ATTACHMENT 2 - DESIGN NARRATIVE 691GE-20-202 Amb-EHRM.pdf

PDF 622 KB Posted

Attached to
Z1DA--ERHM Infrastructure Upgrades, LAACC Federal contract opportunity
Solicitation number
36C26221B0006_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This federal contract opportunity is for Electronic Health Record Modernization (EHRM) Infrastructure Upgrades at the VA Los Angeles Ambulatory Care Center located in Los Angeles, California. Work includes general construction, alterations, mechanical, electrical work, and utility systems necessary to improve facility infrastructure supporting the VA's New EHRM deployment. The requirement is between $2-5 million and will be procured as a 100% Service-Disabled Veteran-Owned Small Business set-aside. The North American Industry Classification Code is 236220 for Commercial and Institutional Building Construction with a size standard of $39.5 million. A site visit will be scheduled after release of the Invitation for Bid on or around May 21, 2021 via beta.sam.gov. The point of contact for the project is Maria Cruz-Thompson, Contracting Specialist at the Network Contracting Office 22 Long Beach, who can be reached at maria.cruz-thompson@va.gov.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project # 691GE‐20‐202

A/E Services for

“Electronic Health Record Moderrnization (EHRM)

Infrastructure Upgrades”

Los Angeles Ambulatory Care Clinic

VA Contract No: VA262‐16‐D‐0158

Final Submittal

March 11, 2021

Submitted To:

Mr. Michael C. Nostitz VAGLA Project Engineering Section

Project Manager, COR II, FEC I Department of Veterans Affairs

11301 Wilshire Blvd Building 218, R325A

Los Angeles, CA 90073

Submitting Prime Contractor:

KAL Architects, Inc.

12‐J Mauchly Irvine, CA 92618

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

VA LOS ANGELES AMBULATORY CARE

CENTER

VA LOS ANGELES CALIFORNIA

03/11/2021

DESIGN NARRATIVE

Final Submittal

Date: March 11, 2021

VA Contract: VA 262‐16‐D‐0158

VA Project no.: 691GE‐20‐202

KAL Project no.: 16DVA218.12

EHRM Infrastructure Upgrades Design Narrative

ELECTRONIC HEALTH RECORD

MODERNIZATION INFRASTRUCTURE (EHRM)

UPGRADES

VA LOS ANGELES AMBULATORY CARE CENTER

LOS ANGELES CALIFORNIA

DESIGN NARRATIVE

OUTLINE

1. Code Criteria Search

2. General

3. Architecture

4. Structural

5. Mechanical

6. Plumbing

7. Electrical

8. Fire Protection

9. Environmental

10. Phasing

EXHIBITS

1. PSDM Requirements

2. Cabling

3. VA ALERTS

APPENDICES

A. Cut Sheets

i. Equipment

ii. Electrical

iii. Fire Rated Assembly

iv. Anchor Bolts

B. Photo Sheets C. Calculations

ACKNOWLEDGEMENTS

VA Project Team

EHRM Infrastructure Upgrades Design Narrative

1. CODE CRITERIA SEARCH

The most current editions of the following reference publications, as published, adopted, or amended by VA, were reviewed to conduct the feasibility analysis of this this Project:

PG‐18‐1 VA Master Construction Specifications Index

PG‐18‐3 VA Design and Construction Procedures

PG‐18‐4 VA National CAD Standard Details

PG‐18‐6 VA Equipment Reference Manual

H‐18‐8 VA Handbook, Seismic Design Requirements

PG‐18‐10 VA Design Manuals (by discipline)

PG‐18‐12 VA Design Guides

VA Office of Information and Technology (OIT)

- Infrastructure Standards for Telecommunications Spaces

VA Office of the Electronic Health Record Modernization

PG‐18‐13 VA Barrier Free Design Guide

PG‐18‐15 VA A/E Submission Instructions and Requirements

PG‐18‐17 VA Environmental Compliance Manual

VA Design Alerts

VA Standards Alerts

VA Fire Protection Design Manual

VA Signage Design Guide

VA Physical Security Design Manual for VA Facilities

ASHRAE 62.1 Ventilation for Acceptable Indoor Air Quality

ASHRAE 90.1 Energy Standard for Buildings except Low‐Rise Residential Buildings

ASHRAE 140 Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs

NFPA 13 Standard for the Installation of Sprinkler Systems

NFPA 70 National Electrical Code (NEC)

NFPA 72 National Fire Alarm and Signaling Code

NFPA 99 Standard for Health Care Facilities

EHRM Infrastructure Upgrades Design Narrative

NFPA 101 Life Safety Code

IBC International Building Code

IMC International Mechanical Code

IPC International Plumbing Code

ANSI/IEEE C2 National Electrical Safety Code

ASCE/SEI 7 Minimum Design Loads for Buildings and other Structures

ABAAS Architectural Barriers Act Accessibility Standards

Accessibility for facilities designed, constructed, altered, or leased with federal funds shall fully comply with the ABAAS. VA may, at its discretion, require more stringent state and local codes such as

California Title 24 (CBC Chapter 11B) to be applied in a given situation and any variances to the above codes and standards shall be incorporated.

2. GENERAL

2.1 Description

This project is part of VA’s nationwide initiative to improve the facility infrastructure that supports the deployment of the Department of Veterans Affairs’ New Electronic Health Record

Modernization (EHRM) For the Los Angeles ACC Medical Facility at 351 East Temple Street, Los

Angeles, CA 90012. This project will provide a complete design of all communication cabling and

IT equipment to meet Cerner infrastructure requirements. The new CAT 6A cabling will consist of, but not be limited to:

- Fiber Infrastructure Cabling

- Communication Cable

In addition, IT Equipment will require upgrading which will consist of, but not be limited to:

- Data Cabinets

- Data Racks

- Patch Panels

- Rack Sensors

- Uninterruptible Power Supply (UPSs)

- Power Distribution Unit (PDUs)

Furthermore, additional dedicated electrical outlets will be needed for the UPSs.

There will be a total of two new Telecommunications Rooms (TRs) designated by the A/E from existing rooms, one on the second floor and another on the fourth floor.

2.2 Telecommunication Rooms (TR)

One new TR on the second floor and another on the fourth floor will be designated to eliminate

IT service from the third floor that feeds the second and fourth floors. The existing building chiller water system will be utilized as the cooling source. A new Telecom Room Fan Coil Unit (TFC) will be provided in each TR, which will incorporate temperature and humidity control with display to

EHRM Infrastructure Upgrades Design Narrative meet VA and OIT standard requirements.

3. ARCHITECTURE

3.1 The Main Computer Room (MCR) is located on the first floor in Room A114. New UPS’s and

Data Cabinets will be installed in the room.

Additional Room B122 serves as a supplemental TR for the first floor. New Racks will be installed in the room.

The second floor Pharmacist Room B201 will serve as the new TR Room for the second floor.

New Racks will be installed in the room.

The existing third floor TR Room A312, will remain in place. Cabling to second and fourth floors will be removed, it will serve only the third floor. New Racks will be installed in the room.

A portion of fourth floor Group Therapy Room B444 will be converted to a TR Room B444A. New

Racks will be installed in the room.

The existing fifth floor TR Room A502 will remain in use and serve the fifth floor. New Racks will be installed in the room.

3.2 Finishes

3.2.1 The existing Main Computer Room has raised access flooring, painted gypboard walls, and acoustical tile ceiling; the existing access flooring at the Main Computer Room will remain in place. The existing ramp will remain in place.

The perimeter walls of the Main Computer Room extend to the underside of the structure above (steel studs, gypboard both sides). During construction, the walls will be inspected, all penetrations will be sealed. The exposed walls will be painted.

The existing acoustical tiles will be replaced with “Clean Room” type acoustical tiles.

All existing ceiling mounted devices (lighting, smoke detectors, and HVAC registers etc.) will remain for ceiling tile replacement.

3.2.2 The existing third floor TR Room A312 has VCT flooring, painted gypboard walls and acoustic tile ceiling. The ceiling will be replace with hard lid gypboard ceiling

Static dissipative resilient floor tiles will be installed in all TR rooms.

The perimeter walls of all TR rooms will be painted and sealed to underside of new/existing gyp board ceiling.

EHRM Infrastructure Upgrades Design Narrative

The existing gypboard ceiling will remain on the fifth floor TR room A502; the second third and fourth floor TRs the ceiling will be framed, and new gyp board ceiling will be installed.

3.3 Doors

3.3.1 The new door to the new TR Room B444A on the 4th Floor will have a card reader and locks to match proposed VA standards, as indicated in Figure 1, TR Room Door.

Figure 1, TR Room Door

4. STRUCTURAL

4.1 General

4.1.1 Codes:

The support and anchorage of the non‐structural components to comply with H‐18‐8

Seismic Design Requirements dated October 2019, IBC 2018 International Building

Code, and ASCE 7‐Minimum Design Loads for Buildings and Other Structures.

EHRM Infrastructure Upgrades Design Narrative

4.1.2 Design Criteria:

Seismic Design Data

Seismic Importance Factor I = 1.5

Mapped Spectral Response Ss = 1.972 S1 = 0.703

SDS = 1.578

4.2 Existing Building Structure

The existing building is steel framed and was designed in 1988. The existing first floor consists of a 3‐inch metal deck with a 7‐inch thick of light weight concrete topping. Floors above the first level consists of 3‐inch metal deck with 3 ¼ inch thick light weight concrete topping. The deck spans between steel beams which in turn are supported by steel columns. The foundations of the building are spread footings.

4.3 New Work

The structural scope of the work is to provide support and anchorage of the IT equipment and suspended mechanical fan coil units.

The mechanical fan‐coil units are hung from the existing concrete filled metal deck by rods. The units are braced each way by seismic cables which are attached to the deck.

The UPS unit for the IT is located on the first floor in the existing computer room which has raised access floor system. The UPS is supported on a floor stand which is anchored to the existing concrete filled metal deck. Anchorage of the Distribution cabinets mounted on top of the raised floor access panels is provided by through threaded rods connected to the concrete anchors.

The IT Data cabinets are anchored to the existing floor deck.

5. MECHANICAL

5.1 HVAC System

5.1.1 Each Telecommunications Room (TR) will have a ducted 3‐ton chilled water fan coil unit, except TR B236, to maintain space temperature. TR B236 will have a 1‐1/2‐ ton fan coil unit. Each fan coil will have a digital thermostat/controller with display showing room temperature and humidity. These fan coil units will not have humidity control per OIT Infrastructure Standard for Telecommunications Space.

5.1.2 Fan coil units will be located outside of small TRs to avoid the potential of leak either from the chilled water pipes or clogged condensate drain directly over the IT equipment. Fan coil units will be located inside a large TR where these fan coil units can be installed away from the IT equipment.

5.1.3 OIT Infrastructure Standard for Telecommunications Space classified TR as Network

Support Centers (NSC). Per OIT Standards section 3.1.3.11, water detection monitoring is not required. Under current system design, a point water detection system will be provided to monitor the secondary drain pan should the primary condensate drain fail.

EHRM Infrastructure Upgrades Design Narrative

The water detection system will be tied into the Building Automation System which allows on site building engineer to correct deficiency.

5.1.4 The 2‐pipe fan coil units will tie into the building’s existing chilled water loop, which is located in the Mechanical Rooms on each floor; only the fan coil unit on the first floor will tie into a chilled water riser, which is located outside of a Mechanical Room.

5.1.5 Supply and return air will be ducted from fan coil unit. The return air grille will have a filter frame capable to house a standard 20”x20”x1” filter.

5.1.6 Overhead pressurized and non‐pressurized pipes are shown on drawing M401. Drip pans will be installed below these pipes and drain to TR room entrance.

5.1.7 Building air conditioning system will be used to provide positive pressure for all TR rooms. Small TR rooms will have 3 air change per hour (ACH) and large TR room will have 2 ACH.

5.2 HVAC System Capacity

5.2.1 The fan coil unit size will be based on two CyberPower 3 KVA/2.7 KW UPS power output which IT equipment are required to operate. Provide IT equipment heat rejection data, if possible, for an accurate heat load calculation.

5.2.2 Based on the 1988 HVAC record drawings, the existing chilled water plant is capable of providing 1660 GPM of chilled water and the building is using 1312 GPM. The total chilled water consumed by the new fan coil units will be 42 GPM, well within the maximum capacity of the chill water plant.

6. PLUMBING

6.1 Plumbing System

6.1.1 Insulated Condensate drain and trap will be provided for each new fan coil unit.

Condensate will be indirectly drain to the nearest mop sink, or tail piece of a lavatory.

7. ELECTRICAL

7.1 Overview

7.1.1 The intent of the project is to provide new communication cabling and IT equipment;

replacing existing items to meet Cerner Infrastructure requirements.

7.1.2 The new communication cabling will include, but is not limited to the following:

OM4 multi‐mode fiber optic cables for backbone cable connections between

Main Computer Room (MCR) and each satellite Telecommunication Room (TR)

OM4 multiple mode fiber optic patch cables at the MCR and at the TRs

CAT 6A communication cables as horizontal cable connections from the MCR and the TRs serving telecom outlets

7.1.3 New IT equipment will include, but is not limited to the following:

New floor mounted data cabinets at the MCR to accommodate the following, but not limited to:

o Existing relocated or new IT equipment from telecom service providers

EHRM Infrastructure Upgrades Design Narrative o New telecom head‐end equipment (i.e. network core switches, network switches and wireless LAN controllers) provided by VA OIT o New fiber optic patch panels o New horizontal cable patch panels o New data cabinets installed Power Distribution Units (PDUs) o New floor mounted stand‐alone Uninterruptible Power Supply (UPSs) o New horizontal and vertical cable management system o New data cabinet mounted environment sensors

New floor mounted data racks at each TR to accommodate the following, but not limited to:

o New rack mounted fiber optic patch panels for backbone cable connections o New telecom head‐end equipment (i.e. network switches and wireless

LAN controllers) provided by VA OIT o New horizontal cable patch panels o New data rack installed Power Distribution Units (PDUs) o New data rack installed Uninterruptible Power Supply (UPSs) o New horizontal and vertical cable management system o New data rack mounted environment sensors

7.1.4 Electrical support for the new IT equipment:

Reuse existing NEMA 5‐20R receptacles or provide new NEMA 5‐20R receptacles with red faceplate in the MCR and the TRs. The receptacles shall be fed by Critical Branch essential electrical system for the building, to meet VA standard requirement.

Provide new NEMA L21‐20R receptacles to feed new data cabinets and provide new NEMA L6‐20R receptacles to feed new data racks per VA OIT standard requirements.

Provide proper grounding for the new telecom system for the project.

7.2 Existing Telecom Rooms

7.2.1 Minimum Point of Entry (MPOE): MPOE room P201 is located on P2 level of the building, which receives Outside Plant Cables (OSP) from service providers for the building. Fiber optic cables are routed through 24‐inch wide ladder trays in the room to upstairs to the Main Computer Room (MCR) A114 on the first floor. The backbone cable connection between the MPOE and the MCR will remain to reuse for this project.

7.2.2 Main Computer Room: The Main Computer Room A114 is located on the first floor and the whole room is covered by a raised floor with floor tiles. With field measurement, clear space from top of concrete floor slab to bottom of raised floor tiles is about 11" and the floor tile is approximately 1" thick. Each floor tile is supported by pestels at four corners of the tile.

Six 2‐post data racks are installed in the room, which include two separate racks for telecom service equipment from service providers, AT&T and Time

Warner, respectively. The remaining data racks accommodate network

EHRM Infrastructure Upgrades Design Narrative equipment (i.e. fiber splice boxes, core switches, voice gateways, and wireless

LAN controllers, etc.).

Both vertical and horizontal cable management rings were observed on the data racks. However, most of the cables are not run in horizontal management rings so they are not well organized, when routed from the racks to conduit sleeves above the racks to space above the suspended ceiling.

Conduit sleeves above the racks are used to route fiber optic and horizontal cables from the data racks to space above the suspended ceiling.

Both ladder tray and mesh tray are used to run cables above the data racks.

A double section UPS with battery cabinet and 2‐section UPS electrical panel

“UPS‐P1” and “UPS‐P2” serve the Main Computer Room. The UPS is an Eaton

“93E‐60/40”, 32KW/40KVA UPS with 208VAC output. The UPS appears fairly new and is in good condition. However, the single group of batteries serve both panels “UPS‐P1” and “UPS‐P2”, which doesn’t meet A/B side redundancy requirement from VA OIT standard.

The MCR A114 serves data outlets at west portion of the first floor.

7.2.3 Telecom Room B122:

The Telecom Room accommodates two 2‐post data racks with network equipment and patch panels serving data outlets at east portion of the first floor.

Fiber splice boxes are mounted on a 2 x 4‐foot plywood backboard on the wall and receive fiber optic backbone cables from MCR A114.

Horizontal cables are routed through ladder trays above the racks to space above the ceiling through conduit sleeves on the back wall. The existing cable installation is lacking in cable management.

7.2.4 Telecom Room A312:

There is no existing Telecom Room on the second floor and on the fourth floor serving telecom outlets on those floors.

The Telecom Room A312 on the third floor accommodates nine 2‐post data racks with network equipment and patch panels serving data outlets on the second floor, third floor, and fourth floor.

Fiber splice boxes are mounted on a 2 x 4‐foot plywood backboard on the wall and receive fiber optic backbone cables from MCR A114.

Some horizontal cables are routed through ladder trays above the racks to space above the ceiling through conduit sleeves on the back wall. Other cables are routed through poke‐through conduit sleeves on floor. The existing cable installation is lacking in cable management.

7.2.5 Telecom Room A502:

The Telecom Room A502 on the fifth floor accommodates two 2‐post data racks with network equipment and patch panels serving data outlets on the fifth floor.

Fiber splice boxes are mounted on a 2 x 4‐foot plywood backboard on the wall and receive fiber optic backbone cables from MCR A114.

EHRM Infrastructure Upgrades Design Narrative

Horizontal cables are routed through ladder trays above the racks to space above the ceiling through conduit sleeves on the back wall. The existing cable installation is lacking in cable management.

7.3 Proposed Electrical Work for the Project

7.3.1 New Cables:

7.3.1.1 Backbone Cables: New 24‐strand OM4 multi‐mode fiber optic cables within one 2‐inch inner‐duct in two 4‐inch conduits ((1) 4‐inch conduit as spare) will be provided from MCR A114 to each Telecom Room.

7.3.1.2 Horizontal Cables:

The existing horizontal cables are CAT 5 or CAT 5E cables, which utilize technology over 20 years old and have limited bandwidth (100MHz). They will be replaced by new CAT 6A cables for the project. The existing cables are currently routed in above‐ceiling slab suspend mounted 6”x6” metallic wireway along with telephone and MATV system conductors.

CAT 6A cable is augmented version of original CAT 6 cable. CAT 6A cables make use of their higher standards by allowing full 10GBASE‐T transmission speeds of up to 10 Gbps, at 500MHz of signal bandwidth, over 100 meters (330 feet). The 100 meters (330 feet) consists of 10 meters (35 feet) for patch cables and 90 meters (295 feet) for total fixed cabling.

All horizontal UTP CAT 6A cables shall be terminated to T568B per OIT

Design Guide Templates.

7.3.1.3 Cable Route:

Cable trays will be provided in the MCR and in the TRs to route cables in the TRs. Provide dividers in the trays so fiber optic cables and CAT 6A cables will be routed separately in the same trays.

Unless otherwise noted, all the cables out of the MCR and the TRs will be routed in the existing 6”x6” wireways, or installed on new J‐hooks above the suspended ceiling in corridors, if the existing wireway is more than

50% filled with existing and new cables. J‐hooks will be provided no more than 5 feet apart and will be supported from building structure. Cable route will be coordinated with existing equipment, pipes and ductwork above the ceiling. Conduit sleeves will be provided for cable penetrations through walls, floors, and ceilings. Fire stopping will be provided for conduit penetrations through fire rated walls, floors, and ceilings. Where fire rated penetrations are required, UL listed assemblies shall be used.

7.3.2 Diamond Analysis:

So as to ensure new telecom system performance with CAT 6A cabling to meet Cerner

Infrastructure requirements, Design Guide document ‘SOCAMES 6 Design Alert 1’ by

VA OIT provides a three‐dimensional estimation approach called ‘Diamond Analysis.’

It was provided to assure that the fixed cables being installed don’t exceed the

EHRM Infrastructure Upgrades Design Narrative specified UTP cable segment of 90 meters (295 feet) from existing or new Telecom

Rooms. Diagonal radius of 80 meters (262 feet) is used to draw a diamond shape using the TR as the center of the diamond. The 80‐meter (262‐foot) coverage instead of 90‐ meter (295‐foot) is used “in order to account for vertical cable distance, installation of slack for bypassing obstructions, cable management, bend radii and other in‐situ obstacles” per the ‘SOCAMES 6 Design Alert 1.’

The existing Main Computer Room and existing Telecom Rooms will be utilized for the project, plus a new TR room B201 for the second floor and a new TR room B444A for the fourth floor respectively. See Sheet GI‐101 for UTP horizontal cable distance assessment (Diamond Analysis) for all the TRs for the building, per ‘SOCAMES 6 Design

Alert 1.’

7.3.3 New Telecom Outlets:

7.3.3.1 Wall Outlets:

The majority of existing wall mounted telecom outlets use 4‐port outlets with a single‐gang back‐box and faceplate per outlet. A few telecom outlets use 1‐port or 6‐port outlets with a single‐gang back‐box and faceplate per outlet. While replacing all existing CAT 5 and CAT 5E cables by new CAT 6A cables existing back‐boxes for the telecom outlets may remain for reuse. All existing telecom jacks will be replaced by new CAT 6A

RJ45 jacks with new faceplates for the outlets. The new 4‐port telecom outlets will consist of three jacks with Gray, White, and Blue colors respectively and the fourth as blank with cover. Stainless steel faceplate will be used as cover for the new telecom outlets. Three color coded CAT

6A cables with Gray, White, and Blue colors will be provided for color coded jacks for each of the outlets accordingly.

7.3.3.2 Wireless Access Point (WAP):

Ceiling surface mounted WAPs are located throughout the buildings. All the existing cables for the WAPs will be replaced by new CAT 6A cables.

Above ceiling or wall mounted 2‐port data outlet will be used for each ceiling or wall mounted WAP.

7.3.4 Labeling:

Labels will be provided for each wall outlet and outlet for WAP, with an identification number for each outlet. The identification number will include the information of

“from which Telecom Room (TR#), from which Data Rack (DR#), from which Patch

Panel (PP#), and from which Port of the Patch Panel (PO#)” the cable is fed, “to which

Room (RM#), to which Telecom Outlet (TO#), and to which Jack of the Outlet (J#).” The proposed numerical format for the outlet ID is as below –

TR# ‐ DR# ‐ PP# ‐ PO# ‐ RM# ‐ TO# ‐ J#

All the new cabling will also be tagged on both ends of the cable and in any pullbox required, with the same label(s) as data jack(s) fed by the cable(s).

All labeling shall be ANSI/TIA/EIA/606C compliant. They shall be machine printed with black lettering on white field.

EHRM Infrastructure Upgrades Design Narrative

With labeling for the new telecom outlets, Contractor shall update a template for new cabling inventory for the project. The template in Excel will be provided from VA

Project Manager per Contractor's request. The new cabling inventory spreadsheet will be saved in an electronic file with a hard copy attached to data cabinets/racks for future management, updating, and trouble shooting.

7.3.5 Main Computer Room A112:

7.3.5.1 New Data Cabinets: Four new OIT standard Data Cabinets will be flush mounted on raised floor with floor stands on concrete floor slab below raised floor. The Data Cabinets will be anchored and support from the floor stands. See structural design for Data Cabinet installation requirement. The new Data Cabinets will accommodate the following:

Existing service equipment from AT&T and Time Warner

New fiber optic patch panels to receive existing fiber optic cables from

MPOE on P2 level

New equipment provided by VA OIT (i.e. core switches, network switches, voice gateways, and wireless LAN controllers, etc.)

New 48‐port patch panels for CAT 6A cables

New data cabinets installed Power Distribution Units (PDUs)

New horizontal and vertical cable management system

New data cabinet mounted environment sensors

New water leakage detection loop connection

3‐foot clearance around the new data cabinets shall be maintained per OIT standard.

7.3.5.2 New UPS System

The existing UPS system (E)”UPS” in the MCR consists of a single group of batteries, a UPS, a step‐down transformer and two section panels “UPS‐

P1” and UPS‐P2”. It doesn’t provide any redundancy so not meet VA OIT requirement for UPS.

Two new UPS systems (N)”UPS‐A” and (N)”UPS‐B” will be provided to replace the existing (E)”UPS”. New Galaxy VS 40KW UPS system from APC

(Schneider Electric) is used as design basis. Each of two new double‐ convertion UPS systems will consist of four sections – a UPS cabinet with rectifier, inverter; a Lithium (Li‐Ion) battery cabinet with strings of chargeable batteries and battery breaker; a maintenance bypass cabinet with unit input breaker to receive 480V, 3‐phase power, maintenance bypass breaker, unit output breaker and output transformer to step down

480V to 208Y/120V; and a Power Distribution Unit with two 42‐pole electrical panels (N)"UPS‐PA" and (N)"UPS‐PB".

Each new UPS system will be rated as 40KW/40KVA with 480V, 3‐phase input and a 208Y/120V, 3‐phase, 4‐wire output. An existing 150A/3P circuit breaker at existing switchboard “1ESS” in Emergency Switchgear

EHRM Infrastructure Upgrades Design Narrative

Room P201 on P2 level feeds the existing (E)”UPS”. Switchboard "1ESS" feeds mechanical loads and others. It is considered as Equipment Branch of the Essential Electrical System. Per part 8.5.3 of VA Telecommunications and Special Telecommunications System Design Manual (FEB. 2016)", "Electrical power (for Main Computer Room) shall be on critical branch of the Essential Electrical System." Existing switchboard "2ESS" is considered as Critical Branch of the ESS. The new (N)”UPS‐A” and (N)”UPS‐B” will be fed from the switchboard "2ESS" with two new 80A/3P feeder breakers in space of the existing switchboard. 30‐day meter reading of the existing switchboard has been provided for the project in order to determine its peak demand for reusage to accommodate new loads, per NEC 220.87.

The new (N)”UPS‐A” will be installed and connected prior to disconnect and remove the existing (E)”UPS”, to minimize downtime of UPS backup.

Each of the two new UPS systems will provide 40 minutes runtime to backup essential load in the MCR. Battery Monitoring System (BMS) is provided with the new systems. Disconnect switches with external connections will be provided for the BMS and low voltage cable connections will be provided for the new UPS systems per coordination with the UPS supplier. Grounding Electrode Conductors (GEC) will be provided for the new step‐down transformers for the UPS systems.

7.3.5.3 Provide new below‐raised‐ floor concrete floor mounted twisted‐lock receptacles, NEMA L21‐20R, under data cabinets to serve data cabinet mounted PDUs, per “VA CFM/OIT Design Guide Templates for Critical

Telecommunications Spaces in Clinical and Non‐Clinical Environments.”

Provide a 208/120V, 3‐phase, 4‐wire circuit from the new UPS panels

(N)”UPS‐PA” and (N)”UPS‐PB” at MCR dedicated for each twisted‐lock receptacle.

7.3.5.4 Provide mesh type cable trays above data cabinets for cable runs to and from the data cabinets. The mesh cable trays will be supported from concrete slab above drop ceilings. Seismic bracing will be provided for long thread rod supports above the ceiling.

Provide wall mounted conduit sleeves to route cables from cable trays to space above ceiling.

7.3.5.5 The MCR A114 will serve telecom outlets at west portion of the first floor of the building with new CAT 6A cables.

7.3.6 Telecom Rooms:

7.3.6.1 Existing Telecom Rooms B122 on the first floor, A312 on the third floor, and A502 on the fifth floor will be reused to serve telecom outlets on the related floors.

7.3.6.2 The existing Pharmacist Room B201 will be reassigned as a new Telecom

Room to serve all telecom outlets on the second floor.

EHRM Infrastructure Upgrades Design Narrative

7.3.6.3 A portion of the existing Group Therapy Room B444 will be reassigned as a new Telecom Room B444A to serve all telecom outlets on the fourth floor.

7.3.6.4 New 4‐post data racks with base plates anchored to concrete floors will be provided for each of the TR’s. Per VA OIT standard, 7 feet tall, 23.75 inches wide and 30 inches deep cable management racks with 45 Rack Mount

Unit (RMU) space, Legrand Mighty Mo 20 or equivalent, will be provided as the new data racks. However, per coordination with Legrand tech support, Mighty Mo 20 racks are not seismic rated. New data racks provided shall be seismic rated per confirmation from VA. To provide sufficient rack mount unit spaces, the number of new data racks to be provided for each of the TR’s is as below:

TR B122 – (2) data racks TR B201 – (3) data racks

TR A312 – (3) data racks

TR B444 – (2) data racks

TR A502 – (2) data racks Rack mounted equipment will include fiber optic patch panel to receive

OM4 backbone cables from MCR A114, network equipment provided by

OIT and 48‐port patch panels for horizontal cables. A horizontal cable manager will be provided below each patch panel. Vertical cable managers along front sides of the racks will be provided.

Two CyberPower OL3000RTXL2UHVN UPS's will be mounted on the racks.

Each CyberPower UPS is rated as 208VAC, 1‐phase, 2.7KW/3KVA. Two

208V, 1‐phase, 20A Vertical Power Distribution Units (PDUs) will be provided for the racks. Two new, above data racks, ceiling mounted twisted‐lock receptacles with NEMA L6‐20R configuration, will be provided to serve the rack mounted UPS's, which will feed rack mounted

PDU's.

As design intent, we try to maintain 3 feet clearance in front of and at both sides of the new data racks in the TRs; however, some TRs have limited space. Maintaining existing racks/equipment operational while providing new racks/equipment in the same rooms will add some challenges. The

OIT standard rack, Legrand Mighty Mo 20 or equivalent, is a 4‐post rack, which will occupy more floor space than a regular 2‐post rack. Close coordination with the VA facility and with VA OIT has been performed to ensure the number of new data racks can fit in the room and also meet project and OIT standard requirements. Chatsworth Product (CPI) 19" wide, 4‐post, adjustable server rack is proposed for the project. It is

Seismic rated with 45 Rack Mount Space (RMU) and will take less space than the Mighty Mo 20 rack. Mighty Mo 20 rack is not seismic rated.

7.3.6.5 Power for the Telecom Rooms:

EHRM Infrastructure Upgrades Design Narrative

Two 208/120V, 1‐phase, 3‐wire with grounding circuits will be provided for the two twisted‐lock receptacles at each TR. The circuits will be from nearby 208/120V branch panels from existing Critical Branch essential electrical system. The new telecom loads from each TR will be supplied by circuits from a panel on the same floor.

New 120VAC, 20A receptacles with red faceplates will be provided at TRs.

The receptacles will be fed by Critical Branch essential electrical system.

New Telecom Room Fan Coil Unit (TFC) will be provided for each TR. A

208VAC, 20A circuit from nearby branch panel from existing Equipment

Branch essential electrical system will be provided for each new TFC, per

VA design standard. Because the existing Equipment Branch 208/120V panels are located on P2 and roof levels only, the new circuits for TFCs will be fed from these panels. The new TFCs for TRs on the first and second floors will be served by the panel on P2 level and TFCs for TRs on the third, fourth, and fifth floors will be supplied by the panel on the roof level. All the junction boxes and local disconnects serving the new TFCs at the new

TRs shall be permanently labeled for which panel and circuit and which floor the circuit is from.

Where the existing branch panels are used for new loads, 30‐day meter reading of them is required to determine peak demand of the panels, per

NEC 220.87. It is permissible to use 14‐day meter reading to determine existing peak demand, per government’s response to RFI 01. If the panel will be overloaded with the new loads or the panel is out of circuit for the new loads, a new panel will be provided to accommodate project needs.

Load calculation for its upstream step‐down transformer and the related

480/277V panel has been provided to ensure the existing transformer and the upstream panel are not overloaded with new loads for the project.

7.3.7 Grounding and Bonding for Telecom:

No grounding or bonding is currently dedicated for the telecom system for the building; a new grounding and bonding system will be provided. It will consist of the following per VA Telecom Design Manual and TIA/EIA standards:

A Telecom Main Grounding Busbar (TMGB) at MPOE P201 on P2 level

A Telecom Grounding Busbar (TGB) at MCR and at MCR and at each TR

Bonding conductor connection will be provided between TMGB at MPOE and existing Main Grounding Busbar at Main Service Switchgear “MSSA” at Main

Electrical Room P205 on P2 level. Intersystem bonding terminations will be provided for connecting the intersystem bonding conductors between the two systems.

Telecom bonding backbone connections will be provided between TMGB and

TGBs.

Bonding connections will be provided from TGB’s to nearby building steel structure, to grounding busbar at nearby electrical panels, pathways (conduit

EHRM Infrastructure Upgrades Design Narrative sleeves and cable trays) for telecom cables, data cabinets and racks, telecom equipment, and new electrostatic discharge flooring at each TR, etc. Bonding jumpers will be provided at cable trays and at the data cabinets and racks.

Bonding connections will also be provided for the existing raised floor on the

MCR.

7.3.8 Construction Phasing for Electrical:

7.3.8.1 Construction sequence should be considered and coordinated to minimize impact on existing facility operation during the construction. Contractor shall coordinate with VA facility, project manager and VA OIT and provide new telecom system including data cabinets, data jacks, equipment, cables, pathway, and all required connections prior to disconnecting and removing existing telecom systems, in order to minimize service downtime for the areas to be worked.

7.3.8.2 For existing telecom room with limited space, Contractor shall carefully unbolt and slightly move/rotate existing data racks to save space for new data jacks. Existing equipment and cabling shall be supported and protected while installing the new equipment.

7.3.8.3 The existing third floor TR Room A312 supplies cables for data outlets on the second, third, and fourth floors. For those three floors, proposed work sequence is as below:

1) New TR and equipment on the second floor and fourth floor with associated cabling should be installed prior to work on the third floor.

2) Disconnecting and removing existing data racks, equipment, and cabling in Room A312 serving the second and fourth floors.

3) Install new data racks serving the third floor at the existing rack locations for the second and fourth floors. Unbolt and slightly move/rotate existing racks for the third floor if required for the new rack installation.

4) Disconnecting and removing existing remaining data racks, equipment, and cabling in Room A312 after new racks, equipment, and cabling installed for the third floor.

7.3.8.4 For the telecom work, which requires equipment disconnection and/or reconnection, and for any electrical panels or transformers to be replaced for the project, the work should be scheduled at night or in weekends so the electrical replacement work will have minimum impact on the facility daily operation.

8. FIRE PROTECTION

8.1 Fire Sprinkler

The Fire Protection for the Main computer Room and existing/new TR Rooms will be provided from existing Wet‐Type Fire Sprinkler System which is currently protecting the proposed space.

EHRM Infrastructure Upgrades Design Narrative

8.2 Fire Alarm

The existing fire alarm system will remain in place. It will be reconfigured for the adjustments made for this project, as needed.

9. ENVIRONMENTAL

9.1 Asbestos and Lead

There is no lead paint or asbestos known or suspected within LAACC. The bui lding was bui lt in 1992; i ts Total GSF is 201,395.

10. PHASING

10.1 Phasing

The project wi l l be phased as indicated on drawings.

EHRM INFRASTRUCTURE UPGRADES Design Narrative

EXHIBIT 1

PSDM REQUIREMENTS

PSDM # Description Commentary

5.4 Main Computer Room

5.4.3 Construction Surrounding walls and partitions shall be fire resistive construction and extend from slab to slab.

5.4.3.1 HVAC HVAC being addressed under a separate project (not in project scope)

5.4.3.2 Power

An existing 40KVA UPS and a 2‐section UPS panel was recently installed as backup power for the MCR. We bellieve the UPS must have been connected to building Essential Electrical System (ESS), powered by the existing generator. However, a RFI has been sent to request as‐builts for the UPS.

8.1.3 Telecommunications

8.1.3.1 Number of Service

It is our understanding that there are 2 telecom services coming in the building, one from AT&T and the other one from Times Warner. The service enter the MPOE (DEMARC) room P202 on P2 level. No work at MPOE is in the scope for this project.

8.1.3.2 Separation of Service No work at MPOE is in the scope for this project.

8.1.3.3 Redundant service paths to DEMARC No work at MPOE is in the scope for this project.

9.2.2 Uninterruptible Power Supply (UPS)

9.2.2.1 Modularity For the project, new UPS's will be data cabinet and data rack mounted. They will be OIT standard ones for modularity.

9.2.2.2 Space for UPS Sufficient Rack Mount Space (RMU) at new data cabinets and at new data racks will be provided for the UPS's.

9.2.2.3 Battery Run Time New UPS's will be specified with a minimum of 20 minutes of full rated output.

9.3.1 Demarcation Room

9.3.1.1 Location Existing MPOE (DEMARC) room is located at P202 on P2 level. No work at MPOE is in the scope for this project.

9.3.1.2 HVAC No HVAC provided (not in project scope)

9.3.1.3 Power No work at MPOE is in the scope for this project.

9.3.1.4 Conduit Pathways No work at MPOE is in the scope for this project.

9.3.2 Main Computer Room

9.3.2.1 Location The existing MCR is located at Room A114 on the 1st floor.

9.3.2.2 HVAC HVAC being addressed under a separate project (not in project scope)

9.3.2.3 Power

An existing 40KVA UPS and a 2‐section UPS panel was recently installed as backup power for the MCR. We bellieve the UPS must have been connected to building Essential Electrical System (ESS), powered by the existing generator. However, a RFI has been sent to request as‐builts for the UPS.

9.3.2.4 Conduit Pathways Existing backbone cable connection between the DEMARC and the MCR will be reused.

9.3.3 Telecommunications Rooms (TR)

9.3.3.1 HVAC

Fan coil units used for maintaining Telecommunications Room temperature will be connected to emergency power, which is backed by the generator should there be a power disruption.

9.3.3.2 Power

New data rack mounted UPS's will be provided at TR. The new UPS's will be OIT standard ones to meet run time requirement. The rack mounted equipment including UPS will be powered by existing nearby critical branch panel, which is fed by building generator. Wall mounted receptacles will be provided at TR, which will be fed by critical branch panel as well. New FCU for the TR's will be powered by existing equipment branch panel, which is fed by building generator.

9.3.4 Wireless Local Area Network System

Data cable connection to existing Wireless Access Point (WAP) will be replaced by CAT6A cables, which is the same type as new cables for other telecom outlets for the project.

Department of Veterans Affairs Physical Security Design Manual January 2015

5.3 Childcare/Development Center

This section supplements Program Guide (PG-18-9) Space Planning Criteria for VA Facilities, #420 Childcare/Development Center which shall remain in full force and effect.

Childcare/development centers shall also meet the licensure requirements of the jurisdiction in which they are located, as well as the requirements of VA Handbook 0730 Security and Law Enforcement, Appendix B, as they apply.

5.3.1 Adjacencies

When located within a portion of a main VA facility, such as a hospital, childcare/development centers shall be located on the ground floor away from main building entrance with separate access area for drop-off and pick-up.

5.3.2 Entrances

Doors shall be provided with an intercom to the reception desk with remote access from the desk.

5.3.2.1 Public entrances: Doors to childcare/development centers, including the main entrance and secondary entrances, shall be controlled and monitored.

5.3.2.2 Emergency exits: Emergency egress doors from childcare/development centers shall be controlled and monitored.

5.3.3 Construction

No additional physical security requirements.

5.3.4 Security

All entrances, including drop-off and pick-up areas, playgrounds, and other outdoor areas where children may be while at the childcare/development center shall be monitored by

VASS.

5.4 Main Computer Room

This section applies to the main computer room. In addition to the requirements of this section, NFPA 75: Protection of Electronic Computer/Data Processing Equipment shall apply.

This section supplements the Office of Information and Technology Design Guide.

5.2.5 Existing Facility – Cache

Existing caches shall comply with the requirements of section 5.2.

5.3.5 Existing Facility – Childcare/Development Center

Entrances and security for existing childcare/development centers shall comply with the requirements of sections 5.3.2 and 5.3.4.

Mission Critical Facilities

5.4.1 Adjacencies

The main computer room shall not be located in a high risk area and shall be located not closer than 50 feet (15 m) in any direction to main entrance lobbies, loading docks, and mailrooms, critical utilities, and in no case directly above or below such spaces.

5.4.2 Entrances

Entrance doors to the main computer room and other computer rooms shall be controlled and monitored.

5.4.3 Construction

Surrounding walls and partitions shall be fire resistive construction and extend from slab to slab.

5.4.3.1 HVAC: All vents, ducts, and similar openings in excess of 96 square inches (620 cm2) that enter or pass through a perimeter partition of the main computer room shall be protected with either bars or grills. Where one dimension of the duct measures less than six inches (150 mm) or duct is less than 96 square inches (620 cm2), bars are not required; however, all ducts shall be treated to provide sufficient sound attenuation. Where bars are used, they shall be 1/2 inch (12.7 mm) diameter steel welded vertically and horizontally six inches (150 mm) on center; where grills are used, they shall be of 9-gauge expanded steel.

Openings in construction above ceilings or below raised access floors shall be protected as above.

5.4.3.2 Power: The main computer room equipment and its supporting HVAC services shall be backed by the standby electrical system. Refer to the VA Electrical Design Manual for specific loads to be connected to the EES and UPS power.

5.4.4 Security

All doors between the computer room and public space shall have motion-activated VASS camera coverage on the computer room side of the door. The space shall be controlled by physical access control and monitored by intrusion detection system (boundary only).

5.5 Emergency Department

This section supplements Program Guide (PG-18-9) Space Planning Criteria for VA Facilities, #262 Ambulatory Care (Hospital Based).

5.5.1 Adjacencies

5.5.1.1 Vehicular Access: Only ambulances and emergency vehicles shall be allowed within 50 feet (15 m) of the emergency department entrance; however, no vehicle

5.4.5 Existing Facility – Main Computer Room

Existing main computer rooms shall comply with the requirements of section 5.4.

Mission Critical Facilities rkalwani Highlight within a mission critical building envelope, when possible, or be protected by limited-access masonry enclosures and be located a minimum of 50 feet (15 m) in all directions from high-risk areas. Coordinate with the serving utility.

8.1.3 Telecommunications

8.1.3.1 Number of services: Two services from each telecommunications provider are required, preferably with delivery from different central offices or sites.

8.1.3.2 Separation of services: Telecommunications cable pathways shall be underground, located away from other utility services, and located away from high-risk areas. Where more than one service is obtained, services shall be separated by a minimum distance of 50 feet (15 m).

8.1.3.3 Redundant service paths to demarc: The demarc is the separation point between utility-owned and VA-owned equipment. Telecommunications cable pathways shall be designed to provide redundant services to the demarc from the street or property line where the interface with the service provider takes place.

Redundant conduit paths shall be separated by a minimum distance of 50 feet (15 m).

8.2 Site Distribution

8.2.1 Mechanical

8.2.1.1 Steam, chilled water, water, and fuel system distribution: Distribution systems shall be underground and shall be looped systems, such that an interruption at any one point can be isolated and service maintained to the facility. Piped utility systems, in particular fuel systems, shall include enhanced capability to resist external forces. Steam and condensate piping shall be installed above grade and not be located in high risk areas.

8.2.1.2 Separation of sanitary sewer and storm drain systems: Sanitary sewer and storm drain systems shall be separate.

8.2.1.3 Manhole and handhole covers: Manholes and handholes shall be equipped with lockable covers.

8.2.2 Electrical

8.1.4 Existing Facility – Utility Entrances

8.1.4.1 Existing facilities shall comply with the redundancy requirements of section 8.1.

8.1.4.2 Relocate existing mechanical and electrical equipment to comply with section 8.1. Where existing equipment cannot be relocated to within an existing building envelope, protect the equipment with screen walls or barriers that comply with Chapters 6 and 7.

Mission Critical Facilities rkalwani Highlight rkalwani Highlight rkalwani Highlight rkalwani Highlight

9.2.1.4 Emergency connections: Include an exterior emergency quick connection and all associated equipment for the ESS at or near the location of the EES distribution equipment.

9.2.2 Uninterruptible Power Supply (UPS)

Provide UPS equipment for critical telecommunications and computer equipment. The telecommunications facilities include the entrance facility (demarc), main computer room, and telecommunications rooms. UPS equipment provides power during the time gap between loss of utility power and energization of the EES or standby electrical systems. UPS also provides power for an orderly shutdown of equipment in the event EES or standby electrical systems do not operate properly.

9.2.2.1 Modularity: Where multiple UPS are used, they shall be identically sized to allow for interchangeability.

9.2.2.2 Space for UPS: Provide required UPS floor space in rooms which require UPS-backed power.

9.2.2.3 Battery runtime: Size battery systems for a minimum of 20 minutes of full rated output. Individual project needs may dictate a longer runtime.

9.3 Telecommunications Systems

Refer to Chapter 5 for functional area requirements.

9.3.1 Demarcation Room

The demarcation room (demarc) is where all telecommunications services from all service providers are delivered to the building and contains the separation points between utility-owned and VA-owned equipment and cabling.

9.3.1.1 Location: The demarc room shall be located above grade and above the 100-year floodplain and within a mission critical building envelope. The room shall not be located adjacent to the main computer room. The room shall be located at least 50 feet (15 m) from high-risk areas, shall not be located within 25 feet (7.62 m) of an outside wall or delivery area, and shall not be located directly below laboratories, kitchens, laundries, toilets, showers, or other areas where water service is provided.

9.3.1.2 HVAC: The demarc room shall be provided with generator-backed HVAC service.

9.3.1.3 Power: All equipment in the demarc room shall be powered from UPS equipment that will provide a minimum of 4 hours of service at full rated output. In addition, a risk analysis shall be performed to demonstrate the need for compliance

9.2.3 Existing Facility – Electrical Systems

9.2.3.1 Standby electrical system: Existing facilities in regions prone to hurricanes (in accordance with ASCE 7-10) and zones of Moderate-High or greater seismicity (refer to VA H-18-8) shall comply with section 9.2.1. Facilities outside these areas or zones are encouraged to comply with section 9.2.1.

9.2.3.1 UPS: Existing facilities shall comply with section 9.2.2.

Mission Critical Facilities rkalwani Highlight with NEC Article 708, Critical Operations Power Systems. Compliance with the provisions of NEC 708 may be required for the electrical systems serving the demarc room, including but not limited to upstream electrical distribution equipment.

9.3.1.4 Conduit pathways: Conduit pathways used to interconnect the demarc room and the main computer room shall be configured in a ring topology to provide two pathways between the two locations.

9.3.2 Main Computer Room

The main computer room contains all of the main telephone switching and data processing equipment for the mission critical facility.

9.3.2.1 Location: The main computer room shall be located above grade and above the 100-year floodplain and within a secure area of the building, on the ground floor or higher.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .