FLUSH WITH BOTH SIDES OF
WALL
PASS-THROUGH PIPE, RE:
INDIVIDUAL SHEETS FOR SIZE
CALL-OUT
SBP
ESCUTCHEON, SEAL
AROUND OUTER
EDGE AND PAINT
5'8" GWB, RE: TO
DETERMINE REQUIREMENT
BY PENETRATION HEIGHT
AT GWB PENETRATIONS
CENTER A 1'-0" LENGTH OF
HAT CHANNEL ABOVE AND
BELOW PENETRATION
/5 A-101
HVAC SUPPLY
REGISTER
LED RECESSED 24" x 24" LIGHT
CEILING MOUNT HORN STROBE
HVAC RETURN
REGISTER
HEAT DETECTOR
WALL RECEPTACLE, RE: E-101
PANEL BOARD, RE: E-101
REPLACE EXISTING FASTENERS
ALONG EXTERIOR OF WEAPONS
PASS-THROUGH WITH NON-
REVERSING TAMPER RESISTANT
FASTENERS, (TYP.)
NOTE THIS VIEW:
1. REMOVE ALL EXISTING PAINT FROM
PASS-THROUGH WELDED WIRE
MESH
2. REPAINT WELDED WIRE MESH AND
FRAME TO MATCH COLOR OF NEW
DOOR.
REMOVE EXISTING
DOOR AND FRAME
SAWCUT AND REMOVE CMU
AS NEEDED FOR
INSTALLATION OF NEW
DOOR. CONFIRM CLEAR
OPENING REQUIREMENTS
WITH MANUFACTURER
PRIOR TO CUTTING AND
REMOVAL OF CMU.
DOOR INSTALLATION NOTES
1. DELIVERY OF THE CLASS 5 DOOR MUST BE COORDINATED WITH CONSTRUCTION MANAGER.
2. MANUFACTURERS REP MUST BE ON-SITE FOR INSTALLATION.
3. CONTRACTOR TO PROTECT EXISTING CONSTRUCTION AND FINISHES. DAMAGES RESULTING
FROM THIS WORK MUST BE REPAIRED TO THE SATISFACTION OF THE AFFS CONSTRUCTION
MANAGER AT NO COST TO THE GOVERNMENT..
4. ANY DISASSEMBLY OF STRUCTURE BY THE CONTRACTOR TO AID DOOR DELIVERY OR
INSTALLATION WILL BE RETURNED TO EXISTING CONDITION OR REPLACED WITH NEW
MATERIALS OF THE SAME DIMENSION, QUALITY, AND COLOR AT NO ADDITIONAL COST TO
THE GOVERNMENT.
ARCHITECTURAL GENERAL NOTES
1. THE CONTRACTOR TO IMMEDIATELY NOTIFY THE CONSTRUCTION MANAGER OF ANY
DISCREPANCIES BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, AND/OR BETWEEN
THE CONSTRUCTION DOCUMENTS AND ACTUAL JOB CONDITIONS WHICH WILL AFFECT THE
EXECUTION OF THE WORK AS INDICATED.
2. ALL ROMS ADJACENT TO CONSRTUCTION AREA MUST REMAIN ACCESSIBLE BY FACILITY
EMPLOYEES. DO NOT BLOCK DOORWAYS.
3.
4. CONTRACTOR TO VERIFY AND ALL DIMENSIONS DURING THE CONSTRUCTION LAYOUT OF
THE WORK. THE FOLLOWING GUIDANCE APPLIES TO DIMENSIONS USED ON THE
ARCHITECTURAL DRAWINGS:
A. THE CONTRACTOR WILL USE DIMENSIONS INDICATED ON THE DRAWINGS.
B. DO NOT SCALE FROM THE DRAWINGS.
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
A-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
FL
O
O R
P
LA
N , D
E
TA
IL
S
, A N
D D
E C
O N
S
TR
U C
TI
O
N N
O
TE
S
B. DECOCQ
09/15/2023
XTLF15-1018
J MORGAN
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
3/8" = 1'-0"3
COMPOSITE FLOOR PLAN AA&E 128
2'1' 4'0
SCALE: 1/2" = 1'-0" KEY PLAN3/8" = 1'-0"4
REFLECTED CEILING PLAN AA&E 128
3" = 1'-0"9
GSA DOOR JAMB/HEADER DETAIL
3" = 1'-0"7
WALL DETAIL @ ISSUE WINDOW
1/2" = 1'-0"1
DECONSTRUCTION @ DOOR
1 1/2" = 1'-0"5
WALL DETAIL (TYP.)
3" = 1'-0"6
INSIDE CORNER DETAIL
1'0 6"3"
SCALE: 3" = 1'-0"
2'0 1'6"
SCALE: 1 1/2" = 1'-0"
3" = 1'-0"10
INTERIOR WALL PENETRATION
N
PLAN LEGEND
NTS8
ISSUE WINDOW RENOVATION
DECONSTRUCTION
1/2" = 1'-0"2
ELEVATION AT DOOR
N
N
0 2' 4' 8'
SCALE: 3/8" = 1'-0"
S-101
SCHEMATIC DIAGRAM TO SHOW
PANEL ORIENTATION TO TRUSS
AND FASTENER LAYOUT.
CONTRACTOR TO VERIFY JOIST
LOCATIONS AND DETERMINE
ACTUAL PANEL EDGE LOCATIONS.
EXISTING TRUSS, TYP.
4' X 8' SBP PANEL, TYP.
LONG EDGE PERPENDICULAR TO
TRUSS CORD.
STAGGER PANEL EDGES
6 x 3-1/2 x 3/8" PERIMETER
SHELF ANGLE, CONTINUOUS,
MITER AT CORNERS.
3/8" X 2" CARRIAGE BOLT, TAMPER
RESISTANT HEAD, 24" O.C., SECURE SBP
TO TOP OF SHELF ANGLE, NUT SIDE
DOWN.
SBP AT CEILING
SQUARE U-BOLT, STRADDLE
BOTTOM CHORD OF TRUSS.
SECURE PANEL THROUGH
CHANNEL WITH A STEEL LOCK
WASHER AND NUT.
EXISTING TRUSS
EXISTING CMU WALL
2'1' 4'0
SCALE: 3/4" = 1'-0"
1'0 6"3"
SCALE: 3" = 1'-0"N
2" TYP2"
TYP, MAY SHIFT BOLT UP TO 6" FROM
PANEL EDGE AS REQUIRED TO CLEAR
JOIST WEB INTERFERENCE. 3/8" X 4" CARBON STEEL
LARGE DIAMETER CONCRETE
ANCHORS, 24" O.C.
3/16"X 2-3/4" CONCRETE HEX
HEAD SCREW ANCHORS 24"
O.C. EACH WAY ALONG PANEL
EDGES AND FIELD.
0' - 6" MAXIMUM
S-101
NN
STRUCTURAL NOTES FOR CEILING PANELS:
1. ALL PANELS SHALL RUN THE LONG EDGE
PERPENDICULAR TO DIRECTION OF TRUSS.
2. PANEL SHORT EDGE SHALL ALIGN WITH CENTER
LINE OF BOTTOM CHORD OF TRUSS.
3. PANEL PERIMETER EDGE SHALL BE SECURED TO
SHELF ANGLE. MAINTAIN A 1/4" GAP BETWEEN
EDGE AND WALL FACE.
MECH ROOM
ELECT. ROOM
AA&E
3/8"-16 THREAD SIZE, 4"
INSIDE WIDTH, 3" HEIGHT
SQUARE U-BOLT, 22" O.C.
ALONG JOIST.
EXISTING TRUSS
SBP AT CEILING
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
S-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
S
TR
U C
TU
R
A L
R C
P , S
T R
U C
TU
R
A L
W A
LL
S
E C
TI
O
N S
, A N
D S
TR
U
C
TU
R A
L N
O
TE
S
B. DECOCQ
09/15/2023
XTLF15-1018
C. TAYLOR
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
3/4" = 1'-0"1
AA&E 128 CEILING PANEL PLAN- STRUCTURAL
3" = 1'-0"2
SBP WALL AND CEILING CONNECTIONS IN AA&E 128
3" = 1'-0"3
SECTION AT TRUSS, (TYP.)
H F
J
STO
OFFICE
OFFICE
MECH ROOM
RECEPTION
OFFICE
120A
DETENTION
AA&E
CORRIDOR
DUTY DESK
LOBBY
AA&E
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
FA-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
F
IR
E A
L A
R M
P
L A
N
MICHAEL
JORDAN
08/29/2023
XTLF15-1018
CODY HANEY
DATE: 08/29/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
FIRE ALARM NOTES
EXISTING FIRE ALARM JUNCTION BOX MUST REMAIN.
EXISTING HORN STROBE AND SMOKE DETECTOR MUST BE REMOVED, STORED AND
REINSTALLED.
PULL WIRING BACK TO JUNCTION BOX AND RECONNECT DEVICES IN HALLWAY DURING
CONSTRUCTION.
DURING CONSTRUCTION, INSTALL A MC CABLE THROUGH 3/4" CONDUIT WALL
PENETRATION IN A ROOM AFTER WALLS HAVE BEEN REINFORCED.
1/8" = 1'-0"1
FIRE ALARM AA&E 128
NTS2
FIRE ALARM
JUNCTION BOX
REMOVE AND STORE HORN PROBE
REMOVE AND STORE HEAT SENSOR
FIRE ALARM
PENETRATION
GENERAL NOTES
1. CONTRACTOR MUST VERIFY LOCATION AND DISTANCE OF EQUIPMENT AND
WIRING ON THIS SHEET IN THE FIELD.
2. REFER TO SHEET A-101 FOR DETAILS ON WALL PENETRATION.
3. CONTRACTOR MUST VERIFY IN FIELD EQUIPMENT LOCATION AND WIRING TO JUNCTION
BOX.
4. REINSTALL IN SAME GENERAL LOCATION AS PRIOR TO CONSTRUCTION START.
COORDINATE FIRE ALARM EQUIPMENT LOCATIONS WITH LED LIGHTING AND HVAC
REGISTERS.
5. FIRE ALARM CONTROL PANEL IS LOCATED IN THE GENERATOR ROOM.
KEY PLAN
N
8'4' 16'0
SCALE: 1/8"=1'-0"
STO
INTERR.
OFFICE
OFFICE
MECH ROOM
RECEPTION
ROUTE CONDENSATE LINE
UNDER RETURN PLENUM
TO FLOOR DRAIN.
ROUND TAP INTO BOTTOM OF
ZONE 5 SUPPLY DUCT.
DH
DC
INSTALL DEHUMIDIFIER
CONTROLLER. WIRE TO THE
DEHUMIDIFIER IN THE MECHANICAL
ROOM. RE: SHEET A-101 FOR WALL
PENETRATION DETAIL.
INCLUDE THE MIN.
REQUIRED LENGTH OF
FLEX DUCT AT
DEHUMIDIFIER INLET
AND OUTLET FOR
VIBRATION ISOLATION.
AIR
HANDLING
UNIT
RETURN
TRUNK
ZONE 5 SUPPLY DUCT
ROUND TAP INTO RETURN PLENUM
M-101
10"ø 10"ø
M-101
T
CAP EXISTING
DUCT
COORDINATE WITH
ARCHITECTURAL TO
ALIGN CEILING GRID IN
ORDER TO CENTER
SUPPLY DIFFUSER
UNDER EXISTING DUCT.
16"x7"
30"x8"
16"x8"
12" ROUND TAP INTO
EXISTING DUCT. 12"
FLEXIBLE DUCT TO
REGISTER.
EXISTING
THERMOSTAT
TO REMAIN.
THIS DUCT SERVES OTHER PARTS
OF THE BUILDING. DISASSEMBLE
AND REINSTALL BACK TO EXISTING
CONDITION. COORDINATE
DOWNTIME OF OTHER AREAS WITH
CONSTRUCTION MANAGER.
SD-1
400 CFM
RG-1
100 CFM
100 CFM1
USE EXISTING
DAMPERS FOR
TAB.
CAP
EXISTING
DUCT AA&E
DH
FLEX.
DUCT
ROUTE
CONDENSATE
LINE UNDER
RETURN
PLENUM TO
FLOOR DRAIN.
AIR
HANDLING
UNIT
ZONE 5 SUPPLY DUCT
RETURN
PLENUM
10"ø
10"ø
RETURN
PLENUM
AIR
HANDLING
UNIT
ZONE 5
SUPPLY
DUCT
EXISTING
FLOOR
DRAIN
LINETYPE LEGEND
NEW DUCT
DEMO DUCT
EXISTING DUCT
CONDENSATE LINE
MECH ROOM
ELECT. ROOM
AA&E
ELECTRICAL
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
M-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
M E
C H
A N
IC
A
L P
L A
N
EDGAR
ESTRADA
09/15/2023
XTLF15-1018
CHARLES
SNYDER
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
1/4" = 1'-0"1
MECHANICAL FLOOR PLAN
SHEET NOTES
1. CONFIGURE THE CONTROLS TO LIMIT THE RELATIVE HUMIDITY TO NO GREATER THAN 40%.
2. ALWAYS MAINTAIN A CONSTANT DOWNWARD SLOPE FROM THE DEHUMIDIFIER
CONDENSATE DRAIN TO FLOOR DRAIN AND DO NOT ALLOW SOFT TUBING TO CURL UP
WHICH MAY RESULT IN AIR LOCK.
3. PROVIDE EXTERIOR INSULATION ON ALL NEW DUCTWORK IN THE MECHANICAL ROOM AND
NEW SUPPLY DUCTWORK ABOVE THE OCCUPIED SPACE.
4. IN THE AREA OF WORK, DISASSEMBLE AND REINSTALL DUCTWORK SHOWN AS
"EXISTING". IN THE EVENT OF DAMAGE DURING DISASSEMBLY OR REINSTALLATION,
REPLACE DAMAGED COMPONENTS WITH LIKE KIND AND QUALITY. PROVIDE THE PORTIONS
OF DUCTWORK SHOWN AS "NEW".
5. DUCTS MUST BE INSTALLED IN ACCORDANCE WITH "SMACNA - HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE, 4TH EDITION".
6. PROVIDE CONDENSATE DRAIN PIPING IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS.
1/4" = 1'-0"2
SOUTH ELEVATION AT AHU
1/4" = 1'-0"3
EAST ELEVATION AT AHU
DH
KEY NOTES
THIS AIR SUPPLY SUBJECT TO TAB (TESTING, ADJUSTING, AND BALANCING).
PROVIDE FLOOR-ANCHORED PLATFORM FOR DEHUMIDIFIER. PLATFORM MUST HAVE A
MINIMUM HEIGHT OF 4 INCHES FOR CONDENSATE DRAINAGE. CAP THE DEHUMIDIFIER'S
OUTSIDE AIR INTAKE AS IT IS NOT USED IN THIS APPLICATION.
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
KEY PLAN
N
M
F
J
H
D
J
H
F
M G
F C
I
STO
OFFICE
OFFICE
MECH ROOM
ELECT. ROOM
OFFICE
RECEPTION
GUARD MOUNT
AA&E
CORRIDOR
ADV
MDP
PANEL PPB
ADV
WALL PENETRATION
MOTION SENSOR
CAMERAS
QUADPLEX RECEPTACLE
DUPLEX RECEPTACLE
EMERGENCY LIGHT
DEMOLISHED 2' x 4'
FLUORESCENT LIGHT
NEW 2' x 2' LED LIGHT
SINGLE POLE LIGHT SWITCH
DIMMER LIGHT SWITCH
ELECTRICAL PANEL
ADVANTOR CAMERA
SYSTEM BOX
EXISTING TELEPHONE
JUNCTION BOX
DUPLEX RECEPTACLE,
GFCI
HEAT DETECTOR
FIRE ALARM - HORN STROBE
CEILING MOUNT
WIRING CONCEALED IN CEILING
OR WALLS. ALL WIRES ARE #12
AWG MINIMUM
EXPOSED RACEWAY
MECH ROOM
ELECT. ROOM
AA&E
ELECTRICAL
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
ED-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
E L
E C
T R
IC
A
L D
E C
O N
S T
R U
C T
IO
N
P L
A N
S A
N D
D E
T A
IL
S
MICHAEL
JORDAN
09/15/2023
XTLF15-1018
RYAN
SUDLOW
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
DETAIL ELECTRICAL NOTES FOR DEMOLITION
DECONSTRUCT EXISTING ELECTRICAL PANEL PPB IN AA&E ROOM AS SHOWN IN PICTURE 2.
DECONSTRUCT EXISTING FLUORESCENT LIGHTING IN AA&E ROOM AS SHOWN IN PICTURE 3.
EXISTING LOCATION OF ADVANTOR SYSTEM FOR REFERENCE ONLY.
COORDINATE WITH AFFS CONSTRUCTION MANAGER ON THE REMOVAL AND STORAGE OF
THE CAMERAS WITHIN AA&E ROOM AS SHOWN IN PICTURE 4.
DECONSTRUCT EXISTING RECEPTACLES AND LIGHT SWITCHES IN AA&E ROOM.
DECONSTRUCT EXISTING EMERGENCY LIGHT IN AA&E ROOM AS SHOWN IN PICTURE 5.
TELEPHONE MUST BE REMOVED AND STORED.
DECONSTRUCT EXISTING "OUTSIDE HALL LIGHTS" SWITCH. NEW LIGHT SWITCH MUST BE
RECONNECTED TO "OUTSIDE HALL LIGHTS" AND ROUTED THROUGH PENETRATION DETAIL,
REFERENCE A-101 SHEET.
NTS2
DECONSTRUCT EXISTING PANEL PPB
NTS3
DECONSTRUCT CEILING LIGHTS
NTS4
REMOVE AND STORE ADVANTOR SYSTEM
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
EXISTING ADVANTOR LOCATION, FOR
REFERENCE ONLY.
GENERAL NOTES
1. CONTRACTOR MUST VERIFY LOCATION AND DISTANCE OF EQUIPMENT AND
WIRING ON THIS SHEET IN THE FIELD.
DECONSTRUCT LIGHTING
DECONSTRUCT LIGHTING
DECONSTRUCT LIGHTING
DECONSTRUCT EXISTING PANEL PPB
NTS5
DECONSTRUCT EMERGENCY LIGHT
NTS6
DECONSTRUCT LIGHTING SWITCHES
DECONSTRUCT BOTH
LIGHTING SWITCHES
1/4" = 1'-0"1
ELECTRICAL DECONSTRUCTION AA&E 128
DECONSTRUCT EMERGENCY LIGHT
DECONSTRUCT RECEPTACLE
ELECTRICAL SYMBOLS:
N
KEY PLAN
COORDINATE THE REMOVAL AND
STORAGE OF CAMERA SYSTEM WITH AFFS
CONSTRUCTION MANAGER
GFCI
DD
M
M
18"
18"
18"
PANEL PPB - 2
RADIO SHELF 2
RADIO SHELF 1
RADIO SHELF 3
RADIO SHELF 4
DUPLEX
DUPLEX
DUPLEX
STO
OFFICE
OFFICE
MECH ROOM
ELECT. ROOM
OFFICE
OFFICE
RECEPTION
OFFICE
120A
GUARD MOUNT
AA&E
CORRIDOR
DUTY DESK
LOBBY
ADV
CONNECT TO
BASE STATION RADIO
TO RADIO
TELEPHONE LINE
PENETRATION
COMMUNICATION
PENETRATION
TO
COMMUNICATION
FIRE ALARM
PENETRATION
ADVANTOR SYSTEM
TO CAMERA
SYSTEM
4 x 1 1/4" 4 x 3/4"
MULTIPLE PENETRATIONS
FOR MULTIPLE SYSTEMS
STO
OFFICE
OFFICE
MECH ROOM
ELECT. ROOM
OFFICE
OFFICE
RECEPTION
OFFICE
120A
GUARD MOUNT
AA&E
CORRIDOR
DUTY DESK
LOBBY
TO OUTSIDE
HALL LIGHTING
MECH ROOM
ELECT. ROOM
AA&E
ELECTRICAL
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
E-101
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
E
LE
C
TR
IC
A
L P
O W
E R
A N
D L
IG
H
T
IN
G P
LA
N
S
MICHAEL
JORDAN
09/15/2023
XTLF15-1018
RYAN
SUDLOW
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
ELECTRICAL NOTES
PROVIDE AND INSTALL NEW SURFACE MOUNTED PANEL PPB FOR
SUPPORTING AA&E ROOM (ROOM 128) EQUIPMENT ONLY.
ADDITIONALLY, PROVIDE AND INSTALL NEW SURFACE MOUNTED PANEL
PPD FOR SUPPORTING REMAINING CIRCUITS OUTSIDE OF AA&E ROOM.
CIRCUITS OUTSIDE AA&E ROOM MUST BE MOVED TO NEW PANEL PPD
LOCATED (ROOM 144). PICTURE 3 SHOWS LOCATION OF SURFACE
MOUNTED NEW PANEL PPD.
PROVIDE AND INSTALL NEW SURFACE MOUNTED QUADPLEX
RECEPTACLES IN AA&E ROOM (ROOM 128). COORDINATE LOCATIONS
OF QUADPLEX WITH SECURITY FORCES.
PROVIDE 4 x WALL PENETRATION FOR CONDUIT THAT IS 1 1/4". FOR
WALL PENETRATION DETAILS REFER TO A-101.
PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE FOR
DEHUMIDIFIER IN MECHANICAL ROOM (ROOM 107). COORDINATE
LOCATION WITH CONSTRUCTION MANAGER TO ENSURE OUTLET IS
WITHIN REACH TO POWER DEHUMIDIFIER. REFER TO PICTURE 4 FOR
LOCATION.
PROVIDE AND INSTALL NEW CIRCUIT BREAKERS IN MDP FOR NEW
PANEL PPD (ROOM 144), FOR MECHANICAL ROOM'S DEHUMIDIFIER
(ROOM 107) AND MAIN CIRCUIT BREAKER.
PROVIDE AND INSTALL NEW EMERGENCY LIGHT SURFACE MOUNTED IN
AA&E ROOM (ROOM 128) AND DUPLEX RECEPTACLE TO POWER
EMERGENCY LIGHT.
RECEPTACLES NEXT TO RADIOS, MUST HAVE THREE (3) DUPLEX
OUTLETS SURFACE MOUNTED PROVIDED, INSTALLED AND ALIGNED
VERTICALLY WITH EACH RADIO SHELF. REFER TO PICTURE 5.
UTILIZE EXISTING WALL PENETRATION TO POWER NEW PANEL PPB.
REFER TO SHEET A-101 DETAILS ON WALL PENETRATION. CONDUIT IS
FOR 3 AWG ELECTRICAL LINES IN 2" CONDUIT.
ENSURE WALL PENETRATION IS PROVIDED FOR RADIOS. REFER TO
SHEET A-101 DETAILS ON WALL PENETRATION. CONDUIT IS FOR 1 1/4"
CONDUIT.
PROVIDE 4 x WALL PENETRATION AND REINSTALL TELEPHONE AND
ROUTE TELEPHONE LINE THROUGH ONE WALL PENETRATION. CONDUIT
SIZE IS 3/4". FOR WALL PENETRATION DETAILS REFER TO SHEET A-101.
PROVIDE WALL PENETRATION FOR CAMERA SYSTEM. REFER TO SHEET
A-101 DETAILS ON WALL PENETRATION. CONDUIT IS FOR 1 1/4"
CONDUIT. COORDINATE WITH AFFS CONSTRUCTION MANAGER ON THE
INSTALLATION OF THE CAMERA SYSTEM.
PROVIDE WALL PENETRATION FOR COMMUNICATION LINES. BASE
COMMUNICATION TO RECONNECT COMMUNICATION LINES.
CONTRACTOR TO PROVIDE CONDUIT AND SURFACE MOUNTED BOX
FOR COMMUNICATION LINE. REFER TO SHEET A-101 DETAILS ON WALL
PENETRATION. CONDUIT IS FOR 3/4" CONDUIT.
REFER TO FA-101 FOR FIRE ALARM PENETRATION.
NTS4
INSTALLATION RECEPTACLE IN MECH. ROOM
NTS5
DUPLEX RECEPTACLES FOR RADIOS
10'6'0 2'
SCALE 3/16" = 1'-0"
N
NEW PPD PANEL
NEW
GFCI
PPB - 9
PPB - 7
3/16" = 1'-0"1
ELECTRICAL CONSTRUCTION AA&E 128
PPB PANEL
MDP
PANEL PPB
MDP
ELECTRICAL LIGHTING NOTES
PROVIDE AND INSTALL NEW RECESSED MOUNTED 2' x 2' LED PANELS
IN AA&E ROOM (ROOM 128). INSTALL NEW SURFACE MOUNTED DIMMER
SWITCH AND LIGHT SWITCH FOR OUTSIDE LIGHTS.
PROVIDE AND INSTALL SURFACE MOUNTED DIMMER LIGHT SWITCH FOR
AA&E ROOM (ROOM 128).
PROVIDE AND INSTALL OUTSIDE HALL LIGHTS SWITCH, ROUTE WIRING
THROUGH WALL PENETRATION. WALL PENETRATION DETAILS CAN BE
FOUND ON SHEET A-101.
PROVIDE AND INSTALL WALL MOUNTED DUPLEX TO SUPPORT LED EMERGENCY
LIGHT.
PROVIDE AND INSTALL LED EMERGENCY LIGHT AND CONNECT TO NEW
DUPLEX.
PPB - 1
PPB - 3 PPB - 5
PPB - 8
MDP - 3
MDP - 18
MDP - 24
PANEL PPD
PANEL PPD
A
B
C
D
A
A
A A
A
A A
A
A
B
C
E
3/16" = 1'-0"2
ELECTRICAL LIGHTING AA&E 128
PPB - 2
POWER EXISTING
PENETRATION
GENERAL NOTES
1. CONTRACTOR MUST VERIFY LOCATION, DISTANCE OF EQUIPMENT AND
WIRING ON THIS SHEET IN THE FIELD.
2. ALL CONDUITS THAT PENETRATE THE WALL MUST BE RIGID.
3. STEEL PLATES FROM A-101 MUST BE BONDED AND GROUNDED.
8 9 10
TO CAMERAS
COMMUNICATION
LINES
E
D
NTS3
ROOM 144 PANEL LOCATION
MDP DEMOLISHED
PANEL PPB
NOTE: THIS RISER DOES NOT REPRESENT THE FULL RISER DIAGRAM. Refer to AS-BUILT FOR A FULL RISER DIAGRAM.
RATED 800 AMPS
208Y/120
3 PH / 4 WIRE
TRANSFORMER
EXISTING
225 kVA
208Y/120
3.34% IZ
EXISTING
METER
EXISTING18,000
NOTE: DEMOLISH WIRE BACK TO MDP, DEMOLISH CONDUIT ONLY IN AA&E ROOM.
MDP NEW PANEL PPB NEW PANEL PPD
208Y/120
100 AMPS
3 PH/4 WIRE
100 AMP MCB
30 CIRCUIT
208Y/120
800 AMPS
3 PH/4 WIRE
TRANSFORMER
EXISTING
225 kVA
208Y/120
3.34% IZ
18,000
1 AWG, 100 AMPS
METER
10,000 10,000
NOTE: THIS RISER DOES NOT REPRESENT THE FULL RISER DIAGRAM. Refer to AS-BUILT FOR A FULL RISER DIAGRAM.
1 AWG, 100 AMPS
208Y/120
100 AMPS
3 PH/4 WIRE
100 AMP MCB
30 CIRCUIT
SPD SPD
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
E-601
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
E L
E C
T R
IC
A
L P
L A
N S
R
IS
E
R A
N D
S C
H E
D U
L E
MICHAEL
JORDAN
09/15/2023
XTLF15-1018
RYAN
SUDLOW
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
NTS3
FEEDER SCHEDULE
NTS1
PARTIAL RISER DEMOLITION DIAGRAM
NTS2
PARTIAL RISER CONSTRUCTION DIAGRAM
FEEDER SCHEDULE NOTES
1. CONDUIT SIZED BASED ON CONDUCTOR PROPERTIES LISTED IN THE CURRENT NEC EDITION, CHAPTER 9, TABLES 5 AND 5A. CONDUIT AREAS LISTED CHAPTER 9, TABLE 4 FOR EMT WITH 40% FILL. OTHER CONDITIONS MAY REQUIRE
A LARGER CONDUIT, SUCH AS UNDERGROUND PVC, SIZED FOR NEC.
2. GROUND SIZES: EQUIPMENT GROUNDING CONDUCTOR BASED ON NEC TABLE 250.122 - COPPER / GROUNDING
ELECTRODE CONDUCTOR BASED ON NEC TABLE 250.66 - COPPER.
3. CONDUCTOR SIZES BASED ON NEC TABLE 310.15 - COPPER 75°C
ARC FLASH NOTES
1. ALL SWITCHBOARDS AND PANELBOARDS SHALL HAVE A LABEL APPLIED TO WARN OF POTENTIAL ARC FLASH HAZARDS.
2. LABEL SHALL BE USED AS SHOWN:
FAULT CURRENT NOTES
1. SYMBOL BELOW REPRESENTS THE AVAILABLE FAULT CURRENT IN RMS SYMMETRICAL AMPS AT THE RESPECTIVE
TRANSFORMER, PANEL, OR EQUIPMENT.
2. FAULT CURRENT CALCULATIONS ARE BASED ON AVAILABLE FAULT CURRENT OF 22,853 AMPS AT THE TRANSFORMER'S
SECONDARY SIDE.
XX,XXX
DRAWING SIZE INTENDED TO BE
24" x 36"
1 1/2"(ACTUAL SIZE)
UNITED STATES AIR FORCE
AIR EDUCATION
TRAINING COMMAND
VANCE AIR FORCE BASE
ENID, OKLAHOMA
140 Channel St., Suite 205 Vance AFB, OK 73705
(580) 213−7772
CA# 8716
30 JUNE 2024
DRAWN BY:
DATE:
PROJECT NO.:
CHECKED BY:
DESIGN STAGE:
E-602
−1
R E
P A
IR
S
F S
A A
E
S T
O R
A G
E , B
E L
E C
T R
IC
A
L P
L A
N S
R
IS
E
R A
N D
S C
H E
D U
L E
MICHAEL
JORDAN
09/15/2023
XTLF15-1018
RYAN
SUDLOW
DATE: 09/15/2023
100%
15-1018 REPAIR SFS AA&E STORAGE, B527
R e v is io n
N u m b e r
D e s c ri p ti o n
D a te
NTS2
NEW PPB PANEL SCHEDULE
NTS3
NEW PPD PANEL SCHEDULE
NTS1
MDP PANEL SCHEDULE
| AA&E_CentModel_detached_BDecocqCVNN4 |
| G-001 - COVER |
| G-002 - HAUL ROUTE, ABBREVIATIONS, AND COMMON SYMBOLOGY |
| A-101 - FLOOR PLAN, DETAILS, AND DECONSTRUCTION NOTES |
| S-101 - STRUCTURAL RCP, STRUCTURAL WALL SECTIONS, AND STRUCTURAL NOTES |
| FA-101 - FIRE ALARM - PLAN |
| M-101 - MECHANICAL PLAN |
| ED-101 - ELECTRICAL DECONSTRUCTION PLANS AND DETAILS |
| E-101 - ELECTRICAL POWER AND LIGHTING PLANS |
| E-601 - ELECTRICAL PLANS - RISER AND SCHEDULE |
| E-602 - ELECTRICAL PLANS - RISER AND SCHEDULE |
File details come from the government source that posted it. Updated .