SOLICITATION # 36C77624R0040
Construction of Valley Site Improvements Project No. 650-348- Providence, RI
TECHNICAL QUESTIONS AND VA RESPONSE TRACKING SHEET
ITEM
NO.
| DATE QUESTION RECEIVED |
| DATE QUESTION ANSWERED |
| QUESTION |
| GOVERNMENT RESPONSE |
| 1. |
| 2/21/2024 |
| 2/23/2024 |
| The Single Line Diagram on Drawing E-900 indicates the service lateral to be 4-#1 conductors. Since this installation is single phase, should this only be 3-#1 conductors? |
| This is a single-phase service and only 3-#1 conductors will be required. |
| 2. |
| 2/21/2024 |
| 2/23/2024 |
| The Fence & Gate Grounding Detail “FG” on Drawing E-503 appears to be a detail for a swinging personnel door. Can a detail be provided for the Sliding Gate to be installed on this project? |
| There is no reason to bond a sliding gate. The requirement is to bond the posts on each end that support the gate. There is no detail because there is no bonding. |