Attachment 2 - 250401 Angell JC Mult. Build Elec_PERMIT SET.pdf

PDF 2 MB Posted

Attached to
Angell Electrical Deficiencies
Solicitation number
12441926Q0019
Issued by

About this file

This document is a set of electrical construction plans and specifications for the Angell Job Corps Civilian Conservation Center located at 335 NE Blodgett Road, Yachats, Oregon 97498. The project involves electrical work at two main buildings: Building 2083 (Administration Building) and Building 2889 (Gymnasium Building).

The specifications establish general requirements for electrical demolition and power installation work, including field verification of existing conditions, disconnection and relocation of obstructing equipment, removal of abandoned wiring, and coordination with existing systems. All new electrical equipment must be connected into existing systems, with power wiring concealed above accessible ceilings or in walls, and exposed wiring installed in approved surface metal raceway where indicated. Contractors must verify integrity of existing conduits before reuse and provide new raceways where necessary. All wall-mounted devices such as switches, receptacles, and outlets require field coordination with fixed casework, doors, and architectural elements. Fire-rated penetrations through walls, floors, and ceilings must be sealed appropriately. For the Administration Building, the project includes a new 400-amp 240V single-phase service disconnect with existing 100-amp and 30-amp disconnects, along with new panelboards and branch circuits. The Gymnasium Building requires installation of a 600-amp 240V single-phase service disconnect and a 150KVA oil-filled pad-mounted transformer (12.47KV/240V), with replacement of existing 480V heaters with 10KW 240V single-phase heaters and associated branch circuitry. Detailed one-line diagrams, equipment schedules, panel schedules, and exterior support details are provided for both buildings, specifying conductor sizes, conduit requirements, overcurrent protection, and grounding in accordance with NEC Article 250 and applicable standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. THE EXISTING CONDITIONS SHOWN WERE TAKEN FROM AVAILABLE RECORD INFORMATION. FIELD VERIFY ALL CONDITIONS THAT MAY AFFECT CONSTRUCTION. IF ANY DISCREPANCIES ARE DISCOVERED, NOTIFY THE

CONTRACTING OFFICER IN WRITING AND REQUEST DIRECTION PRIOR TO COMMENCING WORK.

B. ANY AND ALL EQUIPMENT HAVING ELECTRICAL CONNECTIONS THAT REQUIRE DISCONNECTING AND/OR RE- CONNECTING AS A RESULT OF CONSTRUCTION SHALL BE INCLUDED AS A PART OF THIS CONTRACT.

C. THE EXISTING ELECTRICAL DEVICES, CONDUIT, AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED UNLESS OTHERWISE NOTED. LOCATION IS TO BE AS CLOSE AS

POSSIBLE TO THE ORIGINAL LOCATION.

D. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT TO REMAIN IN SERVICE SHALL BE REMOVED BACK TO THE FIRST ACCESSIBLE JUNCTION BOX WHERE IT SHALL BE TIED OFF AND LABELED AS SPARE WITH CIRCUIT

NUMBER INDICATED.

E. REMOVE ALL ABANDONED WIRE AND CABLING.

DEMOLITION NOTES

1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN

SHEETS.

2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE

NEUTRAL CONDUCTORS.

3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED IN

ACCORDANCE WITH NFPA 70, ARTICLE 250.

4. ALL ELECTRICAL EQUIPMENT IN PORTIONS OF THE BUILDING NOT BEING REMODELED SHALL BE LEFT IN

WORKING CONDITION. RESTORE ANY CIRCUITS INTERRUPTED.

5. ALL NEW LIGHT FIXTURES AND FIXTURES IN AREAS ADJACENT DEMOLITION & CONSTRUCTION AREAS ARE TO BE

THOROUGHLY CLEANED IMMEDIATELY PRIOR TO NOTICE OF SUBSTANTIAL COMPLETION.

6. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE

BASE BID:

A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE

EXISTING SYSTEM AS REQUIRED.

B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN

WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE

INDICATED.

C. WHERE EXISTING CONDUITS ARE INDICATED FOR REUSE, FIELD VERIFY INTEGRITY OF REUSED RACEWAYS PRIOR TO INSTALLATION OF CONDUCTORS. PROVIDE NEW RACEWAYS WHERE EXISTING ARE UNUSABLE.

D. LOCATIONS OF ALL WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLES, AND OUTLETS ARE

SHOWN DIAGRAMMATICALLY. DETERMINE EXACT DEVICE LOCATIONS IN FIELD; COORDINATE

INSTALLATIONS WITH FIXED CASEWORK, DOORS AND RELITES.

E. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING

OF SURFACES PENETRATED.

GENERAL NOTES

@ AT

A/C AIR CONDITIONING(ER)

A (AMP) AMPERE

AC ABOVE COUNTER, ALTERNATING CURRENT

ADJ ADJUSTABLE

ADJT ADJACENT

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

ANN ANNUNCIATOR

ARCH ARCHITECT; ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BKBD BACKBOARD

BKR BREAKER

BLDG BUILDING

C CONDUIT

CAP CAPACITY

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CLR CLEAR

COL COLUMN

COM COMMUNICATION

CPS CYCLES PER SECOND

CT CURRENT TRANSFORMER

CTL CONTROL

CU COPPER

DC DIRECT CURRENT

DISC SW DISCONNECT SWITCH

DISC DISCONNECT

DN DOWN

DWG DRAWING

E EXIST, EAST

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EGC EQUIPMENT GROUNDING CONDUCTOR

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

ENTR ENTRANCE

EP EXPLOSION PROOF

EPO EMERGENCY POWER OFF

EQUIP/EQP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXH EXHAUST

EXT EXTERIOR

EXIST EXISTING

F FAHRENHEIT/FUSE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FD FIRE DAMPER

FDR FEEDER

FIXT FIXTURE

FLA FULL LOAD AMPS

FSD FIRE/SMOKE DAMPER

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFR GROUND FAULT RELAY

H HEIGHT

HID HIGH INTENSITY DISCHARGE

HOA HAND OFF AUTOMATIC

HOR HORIZONTAL

HP HORSEPOWER

HR HOUR

HT HEIGHT

HW HOT WATER

HZ HERTZ

IBC INTERNATIONAL BUILDING CODE

IC INTERCOM

IES ILLUMINATING

IEEE INSTITUTE OF ELECTRICAL AND

ELECTRONIC ENGINEERS

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCH

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LBS POUNDS

LF LINEAR FEET (FEET)

LRA LOCKED ROTOR AMPS

LS LIFE SAFETY

LT LIGHT

LTG LIGHTING

LV LOW VOLTAGE

ABBREVIATIONS

MAG MAGNETIC

MAN MANUAL

MAT MATERIAL

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MEZZ MEZZANINE

MG MOTOR GENERATOR

MH METAL HALIDE / MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MS MAGNETIC STARTER

MTD MOUNTED

MTG MOUNTING

MTR MOTOR

N NORTH; NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRIC MANUFACTURERS

ASSOCIATION

NESC NATIONAL ELECTRICAL SAFETY CODE

NEUT NEUTRAL

NFPA NATIONAL FIRE PROTECTION

ASSOCIATIONS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

OL OVERLOAD

OS OPTIONAL STANDBY

P PRIMARY

PA PUBLIC ADDRESS

PAR PARALLEL

PB PULL BOX

PE PHOTO ELECTRIC

PF POWER FACTOR

PH PHASE

PIV POST INDICATOR VALVE

PNL PANEL

POC POINT OF CONNECTION

PWR POWER

QTY QUANTITY

R (R) RELOCATE (D)

RAD RADIUS

RECPT RECEPTACLE

REF REFRIGERATOR

RLA RATED LOAD AMPS

RPM REVOLUTIONS PER MINUTE

S SOUTH

SC SECURITY

SCCR SHORT CIRCUIT CURRENT RATING

SD SMOKE DETECTOR

SECT SECTION

SF SUPPLY FAN

SHT SHEET

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPL SPECIAL

SQ SQUARE

STOR STORAGE

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

T THERMOSTAT

TB TERMINAL BOX

TC TIME CLOCK

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

UFC UNIFORM FIRE CODE

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VM VOLTMETER

VOL VOLUME

W WATT, WEST

W/ WITH

W/O WITHOUT

WH WATER HEATER

WHM WATT HOUR METER

WP WEATHERPROOF

X REACTANCE

XFMR TRANSFORMER

XMTR TRANSMITTER

Z IMPEDANCE

& AND

I.E.: THAT IS

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E000

GENERAL NOTES,

ABBREVIATIONS

AND SHEET INDEX

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

ELECTRICAL SHEET INDEX

E000 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX

E001 ELECTRICAL LEGEND

E002 ELECTRICAL POWER - SITE PLAN

E101 ELECTRICAL DEMO - ADMINSTRATION BLDG 2083

E102 ELECTRICAL POWER - ADMINISTRATION BLDG 2083

E201 ELECTRICAL DEMO - GYMNASIUM BLDG 2889

E202 ELECTRICAL POWER - GYMNASIUM BLDG 2889

E601 ADMINISTRATION ONE-LINE DIAGRAM AND PANEL MOUNTING DETAIL

E602 GYM ONE-LINE DIAGRAMS

E701 PANEL SCHEDULES - ADMINISTRATION BLDG 2083

E702 PANEL SCHEDULES - GYMNASIUM BLDG 2889

PROJECT LOCATION - 335 NE Blodgett Rd, Yachats, OR 97498

UNITED STATES DEPARTMENT OF AGRICULTURE

FOREST SERVICE

ELECTRICAL DEFICIENCIES

PACIFIC NORTHWEST REGION

SIUSLAW NATIONAL FOREST

ANGELL JOB CORPS CENTER

LINCOLN COUNTY, OREGON

SYMBOLS LEGEND - GENERAL

DESCRIPTIONSYMBOL

X-XX

N

DRAWING CONSTRUCTION ("FLAG") NOTE

EQUIPMENT IDENTIFIER

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE

PREVIOUS RELEASE)

REVISION REFERENCE

EXISTING TO BE REMOVED (HATCHED)

HEAVY LINEWEIGHT INDICATES NEW WORK

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

POINT OF CONNECTION

DETAIL REFERENCE

DETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

ELEVATION REFERENCE

ELEVATION IDENTIFICATION

NUMBER SHEET WHERE ELEVATION IS DRAWN

SECTION REFERENCE SECTION

IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

NORTH REFERENCE

X

XX.XX

X

XX.XX

X

XX.XX

LIMIT OF DEMOLITION

X-XX-X

T

M

MM

AM

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

TRANSFORMER

AS

POLE-MOUNTED TRANSFORMER

POLE

DELTA

WYE

MEDIUM VOLTAGE CABLE TERMINATOR

LIGHTNING ARRESTORS

SURGE ARRESTORS

NEUTRAL GROUNDING RESISTOR

METER

MICROPROCESSOR CONTROLLED MONITOR

REFER TO SPECIFICATIONS FOR METERING VALUES AND

PROTECTIVE FUNCTIONS

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

INDICATING INSTRUMENT

AM-AMMETER; VM-VOLTMETER; FM-FREQUENCY METER;

kVAR-KILOVAR METER; kWH-KILOWATT HOUR METER;

kWH/D-KILOWATT HOUR DEMAND METER

INSTRUMENT SWITCH

AS-AMMETER SWITCH; VS-VOLTMETER SWITCH;

SS-SYNCHRONIZING SWITCH;

SV-SUPERVISORY (LOCAL-REMOTE) SWITCH

SEPARABLE CONNECTOR

DRAWOUT AC TYPE POWER CIRCUIT BREAKER

SYMBOLS LEGEND - POWER

DESCRIPTION

CIRCUIT BREAKER

ST - INDICATES SHUNT TRIP

BREAKER WITH EXTERNAL GROUND FAULT RELAY AND CT

CIRCUIT BREAKER WITH INTEGRAL GROUND FAULT PROTECTION

MOTOR-OPERATED CIRCUIT BREAKER

SWITCH WITH EXTERNAL GROUND FAULT RELAY AND CT

MOV SURGE PROTECTION

RESISTOR

FUSE

MOTOR THERMAL OVERLOADS - (3) UNLESS OTHERWISE NOTED

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

SOLENOID VALVE

MOTOR-OPERATED VALVE

TERMINAL BLOCK

THERMOSTAT

INDICATING LIGHT - TYPE AS NOTED

A-AMBER; B-BLUE; G-GREEN; R-RED; W-WHITE

BATTERY

CB

A

T

CB ENCLOSED CIRCUIT BREAKER (PLAN VIEW)

xxxA/xP - AMPS/POLESxxxA/xP

ENCLOSED CIRCUIT BREAKER (ONE-LINE DIAGRAM)

xxxA/xP - AMPS/POLES

G G

M G

SV

M

SYMBOL

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

M

C

G

M

M

SD

M

FSD

M

2-POSITION SELECTOR SWITCH

3-POSITION SELECTOR SWITCH HAND-OFF-AUTOMATIC

ON-OFF SELECTOR SWITCH

2-CIRCUIT PUSHBUTTON

PUSHBUTTON SWITCH MOMENTARY CONTACT

EQUIPMENT CONNECTION

GENERATOR

MOTOR CONNECTION

SMOKE DAMPER

FIRE SMOKE DAMPER

STARTER 3-POLE, NEMA SIZE 1 MINIMUM UNLESS NOTED OTHERWISE

COMBINATION STARTER

HP RATED, 3-POLE, NEMA SIZE 1 MINIMUM, UNLESS NOTED

OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED BY

EQUIPMENT MANUFACTURER OR AS NOTED

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

CONTACTOR

RELAY COIL

CR-CONTROL RELAY; TD-TIME DELAY RELAY;

UV-UNDERVOLTAGE RELAY; M-MOTOR

CONTACTOR;

MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS

EQUIPMENT EMERGENCY SHUTDOWN SWITCH

3-POLE UNLESS NOTED OTHERWISE

3-POLE UNLESS NOTED OTHERWISE

CR

SYMBOLS LEGEND - GENERAL

DESCRIPTIONSYMBOL

CONDUIT CONCEALED IN CEILING SPACE OR IN WALL. PROVIDE MINIMUM

3/4" WITH #12 AWG CONDUCTORS AND DEDICATED NEUTRAL EACH

CIRCUIT UNLESS OTHERWISE NOTED ON PLAN. PROVIDE EQUIPMENT

GROUNDING CONDUCTORS SIZED PER NFPA 70.

CONDUIT - CONCEALED IN OR UNDER FLOOR

CONDUIT - ROUTED UNDERGROUND

LOW-VOLTAGE WIRING (CLASS B)

CONDUIT OR CABLE VERTICAL DOWN

CONDUIT OR CABLE VERTICAL UP

CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND

BREAK LINE

CONDUIT SEAL

EXPANSION FITTING

CONDUCTORS - CONNECTED

CONDUCTORS - NOT CONNECTED

JUNCTION BOX

PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE

HANDHOLE

MANHOLE

FLEXIBLE METAL CONDUIT

BRANCH CIRCUIT NUMBERS

PANEL DESIGNATION

HOME RUN TO SOURCE OF SUPPLY

PB

HH

MH

A-1,3,5

UG

LV

J

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

XX

480Y/277V, 3Ø, 4W PANELBOARD

208Y/120V, 3Ø, 4W PANELBOARD

EQUIPMENT CABINET - TYPE AS NOTED

PANELBOARD

TRANSFER SWITCH ( AUTO )

AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)

FEEDER TAG - REFER TO FEEDER SCHEDULE

XXXXXX

SYMBOLS LEGEND - GROUNDING

DESCRIPTIONSYMBOL

GROUND CONNECTION

GROUND ROD

GROUND WELL

AIR TERMINAL

SYMBOLS LEGEND - WIRING DEVICES

DESCRIPTION

SINGLE-POLE WALL SWITCH MOUNT SWITCHES AT 48" AFF. TO TOP, UON.

WALL SWITCH - SUBSCRIPT

SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS

SINGLE SERVICE OR COMBINATION FLUSH FLOOR POKE THRU. REFER TO

FLOOR PLANS FOR DEVICES.

POWER/COMM POLE - FLOOR TO CEILING.

SURFACE MOUNTED FLOOR BOX (PEDESTAL TYPE).

PUSH BUTTON

SIMPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON

NEMA 5-20R, +18" AFF UON

TAMPER RESISTANT, NEMA 5-20R, +18" AFF UON

ISOLATED GROUND, NEMA 5-20R, +18" AFF UON

NEMA 5-20R W/ GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON

SPLIT WIRED, NEMA 5-20R, +18" AFF UON

CONTROLLED, NEMA 5-20R, +18" AFF UON

NEMA 5-20R, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP

DRAWINGS AND ARCHITECTURAL DRAWINGS.

NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE

COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND

ARCHITECTURAL DRAWINGS.

TAMPER RESISTANT, NEMA 5-20R WITH GROUND FAULT CIRCUIT

INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP

DRAWINGS AND ARCHITECTURAL DRAWINGS.

NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18" AFF UON

NEMA 5-20R ON EMERGENCY CIRCUIT MOUNTED ABOVE COUNTER. COORDINATE

WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.

CEILING-MOUNTED, NEMA 5-20R

2 = 2-POLE

3 = 3-WAY

4 = 4-WAY

K = KEYED

LV = LOW-VOLTAGE

OS = OCCUPANCY SENSOR TYPE

OP = OCCUPANCY/PHOTOELECTRIC TYPE

WP = WEATHERPROOF

LOWER CASE LETTER INDICATES SWITCHING GROUP

MOUNT SWITCHES AT +48" AFF. TO TOP, UON. ANY COMBINATION OF

SWITCH TYPES CAN BE USED (IE. 3K = 3-WAY KEYED SWITCH)

SINGLE SERVICE OR COMBINATION FLUSH MOUNTED FLOOR BOX. REFER

TO FLOOR PLANS FOR DEVICES.

SWITCHED RECEPTACLE, NEMA 5-20R, +18" AFF UON

xx

SYMBOL

T T

S S

IG IG

T T

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E001

ELECTRICAL

LEGEND

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

P W R

6" GAS

OH LINES

S.S.

S.S

S .S

S.S.

W A T

WM

IRR

WAT.

W A T

W A T

WV

2892 712

S

D

Y

H

AREA OF WORK

AREA OF WORK

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E002

ELECTRICAL

POWER - SITE

PLAN

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

SHEET NOTES

A. SITE PLAN IS FOR REFERENCE ONLY.

1" = 50'-0"

ELECTRICAL POWER - SITE PLAN

CENTER DIRECTOR

OFFICE

ADMIN OFFICE

RECEPTION

STORAGE

MECH

TOILETXEROX ROOM

COMPUTER

EQUIPMENT

COMMUNICATION'S

MANAGER

MAILING

PURCHASING

TOILET

KITCHEN

CONFERENCE

SUPPORT PERSONEL

SERVICE

OPERATOR SUPPORT

CLERK

STUDENT SUPPORT

SUPERVISOR

A

B

MM

(N)400A 240V

1PH

SERVICE

DISCONNECT

A B

(E) 100A 240V 1PH

DISCONNECTS

(N) 30A 240V 1PH

DISCONNECT

(N) UNI-STRUT

STRUCTURE 1

2 2

7 7

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E101

ELECTRICAL DEMO

- ADMINSTRATION

BLDG 2083

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ELECTRICAL DEMO - ADMINSTRATION BLDG 2083

DEMO SHEET NOTES

A. FOR EQUIPMENT BEING REMOVED OR REPLACED, DE-ENERGIZE THE

EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL. COMPLY WITH OSHA

REQUIREMENTS FOR LOCKING OUT AND TAGGING EQUIPMENT TO PREVENT

INADVERTENT RE-ENERGIZING.

B. VERIFY CIRCUITS, DEVICES, AND EQUIPMENT SCHEDULED FOR REMOVAL TO

ASSURE THAT THEIR REMOVAL WILL NOT ADVERSELY AFFECT ADJACENT

AREAS NOT BEING RENOVATED.

C. MAINTAIN POWER TO ALL CIRCUITS IN AREAS ADJACENT THE CONSTRUCTION

AREA. THIS SHALL INCLUDE ANY CIRCUITS PASSING THROUGH THE

CONSTRUCTION AREA OR CIRCUITS BEING POWERED FROM POWER PANELS

WITHIN THE CONSTRUCTION AREA. EXTEND AND RELOCATE THESE CIRCUITS

AS REQUIRED TO MAINTAIN SERVICE AND TO AVOID INTERFERENCE WITH THE

NEW WORK. NOTIFY THE CONTRACTING OFFICER IN ADVANCE, SHOULD IT BE

NECESSARY TO INTERRUPT POWER TO AREAS ADJACENT TO THIS

CONSTRUCTION AREA.

D. DEMOLITION WORK MUST FOLLOW THE CONSTRUCTION PHASING SEQUENCE

AND MUST BE COORDINATED WITH THE PHASING PLANS, CONSTRUCTION

DRAWINGS, AND WORK OF OTHER TRADES.

E. DEFINITION - THE TERM "CIRCUIT" IN ITS ENTIRETY, SHALL MEAN CONDUIT,

FITTINGS, SUPPORTS, JUNCTION BOXES, AND CONDUCTORS FROM THE

RESPECTIVE PANEL BOARD (POWER SOURCE) TO THE LAST JUNCTION BOX

OR DEVICE, OR THE REMAINING PORTION OF THE CIRCUIT THAT SERVES

EXISTING EQUIPMENT OR AREAS WHICH SHALL REMAIN.

F. VERIFY ALL LIGHTING CIRCUITS WITHIN THE CONSTRUCTION AREA BEFORE

DISCONNECTING POWER. PROVIDE NECESSARY WIRING TO MAINTAIN

LIGHTING IN AREAS ADJACENT TO THIS CONSTRUCTION AREA WHICH WOULD

BE AFFECTED BY THIS DEMOLITION WORK.

G. ALL DEVICES, JUNCTION BOXES, CIRCUIT NUMBERS, EQUIPMENT SIZES, AND

CONDUIT SHOWN ARE FOR REFERENCE ONLY AND MAY NOT INDICATE

CORRECT IDENTIFICATION, SIZES, OR TOTAL QUANTITIES OF ITEMS

SCHEDULED FOR DEMOLITION. VISIT SITE AND FIELD VERIFY THE NUMBER OF

DEVICES WITHIN THE CONSTRUCTION PHASE AREA PRIOR TO BID. REMOVE

ALL DEVICES, EQUIPMENT, MATERIAL, AND CIRCUITS IN THEIR ENTIRETY,

WHICH INTERFERE WITH THE NEW CONSTRUCTION AND NOT SHOWN ON

DRAWINGS AS DIRECTED BY THE CONTRACTING OFFICER.

H. DISPOSAL AND/OR SALVAGING OF MATERIAL AND EQUIPMENT SHALL BE AS

DIRECTED BY THE CONTRACTING OFFICER.

I. FLOOR PLANS NOT TO SCALE.

1. DEMOLISH AND REPLACE OLD STRUCTURE WITH NEW CAST IN CONCRETE

UNI-STRUT STRUCTURE FOR NEW SERVICE EQUIPMENT.

2. DEMOLISH EXISTING CT/METER ENCLOSURES AND REPLACE WITH NEW.

3. DEMOLISH EXISTING 400A DISCONNECTS AND REPLACE WITH NEW.

4. DEMOLISH EXISTING 30A DISCONNECT AND REPLACE WITH NEW.

5. DEMOLISH EXISTING PANEL AND REPLACE WITH NEW 225A 120/240V 1PH 30

SPACE PANEL. BRANCH BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION

BEING REPLACED. INTERCEPT EXISTING FEEDER AND BRANCH CIRCUITS AND

RETERMINATE ON NEW PANELBOARD.

6. NOT USED.

7. FIELD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY

WORK BEING DONE.

FLAG NOTES #

CENTER DIRECTOR

OFFICE

ADMIN OFFICE

RECEPTION

STORAGE

MECH

TOILETXEROX ROOM

COMPUTER

EQUIPMENT

COMMUNICATION'S

MANAGER

MAILING

PURCHASING

TOILET

KITCHEN

CONFERENCE

SUPPORT PERSONEL

SERVICE

OPERATOR SUPPORT

CLERK

STUDENT SUPPORT

SUPERVISOR

A

B

MM

(N)400A 240V

1PH

SERVICE

DISCONNECT

A B

(E) 100A 240V 1PH

DISCONNECTS

(N) 30A 240V 1PH

DISCONNECT

(N) UNI-STRUT

STRUCTURE 1

2 2

7 7

E601

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E102

ELECTRICAL

POWER -

ADMINISTRATION

BLDG 2083

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ELECTRICAL POWER - ADMINSTRATION BLDG 2083

1. REPLACE OLD STRUCTURE WITH NEW CAST IN CONCRETE UNI-STRUT

STRUCTURE FOR NEW SERVICE EQUIPMENT.

2. PROVIDE NEW STAINLESS STEEL CT/METER ENCLOSURES IN EXISTING

LOCATION. INTERCEPT EXISTING FEEDERS.

3. PROVIDE NEW NEMA 3R STAINLESS STEEL 400A DISCONNECTS IN EXISTING

LOCATIONS. INTERCEPT EXISTING FEEDERS.

4. PROVIDE NEW 30A NEMA 3R STAINLESS STEEL DISCONNECT AND INTERCEPT

EXISTING FEEDERS.

5. RE-MOUNT EXISTING 100A DISCONNECTS ONTO NEW UNI-STRUT STRUCTURE.

6. PROVIDE NEW PANEL IN EXISTING LOCATION. 225A 1PH PANEL WITH BRANCH

BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION BEING REPLACED.

INTERCEPT EXISTING FEEDER AND BRANCH CIRCUITS AND RETERMINATE ON

NEW PANELBOARD. PROVIDE NEW PANEL SCHEDULE AND THE APPORPRIATE

LABELS FOR NEW PANEL RE-CONNECTING EXISTING CIRCUITRY.

7. FEILD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY

WORK BEING DONE.

FLAG NOTES #

SHEET NOTES

A. COORDINATE EXACT LOCATION, QUANTITY, & INSTALLATION REQUIREMENTS

OF ALL ELECTRICAL EQUIPMENT & RECEPTACLES INCLUDING MILL &

COUNTER AREAS WITH ARCHITECT/OWNER PRIOR TO ROUGH IN.

B. MAXIMUM NUMBER OF CONDUCTORS IN A CONDUIT SHALL NOT EXCEED 9,

UON.

C. COORDINATE COMPLETE ELECTRICAL INSTALLATIONS SO THAT ALL WORKING

CLEARANCES FOR ALL ELECTRICAL EQUIPMENT ARE PROVIDED AS REQUIRED

PER NEC 110.26. FURTHERMORE, COORDINATE WITH ALL PERTINENT TRADES

SO THAT ELECTRICAL INSTALLATIONS DO NOT PREVENT WORKING AND

MAINTENANCE CLEARANCES TO ANY EQUIPMENT PROVIDED BY OTHERS.

THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT ACCESS PANELS, ACCESS

DOORS, CONTROL PANELS, CONTROL EQUIPMENT/DEVICES, SCREENS, ETC.

D. ALL EQUIPMENT LOCATIONS, CONDUIT ROUTING, EQUIPMENT CONNECTIONS

AND TERMINATION POINTS ARE DIAGRAMMATIC AND SHOWN FOR REFERENCE

ONLY. VERIFY AND COORDINATE EXACT REQUIREMENTS IN FIELD WITH

CONTRACTING OFFICER, AND EQUIPMENT VENDOR.

E. ALL CIRCUITS SHALL HAVE AN INSULATED GROUND WIRE (BOND) SIZED PER

NEC #250.122., #12 MINIMUM GROUND (WIRE NOT SHOWN ON DRAWINGS).

F. COORDINATE ALL CONDUIT SIZES WITH APPLICABLE EQUIPMENT/SYSTEM

VENDORS PRIOR TO BID AND INSTALLATION.

G. CIRCUITS WIRED AS MULTI-WIRE BRANCH CIRCUITS SHALL HAVE

DISCONNECTING MEANS PER NEC 210.4(B).

H. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO

FIELD VERIFY AND ROUTE CONDUIT AND WIRING AS FIELD CONDITIONS

PERMIT. INSTALL PULL/JUNCTION BOXES AS REQUIRED BY NEC.

I. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS

PURPOSE UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT.

THE MARKING SHALL INCLUDE THE IDENTIFICATION OF THE CIRCUIT SOURCE

THAT SUPPLIES THE DISCONNECTING MEANS. THE MARKING SHALL BE OF

SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.

110.22, NEC.

J. FLOOR PLANS NOT TO SCALE.

COMPUTER

LIBRARY

CONTROL / OFFICE

CPP CLASSROOM

WEIGHT/BOXING

ROOM

RECREATION

EQUIPMENT

SHWS

STORAGE

WKILN ROOM

ARTS & CRAFTS

MUSIC ROOM

GAME ROOM

GYMNASIUM

BIKE STORAGE

EXISTING

120/240V, 1PH

JUNCTION BOX

A

C

B

(E) CUSTOMER OWNED

UTILITY POLE

EXISTING

240/480V, 1PH

JUNCTION BOX

2 T

T

7 7

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E201

ELECTRICAL DEMO

- GYMNASIUM

BLDG 2889

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ELECTRICAL DEMO - GYMNASIUM BLDG 2889

DEMO SHEET NOTES

1. EXISTING TRANSFORMER TO BE REMOVED COMPLETE. REMOVE EXISTING

SECONDARY AND PRIMARY CONDUCTORS. SAWCUT BELOW GRADE CONDUIT

AT GRADE AND GROUT SEAL CONDUIT FLUSH TO EXISTING SURFACES.

2. EXISTING SERVICE AND CONDUIT TO BE DEMOLISHED COMPLETE.

3. EXISTING PANEL TO BE REUSED.

4. EXISTING PANEL TO REPLACED.

5. DEMOLISH EXISTING 480V BUSS GUTTER AND HEATER DISCONNECTS.

6. EXISTING 480/120V DRY TYPE TRANSFORMER TO BE REMOVED COMPLETE.

7. EXISTING 240/480V HEATERS TO BE DISCONNECTED, DEMOLISHED AND

REMOVED. TERMINATE CIRCUIT FOR FUTURE USE AT NEAREST J-BOX AND

LABEL WITH CIRCUIT INFORMATION.

8. EXISTING MODINE HER150 HEATER TO BE DISCONNECTED, CARFULLY

REMOVED, AND DELIVERED TO CENTER MAINTENANCE STAFF STORAGE

LOCATION.

9. CONTRACTOR TO DEMOLISH EXISTING 100KVA POLE MOUNTED

TRANSFORMER.

10. EXISTING POLE MOUNTED TRANSFORMER ON GRADE TO BE REMOVED.

11. EXISTING FIBERGLASS ENCLOSURE.

FLAG NOTES #

A. FOR EQUIPMENT BEING REMOVED OR REPLACED, DE-ENERGIZE THE

EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL. COMPLY WITH OSHA

REQUIREMENTS FOR LOCKING OUT AND TAGGING EQUIPMENT TO PREVENT

INADVERTENT RE-ENERGIZING.

B. VERIFY CIRCUITS, DEVICES, AND EQUIPMENT SCHEDULED FOR REMOVAL TO

ASSURE THAT THEIR REMOVAL WILL NOT ADVERSELY AFFECT ADJACENT

AREAS NOT BEING RENOVATED.

C. MAINTAIN POWER TO ALL CIRCUITS IN AREAS ADJACENT THE CONSTRUCTION

AREA. THIS SHALL INCLUDE ANY CIRCUITS PASSING THROUGH THE

CONSTRUCTION AREA OR CIRCUITS BEING POWERED FROM POWER PANELS

WITHIN THE CONSTRUCTION AREA. EXTEND AND RELOCATE THESE CIRCUITS

AS REQUIRED TO MAINTAIN SERVICE AND TO AVOID INTERFERENCE WITH THE

NEW WORK. NOTIFY THE CONTRACTING OFFICER IN ADVANCE, SHOULD IT BE

NECESSARY TO INTERRUPT POWER TO AREAS ADJACENT TO THIS

CONSTRUCTION AREA.

D. DEMOLITION WORK MUST FOLLOW THE CONSTRUCTION PHASING SEQUENCE

AND MUST BE COORDINATED WITH THE PHASING PLANS, CONSTRUCTION

DRAWINGS, AND WORK OF OTHER TRADES.

E. DEFINITION - THE TERM "CIRCUIT" IN ITS ENTIRETY, SHALL MEAN CONDUIT,

FITTINGS, SUPPORTS, JUNCTION BOXES, AND CONDUCTORS FROM THE

RESPECTIVE PANEL BOARD (POWER SOURCE) TO THE LAST JUNCTION BOX

OR DEVICE, OR THE REMAINING PORTION OF THE CIRCUIT THAT SERVES

EXISTING EQUIPMENT OR AREAS WHICH SHALL REMAIN.

F. VERIFY ALL LIGHTING CIRCUITS WITHIN THE CONSTRUCTION AREA BEFORE

DISCONNECTING POWER. PROVIDE NECESSARY WIRING TO MAINTAIN

LIGHTING IN AREAS ADJACENT TO THIS CONSTRUCTION AREA WHICH WOULD

BE AFFECTED BY THIS DEMOLITION WORK.

G. ALL DEVICES, JUNCTION BOXES, CIRCUIT NUMBERS, EQUIPMENT SIZES, AND

CONDUIT SHOWN ARE FOR REFERENCE ONLY AND MAY NOT INDICATE

CORRECT IDENTIFICATION, SIZES, OR TOTAL QUANTITIES OF ITEMS

SCHEDULED FOR DEMOLITION. VISIT SITE AND FIELD VERIFY THE NUMBER OF

DEVICES WITHIN THE CONSTRUCTION PHASE AREA PRIOR TO BID. REMOVE

ALL DEVICES, EQUIPMENT, MATERIAL, AND CIRCUITS IN THEIR ENTIRETY,

WHICH INTERFERE WITH THE NEW CONSTRUCTION AND NOT SHOWN ON

DRAWINGS AS DIRECTED BY THE CONTRACTING OFFICER.

H. DISPOSAL AND/OR SALVAGING OF MATERIAL AND EQUIPMENT SHALL BE AS

DIRECTED BY THE CONTRACTING OFFICER.

I. FLOOR PLANS NOT TO SCALE.

T

COMPUTER

LIBRARY

CONTROL / OFFICE

CPP CLASSROOM

WEIGHT/BOXING

ROOM

RECREATION

EQUIPMENT

SHWS

STORAGE

WKILN ROOM

ARTS & CRAFTSMUSIC ROOM

GAME ROOM

GYMNASIUM

BIKE STORAGE

2DP

600A 240V 1PH

SERVICE

DISCONNECT

(N) 150KVA OIL FILLED

12470/240V, 1PH PAD

MOUNTED

TRANSFORMER

A C

B

(E) CUSTOMER OWNED

UTILITY POLE

T

T

T

B-26,28

B-27,29

A-25,27

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E202

ELECTRICAL

POWER -

GYMNASIUM BLDG

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ELECTRICAL POWER - GYMNASIUM BLDG 2889

1. CONTRACTOR TO PROVIDE NEW CONCRETE PAD MOUNTED 150KVA

TRANSFORMER TO FEED NEW 600A SERVICE.

2. PROVIDE NEW 600A 1PH NEMA 3R SERVICE DISCONNECT FOR NEW SERVICE.

3. PROVIDE NEW 600A 1PH DISTRIBUTION PANEL TO BACK FEED EXISTING

PANELS FROM EXISTING SERVICES 1 &2 AFTER DEMO PHASE.

4. PROVIDE NEW 400A 1PH 42 CIRCUIT PANEL TO REPLACE EXISTING PANEL IN

SE CORNER OF GYM UTILIZING EXISTING FEEDER.

5. PROVIDE NEW FEEDER FOR EXISTING 400A 1PH PANEL IN WEIGHT ROOM.

6. RE-FEED EXISTING PANEL TO NEW DISTRIBUTION PANEL 2DP.

7. PROVIDE NEW DOOR TO EXISTING 400A 1PH PANEL. MATCH MAKE AND

MODEL.

8. NOT USED.

9. FIELD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY

WORK BEING DONE.

10. NEW ELECTRIC HEATERS TO BE INSTALLED WITH LOW VOLTAGE KIT, LOW

VOLTAGE THERMOSTATS, AND PROTECTIVE CAGES FOR HEATERS AND

THERMOSTATS.

FLAG NOTES #

SHEET NOTES

A. COORDINATE EXACT LOCATION, QUANTITY, & INSTALLATION REQUIREMENTS

OF ALL ELECTRICAL EQUIPMENT & RECEPTACLES INCLUDING MILL &

COUNTER AREAS WITH ARCHITECT/OWNER PRIOR TO ROUGH IN.

B. MAXIMUM NUMBER OF CONDUCTORS IN A CONDUIT SHALL NOT EXCEED 9,

UON.

C. COORDINATE COMPLETE ELECTRICAL INSTALLATIONS SO THAT ALL WORKING

CLEARANCES FOR ALL ELECTRICAL EQUIPMENT ARE PROVIDED AS REQUIRED

PER NEC 110.26. FURTHERMORE, COORDINATE WITH ALL PERTINENT TRADES

SO THAT ELECTRICAL INSTALLATIONS DO NOT PREVENT WORKING AND

MAINTENANCE CLEARANCES TO ANY EQUIPMENT PROVIDED BY OTHERS.

THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT ACCESS PANELS, ACCESS

DOORS, CONTROL PANELS, CONTROL EQUIPMENT/DEVICES, SCREENS, ETC.

D. ALL EQUIPMENT LOCATIONS, CONDUIT ROUTING, EQUIPMENT CONNECTIONS

AND TERMINATION POINTS ARE DIAGRAMMATIC AND SHOWN FOR REFERENCE

ONLY. VERIFY AND COORDINATE EXACT REQUIREMENTS IN FIELD WITH

CONTRACTING OFFICER, AND EQUIPMENT VENDOR.

E. ALL CIRCUITS SHALL HAVE AN INSULATED GROUND WIRE (BOND) SIZED PER

NEC #250.122., #12 MINIMUM GROUND (WIRE NOT SHOWN ON DRAWINGS).

F. COORDINATE ALL CONDUIT SIZES WITH APPLICABLE EQUIPMENT/SYSTEM

VENDORS PRIOR TO BID AND INSTALLATION.

G. CIRCUITS WIRED AS MULTI-WIRE BRANCH CIRCUITS SHALL HAVE

DISCONNECTING MEANS PER NEC 210.4(B).

H. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO

FIELD VERIFY AND ROUTE CONDUIT AND WIRING AS FIELD CONDITIONS

PERMIT. INSTALL PULL/JUNCTION BOXES AS REQUIRED BY NEC.

I. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS

PURPOSE UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT.

THE MARKING SHALL INCLUDE THE IDENTIFICATION OF THE CIRCUIT SOURCE

THAT SUPPLIES THE DISCONNECTING MEANS. THE MARKING SHALL BE OF

SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.

110.22, NEC.

J. FLOOR PLANS NOT TO SCALE.

M M

(N) 200A 120/240V

CT CAN

A

(N) 200A 120/240V

CT CAN

B

(N) 400A 120/240V

SERVICE

DISCONNECT

(N) 400A 120/240V

SERVICE

DISCONNECT

(E)100A 120/240V

DISCONNECT

(N)100A 120/240V

DISCONNECT

(N) 30A 120/240V

DISCONNECT

NEMA 3R

EXTERIOR

NEMA 1

INTERIOR

1 1

ADMINISTRATION

BUILDING 2083

TO

UTILITY

5 5 5

3 3 4

(N)

225A

1PH

120/240V

(N)

225A

1PH

120/240V

5 5

6 6

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E601

ADMINISTRATION

ONE-LINE DIAGRAM

AND PANEL

MOUNTING DETAIL

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ANGELL JC ADMINISTRATION 2083 ONE-LINE DIAGRAM

1. THE EXISTING BELOW GRADE FEEDERS TO BE INTERCEPTED AND RE-

TERMINATED ONTO NEW SERVICE DISCONNECTS.

2. UNI-STRUT STRUCTURE ANCHORED IN CONCRETE TO REPLACE EXISTING

SUPPORT STRUCTURE.

3. EXISTING 100A DISCONNECTS TO BE REMOUNTED ONTO NEW STUCTURE.

4. NEW 30A 1PH DISCONNECT TO REPLACE EXISTING. REMOUNT INTO NEW

STRUCTURE.

5. RE-CONNECT EXISTING FEEDERS.

6. CONFIRM LOCATIONS AND REPLACE EXISTING INTERIOR PANELBOARDS WITH

225A 1PH 120/240V WITH BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION

BEING REPLACED.

FLAG NOTES #

EXTERIOR CT, DISCONNECT SUPOORT DETAIL

N.T.S.

36"

THREADED END

CAPS

(TYPICAL OF 2)

1/2" DIA. CADMIUM

PLATED BOLTS WITH

FLAT WASHERS AND

SILICON SEALER (MIN.

OF 4)

2 1/2" STANILESS

STEEL POSTS

FINISHED

GRADE

CONCRETE

FOOTING

WIDTH

DISCONNECT

OR CT

2"

36"

2"

STAINLESS STEEL UNI-STRUT,

SIZE PER STRUCTURAL

ENGINEER DESIGN, TYPICAL

CT OR

DISCONNECT

CT OR

DISCONNECT

CONTRACTOR TO ENGAGE LICENSED STRUCTURAL ENGINEER IN THE STATE OF OREGON FOR DESIGN OF SUPPORT SYSTEM. THIS DETAIL IS CONVEY DESIGN INTENT AND IS NOT TO BE USED FOR INSTALLATION.

(E) 400A 120/240V

SERVICE

DISCONNECTSERVICE #1

(E)

400A

1PH

120/240V

(E)

400A

1PH

120/240V

NORTH WALL

GYM

SE CORNER

GYM

SERVICE #2

(E) CLPUD

240/480VXFMR

(E) BUSS GUTTER

(E)

200A

1PH

120/240V

(E) (E) (E) (E) (E) (E) (E)

HEATERS HEATERS HEATERS HEATERS HEATERS HEATERS

(E) 37.5KVA

XFMR

(E) 100KVA

120/240v

XFMR

(N) 2DP

600A

1PH

120/240V

(N) 150KVA, 12.47KV/240V, 1PH

OIL FILLED PAD MOUNT XFMR

(N) 600A 120/240V

NEMA 3R SERVICE

DISCONNECT

(N)

400A

1PH

120/240V

REMOVE ALL (5) 480V HEATERS,

REPLACE WITH 3, 10 KW 240V, 1PH

HEATERS OF EQUAL KW OUTPUT.

SEE PANEL AND EQUIPMENT

SCHEDULES

NEMA 3R

EXTERIOR

NEMA 1

INTERIOR

GYM

BUILDING 2083

4 4 4 4 4 4

SE CORNER

GYM

BOXING

ROOM

(E)

400A

1PH

120/240V

EXISTING 12470V OVERHEAD

TRANSMISSION LINES

EXISTING UTILITY POLE

FIBERGLASS

ENCLOSURE

NEMA 3R

EXTERIOR

NEMA 1

INTERIOR

EXTERIOR

EXTERIOR

(3) #8 MV-105 COPPER WITH

CONCENTRIC SHIELD IN 3"C.

6'X6'X4" CONCRETE PAD

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E602

GYM ONE-LINE

DIAGRAMS

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

N.T.S.

ANGELL JC GYM 2889 ONE-LINE DIAGRAM

1. DEMO EXISTING 400A DISCONNECT AND FEEDER.

2. NEW 600A 1PH 120/240V PANEL TO BE LOCATED ON THE SOUTHSIDE OF THE

CPP CLASSROOM WALL. BACK FEED ALL 120/240V PANELS ASSOCIATED WITH

SERVICE 1&2.

3. DEMO EXISTING BUSS GUTTER AND ALL 240/480V EQUIPMENT, AND FEEDERS

BACK TO THE PAD MOUNTED TRANSFORMER FEEDING SERVICE #2.

4. EXISTING 240/480V HEATERS TO BE DEMOLISHED. NEW 120/240V HEATERS TO

BE INSTALLED. SEE DEMO SHEET E201 FOR FURTHER CLARIFICATION.

5. DEMO EXISTING GROUND MOUNTED (POLE POTTED) 100 KVA TRANSFORMER

IN EXISTING FIBERGLASS ENCLOSURE. REMOVE ALL EXISTING CONDUCTORS

IN EXISTING RACEWAYS. RACEWAYS TO REMAIN.

6. CONTRACTOR TO PROVIDE AND INSTALL NEW 150KVA TRANSFORMER

COMBINING EXISTING SERIVICES 1 AND 2 INTO A SINGLE SERVICE.

7. REPLACE EXISTING DOOR WITH NEW.

8. RE-USE EXISTING FEEDER FOR SE GYM PANEL.

9. DEMO EXISTING SE GYM PANEL AND REPLACE WITH NEW 400A 1PH 120/240V

42 CIRCUIT PANELBOARD UTILIZING EXISTING FEEDER.

10. PROVIDE NEW FEEDER TO EXISTING BOXING ROOM PANEL OUT OF NEW 600A

SERVICE.

11. PROVIDE NEW BELOW GRADE FEEDER TO EXISTING CUSTOMER OWNED

UTILITY POLE PROVIDE FUSIBLE DISCONNECT LINK WITH HOT STICK

PROVISION FOR EACH CONDUCTOR TAPPED TO OVER HEAD TRANSMISSION

LINES.

FLAG NOTES #

600N 2 3" 3#350, #350N #1

600 2 3" 3#350 #1

400N 2 2" 2#3/0, #3/0N #2

400 2 2" 2#3/0 #2

380N 1 3" 2#500, #500N #2

380 1 3" 2#500 #2

350N 1 3" 2#500, #500N #2

350 1 3" 2#500 #2

300N 1 3" 2#350, #350N #4

300 1 3" 2#350 #4

250N 1 2-1/2" 2#250, #250N #4

250 1 2-1/2" 2#250 #4

225N 1 2" 2#4/0, #4/0N #4

225 1 2" 2#4/0 #4

200N 1 2" 2#3/0, #3/0N #6

200 1 2" 2#3/0 #6

175N 1 2" 2#2/0, #2/0N #6

175 1 2" 2#2/0 #6

150N 1 2" 2#1/0, #1/0N #6

150 1 2" 2#1/0 #6

125N 1 1-1/2" 2#1, #1N #6

125 1 1-1/2" 2#1 #6

100N 1 1-1/2" 2#1, #1N #8

100 1 1-1/2" 2#1 #8

90N 1 1-1/4" 2#2, #2N #8

90 1 1-1/4" 2#2 #8

80N 1 1-1/4" 2#2, #2N #8

80 1 1-1/4" 2#2 #8

CODE

PARALLEL

SETS

CONDUIT SIZE CONDUCTOR SIZE GROUND CONDUCTOR

CONDUCTORS #1 AWG OR SMALLER ARE SIZED BASED ON 60 DEGREE TABLES

COPPER CONDUCTORS

1-PHASE FEEDER SCHEDULE

1) NEMA-3R FUSED DISCONNECT SWITCH.

2) PROVIDE MOTOR-RATED SWITCH, WITH WP COVER, AS DISCONNECT.

3) PROVIDE MOTOR-RATED SWITCH AS DISCONNECT.

4) EXHAUST FAN SHARES CIRCUIT WITH OTHER EXHAUST FANS.

5) WATER HEATER SHARES CIRCUIT WITH OTHER WATER HEATER.

FLA:

HP:

KVA:

KW:

MCA:

MOCP:

OFOI:

OFCI:

W:

WP:

VA:

FULL LOAD AMPERES

HORSEPOWER

KILOVOLT-AMPERES

KILOWATTS

MINIMUM CIRCUIT AMPACITY

MAXIMUM OVERCURRENT PROTECTIVE DEVICE

OWNER-FURNISHED, OWNER-INSTALLED

OWNER-FURNISHED, CONTRACTOR-INSTALLED

WATTS

WEATHERPROOF

VOLT-AMPERE

1) DISCONNECTS ARE SHOWN AS FRAME RATING / FUSE SIZE.

2) PROVIDE DUCT SMOKE DETECTORS FOR ALL HVAC UNITS SUPPLYING 2,000 CFM

OR MORE. COORDINATE WITH FIRE ALARM CONTRACTOR.

3) ALL 120V, 15A AND 20A RECEPTACLES AND/OR EQUIPMENT CIRCUITS SHALL BE

GFCI PROTECTED PER NOTE 2, UNLESS NOTED OTERWISE/

SCHEDULE NOTES: ABBREVIATION: SCHEDULE GENERAL NOTES

MECHANICAL EQUIPMENT CONNECTION SCHEDULE

NO. EQUIPMENT DESCRIPTION LOCATION KW MCA MOCP VOLTAGE

PHASES

CONDUIT

SIZE

WIRE SIZE DISC/FUSE/POLES CIRCUIT

NUMBER

NOTES

1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 A - 25,27

1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 B - 27,29

1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 B - 26,28

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E701

PANEL SCHEDULES

- ADMINISTRATION

BLDG 2083

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 0 A 0 A

Total Load: 0 VA 0 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 -- -- -- -- 0 VA 0 VA -- -- -- -- 24

21 (E) OFFICE FURNACE 20 A 2 0 VA 0 VA 2 100 A (E) NEW PANEL 22

19 -- -- -- -- 0 VA 0 VA -- -- -- -- 20

17 (E) OFFICE FURNACE 30 A 2 0 VA 0 VA 2 100 A (E) "MAIN" SUB-PANEL 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8

5 (E) FURNACE #2 90 A 2 0 VA 0 VA 2 30 A SPARE 6

3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4

1 (E) FURNACE #1 90 A 2 0 VA 0 VA 2 100 A (E) BUILDING MAIN 2

C K T

# ITEM

N O T E

A M P S

P O L E A B

P O L E

A M P S

N O T

E ITEM

C K T

MCB

225 A

A.I.C. RATING:

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: SURFACE

MECH TYPE: BOLT-ON

LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE

NEW PANEL A SCHEDULE

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 0 A 0 A

Total Load: 0 VA 0 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) AO-CD LIGHTS 20

17 (E) PEPSI MACHIE, MICROWAVE, FRIDGE (CONF... 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - HALL,COPYRM, RECPT, PURCH, WOME... 18

15 (E) STUDENT RECEPTIONIST 20 A 1 0 VA 0 VA 1 20 A (E) HALL LIGHTS - EAST HALLWAY 16

13 (E) COPIER, EXIT SIGN 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - SSS, PERSONNEL, RECORDS 14

11 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - FURNACE, FORMS, COFFEE ROOM 12

9 (E) REGULAR OUTLETS: AO, CD, RECPTION 20 A 1 0 VA 0 VA 1 20 A (E) UNKNOWN TBD 10

7 (E) BATHROOMS 20 A 1 0 VA 0 VA 1 20 A (E) OUTSIDE LIGHTS 8

5 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) MAILROOM REG OUTLETS 6

3 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) UNKNOWN TBD 4

1 (E) WATERHEATER DISCONNECTED? 20 A 1 0 VA 0 VA 1 20 A (E) WATERHEATER DISCONNECTED? 2

C K T

# ITEM

N O T E

A M P S

P O L E A B

P O L E

A M P S

N O T

E ITEM

C K T

MCB

225 A

A.I.C. RATING:

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: RECESSED

RECEPTION TYPE: BOLT-ON

LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE

PANEL B SCHEDULE

SAZAN #

Drawn:

Checked:

Date:

Contents:

Project:

Sheet Number:

# DESCRIPTION DATE

111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204

Tel 503.416.2400 Fax 503.416.2087

4/ 1/

:3

5:

P M

4/ 1/

:3

5:

P M

E702

PANEL SCHEDULES

- GYMNASIUM

BLDG 2889

04/02/2025

D45-24001

Checker

Author

100% CD

UNITED STATES

DEPARTMENT

OF

AGRICULTURE

ANGELL JOB CORPS

CIVILIAN

CONSERVATION

CENTER

D45-24001

335 NE BLODGETT

ROAD

YACHATS, OR 97498

Notes:

Total Est. Demand Current: 42 A

Total Conn. Current: 42 A

Total Est. Demand: 10000 VA

Total Conn. Load: 10000 VA

Heating 10000 VA 100.00% 10000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 42 A 42 A

Total Load: 5000 VA 5000 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 -- -- -- -- 5000 VA 0 VA 1 20 A SPARE 28

25 GYM HEATER 60 A 2 5000 VA 0 VA 1 20 A SPARE 26

23 (E) PLUGS - TV ROOM 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 24

21 (E) GAME ROOM + OUTSIDE LIGHT 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 22

19 (E) INTERNET BOOSTER 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS - TV & POOL ROOMS 20

17 (E) PLUGS 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS & PLUGS W WALL 18

15 (E) LIGHTS 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS - WEST & NORTH 16

13 (E) PLUGS 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 14

11 -- -- -- -- 0 VA 0 VA -- -- -- -- 12

9 (E) PIZZA OVEN 60 A 2 0 VA 0 VA 2 20 A (E) OFFICE HEAT 10

7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8

5 (E) HEAT - SW MULTIPURPOSE ROOM 30 A 2 0 VA 0 VA 2 30 A SPARE 6

3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4

1 (E) HEAT 30 A 2 0 VA 0 VA 2 30 A (E) HEAT - NE MULTIPURPOSE ROOM 2

C K T

# ITEM

N O T E

A M P S

P O L E A B

P O L E

A M P S

N O T

E ITEM

C K T

MCB

400 A

A.I.C. RATING:

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: RECESSED

WEIGHT/BOXING ROOM TYPE: BOLT-ON

LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE

PANEL A SCHEDULE

Notes:

Total Est. Demand Current: 83 A

Total Conn. Current: 83 A

Total Est. Demand: 20000 VA

Total Conn. Load: 20000 VA

Heating 20000 VA 100.00% 20000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 83 A 83 A

Total Load: 10000 VA 10000 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 -- -- -- -- 5000 VA 0 VA 1 20 A SPARE 30

27 GYM HEATER 60 A 2 5000 VA 5000 VA -- -- -- -- 28

25 (E) CHLORIDE CHARGER 20 A 1 0 VA 5000 VA 2 60 A GYM HEATER 26

23 (E) OUTLETS; ARTS STOR. 20 A 1 0 VA 0 VA 1 20 A (E) OUTLETS; BAND 24

21 (E) OUTLETS; BAND 20 A 1 0 VA 0 VA 1 20 A (E) OUTLETS; ARTS STOR. 22

19 (E) LITES; ARTS SOUTH 20 A 1 0 VA 0 VA 1 20 A (E) LITES; KILN. DRESS. TOIL. SHOWER 20

17 (E) LITES; ARTS NORTH 20 A 1 0 VA 0 VA 1 20 A (E) LITES & OUTSIDE FANS 18

15 (E) LITES; WEST RM 20 A 1 0 VA 0 VA -- -- -- -- 16

13 (E) OUTLETS; TOIL. KILN. DRESS. 20 A 1 0 VA 0 VA 2 60 A (E) KILN 14

11 -- -- -- -- 0 VA 0 VA -- -- -- -- 12

9 (E) HEATER 20 A 2 0 VA 0 VA 2 60 A (E) KILN 10

7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8

5 (E) HEATER 20 A 2 0 VA 0 VA 2 20 A (E) HEATER 6

3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4

1 (E) HEATER 30 A 2 0 VA 0 VA 2 30 A (E) HEATER 2

C K T

# ITEM

N O T E

A M P S

P O L E A B

P O L E

A M P S

N O T

E ITEM

C K T

MCB

400 A

A.I.C. RATING:

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: RECESSED

GYMNASIUM TYPE: BOLT-ON

LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE

PANEL B SCHEDULE

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 0 A 0 A

Total Load: 0 VA 0 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 30

27 (E) SCOREBOARD #1 20 A 1 0 VA 0 VA 1 20 A (E) SPARE CIRCUIT TO GYM FLOOR ATTIC J-BOX 28

25 (E) FIRE ALARM 20 A 1 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 26

23 -- -- -- -- 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 24

21 (E) OVEN 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 22

19 -- -- -- -- 0 VA 0 VA 1 20 A (E) WORKOUT ROOM LIGHTS 20

17 SPARE 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 18

15 -- -- -- -- 0 VA 0 VA 1 20 A (E) WING LIGHTS POOL AREA 16

13 (E) MEN'S ROOM PLUGS 30 A 2 0 VA 0 VA 1 20 A (E) POOL AREA 14

11 -- -- -- -- 0 VA 0 VA 1 20 A (E) EXIT LIGHTS 12

9 (E) DRYER MEN'S BATHROOM 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLR POOL GAME AREA 10

7 -- -- -- -- 0 VA 0 VA 1 20 A (E) SCOREBOARD #2 8

5 (E) UNIT HEAT - DRESSING 30 A 2 0 VA 0 VA 1 20 A (E) LIGHTS - SHOWER, TOILET, LOCKER 6

3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4

1 (E) SPARE 30 A 2 0 VA 0 VA 2 20 A (E) UNIT HEAT - TOILET 2

C K T

# ITEM

N O T E

A M P S

P O L E A B

P O L E

A M P S

N O T

E ITEM

C K T

MCB

400 A

A.I.C. RATING:

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: RECESSED

WEIGHT/BOXING ROOM TYPE: BOLT-ON

LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE

PANEL C SCHEDULE

Sheets
E000 - GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E001 - ELECTRICAL LEGEND
E002 - ELECTRICAL POWER - SITE PLAN
E101 - ELECTRICAL DEMO - ADMINSTRATION BLDG 2083
E102 - ELECTRICAL POWER - ADMINISTRATION BLDG 2083
E201 - ELECTRICAL DEMO - GYMNASIUM BLDG 2889
E202 - ELECTRICAL POWER - GYMNASIUM BLDG 2889
E601 - ADMINISTRATION ONE-LINE DIAGRAM AND PANEL MOUNTING DETAIL
E602 - GYM ONE-LINE DIAGRAMS
E701 - PANEL SCHEDULES - ADMINISTRATION BLDG 2083
E702 - PANEL SCHEDULES - GYMNASIUM BLDG 2889

File details come from the government source that posted it. Updated .