Attachment 16 - Electrical 4 of 4.pdf
PDF 7 MB Posted
- Attached to
- Y1LZ--650-348 Construction of Valley Street Parking Lot Improvements Minor Construction- Providence, RI
- Solicitation number
- 36C77624R0040
About this file
This document package includes construction drawings and specifications for electrical, communications, and security systems for parking lot improvements at the Providence VA Medical Center in Rhode Island. The drawings detail requirements for site lighting, closed circuit television cameras, emergency call stations, a site utility cabinet, telecommunications conduits and handholes. Electrical work includes a service entrance, panelboards, site lighting circuits, and receptacles. Communications scope involves installing fiber optic cable, copper voice lines, and related termination equipment. Security requirements cover integrating new cameras into the existing VA video surveillance system. The related solicitation is for minor construction services under contract number 36C77624R0040 with the Department of Veterans Affairs for the Valley Street Parking Lot Improvements project located in Providence, Rhode Island.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
CONSTRUCTION
DOCUMENTS
VAMC PROVIDENCE
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SITE IMPROVEMENTS AT
500 VALLEY STREET
PROVIDENCE, RI 02919
650-348
N/A Project Director
Revisions: Date:
Patriot Design, LLC A Fort Hill / HCS Group Joint Venture 8403 Crossland Loop Montgomery, AL
JDW TAT06-09-2023
PANELBOARD SCHEDULE,
DETAILS, AND REQUIREMENTS
E-700
AutoCAD SHX Text
%%UTYPICAL PANELBOARD DETAILS AND REQUIREMENTS
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
1. PANELBOARD & PANELBOARD INSTALLATION TO BE IN ACCORDANCE WITH NFPA 70, PANELBOARD & PANELBOARD INSTALLATION TO BE IN ACCORDANCE WITH NFPA 70, CURRENT NEC. ALL PANELBOARDS SHALL BE UL LISTED AND INSTALLED IN ACCORDANCE WITH THIS LISTING AND FULLY SUPPORTED BY MEANS DESIGNED FOR THAT LISTED INSTALLATION. ALL CLEARANCES REQUIRED BY CODE SHALL BE MAINTAINED AS A MINIMUM. 2. EACH PANELBOARD SHALL BE FURNISHED COMPLETE WITH THE PROPERLY SIZED CAN, EACH PANELBOARD SHALL BE FURNISHED COMPLETE WITH THE PROPERLY SIZED CAN, INTERNAL HARDWARE, DEVICES, COMPONENTS, SUPPORTING STRUCTURES, ETC., FOR A COMPLETE INSTALLATION TO PROVIDE THE DESIGNED PERFORMANCE UNDER THE AMBIENT CONDITIONS ENCOUNTERED. ALL DEVICES, COMPONENTS, FITTINGS, SUPPORTS, ETC., SHALL BE COORDINATED TO PROVIDE A COMPLETE UL LISTED INSTALLATION. ALL DEVICES INSTALLED SHALL HAVE AN INTERRUPTING RATING GREATER THAN OR EQUAL TO THE SPECIFIED SCCR. 3. EACH PANELBOARD SHALL BE FURNISHED WITH A GROUND BAR BONDED TO THE PANEL EACH PANELBOARD SHALL BE FURNISHED WITH A GROUND BAR BONDED TO THE PANEL ENCLOSURE. THIS GROUND BUS SHALL BE UTILIZED TO BOND ALL GROUNDING PROVISIONS IN ORDER TO ESTABLISH EQUAL POTENTIAL TO ALL GROUNDED COMPONENTS OF THE POWER SYSTEM NETWORK. 4. PANELBOARD CANS SHALL BE RIGID AND CONTAIN KNOCK-OUT PROVISIONS TO PANELBOARD CANS SHALL BE RIGID AND CONTAIN KNOCK-OUT PROVISIONS TO FACILITATE THE TERMINATION OF THE NUMBER AND SIZE OF CONDUIT SYSTEMS REQUIRED. 5. THE TERMINATION POINT OF THE FEEDER SERVING EACH ASSEMBLY SHALL BE AT THE THE TERMINATION POINT OF THE FEEDER SERVING EACH ASSEMBLY SHALL BE AT THE NEAREST POINT OF FEEDER ENTRY TO MINIMIZE CONDUCTOR FILL IN THE CAN. COORDINATE TOP/BOTTOM FEED PANELBOARD PROVISIONS WITH EACH FEEDER INSTALLATION. 6. PROVIDE THE PROPERLY SIZED CONDUCTOR TERMINATION POINTS OR LUGS (MULTIPLE PROVIDE THE PROPERLY SIZED CONDUCTOR TERMINATION POINTS OR LUGS (MULTIPLE LUGS WHEN PARALLEL FEEDERS ARE USED) FOR THE NUMBER AND SIZE CIRCUITS INDICATED. 7. CONDUCTORS, SPLICES AND TERMINATIONS SHALL BE ACCESSIBLE. ONLY CONDUCTORS CONDUCTORS, SPLICES AND TERMINATIONS SHALL BE ACCESSIBLE. ONLY CONDUCTORS RATED AND SIZED FOR THE TEMPERATURE OF THE TERMINATION SHALL BE USED. 8. PANELBOARDS SHALL NOT BE INSTALLED IN CONTACT WITH COMBUSTIBLE MATERIALS. PANELBOARDS SHALL NOT BE INSTALLED IN CONTACT WITH COMBUSTIBLE MATERIALS. ADEQUATE SPACE FOR AIR CIRCULATION AND CODE COMPLIANCE SHALL BE PROVIDED AS A MINIMUM. FURNISH SPACERS, WASHERS, SUPPORT DEVICES, ETC., AS REQUIRED TO MAINTAIN PROPER CLEARANCES. EXTERIOR PANELS SHALL CONTAIN AT LEAST 15mm(0.6") OF AIR SPACE BETWEEN THE CABINET AND SURFACE. 9. EACH PANELBOARD SHALL BE FURNISHED WITH THE FOLLOWING ACCESSORIES: EACH PANELBOARD SHALL BE FURNISHED WITH THE FOLLOWING ACCESSORIES: * DOOR - IN - DOOR TRIM * TWO KEYS * ONE-HALF PINT CONTAINER OF TOUCH-UP PAINT FOR EACH SURFACE MOUNTED PANELBOARD * METAL DIRECTORY FRAME WITH TYPED DIRECTORY * FILLER PLATES FOR KNOCK-OUT SPACES FOR UNUSED OPENINGS 10. PROVIDE ARC-FLASH HAZARD WARNING SIGNS PER NFPA 70 & 70E. PROVIDE ARC-FLASH HAZARD WARNING SIGNS PER NFPA 70 & 70E. * REFER TO ANSI Z535.4 * LOCATE ON FRONT OF DOOR.
AutoCAD SHX Text
DETAIL - TYPICAL PANELBOARD PROVISIONS
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text SPACE NOTES: 1. DIMENSIONS SHOWN ARE MINIMUM. DIMENSIONS SHOWN ARE MINIMUM. 2. WORKING SPACE IS DEFINED AS THE SPACE IN FRONT OF THE PANEL FOR EXAMINATION, WORKING SPACE IS DEFINED AS THE SPACE IN FRONT OF THE PANEL FOR EXAMINATION, ADJUSTMENTS, SERVICING AND/OR MAINTENANCE WHILE ENERGIZED. IN ALL CASES WORK SPACES SHALL PERMIT AT LEAST A 90 DEG. OPENING OF EQUIPMENT DOORS OR HINGED PANELS. WIDTH: 762mm(30") OR WIDTH OF EQUIPMENT (WHICHEVER IS GREATER) HEIGHT: 2.0m(6'-6") FROM FLOOR OR HEIGHT OF EQUIPMENT. (WHICHEVER IS GREATER) DEPTH: DEPENDS ON CONDITIONS OUTLINED IN PANEL WORKING SPACES CHART. 3. DEDICATED ELECTRICAL SPACE IS DEFINED AS THE SPACE EQUAL TO THE WIDTH AND DEDICATED ELECTRICAL SPACE IS DEFINED AS THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT, EXTENDING FROM FLOOR TO A HEIGHT OF 1.8m(6'-0") ABOVE THE EQUIPMENT OR TO THE STRUCTURAL CEILING. (WHICHEVER IS LOWER) 4. SEE NFPA 70, CURRENT NEC.SEE NFPA 70, CURRENT NEC.
AutoCAD SHX Text
PANELBOARD SCHEDULE & DETAIL - KEY LEGEND
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
MAINS & CIRCUIT BREAKERS
AutoCAD SHX Text
MISC. TERMS
AutoCAD SHX Text
A AMPERE AMPERE PH PHASE PHASE V VOLTAGE VOLTAGE W WIRE WIRE Y WYE WYE DELTA
AutoCAD SHX Text
F FLUSH FLUSH FS FREE STANDING FREE STANDING S SURFACESURFACE
AutoCAD SHX Text GF GROUND FAULT CIRCUIT INTERRUPTER L LOCKHANDLE TYPE MCB MAIN CIRCUIT BREAKER MLO MAIN LUGS ONLY SD SWITCH DUTY ST SHUNT TRIP TYPE
AutoCAD SHX Text AIC AMPERE INTERRUPTING CAPACITY AMPERE INTERRUPTING CAPACITY BCB BOLT-ON CIRCUIT BREAKER BOLT-ON CIRCUIT BREAKER SCCR SHORT CIRCUIT CURRENT RATING SHORT CIRCUIT CURRENT RATING FUS FUSIBLE SWITCH FUSIBLE SWITCH LC LOAD CENTER LOAD CENTER SE SERVICE ENTRANCESERVICE ENTRANCE
AutoCAD SHX Text
DIMENSION BLOCK
AutoCAD SHX Text
REF
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
SI
AutoCAD SHX Text
ENGLISH
AutoCAD SHX Text 1m
AutoCAD SHX Text .38m
AutoCAD SHX Text 2.0m
AutoCAD SHX Text 6'-7"
AutoCAD SHX Text 1'-3"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text
%%USURFACE MTG.
AutoCAD SHX Text SURFACE CAN FULLY SUPPORTED 15mm(0.6") OFF WALL. SEE NOTE 8 THIS SHEET
AutoCAD SHX Text
SURFACE COVER
AutoCAD SHX Text
WALL CONSTRUCTION
AutoCAD SHX Text
BRANCH CIR & FEEDER CONDUITS (TYPICAL)
AutoCAD SHX Text D
AutoCAD SHX Text 1.82m
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text D
AutoCAD SHX Text
PANEL-A
AutoCAD SHX Text
120/208V, 3PH,4W 225 AMPERE FED FROM PNL-? CIR. BKR #?
AutoCAD SHX Text
EXTRA KEY KEPT IN PANEL
AutoCAD SHX Text
VAULT HANDLE WITH PADLOCKABLE CONSTRUCTION
AutoCAD SHX Text
TYPED CIRCUIT DIRECTORY IN METAL FRAME
AutoCAD SHX Text
FIELD INSTALLED NAMEPLATE
AutoCAD SHX Text
IDENTIFICATION PLATE AND UL LABEL
AutoCAD SHX Text
CIRCUIT BREAKER INSTALLATION
AutoCAD SHX Text
%%UTYPICAL FRONT VIEW - NEMA 3R AND 4X
AutoCAD SHX Text
GASKETED DOOR
AutoCAD SHX Text
PANEL WORKING SPACES
AutoCAD SHX Text NOTE: WHERE THE CONDITIONS ARE AS FOLLOWS: CONDITION 1 - EXPOSED LIVE PARTS ON ONE SIDE OF THE WORKING SPACE AND NO - EXPOSED LIVE PARTS ON ONE SIDE OF THE WORKING SPACE AND NO LIVE OR GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING SPACE, OR EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING SPACE THAT ARE EFFECTIVELY GUARDED BY INSULATING MATERIALS. CONDITION 2 - EXPOSED LIVE PARTS ON ONE SIDE OF THE WORKING SPACE AND - EXPOSED LIVE PARTS ON ONE SIDE OF THE WORKING SPACE AND GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING SPACE. CONCRETE, BRICK, OR TILE WALLS SHALL BE CONSIDERED AS GROUNDED. CONDITION 3 - EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING SPACE. - EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING SPACE.
AutoCAD SHX Text
%%UWORKING CLEARANCE DIAGRAM
AutoCAD SHX Text
WORKING SPACE (SEE SPACE NOTE 2)
AutoCAD SHX Text
DEDICATED ELECTRICAL SPACE (SEE SPACE NOTE 3)
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
LINE OF STRUCTURAL CEILING
AutoCAD SHX Text
TYPICAL BRANCH CKT OR FEEDER
AutoCAD SHX Text
SPARE CONDUIT
AutoCAD SHX Text PANEL NAME - 12.7mm(1/2") HIGH WHITE LETTERS
AutoCAD SHX Text PANEL VOLTAGE - 6.35mm(1/4") HIGH WHITE LETTERS
AutoCAD SHX Text SERVICE TO THIS PANEL - 6.35mm(1/4") HIGH WHITE LETTERS
AutoCAD SHX Text
MICARTA ENGRAVED NAMEPLATE SHALL BE AS NOTED:
AutoCAD SHX Text
120/208V, 3PH,4W 225 AMPERE FED FROM PNL-? CIR. BKR #?
AutoCAD SHX Text PANEL AMPERE RATING - 6.35mm(1/4") HIGH WHITE LETTERS
AutoCAD SHX Text
PANEL-?
AutoCAD SHX Text
SEE NOTE 11 THIS SHEET
AutoCAD SHX Text
NOMINAL VOLTAGE TO GROUND
AutoCAD SHX Text
CONDITION 1
AutoCAD SHX Text
CONDITION 2
AutoCAD SHX Text
CONDITION 3
AutoCAD SHX Text
MINIMUM CLEAR DISTANCE
AutoCAD SHX Text 0-150
AutoCAD SHX Text 151-600
AutoCAD SHX Text 914mm (3')
AutoCAD SHX Text 914mm (3')
AutoCAD SHX Text 1.07m (3'-6")
AutoCAD SHX Text 914mm (3')
AutoCAD SHX Text 914mm (3')
AutoCAD SHX Text 1.22m (4')
AutoCAD SHX Text
TYP. PANEL NAMEPLATE
AutoCAD SHX Text
%%UTYPICAL PANELBOARD 1-PHASE
AutoCAD SHX Text
%%UCIRCUITING DIAGRAM
AutoCAD SHX Text G R D B U S
AutoCAD SHX Text
CONTINUED AS INDICATED
AutoCAD SHX Text
CIR NO'S (TYP)
AutoCAD SHX Text
PHASE BUS BAR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
NEUTRAL BUS
AutoCAD SHX Text A
AutoCAD SHX Text E701
AutoCAD SHX Text
PANELBOARD SCHEDULE AND DETAIL NOTES
apunt Stamp apunt Stamp
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Fi le
P at h
CONSTRUCTION
DOCUMENTS
VAMC PROVIDENCE
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SITE IMPROVEMENTS AT
500 VALLEY STREET
PROVIDENCE, RI 02919
650-348
N/A Project Director
Revisions: Date:
Patriot Design, LLC A Fort Hill / HCS Group Joint Venture 8403 Crossland Loop Montgomery, AL
JDW TAT06-09-2023
SECURITY SYSTEM AND EMERGENCY
CALL STATION REQUIREMENTS
E-801
E M E R G E N C Y
AutoCAD SHX Text
AND EMERGENCY CALL STATION(EC) RISER DIAGRAM
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
SITE UTILITY CABINET
AutoCAD SHX Text
FIBER MEDIA CONVERTER
AutoCAD SHX Text
CLOSED CIRCUIT TELEVISION PAN/TILT/ZOOM EXTERIOR CAMERA
AutoCAD SHX Text
UNINTERRUPTIBLE POWER SUPPLY
AutoCAD SHX Text
CAT6E CABLE IN 1" CONDUIT
AutoCAD SHX Text
CCTV AND EMERGENCY CALL STATION EQUIPMENT LEGEND
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
UPS
AutoCAD SHX Text
CAT6E
AutoCAD SHX Text
CON
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UPS
AutoCAD SHX Text
1. PROVIDE ALL MODIFICATIONS REQUIRED TO PROVIDE ALL MODIFICATIONS REQUIRED TO EXISTING PANELS, PROGRAMMING, ETC. IN ORDER TO CONNECT THE PARKING LOT CAMERAS TO THE EXISTING VA CAMERA SYSTEM INFRASTRUCTURE. * PROVIDE NEW POWERED SWITCH PROVIDE NEW POWERED SWITCH * PROVIDE POE INJECTOR. PROVIDE POE INJECTOR. * PROVIDE FIBER MEDIA CONVERTER PROVIDE FIBER MEDIA CONVERTER * PROVIDE A UPS PLUG - IN DEVICE.PROVIDE A UPS PLUG - IN DEVICE.
AutoCAD SHX Text
CON
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
AutoCAD SHX Text POWERED SWITCH. SEE SPECIFICATIONS. POE INJECTOR. SEE SPECIFICATIONS. FIBER TO ETHERNET MEDIA CONVERTER. SEE SPECIFICATIONS. UPS DEVICE. SEE SPECIFICATIONS. SINGLE MODE 12 STRAND FIBER * SEE TELECOM SLD SHEET E-802 SEE TELECOM SLD SHEET E-802 FIBER PATCH PANEL. SEE SPECIFICATIONS. CAT6E CABLE IN 1" CONDUIT 6 PAIR 24AWG COPPER TELEPHONE CABLE. CMR JACKET, GRAY COLOR, TERMINATE AS REQUIRED ON PROTECTOR BLOCKS. 110 BLOCK VOICE PUNCHDOWN. * 10 PAIR 10 PAIR * RACK MTD IN SITE UTILITY CABINET RACK MTD IN SITE UTILITY CABINET ENCLOSURE.
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
KEYED NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TO BLDG 32
AutoCAD SHX Text
CCTV HUB LOCATION
AutoCAD SHX Text
AutoCAD SHX Text
CONSTANT-ON BLUE LAMP
AutoCAD SHX Text
WITH STROBE OR BEACON.
AutoCAD SHX Text
POLE SHALL BE ADA COMPLIANT
AutoCAD SHX Text
BRANCH CIRCUIT
AutoCAD SHX Text
CONDUCTORS (THWN)
AutoCAD SHX Text
TELEPHONE/BEACON CONNECTION
AutoCAD SHX Text
TELEPHONE LIGHT
AutoCAD SHX Text
EMERGENCY TELEPHONE SINGLE
AutoCAD SHX Text
BUTTON FLUSH MOUNTED
AutoCAD SHX Text 108"
AutoCAD SHX Text
PROVIDE CAT. 6 VOICE
AutoCAD SHX Text
CABLE IN 1/2" CORRUGATED
AutoCAD SHX Text
TUBING (CARLON "CARFLEX
AutoCAD SHX Text
EFT" OR EQUAL WITH
AutoCAD SHX Text
REQUIRED COUPLINGS AND
AutoCAD SHX Text
TERMINAL ADAPTERS)
AutoCAD SHX Text
BRANCH CIRCUIT
AutoCAD SHX Text
CONDUCTORS
AutoCAD SHX Text
41-5/8" TO BUTTON
AutoCAD SHX Text
HANDHOLE
AutoCAD SHX Text
BRANCH CIRCUIT GROUND
AutoCAD SHX Text
CONDUCTOR SHALL BE
AutoCAD SHX Text
BONDED TO POLE
AutoCAD SHX Text
DRILL 1/8" WEEP
AutoCAD SHX Text
HOLE 1/2" OFF BASE
AutoCAD SHX Text 2"
AutoCAD SHX Text 12"
AutoCAD SHX Text 3"
AutoCAD SHX Text 24"
AutoCAD SHX Text
SIDEWALK
AutoCAD SHX Text
EXTEND SIDEWALK AROUND
AutoCAD SHX Text
BASE. MINIMUM 48" WIDE
AutoCAD SHX Text
TEXT AND EMBLEM IN
AutoCAD SHX Text
WHITE ON ALL FOUR SIDES
AutoCAD SHX Text
ANCHOR BOLT. TOTAL OF 4.
AutoCAD SHX Text 33"
AutoCAD SHX Text
3,000 PSI CONCRETE BASE
AutoCAD SHX Text
REINFORCEMENT CAGE SHALL BE
AutoCAD SHX Text
(4) #4 REBARS WITH (3) #4 REBAR
AutoCAD SHX Text
TIES, AND (1) 18" ROUND SONOTUBE
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text
SYMBOL:
AutoCAD SHX Text
CONDUIT FOR 120VAC POWER.
AutoCAD SHX Text
POLE MTD EMERGENCY CALL STATION
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
EMERGENCY CALL STATION - SEE DETAIL B/E-801
AutoCAD SHX Text
EC
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
EC
AutoCAD SHX Text
SEE DETAIL B,
AutoCAD SHX Text
THIS SHEET
AutoCAD SHX Text
TYPICAL CLOSED CIRCUIT TELEVISION (CCTV)
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
EC
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text C
AutoCAD SHX Text
SITE LIGHTING POLE
AutoCAD SHX Text
TYPICAL EXTERIOR POLE MOUNT PTZ CCTV CAMERA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WALL MOUNT ADAPTER
AutoCAD SHX Text
POLE MOUNT ADAPTER
AutoCAD SHX Text
* SEE SHEET E600
AutoCAD SHX Text
* SEE SHEETS E101 & E600 SEE SHEETS E101 & E600 * MTG HEIGHT SHALL BE 8' MTG HEIGHT SHALL BE 8' ABOVE CONCRETE BASE
AutoCAD SHX Text
FESTOON RECEPTACLE (WHEN NOTED)
AutoCAD SHX Text
* MTG HEIGHT SHALL MTG HEIGHT SHALL BE 20' ABOVE CONCRETE BASE
AutoCAD SHX Text
PTZ CCTV
AutoCAD SHX Text
CCTV
AutoCAD SHX Text
* CAT6E, 1/2" CORRUGATED CAT6E, 1/2" CORRUGATED LIQUID-TIGHT TUBING * PROVIDE REQUIRED PROVIDE REQUIRED COUPLINGS AND TERMINAL ADAPTERS
AutoCAD SHX Text
* MTG HEIGHT SHALL BE 25' MTG HEIGHT SHALL BE 25' ABOVE CONCRETE BASE. * SEE SHEET E600.SEE SHEET E600.
AutoCAD SHX Text
SITE LIGHTING LUMINAIRE
AutoCAD SHX Text
* NEMA 5-20R, GFCI, WEATHER NEMA 5-20R, GFCI, WEATHER PROOF IN-USE COVER * MTG HEIGHT SHALL BE 20' ABOVE MTG HEIGHT SHALL BE 20' ABOVE CONCRETE BASE
AutoCAD SHX Text
CCTV RECEPTACLE (WHEN NOTED)
AutoCAD SHX Text
LIGHTING CIRCUIT
AutoCAD SHX Text
CCTV PTZ POWER CIRCUIT
AutoCAD SHX Text
AutoCAD SHX Text
CONDUIT FOR VOICE COMMUNICATION TO SITE UTILITY CABINET
AutoCAD SHX Text
PATCH
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TO BLDG 32
AutoCAD SHX Text
TELEPHONE CONNECTION
AutoCAD SHX Text apunt Stamp
E-802
COMMUNICATIONS SINGLE LINE
DIAGRAM AND DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Fi le
P at h
CONSTRUCTION
DOCUMENTS
VAMC PROVIDENCE
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SITE IMPROVEMENTS AT
500 VALLEY STREET
PROVIDENCE, RI 02919
650-348
N/A Project Director
Revisions: Date:
Patriot Design, LLC A Fort Hill / HCS Group Joint Venture 8403 Crossland Loop Montgomery, AL
JDW TAT06-09-2023
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
FRONT VIEW
AutoCAD SHX Text
HVAC SYSTEM
AutoCAD SHX Text
SITE UTILITY CABINET ENCLOSURE
AutoCAD SHX Text B
AutoCAD SHX Text E802
AutoCAD SHX Text
TELECOM SINGLE LINE DIAGRAM
AutoCAD SHX Text
1. ENCLOSURE SHALL BE NEMA 3R (CLOSED LOOP ENCLOSURE SHALL BE NEMA 3R (CLOSED LOOP A/C) WITH LOCKING DOORS AND CREAM COLORED ALUMINUM FINISH. 2. ENCLOSURE SHALL BE CAPABLE OF ACCEPTING ENCLOSURE SHALL BE CAPABLE OF ACCEPTING RAILS FOR RACKING OF EQUIPMENT. 3. HVAC SYSTEM SHALL BE NEMA 3R RATED. HVAC SYSTEM SHALL BE NEMA 3R RATED. VOLTAGE SHALL BE 240V 1 . HVAC SYSTEMSHALL BE COMPATIBLE WITH THE ENCLOSURE MANUFACTURER AND BE CAPABLE OF MOUNTING TO THE SIDE OF THE ENCLOSURE. 4. FURNISH WITH RACKS AND TERMINATION DEVICES FURNISH WITH RACKS AND TERMINATION DEVICES FOR FIBER AND COPPER. 5. SITE UTILITY CABINET ENCLOSURE SHALL BE SITE UTILITY CABINET ENCLOSURE SHALL BE LOCATED ON BACKBOARD P. SEE SHEETS E-504 AND E-900.
AutoCAD SHX Text
DETAIL NOTES
AutoCAD SHX Text
FEEDER SCHEDULE
AutoCAD SHX Text A
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
1. FURNISH AND INSTALL A FIBER AND VOICE FURNISH AND INSTALL A FIBER AND VOICE TELEPHONE INTERCONNECTION SYSTEM. 2. PROVIDE HANDHOLES AND PULL BOXES AS PROVIDE HANDHOLES AND PULL BOXES AS REQUIRED. 3. SEE COMMUNICATIONS SITE PLAN, SHEET SEE COMMUNICATIONS SITE PLAN, SHEET E-102. 4. COORDINATE WITH VAMC TELECOMMUNICATION COORDINATE WITH VAMC TELECOMMUNICATION PERSONNEL FOR LOCATION TO LAND FIBER STRANDS AND VOICE TELEPHONE COPPER. * CCTV SYSTEM CCTV SYSTEM * EMERGENCY CALL SYSTEM EMERGENCY CALL SYSTEM
AutoCAD SHX Text
SINGLE LINE DIAGRAM NOTES
AutoCAD SHX Text INSTALL PROTECTOR MODULE FOR CABLE TERMINATIONS VERTICAL 4"RMC RISER ON EXTERIOR OF BLDG. NEMA 3R PULLBOX FOR FIBERDUCT BANK PENETRATION INTO BLDG. SIZE AS REQUIRED. PENETRATE WALLS FOR CONDUIT ENTRY. * PATCH/REPAIR/PAINT TO MATCH EXISTING. PATCH/REPAIR/PAINT TO MATCH EXISTING. * SEE SHEET E-506.SEE SHEET E-506.
AutoCAD SHX Text
SINGLE LINE DIAGRAM KEYED NOTES
AutoCAD SHX Text
AutoCAD SHX Text
PLAN VIEW
AutoCAD SHX Text
ISOMETRIC VIEW
AutoCAD SHX Text
NEW VA
AutoCAD SHX Text
PARKING LOT
AutoCAD SHX Text
TELECOM ROOM
AutoCAD SHX Text
SITE UTILITY
AutoCAD SHX Text
CABINET
AutoCAD SHX Text
AutoCAD SHX Text
BLDG 32
AutoCAD SHX Text
BASEMENT LEVEL
AutoCAD SHX Text
HH
AutoCAD SHX Text A
AutoCAD SHX Text
HH
AutoCAD SHX Text
CONCRETE ENCASED DUCT BANK
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text 10"
AutoCAD SHX Text 20"
AutoCAD SHX Text
ENCLOSURE VENT
AutoCAD SHX Text
3 PAIR LOCKING DOOR
AutoCAD SHX Text 24"W
AutoCAD SHX Text 39"H
AutoCAD SHX Text 24"W
AutoCAD SHX Text 24"D
AutoCAD SHX Text 43 7/8"
AutoCAD SHX Text
TYP COMM HANDHOLE
AutoCAD SHX Text
* SEE SHEET E-402
AutoCAD SHX Text
* SEE C/E-401
AutoCAD SHX Text
SEE DETAIL B/E-802
AutoCAD SHX Text J
AutoCAD SHX Text 12 STRAND SINGLE-MODE FIBER OPTIC CABLE 4" CONDUIT & 6 PAIR COPPER TELEPHONE CABLE 4"C
AutoCAD SHX Text
AutoCAD SHX Text
HH
AutoCAD SHX Text
HH
AutoCAD SHX Text
HH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text E802
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
PP
AutoCAD SHX Text B
AutoCAD SHX Text 12 STRAND SINGLE-MODE FIBER OPTIC CABLE 1" CONDUIT & 6 PAIR COPPER TELEPHONE CABLE 1"C
AutoCAD SHX Text
EX: PATCH PANEL AND 110 BLOCKS.
AutoCAD SHX Text
AutoCAD SHX Text B apunt Stamp
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
CONSTRUCTION
DOCUMENTS
VAMC PROVIDENCE
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SITE IMPROVEMENTS AT
500 VALLEY STREET
PROVIDENCE, RI 02919
650-348
N/A Project Director
Revisions: Date:
Patriot Design, LLC A Fort Hill / HCS Group Joint Venture 8403 Crossland Loop Montgomery, AL
JDW TAT06-09-2023
SINGLE LINE DIAGRAM, NOTES,
SYMBOLS AND SCHEDULES
E-900
AutoCAD SHX Text
CIRCUIT BREAKER SCHEDULE
AutoCAD SHX Text
DES
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
MC
AutoCAD SHX Text
MOLDED-CASE
AutoCAD SHX Text
NEMA AB1 THERMAL MAGNETIC
AutoCAD SHX Text
PCB
AutoCAD SHX Text
POWER CIRCUIT BREAKER
AutoCAD SHX Text
ANSI/IEEE C37.13 ANSI C37.16
AutoCAD SHX Text
IC
AutoCAD SHX Text
INSULATED CASE
AutoCAD SHX Text
MCC
AutoCAD SHX Text
MOLDED-CASE
AutoCAD SHX Text
NEMA AB1 MAGNETIC ONLY
AutoCAD SHX Text NOTES: 1. LOW VOLTAGE CIRCUIT BREAKERS SHALL BE IN ACCORDANCE WITH ANSI C37.100 AND UL 489.LOW VOLTAGE CIRCUIT BREAKERS SHALL BE IN ACCORDANCE WITH ANSI C37.100 AND UL 489.
AutoCAD SHX Text
1. THE PURPOSE OF THE DIAGRAM IS TO DEMONSTRATE THE POWER SYSTEM SERVICE THE PURPOSE OF THE DIAGRAM IS TO DEMONSTRATE THE POWER SYSTEM SERVICE REQUIREMENTS, BUS CAPACITIES, FEEDER REQUIREMENTS, LEVELS OF PROTECTION, ETC., IN ORDER TO PROVIDE A COORDINATED AND PROTECTED POWER DISTRIBUTION SYSTEM. 2. AMPERE INTERRUPTING CAPACITY OR SHORT CIRCUIT CURRENT RATINGS ARE AMPERE INTERRUPTING CAPACITY OR SHORT CIRCUIT CURRENT RATINGS ARE INDICATED AT VARIOUS BUSES IN THE SYSTEM AND THE CONTRACTOR SHALL COORDINATE, FURNISH AND INSTALL THE PROPER EQUIPMENT, DEVICES, TERMINATIONS AND MATERIAL AT THOSE LOCATIONS CAPABLE OF INTERRUPTING AND/OR WITHSTANDING THESE CURRENTS WITHOUT DAMAGE IN ACCORDANCE WITH UL AND THE NEC. 3. ALL OVERCURRENT PROTECTIVE DEVICES FOR THIS PROJECT SHALL BE CURRENT ALL OVERCURRENT PROTECTIVE DEVICES FOR THIS PROJECT SHALL BE CURRENT SENSING DEVICES AND SHALL PROTECT ALL BUSES, CONDUCTORS, EQUIPMENT, DEVICES, MOTORS, APPLIANCES, TRANSFORMERS AND SYSTEMS INDICATED. THE FOLLOWING TYPES OF PROTECTION SHALL BE PROVIDED: OVERCURRENT SHORT CIRCUIT OVERLOAD THE FOLLOWING TYPES OF DEVICES ARE TO BE USED AND COORDINATED FOR THIS PROJECT: CIRCUIT BREAKERS FUSES 4. APPLICATION, INSTALLATION AND CONNECTION OF ALL DEVICES SHALL BE IN APPLICATION, INSTALLATION AND CONNECTION OF ALL DEVICES SHALL BE IN ACCORDANCE WITH THE NEC, MANUFACTURER'S RECOMMENDATIONS AND CONTRACT DOCUMENTS. 5. ALL EQUIPMENT LOADS AND PROTECTION ARE TYPICAL AND BASED UPON DESIGN ALL EQUIPMENT LOADS AND PROTECTION ARE TYPICAL AND BASED UPON DESIGN CALCULATIONS FOR BIDDING PURPOSES. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE AND VERIFY WITH ALL DIVISIONS THE ACTUAL NAMEPLATE DATA OF ALL EQUIPMENT AND DEVICES SUPPLIED ON THIS PROJECT. BASE BID SHALL INCLUDE PROVIDING THE PROPER PROTECTIVE DEVICES FOR ALL COMPONENTS OF THE ELECTRICAL SYSTEM IN ACCORDANCE WITH NOTE 3 ABOVE AND AS PER EQUIPMENT MANUFACTURER'S NAMEPLATE DATA OR INSTRUCTIONS. THE CONTRACT DRAWINGS MAY NOT SIZE THE ACTUAL FUSE SIZE FOR CERTAIN SYSTEMS AND THE CONTRACTOR WILL BE RESPONSIBLE TO SIZE IN ACCORDANCE WITH NAMEPLATE DATA AND FURNISH THIS INFORMATION WITH THE AS-BUILT DRAWINGS. 6. CIRCUIT BREAKERS SHALL BE INSTALLED AS INDICATED RATED FOR THE PROPER CIRCUIT BREAKERS SHALL BE INSTALLED AS INDICATED RATED FOR THE PROPER VOLTAGE POTENTIAL, CURRENT, FREQUENCY, AND THE INTERRUPTING RATING INDICATED. CIRCUIT BREAKERS SHALL BE INSTALLED IN UL LISTED ENCLOSURES WITHIN THE ENVIRONMENTAL LIMITATION LISTED OF THE UNIT, SUCH AS AMBIENT TEMPERATURE, HUMIDITY, CLEAN & FREE FROM CONTAMINANTS. CIRCUIT BREAKERS SHALL PROVIDE SIMULTANEOUS DISCONNECTION OF ALL PHASE CONDUCTORS DURING TRIPPING. ALL LOW VOLTAGE CIRCUIT BREAKERS WITHIN THE SYSTEM SHALL BE OF THE SAME MANUFACTURER SO THAT COORDINATION UP AND DOWN STREAM CAN BE FACILITATED. 7. FUSES SHALL BE INSTALLED AS INDICATED, RATED FOR THE PROPER VOLTAGE FUSES SHALL BE INSTALLED AS INDICATED, RATED FOR THE PROPER VOLTAGE POTENTIAL, CURRENT, FREQUENCY, MAXIMUM PEAK LET THROUGH, MAXIMUM CLEARING THERMAL ENERGY (I T), AND THE INTERRUPTING RATING INDICATED. FUSES SHALL BE INSTALLED IN UL LISTED ENCLOSURES WITHIN THE ENVIRONMENTAL LIMITATION LISTING OF THE UNITS, SUCH AS AMBIENT TEMPERATURE, HUMIDITY, CLEAN & FREE FROM CONTAMINANTS. ALL FUSES WITHIN THE SYSTEM SHALL BE OF THE SAME MANUFACTURER SO THAT COORDINATION UP AND DOWN STREAM CAN BE FACILITATED. 8. WHEN APPLYING AND INSTALLING PROTECTIVE DEVICES THE CONTRACTOR SHALL TAKE WHEN APPLYING AND INSTALLING PROTECTIVE DEVICES THE CONTRACTOR SHALL TAKE INTO CONSIDERATION THE FOLLOWING: STEADY STATE CONTINUOUS CURRENT IN-RUSH CURRENT FROM MOTOR STARTING IN-RUSH CURRENT FROM TRANSFORMER MAGNETIZING UNDER LOAD SHORT CIRCUIT WITHSTAND RATINGS-NEC 110-10 AND 240-1 INTERRUPTING RATINGS-NEC 110-9 AND 230-65 CURRENT LIMITING LET THROUGH CURRENTS-NEC 240-11 10. THE CONTRACTOR IS TOTALLY RESPONSIBLE FOR THE INSTALLATION, MARKING AND THE CONTRACTOR IS TOTALLY RESPONSIBLE FOR THE INSTALLATION, MARKING AND CONNECTING OF ALL POWER CONDUCTORS FOR THE PROPER PHASE SEQUENCE AND BALANCED LOADING. PHASE METERS SHALL BE USED TO TEST EACH FEEDER AND MOTOR BRANCH CIRCUIT PRIOR TO CONNECTING LOADS.
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text
DISCONNECT SWITCH - NONFUSIBLE
AutoCAD SHX Text
DISCONNECT - FUSIBLE
AutoCAD SHX Text
MOTOR CONTROLLER
AutoCAD SHX Text
COMBINATION CONTROLLER/CIRCUIT BREAKER
AutoCAD SHX Text
COMBINATION CONTROLLER/FUSED DISCONNECT SWITCH
AutoCAD SHX Text
TRANSFORMER WINDINGS
AutoCAD SHX Text
INSTRUMENT TRANSFORMER
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
ALTERNATING CURRENT POWER SOURCE
AutoCAD SHX Text
DIRECT CURRENT POWER SOURCE
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
NONFUSIBLE SWITCH
AutoCAD SHX Text
FUSIBLE SWITCH
AutoCAD SHX Text
TRANSFER SWITCH
AutoCAD SHX Text
CONTACTS - NORMALLY OPEN
AutoCAD SHX Text
CONTACTS - NORMALLY CLOSED
AutoCAD SHX Text
THERMAL ELEMENT
AutoCAD SHX Text
FUSIBLE ELEMENT
AutoCAD SHX Text
COIL
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
BATTERY
AutoCAD SHX Text
WEATHERHEAD
AutoCAD SHX Text
SPLICE
AutoCAD SHX Text
DRAWOUT CONNECTION
AutoCAD SHX Text
BUILDING PENETRATION/SEAL
AutoCAD SHX Text
CIRCUIT BREAKER (GFCI TYPE)
AutoCAD SHX Text 50G
AutoCAD SHX Text
SINGLE LINE DIAGRAM NOTES
AutoCAD SHX Text
DIAGRAM SYMBOLS
AutoCAD SHX Text
KEYED NOTES
AutoCAD SHX Text
KEYED NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE GROUNDING ELECTRODE. SEE SHEET E-501. * #6CU GRD - GRD BUS #6CU GRD - GRD BUS PROVIDE EXCESS CONDUCTOR FOR FROST LOOP SIZE DISCONNECT SWITCH AS FOLLOWS: * 30A, 240V, 2 POLE, HP RATED- 30A, 240V, 2 POLE, HP RATED- SOLID NEUTRAL * NEMA 3R LOCKABLE NEMA 3R LOCKABLE * MTD ON SP. SEE DETAIL E-505 MTD ON SP. SEE DETAIL E-505 CIRCUIT FOR SITE UTILITY CABINET HVAC * SL-1,3 SL-1,3 * 3#12 & 1#12 GRD - 3/4"C 3#12 & 1#12 GRD - 3/4"C CIRCUIT FOR SITE UTILITY CABINET RECEPTACLE * SL-5, NEMA 5-20R, GFCI SL-5, NEMA 5-20R, GFCI * 2#12 & 1#12 GRD - 3/4"C2#12 & 1#12 GRD - 3/4"C
AutoCAD SHX Text
PNL
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
SPD
AutoCAD SHX Text
SL
AutoCAD SHX Text C
AutoCAD SHX Text
TS
AutoCAD SHX Text
PE
AutoCAD SHX Text M
AutoCAD SHX Text
US
AutoCAD SHX Text SECONDARY: 240V/120, 1PH,60Hz
AutoCAD SHX Text
RHODE ISLAND ENERGY EXISTING POLE
AutoCAD SHX Text
POLE MOUNTED TRANSFORMER
AutoCAD SHX Text
BACKBOARD P
AutoCAD SHX Text
2 1/2" RMC CONDUIT
AutoCAD SHX Text
* BOND TO GRD
AutoCAD SHX Text
RIGID TO PVC ADAPTER
AutoCAD SHX Text
SERVICE LATERAL
AutoCAD SHX Text
4#1 - 2 1/2"C PVC
AutoCAD SHX Text
WP
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
3#1-2"C PVC
AutoCAD SHX Text
AutoCAD SHX Text
TO SITE LIGHTING
AutoCAD SHX Text
SEE SHEET E-101
AutoCAD SHX Text
UTILITY RISER POLE
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
GATE CONTROLLER
AutoCAD SHX Text
3#12 & 1#12 GRD-3/4'C
AutoCAD SHX Text
3#12 & 1#12 GRD-3/4'C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
* SEE SHEETS E101 & E504SEE SHEETS E101 & E504
AutoCAD SHX Text
PROVIDE 30' EXCESS CONDUCTOR FOR UTILITY CONNECTION
AutoCAD SHX Text
NATIONAL GRID METER BASE
AutoCAD SHX Text
SITE UTILITY CABINET ENCLOSURE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INSULATING BUSHING WITH SEAL-OFF FITTING AND DUCT SEAL
AutoCAD SHX Text
RIGID TO PVC ADAPTER
AutoCAD SHX Text
* EXTEND TO 11' AFG
apunt Stamp
File details come from the government source that posted it. Updated .