Attachment 2 - Bill of Quantities.pdf

PDF 913 KB Posted

Attached to
MSB Chiller Replacement, Rome, Italy Federal contract opportunity
Solicitation number
191T7025Q0012
Issued by
Department of State

About this file

The document is a Bill of Quantities (BoQ) for a chiller replacement project at the Mel Sembler Building within the U.S. Embassy compound in Rome, Italy. The BoQ details 15 line items for comprehensive HVAC system replacement, including site preparation, removal of existing equipment, and installation of new components. Key technical specifications include a new air-cooled reversible heat pump with 68 kW heating/cooling capacity, using R454B refrigerant, along with associated piping, valves, insulation, expansion tanks, control panels, and electrical infrastructure upgrades.

The scope of work encompasses complete system replacement with detailed requirements for equipment installation, electrical work, system configuration, and commissioning. Specific requirements include installing flexible closed-cell insulation with antimicrobial protection, new electrical distribution panels, cable replacements, and system integration with the existing Building Automation System (BAS). All work must be performed by manufacturer-authorized technicians, with the contractor required to provide disposal certificates and complete final system testing and cleaning. The document is marked "Sensitive But Unclassified" and is part of a Request for Quotation (RFQ) issued by the Department of State.

View the file

Other files for this federal contract opportunity

Other files attached to MSB Chiller Replacement, Rome, Italy, newest first.
File Type Posted
Amendment 0002 - 191T7025Q0012.pdf PDF
Questions and Answers - 191T7025Q0012.pdf PDF
Amendment 0001 - 191T7025Q0012.pdf PDF
Attachment 1 - Technical Specifications_v2.pdf PDF
Attachment 2 - Bill of Quantities_v2.pdf PDF
SF-1442 - 191T7025Q0012.docx DOCX document
RFQ - 191T7025Q0012.docx DOCX document
Cover Letter - 191T7025Q0012.pdf PDF
Attachment 3 - Form E.O.14173.pdf PDF
Attachment 1 - Technical Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

No. DESCRIPTION QUANTITY

UNITY COST

TOTAL COST

Site preparation including fences, provisional staging area, protection of materials and furniture, protection of floors and walls lump sum

Removal and disposal of the existing the existing air‐cooled chiller and associated buffer tank. The

Contractor will provide disposal certificates to the COR.

lump sum

Supply and installation of new piping, manifolds, valves, strainers, thermometers (scale range: 0‐90 C, Class 1), pressure gauges (scale range: 0‐6 bar, Class 1), expansion tanks as per drawings. Piping shall be treated with anti‐rust. All equipment shall be PN16

Supply and install of new flexible, closed‐cell insulation material with built‐in Microban® antimicrobial protection to protect the piping (AF/Armaflex Class 0) and of aluminum finishing lump sum

Supply and installation of a new air‐cooled reversible heat pump, with 2 scroll compressors and have a heating/cooling capacity of 68 kW. The new unit shall be equipped with built‐in pumps and buffer tank.

Refrigerant gas shall be R454B.

lump sum

6 Supply and installation of a new 100 liters expansion tank on the return pipe. lump sum

Supply and installation of an automatic make‐up water filling unit with pressure gauge and hydraulic disconnector (BA type) to be connected to the return piping of the systems lump sum

8 Supply a new TRACER SC+ and an UC600 control panel lump sum

Create new graphic pages and configure the new reversible heat pump on the BAS as per table below. All the IT work needed to configure the reversible heat pump on the existing BAS (graphic pages, equipment operation rules, etc.) shall be performed by a TRANE authorized technician lump sum

10 Remove existing electrical cables and EMT lump sum

Supply and installation of a new cable FG16OM16 0,6/1 kV, Cca‐s1,d1,a1, 5G16 from the P3/D distribution panel located at the third floor to the new Chiller DP to be installed on the roof.

lump sum

12 Supply and installation of a new EMT for the new cable lump sum

Supply and installation on the roof of a new wall mounted IP 65, with terminals and solid door, electrical distribution panel. Supply and install the new electrical cables as described below. The new panel shall be composed of:

oDisconnector: 4 poles 63 A oMagneto thermic and GFCI serving the Heat Pump: 4 poles, type C, In: 63A, Ith:63A, Idn: 0.50 (AC type), Im: 630A, Icu/Icn: 10kA – electrical cable: FG16OM16 0,6/1 kV, , Cca‐s1,d1,a1, 5G16 lump sum

Test and balance of the system. Start‐up of the unit must be performed by Manufacturer’s authorized technicians lump sum

15 Final cleaning of the premises. lump sum

Total