Attachment 2 - 250401 Angell JC Mult. Build Elec_PERMIT SET.pdf
PDF 2 MB Posted
- Attached to
- Angell Electrical Deficiencies
- Solicitation number
- 12441926Q0019
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a set of electrical construction plans and specifications for the Angell Job Corps Civilian Conservation Center located at 335 NE Blodgett Road, Yachats, Oregon 97498. The project involves electrical work at two main buildings: Building 2083 (Administration Building) and Building 2889 (Gymnasium Building).
The specifications establish general requirements for electrical demolition and power installation work, including field verification of existing conditions, disconnection and relocation of obstructing equipment, removal of abandoned wiring, and coordination with existing systems. All new electrical equipment must be connected into existing systems, with power wiring concealed above accessible ceilings or in walls, and exposed wiring installed in approved surface metal raceway where indicated. Contractors must verify integrity of existing conduits before reuse and provide new raceways where necessary. All wall-mounted devices such as switches, receptacles, and outlets require field coordination with fixed casework, doors, and architectural elements. Fire-rated penetrations through walls, floors, and ceilings must be sealed appropriately. For the Administration Building, the project includes a new 400-amp 240V single-phase service disconnect with existing 100-amp and 30-amp disconnects, along with new panelboards and branch circuits. The Gymnasium Building requires installation of a 600-amp 240V single-phase service disconnect and a 150KVA oil-filled pad-mounted transformer (12.47KV/240V), with replacement of existing 480V heaters with 10KW 240V single-phase heaters and associated branch circuitry. Detailed one-line diagrams, equipment schedules, panel schedules, and exterior support details are provided for both buildings, specifying conductor sizes, conduit requirements, overcurrent protection, and grounding in accordance with NEC Article 250 and applicable standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. THE EXISTING CONDITIONS SHOWN WERE TAKEN FROM AVAILABLE RECORD INFORMATION. FIELD VERIFY ALL CONDITIONS THAT MAY AFFECT CONSTRUCTION. IF ANY DISCREPANCIES ARE DISCOVERED, NOTIFY THE
CONTRACTING OFFICER IN WRITING AND REQUEST DIRECTION PRIOR TO COMMENCING WORK.
B. ANY AND ALL EQUIPMENT HAVING ELECTRICAL CONNECTIONS THAT REQUIRE DISCONNECTING AND/OR RE- CONNECTING AS A RESULT OF CONSTRUCTION SHALL BE INCLUDED AS A PART OF THIS CONTRACT.
C. THE EXISTING ELECTRICAL DEVICES, CONDUIT, AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED UNLESS OTHERWISE NOTED. LOCATION IS TO BE AS CLOSE AS
POSSIBLE TO THE ORIGINAL LOCATION.
D. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT TO REMAIN IN SERVICE SHALL BE REMOVED BACK TO THE FIRST ACCESSIBLE JUNCTION BOX WHERE IT SHALL BE TIED OFF AND LABELED AS SPARE WITH CIRCUIT
NUMBER INDICATED.
E. REMOVE ALL ABANDONED WIRE AND CABLING.
DEMOLITION NOTES
1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN
SHEETS.
2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE
NEUTRAL CONDUCTORS.
3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED IN
ACCORDANCE WITH NFPA 70, ARTICLE 250.
4. ALL ELECTRICAL EQUIPMENT IN PORTIONS OF THE BUILDING NOT BEING REMODELED SHALL BE LEFT IN
WORKING CONDITION. RESTORE ANY CIRCUITS INTERRUPTED.
5. ALL NEW LIGHT FIXTURES AND FIXTURES IN AREAS ADJACENT DEMOLITION & CONSTRUCTION AREAS ARE TO BE
THOROUGHLY CLEANED IMMEDIATELY PRIOR TO NOTICE OF SUBSTANTIAL COMPLETION.
6. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE
BASE BID:
A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE
EXISTING SYSTEM AS REQUIRED.
B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN
WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE
INDICATED.
C. WHERE EXISTING CONDUITS ARE INDICATED FOR REUSE, FIELD VERIFY INTEGRITY OF REUSED RACEWAYS PRIOR TO INSTALLATION OF CONDUCTORS. PROVIDE NEW RACEWAYS WHERE EXISTING ARE UNUSABLE.
D. LOCATIONS OF ALL WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLES, AND OUTLETS ARE
SHOWN DIAGRAMMATICALLY. DETERMINE EXACT DEVICE LOCATIONS IN FIELD; COORDINATE
INSTALLATIONS WITH FIXED CASEWORK, DOORS AND RELITES.
E. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING
OF SURFACES PENETRATED.
GENERAL NOTES
@ AT
A/C AIR CONDITIONING(ER)
A (AMP) AMPERE
AC ABOVE COUNTER, ALTERNATING CURRENT
ADJ ADJUSTABLE
ADJT ADJACENT
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
ANN ANNUNCIATOR
ARCH ARCHITECT; ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BKBD BACKBOARD
BKR BREAKER
BLDG BUILDING
C CONDUIT
CAP CAPACITY
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CLR CLEAR
COL COLUMN
COM COMMUNICATION
CPS CYCLES PER SECOND
CT CURRENT TRANSFORMER
CTL CONTROL
CU COPPER
DC DIRECT CURRENT
DISC SW DISCONNECT SWITCH
DISC DISCONNECT
DN DOWN
DWG DRAWING
E EXIST, EAST
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING CONDUCTOR
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENTR ENTRANCE
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
EQUIP/EQP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXT EXTERIOR
EXIST EXISTING
F FAHRENHEIT/FUSE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FD FIRE DAMPER
FDR FEEDER
FIXT FIXTURE
FLA FULL LOAD AMPS
FSD FIRE/SMOKE DAMPER
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
H HEIGHT
HID HIGH INTENSITY DISCHARGE
HOA HAND OFF AUTOMATIC
HOR HORIZONTAL
HP HORSEPOWER
HR HOUR
HT HEIGHT
HW HOT WATER
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
IES ILLUMINATING
IEEE INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN INCH
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILLS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LBS POUNDS
LF LINEAR FEET (FEET)
LRA LOCKED ROTOR AMPS
LS LIFE SAFETY
LT LIGHT
LTG LIGHTING
LV LOW VOLTAGE
ABBREVIATIONS
MAG MAGNETIC
MAN MANUAL
MAT MATERIAL
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MECH MECHANICAL
MEZZ MEZZANINE
MG MOTOR GENERATOR
MH METAL HALIDE / MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MS MAGNETIC STARTER
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
N NORTH; NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRIC MANUFACTURERS
ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NEUT NEUTRAL
NFPA NATIONAL FIRE PROTECTION
ASSOCIATIONS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OL OVERLOAD
OS OPTIONAL STANDBY
P PRIMARY
PA PUBLIC ADDRESS
PAR PARALLEL
PB PULL BOX
PE PHOTO ELECTRIC
PF POWER FACTOR
PH PHASE
PIV POST INDICATOR VALVE
PNL PANEL
POC POINT OF CONNECTION
PWR POWER
QTY QUANTITY
R (R) RELOCATE (D)
RAD RADIUS
RECPT RECEPTACLE
REF REFRIGERATOR
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S SOUTH
SC SECURITY
SCCR SHORT CIRCUIT CURRENT RATING
SD SMOKE DETECTOR
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPL SPECIAL
SQ SQUARE
STOR STORAGE
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
T THERMOSTAT
TB TERMINAL BOX
TC TIME CLOCK
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
UFC UNIFORM FIRE CODE
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UV UNIT VENTILATOR
V VOLT
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VM VOLTMETER
VOL VOLUME
W WATT, WEST
W/ WITH
W/O WITHOUT
WH WATER HEATER
WHM WATT HOUR METER
WP WEATHERPROOF
X REACTANCE
XFMR TRANSFORMER
XMTR TRANSMITTER
Z IMPEDANCE
& AND
I.E.: THAT IS
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E000
GENERAL NOTES,
ABBREVIATIONS
AND SHEET INDEX
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
ELECTRICAL SHEET INDEX
E000 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E001 ELECTRICAL LEGEND
E002 ELECTRICAL POWER - SITE PLAN
E101 ELECTRICAL DEMO - ADMINSTRATION BLDG 2083
E102 ELECTRICAL POWER - ADMINISTRATION BLDG 2083
E201 ELECTRICAL DEMO - GYMNASIUM BLDG 2889
E202 ELECTRICAL POWER - GYMNASIUM BLDG 2889
E601 ADMINISTRATION ONE-LINE DIAGRAM AND PANEL MOUNTING DETAIL
E602 GYM ONE-LINE DIAGRAMS
E701 PANEL SCHEDULES - ADMINISTRATION BLDG 2083
E702 PANEL SCHEDULES - GYMNASIUM BLDG 2889
PROJECT LOCATION - 335 NE Blodgett Rd, Yachats, OR 97498
UNITED STATES DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL DEFICIENCIES
PACIFIC NORTHWEST REGION
SIUSLAW NATIONAL FOREST
ANGELL JOB CORPS CENTER
LINCOLN COUNTY, OREGON
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
X-XX
N
DRAWING CONSTRUCTION ("FLAG") NOTE
EQUIPMENT IDENTIFIER
MATCHLINE
REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE
PREVIOUS RELEASE)
REVISION REFERENCE
EXISTING TO BE REMOVED (HATCHED)
HEAVY LINEWEIGHT INDICATES NEW WORK
LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION
POINT OF CONNECTION
DETAIL REFERENCE
DETAIL IDENTIFICATION NUMBER
SHEET WHERE DETAIL IS DRAWN
ELEVATION REFERENCE
ELEVATION IDENTIFICATION
NUMBER SHEET WHERE ELEVATION IS DRAWN
SECTION REFERENCE SECTION
IDENTIFICATION NUMBER
SHEET WHERE SECTION IS DRAWN
NORTH REFERENCE
X
XX.XX
X
XX.XX
X
XX.XX
LIMIT OF DEMOLITION
X-XX-X
T
M
MM
AM
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
TRANSFORMER
AS
POLE-MOUNTED TRANSFORMER
POLE
DELTA
WYE
MEDIUM VOLTAGE CABLE TERMINATOR
LIGHTNING ARRESTORS
SURGE ARRESTORS
NEUTRAL GROUNDING RESISTOR
METER
MICROPROCESSOR CONTROLLED MONITOR
REFER TO SPECIFICATIONS FOR METERING VALUES AND
PROTECTIVE FUNCTIONS
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
INDICATING INSTRUMENT
AM-AMMETER; VM-VOLTMETER; FM-FREQUENCY METER;
kVAR-KILOVAR METER; kWH-KILOWATT HOUR METER;
kWH/D-KILOWATT HOUR DEMAND METER
INSTRUMENT SWITCH
AS-AMMETER SWITCH; VS-VOLTMETER SWITCH;
SS-SYNCHRONIZING SWITCH;
SV-SUPERVISORY (LOCAL-REMOTE) SWITCH
SEPARABLE CONNECTOR
DRAWOUT AC TYPE POWER CIRCUIT BREAKER
SYMBOLS LEGEND - POWER
DESCRIPTION
CIRCUIT BREAKER
ST - INDICATES SHUNT TRIP
BREAKER WITH EXTERNAL GROUND FAULT RELAY AND CT
CIRCUIT BREAKER WITH INTEGRAL GROUND FAULT PROTECTION
MOTOR-OPERATED CIRCUIT BREAKER
SWITCH WITH EXTERNAL GROUND FAULT RELAY AND CT
MOV SURGE PROTECTION
RESISTOR
FUSE
MOTOR THERMAL OVERLOADS - (3) UNLESS OTHERWISE NOTED
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
SOLENOID VALVE
MOTOR-OPERATED VALVE
TERMINAL BLOCK
THERMOSTAT
INDICATING LIGHT - TYPE AS NOTED
A-AMBER; B-BLUE; G-GREEN; R-RED; W-WHITE
BATTERY
CB
A
T
CB ENCLOSED CIRCUIT BREAKER (PLAN VIEW)
xxxA/xP - AMPS/POLESxxxA/xP
ENCLOSED CIRCUIT BREAKER (ONE-LINE DIAGRAM)
xxxA/xP - AMPS/POLES
G G
M G
SV
M
SYMBOL
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
M
C
G
M
M
SD
M
FSD
M
2-POSITION SELECTOR SWITCH
3-POSITION SELECTOR SWITCH HAND-OFF-AUTOMATIC
ON-OFF SELECTOR SWITCH
2-CIRCUIT PUSHBUTTON
PUSHBUTTON SWITCH MOMENTARY CONTACT
EQUIPMENT CONNECTION
GENERATOR
MOTOR CONNECTION
SMOKE DAMPER
FIRE SMOKE DAMPER
STARTER 3-POLE, NEMA SIZE 1 MINIMUM UNLESS NOTED OTHERWISE
COMBINATION STARTER
HP RATED, 3-POLE, NEMA SIZE 1 MINIMUM, UNLESS NOTED
OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED BY
EQUIPMENT MANUFACTURER OR AS NOTED
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
CONTACTOR
RELAY COIL
CR-CONTROL RELAY; TD-TIME DELAY RELAY;
UV-UNDERVOLTAGE RELAY; M-MOTOR
CONTACTOR;
MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS
EQUIPMENT EMERGENCY SHUTDOWN SWITCH
3-POLE UNLESS NOTED OTHERWISE
3-POLE UNLESS NOTED OTHERWISE
CR
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
CONDUIT CONCEALED IN CEILING SPACE OR IN WALL. PROVIDE MINIMUM
3/4" WITH #12 AWG CONDUCTORS AND DEDICATED NEUTRAL EACH
CIRCUIT UNLESS OTHERWISE NOTED ON PLAN. PROVIDE EQUIPMENT
GROUNDING CONDUCTORS SIZED PER NFPA 70.
CONDUIT - CONCEALED IN OR UNDER FLOOR
CONDUIT - ROUTED UNDERGROUND
LOW-VOLTAGE WIRING (CLASS B)
CONDUIT OR CABLE VERTICAL DOWN
CONDUIT OR CABLE VERTICAL UP
CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND
BREAK LINE
CONDUIT SEAL
EXPANSION FITTING
CONDUCTORS - CONNECTED
CONDUCTORS - NOT CONNECTED
JUNCTION BOX
PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE
HANDHOLE
MANHOLE
FLEXIBLE METAL CONDUIT
BRANCH CIRCUIT NUMBERS
PANEL DESIGNATION
HOME RUN TO SOURCE OF SUPPLY
PB
HH
MH
A-1,3,5
UG
LV
J
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
XX
480Y/277V, 3Ø, 4W PANELBOARD
208Y/120V, 3Ø, 4W PANELBOARD
EQUIPMENT CABINET - TYPE AS NOTED
PANELBOARD
TRANSFER SWITCH ( AUTO )
AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)
FEEDER TAG - REFER TO FEEDER SCHEDULE
XXXXXX
SYMBOLS LEGEND - GROUNDING
DESCRIPTIONSYMBOL
GROUND CONNECTION
GROUND ROD
GROUND WELL
AIR TERMINAL
SYMBOLS LEGEND - WIRING DEVICES
DESCRIPTION
SINGLE-POLE WALL SWITCH MOUNT SWITCHES AT 48" AFF. TO TOP, UON.
WALL SWITCH - SUBSCRIPT
SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS
SINGLE SERVICE OR COMBINATION FLUSH FLOOR POKE THRU. REFER TO
FLOOR PLANS FOR DEVICES.
POWER/COMM POLE - FLOOR TO CEILING.
SURFACE MOUNTED FLOOR BOX (PEDESTAL TYPE).
PUSH BUTTON
SIMPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON
NEMA 5-20R, +18" AFF UON
TAMPER RESISTANT, NEMA 5-20R, +18" AFF UON
ISOLATED GROUND, NEMA 5-20R, +18" AFF UON
NEMA 5-20R W/ GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON
SPLIT WIRED, NEMA 5-20R, +18" AFF UON
CONTROLLED, NEMA 5-20R, +18" AFF UON
NEMA 5-20R, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP
DRAWINGS AND ARCHITECTURAL DRAWINGS.
NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE
COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL DRAWINGS.
TAMPER RESISTANT, NEMA 5-20R WITH GROUND FAULT CIRCUIT
INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP
DRAWINGS AND ARCHITECTURAL DRAWINGS.
NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18" AFF UON
NEMA 5-20R ON EMERGENCY CIRCUIT MOUNTED ABOVE COUNTER. COORDINATE
WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.
CEILING-MOUNTED, NEMA 5-20R
2 = 2-POLE
3 = 3-WAY
4 = 4-WAY
K = KEYED
LV = LOW-VOLTAGE
OS = OCCUPANCY SENSOR TYPE
OP = OCCUPANCY/PHOTOELECTRIC TYPE
WP = WEATHERPROOF
LOWER CASE LETTER INDICATES SWITCHING GROUP
MOUNT SWITCHES AT +48" AFF. TO TOP, UON. ANY COMBINATION OF
SWITCH TYPES CAN BE USED (IE. 3K = 3-WAY KEYED SWITCH)
SINGLE SERVICE OR COMBINATION FLUSH MOUNTED FLOOR BOX. REFER
TO FLOOR PLANS FOR DEVICES.
SWITCHED RECEPTACLE, NEMA 5-20R, +18" AFF UON
xx
SYMBOL
T T
S S
IG IG
T T
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E001
ELECTRICAL
LEGEND
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
P W R
6" GAS
OH LINES
S.S.
S.S
S .S
S.S.
W A T
WM
IRR
WAT.
W A T
W A T
WV
2892 712
S
D
Y
H
AREA OF WORK
AREA OF WORK
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E002
ELECTRICAL
POWER - SITE
PLAN
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
SHEET NOTES
A. SITE PLAN IS FOR REFERENCE ONLY.
1" = 50'-0"
ELECTRICAL POWER - SITE PLAN
CENTER DIRECTOR
OFFICE
ADMIN OFFICE
RECEPTION
STORAGE
MECH
TOILETXEROX ROOM
COMPUTER
EQUIPMENT
COMMUNICATION'S
MANAGER
MAILING
PURCHASING
TOILET
KITCHEN
CONFERENCE
SUPPORT PERSONEL
SERVICE
OPERATOR SUPPORT
CLERK
STUDENT SUPPORT
SUPERVISOR
A
B
MM
(N)400A 240V
1PH
SERVICE
DISCONNECT
A B
(E) 100A 240V 1PH
DISCONNECTS
(N) 30A 240V 1PH
DISCONNECT
(N) UNI-STRUT
STRUCTURE 1
2 2
7 7
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E101
ELECTRICAL DEMO
- ADMINSTRATION
BLDG 2083
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ELECTRICAL DEMO - ADMINSTRATION BLDG 2083
DEMO SHEET NOTES
A. FOR EQUIPMENT BEING REMOVED OR REPLACED, DE-ENERGIZE THE
EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL. COMPLY WITH OSHA
REQUIREMENTS FOR LOCKING OUT AND TAGGING EQUIPMENT TO PREVENT
INADVERTENT RE-ENERGIZING.
B. VERIFY CIRCUITS, DEVICES, AND EQUIPMENT SCHEDULED FOR REMOVAL TO
ASSURE THAT THEIR REMOVAL WILL NOT ADVERSELY AFFECT ADJACENT
AREAS NOT BEING RENOVATED.
C. MAINTAIN POWER TO ALL CIRCUITS IN AREAS ADJACENT THE CONSTRUCTION
AREA. THIS SHALL INCLUDE ANY CIRCUITS PASSING THROUGH THE
CONSTRUCTION AREA OR CIRCUITS BEING POWERED FROM POWER PANELS
WITHIN THE CONSTRUCTION AREA. EXTEND AND RELOCATE THESE CIRCUITS
AS REQUIRED TO MAINTAIN SERVICE AND TO AVOID INTERFERENCE WITH THE
NEW WORK. NOTIFY THE CONTRACTING OFFICER IN ADVANCE, SHOULD IT BE
NECESSARY TO INTERRUPT POWER TO AREAS ADJACENT TO THIS
CONSTRUCTION AREA.
D. DEMOLITION WORK MUST FOLLOW THE CONSTRUCTION PHASING SEQUENCE
AND MUST BE COORDINATED WITH THE PHASING PLANS, CONSTRUCTION
DRAWINGS, AND WORK OF OTHER TRADES.
E. DEFINITION - THE TERM "CIRCUIT" IN ITS ENTIRETY, SHALL MEAN CONDUIT,
FITTINGS, SUPPORTS, JUNCTION BOXES, AND CONDUCTORS FROM THE
RESPECTIVE PANEL BOARD (POWER SOURCE) TO THE LAST JUNCTION BOX
OR DEVICE, OR THE REMAINING PORTION OF THE CIRCUIT THAT SERVES
EXISTING EQUIPMENT OR AREAS WHICH SHALL REMAIN.
F. VERIFY ALL LIGHTING CIRCUITS WITHIN THE CONSTRUCTION AREA BEFORE
DISCONNECTING POWER. PROVIDE NECESSARY WIRING TO MAINTAIN
LIGHTING IN AREAS ADJACENT TO THIS CONSTRUCTION AREA WHICH WOULD
BE AFFECTED BY THIS DEMOLITION WORK.
G. ALL DEVICES, JUNCTION BOXES, CIRCUIT NUMBERS, EQUIPMENT SIZES, AND
CONDUIT SHOWN ARE FOR REFERENCE ONLY AND MAY NOT INDICATE
CORRECT IDENTIFICATION, SIZES, OR TOTAL QUANTITIES OF ITEMS
SCHEDULED FOR DEMOLITION. VISIT SITE AND FIELD VERIFY THE NUMBER OF
DEVICES WITHIN THE CONSTRUCTION PHASE AREA PRIOR TO BID. REMOVE
ALL DEVICES, EQUIPMENT, MATERIAL, AND CIRCUITS IN THEIR ENTIRETY,
WHICH INTERFERE WITH THE NEW CONSTRUCTION AND NOT SHOWN ON
DRAWINGS AS DIRECTED BY THE CONTRACTING OFFICER.
H. DISPOSAL AND/OR SALVAGING OF MATERIAL AND EQUIPMENT SHALL BE AS
DIRECTED BY THE CONTRACTING OFFICER.
I. FLOOR PLANS NOT TO SCALE.
1. DEMOLISH AND REPLACE OLD STRUCTURE WITH NEW CAST IN CONCRETE
UNI-STRUT STRUCTURE FOR NEW SERVICE EQUIPMENT.
2. DEMOLISH EXISTING CT/METER ENCLOSURES AND REPLACE WITH NEW.
3. DEMOLISH EXISTING 400A DISCONNECTS AND REPLACE WITH NEW.
4. DEMOLISH EXISTING 30A DISCONNECT AND REPLACE WITH NEW.
5. DEMOLISH EXISTING PANEL AND REPLACE WITH NEW 225A 120/240V 1PH 30
SPACE PANEL. BRANCH BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION
BEING REPLACED. INTERCEPT EXISTING FEEDER AND BRANCH CIRCUITS AND
RETERMINATE ON NEW PANELBOARD.
6. NOT USED.
7. FIELD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY
WORK BEING DONE.
FLAG NOTES #
CENTER DIRECTOR
OFFICE
ADMIN OFFICE
RECEPTION
STORAGE
MECH
TOILETXEROX ROOM
COMPUTER
EQUIPMENT
COMMUNICATION'S
MANAGER
MAILING
PURCHASING
TOILET
KITCHEN
CONFERENCE
SUPPORT PERSONEL
SERVICE
OPERATOR SUPPORT
CLERK
STUDENT SUPPORT
SUPERVISOR
A
B
MM
(N)400A 240V
1PH
SERVICE
DISCONNECT
A B
(E) 100A 240V 1PH
DISCONNECTS
(N) 30A 240V 1PH
DISCONNECT
(N) UNI-STRUT
STRUCTURE 1
2 2
7 7
E601
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E102
ELECTRICAL
POWER -
ADMINISTRATION
BLDG 2083
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ELECTRICAL POWER - ADMINSTRATION BLDG 2083
1. REPLACE OLD STRUCTURE WITH NEW CAST IN CONCRETE UNI-STRUT
STRUCTURE FOR NEW SERVICE EQUIPMENT.
2. PROVIDE NEW STAINLESS STEEL CT/METER ENCLOSURES IN EXISTING
LOCATION. INTERCEPT EXISTING FEEDERS.
3. PROVIDE NEW NEMA 3R STAINLESS STEEL 400A DISCONNECTS IN EXISTING
LOCATIONS. INTERCEPT EXISTING FEEDERS.
4. PROVIDE NEW 30A NEMA 3R STAINLESS STEEL DISCONNECT AND INTERCEPT
EXISTING FEEDERS.
5. RE-MOUNT EXISTING 100A DISCONNECTS ONTO NEW UNI-STRUT STRUCTURE.
6. PROVIDE NEW PANEL IN EXISTING LOCATION. 225A 1PH PANEL WITH BRANCH
BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION BEING REPLACED.
INTERCEPT EXISTING FEEDER AND BRANCH CIRCUITS AND RETERMINATE ON
NEW PANELBOARD. PROVIDE NEW PANEL SCHEDULE AND THE APPORPRIATE
LABELS FOR NEW PANEL RE-CONNECTING EXISTING CIRCUITRY.
7. FEILD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY
WORK BEING DONE.
FLAG NOTES #
SHEET NOTES
A. COORDINATE EXACT LOCATION, QUANTITY, & INSTALLATION REQUIREMENTS
OF ALL ELECTRICAL EQUIPMENT & RECEPTACLES INCLUDING MILL &
COUNTER AREAS WITH ARCHITECT/OWNER PRIOR TO ROUGH IN.
B. MAXIMUM NUMBER OF CONDUCTORS IN A CONDUIT SHALL NOT EXCEED 9,
UON.
C. COORDINATE COMPLETE ELECTRICAL INSTALLATIONS SO THAT ALL WORKING
CLEARANCES FOR ALL ELECTRICAL EQUIPMENT ARE PROVIDED AS REQUIRED
PER NEC 110.26. FURTHERMORE, COORDINATE WITH ALL PERTINENT TRADES
SO THAT ELECTRICAL INSTALLATIONS DO NOT PREVENT WORKING AND
MAINTENANCE CLEARANCES TO ANY EQUIPMENT PROVIDED BY OTHERS.
THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT ACCESS PANELS, ACCESS
DOORS, CONTROL PANELS, CONTROL EQUIPMENT/DEVICES, SCREENS, ETC.
D. ALL EQUIPMENT LOCATIONS, CONDUIT ROUTING, EQUIPMENT CONNECTIONS
AND TERMINATION POINTS ARE DIAGRAMMATIC AND SHOWN FOR REFERENCE
ONLY. VERIFY AND COORDINATE EXACT REQUIREMENTS IN FIELD WITH
CONTRACTING OFFICER, AND EQUIPMENT VENDOR.
E. ALL CIRCUITS SHALL HAVE AN INSULATED GROUND WIRE (BOND) SIZED PER
NEC #250.122., #12 MINIMUM GROUND (WIRE NOT SHOWN ON DRAWINGS).
F. COORDINATE ALL CONDUIT SIZES WITH APPLICABLE EQUIPMENT/SYSTEM
VENDORS PRIOR TO BID AND INSTALLATION.
G. CIRCUITS WIRED AS MULTI-WIRE BRANCH CIRCUITS SHALL HAVE
DISCONNECTING MEANS PER NEC 210.4(B).
H. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO
FIELD VERIFY AND ROUTE CONDUIT AND WIRING AS FIELD CONDITIONS
PERMIT. INSTALL PULL/JUNCTION BOXES AS REQUIRED BY NEC.
I. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS
PURPOSE UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT.
THE MARKING SHALL INCLUDE THE IDENTIFICATION OF THE CIRCUIT SOURCE
THAT SUPPLIES THE DISCONNECTING MEANS. THE MARKING SHALL BE OF
SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
110.22, NEC.
J. FLOOR PLANS NOT TO SCALE.
COMPUTER
LIBRARY
CONTROL / OFFICE
CPP CLASSROOM
WEIGHT/BOXING
ROOM
RECREATION
EQUIPMENT
SHWS
STORAGE
WKILN ROOM
ARTS & CRAFTS
MUSIC ROOM
GAME ROOM
GYMNASIUM
BIKE STORAGE
EXISTING
120/240V, 1PH
JUNCTION BOX
A
C
B
(E) CUSTOMER OWNED
UTILITY POLE
EXISTING
240/480V, 1PH
JUNCTION BOX
2 T
T
7 7
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E201
ELECTRICAL DEMO
- GYMNASIUM
BLDG 2889
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ELECTRICAL DEMO - GYMNASIUM BLDG 2889
DEMO SHEET NOTES
1. EXISTING TRANSFORMER TO BE REMOVED COMPLETE. REMOVE EXISTING
SECONDARY AND PRIMARY CONDUCTORS. SAWCUT BELOW GRADE CONDUIT
AT GRADE AND GROUT SEAL CONDUIT FLUSH TO EXISTING SURFACES.
2. EXISTING SERVICE AND CONDUIT TO BE DEMOLISHED COMPLETE.
3. EXISTING PANEL TO BE REUSED.
4. EXISTING PANEL TO REPLACED.
5. DEMOLISH EXISTING 480V BUSS GUTTER AND HEATER DISCONNECTS.
6. EXISTING 480/120V DRY TYPE TRANSFORMER TO BE REMOVED COMPLETE.
7. EXISTING 240/480V HEATERS TO BE DISCONNECTED, DEMOLISHED AND
REMOVED. TERMINATE CIRCUIT FOR FUTURE USE AT NEAREST J-BOX AND
LABEL WITH CIRCUIT INFORMATION.
8. EXISTING MODINE HER150 HEATER TO BE DISCONNECTED, CARFULLY
REMOVED, AND DELIVERED TO CENTER MAINTENANCE STAFF STORAGE
LOCATION.
9. CONTRACTOR TO DEMOLISH EXISTING 100KVA POLE MOUNTED
TRANSFORMER.
10. EXISTING POLE MOUNTED TRANSFORMER ON GRADE TO BE REMOVED.
11. EXISTING FIBERGLASS ENCLOSURE.
FLAG NOTES #
A. FOR EQUIPMENT BEING REMOVED OR REPLACED, DE-ENERGIZE THE
EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL. COMPLY WITH OSHA
REQUIREMENTS FOR LOCKING OUT AND TAGGING EQUIPMENT TO PREVENT
INADVERTENT RE-ENERGIZING.
B. VERIFY CIRCUITS, DEVICES, AND EQUIPMENT SCHEDULED FOR REMOVAL TO
ASSURE THAT THEIR REMOVAL WILL NOT ADVERSELY AFFECT ADJACENT
AREAS NOT BEING RENOVATED.
C. MAINTAIN POWER TO ALL CIRCUITS IN AREAS ADJACENT THE CONSTRUCTION
AREA. THIS SHALL INCLUDE ANY CIRCUITS PASSING THROUGH THE
CONSTRUCTION AREA OR CIRCUITS BEING POWERED FROM POWER PANELS
WITHIN THE CONSTRUCTION AREA. EXTEND AND RELOCATE THESE CIRCUITS
AS REQUIRED TO MAINTAIN SERVICE AND TO AVOID INTERFERENCE WITH THE
NEW WORK. NOTIFY THE CONTRACTING OFFICER IN ADVANCE, SHOULD IT BE
NECESSARY TO INTERRUPT POWER TO AREAS ADJACENT TO THIS
CONSTRUCTION AREA.
D. DEMOLITION WORK MUST FOLLOW THE CONSTRUCTION PHASING SEQUENCE
AND MUST BE COORDINATED WITH THE PHASING PLANS, CONSTRUCTION
DRAWINGS, AND WORK OF OTHER TRADES.
E. DEFINITION - THE TERM "CIRCUIT" IN ITS ENTIRETY, SHALL MEAN CONDUIT,
FITTINGS, SUPPORTS, JUNCTION BOXES, AND CONDUCTORS FROM THE
RESPECTIVE PANEL BOARD (POWER SOURCE) TO THE LAST JUNCTION BOX
OR DEVICE, OR THE REMAINING PORTION OF THE CIRCUIT THAT SERVES
EXISTING EQUIPMENT OR AREAS WHICH SHALL REMAIN.
F. VERIFY ALL LIGHTING CIRCUITS WITHIN THE CONSTRUCTION AREA BEFORE
DISCONNECTING POWER. PROVIDE NECESSARY WIRING TO MAINTAIN
LIGHTING IN AREAS ADJACENT TO THIS CONSTRUCTION AREA WHICH WOULD
BE AFFECTED BY THIS DEMOLITION WORK.
G. ALL DEVICES, JUNCTION BOXES, CIRCUIT NUMBERS, EQUIPMENT SIZES, AND
CONDUIT SHOWN ARE FOR REFERENCE ONLY AND MAY NOT INDICATE
CORRECT IDENTIFICATION, SIZES, OR TOTAL QUANTITIES OF ITEMS
SCHEDULED FOR DEMOLITION. VISIT SITE AND FIELD VERIFY THE NUMBER OF
DEVICES WITHIN THE CONSTRUCTION PHASE AREA PRIOR TO BID. REMOVE
ALL DEVICES, EQUIPMENT, MATERIAL, AND CIRCUITS IN THEIR ENTIRETY,
WHICH INTERFERE WITH THE NEW CONSTRUCTION AND NOT SHOWN ON
DRAWINGS AS DIRECTED BY THE CONTRACTING OFFICER.
H. DISPOSAL AND/OR SALVAGING OF MATERIAL AND EQUIPMENT SHALL BE AS
DIRECTED BY THE CONTRACTING OFFICER.
I. FLOOR PLANS NOT TO SCALE.
T
COMPUTER
LIBRARY
CONTROL / OFFICE
CPP CLASSROOM
WEIGHT/BOXING
ROOM
RECREATION
EQUIPMENT
SHWS
STORAGE
WKILN ROOM
ARTS & CRAFTSMUSIC ROOM
GAME ROOM
GYMNASIUM
BIKE STORAGE
2DP
600A 240V 1PH
SERVICE
DISCONNECT
(N) 150KVA OIL FILLED
12470/240V, 1PH PAD
MOUNTED
TRANSFORMER
A C
B
(E) CUSTOMER OWNED
UTILITY POLE
T
T
T
B-26,28
B-27,29
A-25,27
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E202
ELECTRICAL
POWER -
GYMNASIUM BLDG
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ELECTRICAL POWER - GYMNASIUM BLDG 2889
1. CONTRACTOR TO PROVIDE NEW CONCRETE PAD MOUNTED 150KVA
TRANSFORMER TO FEED NEW 600A SERVICE.
2. PROVIDE NEW 600A 1PH NEMA 3R SERVICE DISCONNECT FOR NEW SERVICE.
3. PROVIDE NEW 600A 1PH DISTRIBUTION PANEL TO BACK FEED EXISTING
PANELS FROM EXISTING SERVICES 1 &2 AFTER DEMO PHASE.
4. PROVIDE NEW 400A 1PH 42 CIRCUIT PANEL TO REPLACE EXISTING PANEL IN
SE CORNER OF GYM UTILIZING EXISTING FEEDER.
5. PROVIDE NEW FEEDER FOR EXISTING 400A 1PH PANEL IN WEIGHT ROOM.
6. RE-FEED EXISTING PANEL TO NEW DISTRIBUTION PANEL 2DP.
7. PROVIDE NEW DOOR TO EXISTING 400A 1PH PANEL. MATCH MAKE AND
MODEL.
8. NOT USED.
9. FIELD VERIFY ALL EXISTING AND NEW EQUIPMENT LOCATIONS PRIOR TO ANY
WORK BEING DONE.
10. NEW ELECTRIC HEATERS TO BE INSTALLED WITH LOW VOLTAGE KIT, LOW
VOLTAGE THERMOSTATS, AND PROTECTIVE CAGES FOR HEATERS AND
THERMOSTATS.
FLAG NOTES #
SHEET NOTES
A. COORDINATE EXACT LOCATION, QUANTITY, & INSTALLATION REQUIREMENTS
OF ALL ELECTRICAL EQUIPMENT & RECEPTACLES INCLUDING MILL &
COUNTER AREAS WITH ARCHITECT/OWNER PRIOR TO ROUGH IN.
B. MAXIMUM NUMBER OF CONDUCTORS IN A CONDUIT SHALL NOT EXCEED 9,
UON.
C. COORDINATE COMPLETE ELECTRICAL INSTALLATIONS SO THAT ALL WORKING
CLEARANCES FOR ALL ELECTRICAL EQUIPMENT ARE PROVIDED AS REQUIRED
PER NEC 110.26. FURTHERMORE, COORDINATE WITH ALL PERTINENT TRADES
SO THAT ELECTRICAL INSTALLATIONS DO NOT PREVENT WORKING AND
MAINTENANCE CLEARANCES TO ANY EQUIPMENT PROVIDED BY OTHERS.
THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT ACCESS PANELS, ACCESS
DOORS, CONTROL PANELS, CONTROL EQUIPMENT/DEVICES, SCREENS, ETC.
D. ALL EQUIPMENT LOCATIONS, CONDUIT ROUTING, EQUIPMENT CONNECTIONS
AND TERMINATION POINTS ARE DIAGRAMMATIC AND SHOWN FOR REFERENCE
ONLY. VERIFY AND COORDINATE EXACT REQUIREMENTS IN FIELD WITH
CONTRACTING OFFICER, AND EQUIPMENT VENDOR.
E. ALL CIRCUITS SHALL HAVE AN INSULATED GROUND WIRE (BOND) SIZED PER
NEC #250.122., #12 MINIMUM GROUND (WIRE NOT SHOWN ON DRAWINGS).
F. COORDINATE ALL CONDUIT SIZES WITH APPLICABLE EQUIPMENT/SYSTEM
VENDORS PRIOR TO BID AND INSTALLATION.
G. CIRCUITS WIRED AS MULTI-WIRE BRANCH CIRCUITS SHALL HAVE
DISCONNECTING MEANS PER NEC 210.4(B).
H. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO
FIELD VERIFY AND ROUTE CONDUIT AND WIRING AS FIELD CONDITIONS
PERMIT. INSTALL PULL/JUNCTION BOXES AS REQUIRED BY NEC.
I. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS
PURPOSE UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT.
THE MARKING SHALL INCLUDE THE IDENTIFICATION OF THE CIRCUIT SOURCE
THAT SUPPLIES THE DISCONNECTING MEANS. THE MARKING SHALL BE OF
SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
110.22, NEC.
J. FLOOR PLANS NOT TO SCALE.
M M
(N) 200A 120/240V
CT CAN
A
(N) 200A 120/240V
CT CAN
B
(N) 400A 120/240V
SERVICE
DISCONNECT
(N) 400A 120/240V
SERVICE
DISCONNECT
(E)100A 120/240V
DISCONNECT
(N)100A 120/240V
DISCONNECT
(N) 30A 120/240V
DISCONNECT
NEMA 3R
EXTERIOR
NEMA 1
INTERIOR
1 1
ADMINISTRATION
BUILDING 2083
TO
UTILITY
5 5 5
3 3 4
(N)
225A
1PH
120/240V
(N)
225A
1PH
120/240V
5 5
6 6
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E601
ADMINISTRATION
ONE-LINE DIAGRAM
AND PANEL
MOUNTING DETAIL
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ANGELL JC ADMINISTRATION 2083 ONE-LINE DIAGRAM
1. THE EXISTING BELOW GRADE FEEDERS TO BE INTERCEPTED AND RE-
TERMINATED ONTO NEW SERVICE DISCONNECTS.
2. UNI-STRUT STRUCTURE ANCHORED IN CONCRETE TO REPLACE EXISTING
SUPPORT STRUCTURE.
3. EXISTING 100A DISCONNECTS TO BE REMOUNTED ONTO NEW STUCTURE.
4. NEW 30A 1PH DISCONNECT TO REPLACE EXISTING. REMOUNT INTO NEW
STRUCTURE.
5. RE-CONNECT EXISTING FEEDERS.
6. CONFIRM LOCATIONS AND REPLACE EXISTING INTERIOR PANELBOARDS WITH
225A 1PH 120/240V WITH BREAKERS SIZED TO MATCH EXISTING DISTRIBUTION
BEING REPLACED.
FLAG NOTES #
EXTERIOR CT, DISCONNECT SUPOORT DETAIL
N.T.S.
36"
THREADED END
CAPS
(TYPICAL OF 2)
1/2" DIA. CADMIUM
PLATED BOLTS WITH
FLAT WASHERS AND
SILICON SEALER (MIN.
OF 4)
2 1/2" STANILESS
STEEL POSTS
FINISHED
GRADE
CONCRETE
FOOTING
WIDTH
DISCONNECT
OR CT
2"
36"
2"
STAINLESS STEEL UNI-STRUT,
SIZE PER STRUCTURAL
ENGINEER DESIGN, TYPICAL
CT OR
DISCONNECT
CT OR
DISCONNECT
CONTRACTOR TO ENGAGE LICENSED STRUCTURAL ENGINEER IN THE STATE OF OREGON FOR DESIGN OF SUPPORT SYSTEM. THIS DETAIL IS CONVEY DESIGN INTENT AND IS NOT TO BE USED FOR INSTALLATION.
(E) 400A 120/240V
SERVICE
DISCONNECTSERVICE #1
(E)
400A
1PH
120/240V
(E)
400A
1PH
120/240V
NORTH WALL
GYM
SE CORNER
GYM
SERVICE #2
(E) CLPUD
240/480VXFMR
(E) BUSS GUTTER
(E)
200A
1PH
120/240V
(E) (E) (E) (E) (E) (E) (E)
HEATERS HEATERS HEATERS HEATERS HEATERS HEATERS
(E) 37.5KVA
XFMR
(E) 100KVA
120/240v
XFMR
(N) 2DP
600A
1PH
120/240V
(N) 150KVA, 12.47KV/240V, 1PH
OIL FILLED PAD MOUNT XFMR
(N) 600A 120/240V
NEMA 3R SERVICE
DISCONNECT
(N)
400A
1PH
120/240V
REMOVE ALL (5) 480V HEATERS,
REPLACE WITH 3, 10 KW 240V, 1PH
HEATERS OF EQUAL KW OUTPUT.
SEE PANEL AND EQUIPMENT
SCHEDULES
NEMA 3R
EXTERIOR
NEMA 1
INTERIOR
GYM
BUILDING 2083
4 4 4 4 4 4
SE CORNER
GYM
BOXING
ROOM
(E)
400A
1PH
120/240V
EXISTING 12470V OVERHEAD
TRANSMISSION LINES
EXISTING UTILITY POLE
FIBERGLASS
ENCLOSURE
NEMA 3R
EXTERIOR
NEMA 1
INTERIOR
EXTERIOR
EXTERIOR
(3) #8 MV-105 COPPER WITH
CONCENTRIC SHIELD IN 3"C.
6'X6'X4" CONCRETE PAD
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E602
GYM ONE-LINE
DIAGRAMS
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
N.T.S.
ANGELL JC GYM 2889 ONE-LINE DIAGRAM
1. DEMO EXISTING 400A DISCONNECT AND FEEDER.
2. NEW 600A 1PH 120/240V PANEL TO BE LOCATED ON THE SOUTHSIDE OF THE
CPP CLASSROOM WALL. BACK FEED ALL 120/240V PANELS ASSOCIATED WITH
SERVICE 1&2.
3. DEMO EXISTING BUSS GUTTER AND ALL 240/480V EQUIPMENT, AND FEEDERS
BACK TO THE PAD MOUNTED TRANSFORMER FEEDING SERVICE #2.
4. EXISTING 240/480V HEATERS TO BE DEMOLISHED. NEW 120/240V HEATERS TO
BE INSTALLED. SEE DEMO SHEET E201 FOR FURTHER CLARIFICATION.
5. DEMO EXISTING GROUND MOUNTED (POLE POTTED) 100 KVA TRANSFORMER
IN EXISTING FIBERGLASS ENCLOSURE. REMOVE ALL EXISTING CONDUCTORS
IN EXISTING RACEWAYS. RACEWAYS TO REMAIN.
6. CONTRACTOR TO PROVIDE AND INSTALL NEW 150KVA TRANSFORMER
COMBINING EXISTING SERIVICES 1 AND 2 INTO A SINGLE SERVICE.
7. REPLACE EXISTING DOOR WITH NEW.
8. RE-USE EXISTING FEEDER FOR SE GYM PANEL.
9. DEMO EXISTING SE GYM PANEL AND REPLACE WITH NEW 400A 1PH 120/240V
42 CIRCUIT PANELBOARD UTILIZING EXISTING FEEDER.
10. PROVIDE NEW FEEDER TO EXISTING BOXING ROOM PANEL OUT OF NEW 600A
SERVICE.
11. PROVIDE NEW BELOW GRADE FEEDER TO EXISTING CUSTOMER OWNED
UTILITY POLE PROVIDE FUSIBLE DISCONNECT LINK WITH HOT STICK
PROVISION FOR EACH CONDUCTOR TAPPED TO OVER HEAD TRANSMISSION
LINES.
FLAG NOTES #
600N 2 3" 3#350, #350N #1
600 2 3" 3#350 #1
400N 2 2" 2#3/0, #3/0N #2
400 2 2" 2#3/0 #2
380N 1 3" 2#500, #500N #2
380 1 3" 2#500 #2
350N 1 3" 2#500, #500N #2
350 1 3" 2#500 #2
300N 1 3" 2#350, #350N #4
300 1 3" 2#350 #4
250N 1 2-1/2" 2#250, #250N #4
250 1 2-1/2" 2#250 #4
225N 1 2" 2#4/0, #4/0N #4
225 1 2" 2#4/0 #4
200N 1 2" 2#3/0, #3/0N #6
200 1 2" 2#3/0 #6
175N 1 2" 2#2/0, #2/0N #6
175 1 2" 2#2/0 #6
150N 1 2" 2#1/0, #1/0N #6
150 1 2" 2#1/0 #6
125N 1 1-1/2" 2#1, #1N #6
125 1 1-1/2" 2#1 #6
100N 1 1-1/2" 2#1, #1N #8
100 1 1-1/2" 2#1 #8
90N 1 1-1/4" 2#2, #2N #8
90 1 1-1/4" 2#2 #8
80N 1 1-1/4" 2#2, #2N #8
80 1 1-1/4" 2#2 #8
CODE
PARALLEL
SETS
CONDUIT SIZE CONDUCTOR SIZE GROUND CONDUCTOR
CONDUCTORS #1 AWG OR SMALLER ARE SIZED BASED ON 60 DEGREE TABLES
COPPER CONDUCTORS
1-PHASE FEEDER SCHEDULE
1) NEMA-3R FUSED DISCONNECT SWITCH.
2) PROVIDE MOTOR-RATED SWITCH, WITH WP COVER, AS DISCONNECT.
3) PROVIDE MOTOR-RATED SWITCH AS DISCONNECT.
4) EXHAUST FAN SHARES CIRCUIT WITH OTHER EXHAUST FANS.
5) WATER HEATER SHARES CIRCUIT WITH OTHER WATER HEATER.
FLA:
HP:
KVA:
KW:
MCA:
MOCP:
OFOI:
OFCI:
W:
WP:
VA:
FULL LOAD AMPERES
HORSEPOWER
KILOVOLT-AMPERES
KILOWATTS
MINIMUM CIRCUIT AMPACITY
MAXIMUM OVERCURRENT PROTECTIVE DEVICE
OWNER-FURNISHED, OWNER-INSTALLED
OWNER-FURNISHED, CONTRACTOR-INSTALLED
WATTS
WEATHERPROOF
VOLT-AMPERE
1) DISCONNECTS ARE SHOWN AS FRAME RATING / FUSE SIZE.
2) PROVIDE DUCT SMOKE DETECTORS FOR ALL HVAC UNITS SUPPLYING 2,000 CFM
OR MORE. COORDINATE WITH FIRE ALARM CONTRACTOR.
3) ALL 120V, 15A AND 20A RECEPTACLES AND/OR EQUIPMENT CIRCUITS SHALL BE
GFCI PROTECTED PER NOTE 2, UNLESS NOTED OTERWISE/
SCHEDULE NOTES: ABBREVIATION: SCHEDULE GENERAL NOTES
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
NO. EQUIPMENT DESCRIPTION LOCATION KW MCA MOCP VOLTAGE
PHASES
CONDUIT
SIZE
WIRE SIZE DISC/FUSE/POLES CIRCUIT
NUMBER
NOTES
1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 A - 25,27
1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 B - 27,29
1201 HER 100C HEATER GYM 10.0 42.0 60 A 240 1 3/4" 3#8, 1#10 GND 60/60/2 B - 26,28
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E701
PANEL SCHEDULES
- ADMINISTRATION
BLDG 2083
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A
Total Load: 0 VA 0 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 -- -- -- -- 0 VA 0 VA -- -- -- -- 24
21 (E) OFFICE FURNACE 20 A 2 0 VA 0 VA 2 100 A (E) NEW PANEL 22
19 -- -- -- -- 0 VA 0 VA -- -- -- -- 20
17 (E) OFFICE FURNACE 30 A 2 0 VA 0 VA 2 100 A (E) "MAIN" SUB-PANEL 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8
5 (E) FURNACE #2 90 A 2 0 VA 0 VA 2 30 A SPARE 6
3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4
1 (E) FURNACE #1 90 A 2 0 VA 0 VA 2 100 A (E) BUILDING MAIN 2
C K T
# ITEM
N O T E
A M P S
P O L E A B
P O L E
A M P S
N O T
E ITEM
C K T
MCB
225 A
A.I.C. RATING:
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: SURFACE
MECH TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE
NEW PANEL A SCHEDULE
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A
Total Load: 0 VA 0 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) AO-CD LIGHTS 20
17 (E) PEPSI MACHIE, MICROWAVE, FRIDGE (CONF... 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - HALL,COPYRM, RECPT, PURCH, WOME... 18
15 (E) STUDENT RECEPTIONIST 20 A 1 0 VA 0 VA 1 20 A (E) HALL LIGHTS - EAST HALLWAY 16
13 (E) COPIER, EXIT SIGN 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - SSS, PERSONNEL, RECORDS 14
11 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS - FURNACE, FORMS, COFFEE ROOM 12
9 (E) REGULAR OUTLETS: AO, CD, RECPTION 20 A 1 0 VA 0 VA 1 20 A (E) UNKNOWN TBD 10
7 (E) BATHROOMS 20 A 1 0 VA 0 VA 1 20 A (E) OUTSIDE LIGHTS 8
5 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) MAILROOM REG OUTLETS 6
3 (E) UNKNOWN TBD 20 A 1 0 VA 0 VA 1 20 A (E) UNKNOWN TBD 4
1 (E) WATERHEATER DISCONNECTED? 20 A 1 0 VA 0 VA 1 20 A (E) WATERHEATER DISCONNECTED? 2
C K T
# ITEM
N O T E
A M P S
P O L E A B
P O L E
A M P S
N O T
E ITEM
C K T
MCB
225 A
A.I.C. RATING:
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
RECEPTION TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE
PANEL B SCHEDULE
SAZAN #
Drawn:
Checked:
Date:
Contents:
Project:
Sheet Number:
# DESCRIPTION DATE
111 SW Fifth Ave., Ste. 3210 Portland, Oregon 97204
Tel 503.416.2400 Fax 503.416.2087
4/ 1/
:3
5:
P M
4/ 1/
:3
5:
P M
E702
PANEL SCHEDULES
- GYMNASIUM
BLDG 2889
04/02/2025
D45-24001
Checker
Author
100% CD
UNITED STATES
DEPARTMENT
OF
AGRICULTURE
ANGELL JOB CORPS
CIVILIAN
CONSERVATION
CENTER
D45-24001
335 NE BLODGETT
ROAD
YACHATS, OR 97498
Notes:
Total Est. Demand Current: 42 A
Total Conn. Current: 42 A
Total Est. Demand: 10000 VA
Total Conn. Load: 10000 VA
Heating 10000 VA 100.00% 10000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 42 A 42 A
Total Load: 5000 VA 5000 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 -- -- -- -- 5000 VA 0 VA 1 20 A SPARE 28
25 GYM HEATER 60 A 2 5000 VA 0 VA 1 20 A SPARE 26
23 (E) PLUGS - TV ROOM 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 24
21 (E) GAME ROOM + OUTSIDE LIGHT 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 22
19 (E) INTERNET BOOSTER 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS - TV & POOL ROOMS 20
17 (E) PLUGS 20 A 1 0 VA 0 VA 1 20 A (E) LIGHTS & PLUGS W WALL 18
15 (E) LIGHTS 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS - WEST & NORTH 16
13 (E) PLUGS 20 A 1 0 VA 0 VA 1 20 A (E) PLUGS 14
11 -- -- -- -- 0 VA 0 VA -- -- -- -- 12
9 (E) PIZZA OVEN 60 A 2 0 VA 0 VA 2 20 A (E) OFFICE HEAT 10
7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8
5 (E) HEAT - SW MULTIPURPOSE ROOM 30 A 2 0 VA 0 VA 2 30 A SPARE 6
3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4
1 (E) HEAT 30 A 2 0 VA 0 VA 2 30 A (E) HEAT - NE MULTIPURPOSE ROOM 2
C K T
# ITEM
N O T E
A M P S
P O L E A B
P O L E
A M P S
N O T
E ITEM
C K T
MCB
400 A
A.I.C. RATING:
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
WEIGHT/BOXING ROOM TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE
PANEL A SCHEDULE
Notes:
Total Est. Demand Current: 83 A
Total Conn. Current: 83 A
Total Est. Demand: 20000 VA
Total Conn. Load: 20000 VA
Heating 20000 VA 100.00% 20000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 83 A 83 A
Total Load: 10000 VA 10000 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 -- -- -- -- 5000 VA 0 VA 1 20 A SPARE 30
27 GYM HEATER 60 A 2 5000 VA 5000 VA -- -- -- -- 28
25 (E) CHLORIDE CHARGER 20 A 1 0 VA 5000 VA 2 60 A GYM HEATER 26
23 (E) OUTLETS; ARTS STOR. 20 A 1 0 VA 0 VA 1 20 A (E) OUTLETS; BAND 24
21 (E) OUTLETS; BAND 20 A 1 0 VA 0 VA 1 20 A (E) OUTLETS; ARTS STOR. 22
19 (E) LITES; ARTS SOUTH 20 A 1 0 VA 0 VA 1 20 A (E) LITES; KILN. DRESS. TOIL. SHOWER 20
17 (E) LITES; ARTS NORTH 20 A 1 0 VA 0 VA 1 20 A (E) LITES & OUTSIDE FANS 18
15 (E) LITES; WEST RM 20 A 1 0 VA 0 VA -- -- -- -- 16
13 (E) OUTLETS; TOIL. KILN. DRESS. 20 A 1 0 VA 0 VA 2 60 A (E) KILN 14
11 -- -- -- -- 0 VA 0 VA -- -- -- -- 12
9 (E) HEATER 20 A 2 0 VA 0 VA 2 60 A (E) KILN 10
7 -- -- -- -- 0 VA 0 VA -- -- -- -- 8
5 (E) HEATER 20 A 2 0 VA 0 VA 2 20 A (E) HEATER 6
3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4
1 (E) HEATER 30 A 2 0 VA 0 VA 2 30 A (E) HEATER 2
C K T
# ITEM
N O T E
A M P S
P O L E A B
P O L E
A M P S
N O T
E ITEM
C K T
MCB
400 A
A.I.C. RATING:
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
GYMNASIUM TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE
PANEL B SCHEDULE
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A
Total Load: 0 VA 0 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 30
27 (E) SCOREBOARD #1 20 A 1 0 VA 0 VA 1 20 A (E) SPARE CIRCUIT TO GYM FLOOR ATTIC J-BOX 28
25 (E) FIRE ALARM 20 A 1 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 26
23 -- -- -- -- 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 24
21 (E) OVEN 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 22
19 -- -- -- -- 0 VA 0 VA 1 20 A (E) WORKOUT ROOM LIGHTS 20
17 SPARE 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLOOR LIGHTS 18
15 -- -- -- -- 0 VA 0 VA 1 20 A (E) WING LIGHTS POOL AREA 16
13 (E) MEN'S ROOM PLUGS 30 A 2 0 VA 0 VA 1 20 A (E) POOL AREA 14
11 -- -- -- -- 0 VA 0 VA 1 20 A (E) EXIT LIGHTS 12
9 (E) DRYER MEN'S BATHROOM 30 A 2 0 VA 0 VA 1 20 A (E) GYM FLR POOL GAME AREA 10
7 -- -- -- -- 0 VA 0 VA 1 20 A (E) SCOREBOARD #2 8
5 (E) UNIT HEAT - DRESSING 30 A 2 0 VA 0 VA 1 20 A (E) LIGHTS - SHOWER, TOILET, LOCKER 6
3 -- -- -- -- 0 VA 0 VA -- -- -- -- 4
1 (E) SPARE 30 A 2 0 VA 0 VA 2 20 A (E) UNIT HEAT - TOILET 2
C K T
# ITEM
N O T E
A M P S
P O L E A B
P O L E
A M P S
N O T
E ITEM
C K T
MCB
400 A
A.I.C. RATING:
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
WEIGHT/BOXING ROOM TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/240 1-PH, 3-WIRE
PANEL C SCHEDULE
| Sheets |
| E000 - GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX |
| E001 - ELECTRICAL LEGEND |
| E002 - ELECTRICAL POWER - SITE PLAN |
| E101 - ELECTRICAL DEMO - ADMINSTRATION BLDG 2083 |
| E102 - ELECTRICAL POWER - ADMINISTRATION BLDG 2083 |
| E201 - ELECTRICAL DEMO - GYMNASIUM BLDG 2889 |
| E202 - ELECTRICAL POWER - GYMNASIUM BLDG 2889 |
| E601 - ADMINISTRATION ONE-LINE DIAGRAM AND PANEL MOUNTING DETAIL |
| E602 - GYM ONE-LINE DIAGRAMS |
| E701 - PANEL SCHEDULES - ADMINISTRATION BLDG 2083 |
| E702 - PANEL SCHEDULES - GYMNASIUM BLDG 2889 |