This document contains an abatement plan and specifications for a construction project. The project involves abatement of asbestos containing materials including 9x9 floor tile with mastic, window glazing, and chimney coating at a property located at 500 Valley Street in Providence, Rhode Island. The abatement work will be performed in accordance with government regulations using manual wet methods in negative pressure enclosures with HEPA ventilation. Noted asbestos containing materials and their quantities are the floor tile in the basement, window glazing at the front and side of the building, and black coating on the chimney roof. The related federal contract opportunity is for parking lot improvements at the same Providence location under solicitation number 36C77624R0040 issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files

File Type Posted
Attachment 25 - RFI Responses 2.docx DOCX document
36C77624R0040 Amendment 0002.docx DOCX document
Attachment 23 - February 2019 Aldinger report.pdf PDF
36C77624R0040 Amendment 0001.docx DOCX document
Attachment 21 - April 2009 Jacques Whitford report.pdf PDF
Attachment 20 - RFI Responses.docx DOCX document
Attachment 24 - Phase I II Environmental Property Assessment May 2018.pdf PDF
Attachment 22 - January 2019 SW Cole report.pdf PDF
S02 - 36C77624R0040_1.docx DOCX document
36C77624R0040_1.docx DOCX document
Attachment 5 - Civil 2 of 3.pdf PDF
Attachment 7 - Structural 1 of 3.pdf PDF
Attachment 3 - Existing Conditions.pdf PDF
Attachment 16 - Electrical 4 of 4.pdf PDF
Attachment 14 - Electrical 2 of 4.pdf PDF
Attachment 2 - General.pdf PDF
Attachment 13 - Electrical 1 of 4.pdf PDF
Attachment 12 - Arch.pdf PDF
36C77624R0040_1.docx DOCX document
Attachment 8 - Structural 2 of 3.pdf PDF
Attachment 9 - Structural 3 of 3.pdf PDF
Attachment 15 - Electrical 3 of 4.pdf PDF
Attachment 19 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - Civil 1 of 3.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 6 - Civil 3 of 3.pdf PDF
Attachment 17 - Wage Determination Providence.pdf PDF
Attachment 11 - Landscape.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pb-10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

HA101

A

Fi le

P at h

CONSTRUCTION DOCUMENTS

VAMC PROVIDENCE

830 CHALKSTONE AVENUE

PROVIDENCE, RI 02908

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SITE IMPROVEMENTS AT

500 VALLEY STREET

PROVIDENCE, RI

650-348

N/A Project Director

06-09-2023 MFD ECGRevisions: Date:

Patriot Design, LLC A Fort Hill / HCS Group Joint Venture 8403 Crossland Loop Montgomery, ALMabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA

ABATEMENT PLAN

SEE INSET A

INSET A

NORTH

SUMMARY OF IDENTIFIED ACM

LOCATION DESCRIPTION OF

MATERIALS

PERCENT AND

TYPE OF ASBESTOS

ESTIMATED

QUANTITY

BASEMENT, STAIRS AND

BOILER AREA

9'' X 9'' BROWN FLOOR

TILE 5 % CHRYSOTILE 25 SQUARE FEET

EXTERIOR AND INTERIOR,

FRONT AND SIDE WINDOW GLAZING 2 % CHRYSOTILE 20 EACH

BAY 1, ROOF BLACK CHIMNEY

COATING 20 % CHRYSOTILE 50 SQUARE FEET

1. ASBESTOS CONTAINING MATERIAL (ACM) ABATEMENT AND OTHER HAZARDOUS MATERIAL (OHM) HANDLING AND DISPOSAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL GOVERNMENT REGULATIONS. THE CONTRACTOR SHALL USE MANUAL WET METHODS TO CONTROL THE RELEASE OF DUST WHEN PERFORMING THE REMOVAL OF

ALL ASBESTOS AND NON-ASBESTOS MATERIALS FROM THE WORK AREA.

2. ALL INTERIOR ASBESTOS REMOVAL WORK SHALL BE CONDUCTED WITHIN A NEGATIVE PRESSURE ENCLOSURE. A NEGATIVE AIR PRESSURE OF AT LEAST -0.02 INCHES OF WATER COLUMN, AS MEASURED AT ANY WORK AREA PERIMETER LOCATION, SHALL BE PROVIDED AT ALL TIMES DURING ASBESTOS REMOVAL. NEGATIVE AIR PRESSURE SHALL BE CREATED IN THE WORK AREA USING HEPA FILTERED EXHAUST AND EXHAUSTED TO THE OUTDOORS. THESE HEPA FILTERED EXHAUST UNITS WILL BE USED TO GENERATE AT LEAST FOUR AIR CHANGES PER HOUR INSIDE THE WORK AREA. NEGATIVE AIR PRESSURE IN THE WORK AREA SHALL BE CONTINUOUSLY MONITORED

THROUGH THE USE OF DIGITAL MANOMETERS POSTED OUTSIDE THE WORK AREA.

3. THE CONTRACTOR SHALL REMOVE ACM AND OHM THAT EXISTS WITHIN THE WORK AREAS PRIOR TO DISTURBANCE AND PRIOR TO SALVAGING ANY EQUIPMENT.

4. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND ITEMS REQUIRING ABATEMENT AND DISPOSAL. REFER TO DEMOLITION PLANS FOR FURTHER

INFORMATION. REFER TO SPECIFICATIONS FOR REMOVAL REQUIREMENTS.

5. WORK AREAS WERE SURVEYED TO IDENTIFY HAZARDOUS MATERIALS. REFER TO SPECIFICATION 02 99 99 FOR MABBETT & ASSOCIATES PRE-DEMOLITION HAZARDOUS

MATERIALS SURVEY REPORT FOR 500 VALLEY STREET, PROVIDENCE, RI, DATED MAY 25, 2021 FOR ADDITIONAL INFORMATION. NOT ALL AREAS MAY HAVE BEEN ACCESSIBLE AND HAZARDOUS MATERIALS MAY EXIST WHICH HAVE NOT BEEN IDENTIFIED. IF SUSPECT MATERIALS ARE DISCOVERED WHICH HAVE NOT BEEN PREVIOUSLY IDENTIFIED, THE CONTRACTOR SHALL NOT DISTURB THOSE MATERIALS AND SHALL IMMEDIATELY NOTIFY THE COR.

6. OSHA LEAD REGULATIONS WILL APPLY TO ANY DEMOLITION OPERATION (I.E. SANDING, SCRAPING, CUTTING, AND WELDING) THAT WOULD DISTURB PAINTED SURFACES WHICH CONTAIN LEAD. OCCUPATIONAL EXPOSURE TO LEAD IS REGULATED BY OSHA (29 CFR 1910.1025) AS WELL AS APPLICABLE STATE REGULATIONS. DISPOSAL OF MATERIALS COATED WITH PAINT CONTAINING LEAD IS SUBJECT TO THE USEPA RESOURCE CONSERVATION AND RECOVERY ACT (RCRA) REGULATIONS. REFER TO

SPECIFICATION 02 99 99 FOR FURTHER INFORMATION.

1. THE ABATEMENT CONTRACTOR SHALL REMOVE AND DISPOSE OF 9'' X 9'' FLOOR TITLE AND MASTIC

AS ACM.

2. THE ABATEMENT CONTRACTOR SHALL REMOVE AND DISPOSE OF WINDOWS WITH ASBESTOS

CONTAINING GLAZING AS ACM. GLAZING MATERIALS AREA ASSUMED TO CONTAIN UP TO 50 PARTS

PER MILLION PCB. THE ABATEMENT CONTRACTOR SHALL MANAGE MATERIALS AS NON TSCA

REGULATED WASTE AND DISPOSE AS SOLID WASTE AT A LANDFILL PERMITTED TO ACCEPT WASTE

WITH ASBESTOS AND PCBS.

3. THE ABATEMENT CONTRACTOR SHALL REMOVE AND DISPOSE OF ASBESTOS CONTAINING BLACK

CHIMNEY COATING AS ACM.

ABATEMENT KEY NOTES:

GENERAL ABATEMENT NOTES:

AutoCAD SHX Text

OFFICE-1

AutoCAD SHX Text

OFFICE-2

AutoCAD SHX Text

OFFICE-3

AutoCAD SHX Text

BATH-1

AutoCAD SHX Text

BATH-2

AutoCAD SHX Text

BATH-3

AutoCAD SHX Text

STORAGE-1

AutoCAD SHX Text

STORAGE-2

AutoCAD SHX Text

HALL-2

AutoCAD SHX Text

HALL-1

AutoCAD SHX Text

BAY-1

AutoCAD SHX Text

BAY-2

AutoCAD SHX Text

BAY-3

AutoCAD SHX Text

BAY-4

AutoCAD SHX Text

BAY-5

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

MEZZANINE

AutoCAD SHX Text

MEZZANINE

AutoCAD SHX Text

MEZZANINE

AutoCAD SHX Text

BAY-1 ROOF

AutoCAD SHX Text

CRAWL SPACE

AutoCAD SHX Text

BEAM

AutoCAD SHX Text

FURNACE

AutoCAD SHX Text

OIL TANK

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text F1

AutoCAD SHX Text

BUILDING - ROOF LAYOUT

AutoCAD SHX Text 1/8" = 1'-0"

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text C4

AutoCAD SHX Text

BUILDING - FLOOR LAYOUT

AutoCAD SHX Text 1/8" = 1'-0"

AutoCAD SHX Text 1/8 INCH = ft.

AutoCAD SHX Text

( IN FEET )

AutoCAD SHX Text

GRAPHIC SCALE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CHIMNEY

apunt Stamp apunt Stamp

File details come from the government source that posted it. Updated .