This notice provides details for a federal design-build demolition contract opportunity. The Department of Veterans Affairs seeks proposals to demolish a 103,000 square foot, three story nursing home facility at the Atlanta VA Medical Center. Offerors will be required to provide architectural, structural, civil, mechanical, plumbing, fire suppression, electrical, and environmental documents and services to demolish the building and related site work. The performance period is approximately 540 calendar days from notice to proceed. The contract is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses and has an estimated value between $2,000,000 to $5,000,000. Proposals are due in mid to late November 2020. All questions must be submitted in writing by the specified deadline to the contact provided.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
John_Stephenson
FOR CONSTRUCTION
John_Stephenson
FOR CONSTRUCTION
Warren_Feagin R. P. 12/1/14
HVAC DESIGN DATA
DESIGN CONDITIONS
SUMMER WINTER LOWEST AVERAGE
ANNUAL DEWPOINTTEMP WET BULB TEMP
% HUMIDITY
TEMP DEWPOINT TEMP
% HUMIDITY
°F [°C] °F [°C] °F [°C] °F [°C] °F [°C]
OUTDOOR DESIGN CONDITIONS 93.8 [ 34 ] 77.2 [ 25 ] 48 20.7 [ -6 ] 0 [ -18 ] NA 5.4 [ -15 ]
INDOOR AREA DESIGN CONDITIONS
GENERATOR ROOM 95 [ 35 ] N/A N/A 50 [ 10 ] N/A N/A
ELECTRICAL ROOM 70 [ 21 ] N/A 60 50 [ 10 ] 41 [ 5 ] 30
MECHANICAL ROOM 84 [ 29 ] N/A N/A 50 [ 10 ] N/A N/A
CONTROL ROOM 75 [ 24 ] N/A 60 70 [ 21 ] 37 [ 3 ] 30
WORKROOM 75 [ 24 ] N/A 60 70 [ 21 ] 41 [ 5 ] 30
OFFICE 75 [ 24 ] N/A N/A 60 70 [ 21 ] N/A N/A 30
HRSG ROOM 86 [ 30 ] N/A N/A 40 [ 4 ] N/A N/A
DUCT CONSTRUCTION DETAILS
ROUND DUCT
TAKEOFF FROM LOW
PRESSURE ROUND
DUCT
A/C PREP
BOILER BUILDING A
DEMOLITION PHASE 1
BOILER BUILDING A
INSTALLATION PHASE 1
BOILER BUILDING A
INSTALLATION PHASE 2
BOILER BUILDING A
INSTALLATION PHASE 3
BOILER BUILDING A
DEMOLITION PHASE 2
BOILER BUILDING A
DEMOLITION PHASE 3
BOILER ROOM LOWER LEVEL ENLARGED PLAN - DEMOLITION
BOILER ROOM UPPER LEVEL ENLARGED PLAN - DEMOLITION
STEAM FLOW DIAGRAM - DEMOLITION
GROUND FLOOR PLAN - HVAC
TOILET ROOM EXHAUST
FIRST FLOOR PLAN
SECOND FLOOR PLAN
THIRD FLOOR PLAN
ROOF FLOOR PLAN
SECTIONS - HVAC
HOT WATER UNIT HEATER SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED TYPE UNIT
AIR FLOW MIN CAPACITY
TEMPERATURES
FLOW WPD CONTROL
SEQUENCE
MOTOR
REMARKSEAT EWT POWER
PHASE VOLT RPM
CFM [L/s] BTUH [W] °F [°C] °F [°C] GPM [L/s] FT [Pa] HP [W]
14-UH-1,2,3 E2101 MECHANICAL ROOM VERTICAL HOT
WATER 1500 [ 710 ] 52000 [ 15000 ] 50 [ 10 ] 180 [ 82 ] 5.8 0.37 5 [ 130 ] C-1 0.13 [ 93 ] 1 120 1070 THERMOSTAT CONTROL
14-UH-4,5,6 E4101 MECHANICAL ROOM VERTICAL HOT
WATER 1500 [ 710 ] 52000 [ 15000 ] 50 180 5.8 0.37 5 [ 130 ] C-1 0.13 [ 97 ] 1 120 1070 THERMOSTAT CONTROL
NOTE: CAPACITY IS AT 37% GLYCOL AT LISTED ENTERING AIR TEMPERATURE.
ELECTRIC UNIT HEATER SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED TYPE
AIR FLOW EAT MIN CAPACITY POWER
FAN MOTOR
REMARKSFAN POWER
PHASE VOLT
CFM L/S °F [°C] BTUH [W] AMP PHASE VOLT HP [W]
14-UH-7 EBST2 STAIR 2 HORIZONTAL COIL
RESISTANCE 400 [ 190 ] 50 [ 10 ] 10200 [ 3000 ] 20 1 208 0.08 [ 60 ] 1 208 WALL MOUNTED UNIT
AIR FILTER SCHEDULE
MARK LOCATION AREA AND/OR BLDG
SERVED
SYSTEM
AND/OR
SERVICE
MERV
RATING
AIR FLOW
APD
HOUSING
TYPE
CARTRIDGES
INITIAL CHANGEOVER
SIZE
ARRANGEMENT REMARKS
CFM [L/s] IN [mm] IN [mm] IN [mm]
14-PF-1 EB107 WORKROOM 14-AHU-1 8 3000 [ 1400 ] 0.3 [ 8 ] 0.59 [ 15 ] SIDE 6 24 x 24 x 2 [ 600 x 600 x 50 ] 3 WIDE BY 2 HIGH -----
14-AF-1 EB107 WORKROOM 14-AHU-1 14 3000 [ 1400 ] 0.4 [ 10 ] 0.65 [ 16 ] SIDE 6 24 x 24 x 4 [ 600 x 600 x 300 ] 3 WIDE BY 2 HIGH ----
14-PF-2 E2101 GEN ROOM 14-AHU-2 8 45000 [ 21000 ] 0.3 [ 8 ] 0.6 [ 15 ] SIDE 32 24 x 24 x 2 [ 600 x 600 x 300 ] 4 WIDE BY 8 HIGH ----
14-AF-2 E2101 GEN ROOM 14-AHU-2 14 45000 [ 21000 ] 0.4 [ 10 ] 0.8 [ 20 ] SIDE 32 24 x 24 x 4 [ 600 x 600 x 50 ] 4 WIDE BY 8 HIGH -----
14-PF-3 E2101 GEN ROOM 14-AHU-3 8 45000 [ 21000 ] 0.3 [ 8 ] 0.6 [ 15 ] SIDE 32 24 x 24 x 2 [ 600 x 600 x 300 ] 4 WIDE BY 8 HIGH ----
14-AF-3 E2101 GEN ROOM 14-AHU-3 14 45000 [ 21000 ] 0.4 [ 10 ] 0.8 [ 20 ] SIDE 32 24 x 24 x 4 [ 600 x 600 x 300 ] 4 WIDE BY 8 HIGH ----
14-PF-4 E2101 GEN ROOM 14-AHU-4 8 45000 [ 21000 ] 0.3 [ 8 ] 0.6 [ 15 ] SIDE 32 24 x 24 x 2 [ 600 x 600 x 50 ] 4 WIDE BY 8 HIGH -----
14-AF-4 E2101 GEN ROOM 14-AHU-4 14 45000 [ 21000 ] 0.4 [ 10 ] 0.8 [ 20 ] SIDE 32 24 x 24 x 4 [ 600 x 600 x 400 ] 4 WIDE BY 8 HIGH ----
14-PF-5 E2101 ELECTRICAL ROOM 14-AHU-5 8 16000 [ 7600 ] 0.25 [ 6 ] 0.56 [ 14 ] SIDE 12 24 x 24 x 2 [ 600 x 600 x 50 ] 3 WIDE BY 4 HIGH -----
14-AF-5 E2101 ELECTRICAL ROOM 14-AHU-5 14 16000 [ 7600 ] 0.4 [ 10 ] 0.9 [ 23 ] SIDE 12 24 x 24 x 4 [ 600 x 600 x 100 ] 3 WIDE BY 4 HIGH ----
14-PF-6 E2101 ELECTRICAL ROOM 14-AHU-6 8 16000 [ 7600 ] 0.25 [ 6 ] 0.56 [ 14 ] SIDE 12 24 x 24 x 2 [ 600 x 600 x 100 ] 3 WIDE BY 4 HIGH ----
14-AF-6 E2101 ELECTRICAL ROOM 14-AHU-6 14 16000 [ 7600 ] 0.4 [ 10 ] 0.9 [ 23 ] SIDE 12 24 x 24 x 4 [ 600 x 600 x 300 ] 3 WIDE BY 4 HIGH ----
AIR HANDLING UNIT SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED TYPE AIR FLOW
AIR FLOW
SUPPLY
FAN MARK
RETURN OR
RELIEF FAN
MARK
EXHAUST FAN
MARK
PREFILTER
MARK
AFTER
FILTER
MARK
FINAL FILTER
MARK
HEAT
RECOVERY
MARK
PREHEAT COIL
MARK
COOLING COIL
MARK REHEAT COIL HUMIDIFIER
MARK REMARKSSUPPLY MIN OA RETURN
CFM CFM CFM
14-AHU-1 E2101 GEN ROOM PRE-ENGINEERED VAV 45000 45000 0 14-SF-1 N/A N/A 14-PF-1 14-AF-1 N/A 14-PC-1 14-CC-1 N/A N/A MODULAR, INDOOR, MULTIPLE FAN AHU
14-AHU-2 E2101 GEN ROOM PRE-ENGINEERED VAV 45000 45000 0 14-SF-2 N/A N/A 14-PF-2 14-AF-2 N/A 14-PC-2 14-CC-2 N/A N/A MODULAR, INDOOR, MULTIPLE FAN AHU
14-AHU-3 E2101 GEN ROOM PRE-ENGINEERED VAV 45000 45000 0 14-SF-3 N/A N/A 14-PF-3 14-AF-3 N/A 14-PC-3 14-CC-3 N/A N/A MODULAR, INDOOR, MULTIPLE FAN AHU
14-AHU-4 E2101
ELECTRIC
SWITCHGEAR
ROOM
PRE-ENGINEERED VAV 16000 0 16000 14-SF-4 N/A N/A 14-PF-4 14-AF-4 N/A N/A 14-CC-4 N/A N/A MODULAR, INDOOR, MULTIPLE FAN AHU
14-AHU-5 E2101
ELECTRIC
SWITCHGEAR
ROOM
PRE-ENGINEERED VAV 16000 0 16000 14-SF-5 N/A N/A 14-PF-5 14-AF-5 N/A N/A 14-CC-5 N/A N/A MODULAR, INDOOR, MULTIPLE FAN AHU
14-AHU-6 EB107 WORKROOM PRE-ENGINEERED VAV 3000 800 2200 14-SF-6 N/A N/A 14-PF-6 14-AF-6 N/A N/A 14-PC-6 14-CC-6 N/A N/A MODULAR, INDOOR, AHU
FAN SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW TSP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE REMARKSTYPE
WHEEL CLASS ARRANGEMENT, ROTATION,
AND DISCHARGE
DIAMETER
MIN % EFF DRIVE FAN MAX
RPM
NOMINAL POWER
PHASE VOLT RPM SPEED CONTROL
CFM IN IN BHP HP
14-SF-1 E2101 GEN ROOM 14-AHU-1 45000 3.4 4-FAN ARRAY PLENUM PLENUM II CW ROTATION, DOWN DISCHARGE 24.5 59% DIRECT 1800 55 4 @ 15 3 460 1800 VARIABLE SEE MI-701 PROVIDE WITH 2 VFD
14-SF-2 E2101 GEN ROOM 14-AHU-2 45000 3.4 4-FAN ARRAY PLENUM PLENUM II CW ROTATION,DOWN DISCHARGE 24.5 59% DIRECT 1800 55 4 @ 15 3 460 1800 VARIABLE SEE MI-701 PROVIDE WITH 2 VFD
14-SF-3 E2101 GEN ROOM 14-AHU-3 45000 3.4 4-FAN ARRAY PLENUM PLENUM II CW ROTATION, DOWN DISCHARGE 24.5 59% DIRECT 1800 55 4 @ 15 3 460 1800 VARIABLE SEE MI-701 PROVIDE WITH 2 VFD
14-SF-4 E2101 ELEC
SWITCHGEAR 14-AHU-4 16000 3.1 2-FAN PLENUM PLENUM II CW ROTATION, DOWN
DISCHARGE 22.5 59% DIRECT 1755 13.4 2 @ 7.5 3 460 1800 VARIABLE SEE MI-702 PROIVIDE WITH 2 VFD
14-SF-5 E2101 ELEC
SWITCHGEAR 14-AHU-5 16000 3.1 2-FAN PLENUM PLENUM II CW ROTATION, DOWN
DISCHARGE 22.5 59% DIRECT 1755 13.4 2 @ 7.5 3 460 1800 VARIABLE SEE MI-702 PROVIDE WITH 2 VFD
14-SF-6 EB107 WORKROOM 14-AHU-6 3000 4.7 PLENUM PLENUM II CW ROTATION, SIDE
DISCHARGE 13.5 52% DIRECT 1800 4.1 7.5 3 460 1800 VARIABLE SEE MI-703 ---
14-EF1 EB107 WORKROOM TOILET
EXHAUST 300 0.6 INLINE CABINET BIW I N/A 10.875 37% DIRECT 1660 0.03 1/6 1 115 1725 CONSTANT CONTINOUS ECM MOTOR
14-EF2 CHP ROOF MECHANICAL
LEVEL 3 VENTILATION 4000 0.4 CENTRIFUGAL BIW I CW ROTATION, UPBLAST 21.375 35% DIRECT 860 0.71 3/4 1 208 860 CONSTANT THERMOSTAT HIGH EFFICIENCY MOTOR
14-EF3 STAIR ROOF STAIR VENTILATION 1900 0.4 CENTRIFUGAL BIW I CW ROTATION, DOWNBLAST 24 45% DIRECT 1725 0.44 1/2 1 208 1725 CONSTANT THERMOSTAT HIGH EFFICIENCY MOTOR
NOTE
ALL SELECTIONS ARE BASED ON AN ALTITUDE OF 1,000 ft.
FOUR PIPE FAN COIL UNIT SCHEDULE
MARK LOCATION TYPE
FAN AIR
FLOW
EXTERNAL
APD COOLING REQUIREMENTS HEATING REQUIREMENTS FILTER FAN MOTOR
REMARKS
MIN SENS
CAPACITY
MIN TOTAL
CAPACITY EAT FLOW EWT WPD RUNOUT
SIZE
MIN
CAPACITY EAT Db FLOW EWT WPD RUNOUT
SIZE POWER
PHASE VOLT RPM SPEED
CONTROLDb Wb
CFM IN WG BTUH BTUH °F °F GPM °F FT IN BTUH °F GPM °F FT IN MERV
RATING HP
14-FCU-2 2D230
CEILING
(CASSETTE) 530 0.05 12600 6800 80 67 2.3 45 1.4 7/8 7300 64.3 0.3 180 2.4 5/8 8 1/10 1 208 N/A CONSTANT 1. MANUAL SPEED CONTROL WITH A SELECTOR SWITCH.
SPLIT SYSTEM AIR CONDITIONER HEAT PUMP SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED TYPE
TOTAL SUPPLY AIR
FLOW
MIN. OUTSIDE AIR
FLOW
EXT STATIC
PRESSURE
COOLING CAPACITY HEATING CAPACITY ELECTRICAL DATA
REMARKSMIN TOTAL CAPACITY MIN SENS CAPACITY
MIN SEER
EAT
OSA DESIGN TEMP COMP
Kw MIN. HEAT CAPACITY EAT DB LAT Db OSA DESIGN TEMP INDOOR FAN OUTDOOR UNIT FAN
MCA PHASE VOLTDb Wb CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] MBH KW °F [°C] °F [°C] °F [°C] HP [W] CONTROL HP [w] CONTROL
14-HP-1/FCU-1 CHP ROOF VESTIBULE MINI SPIT 600 [ 280 ] 20 [ 9 ] 0.2 [ 50 ] 18 [ 61 ] 14.4 [ 4 ] 14.3 80 [ 27 ] 67 [ 19 ] [ 94 ] [ 34 ] 2.5 [ 13 ] [ 4 ] 70 [ 21 ] 80 [ 27 ] [ 21 ] [ -6 ] 1/8 [ 93 ] 3-SPEED 1/20 [ 37 ] - 13 1 208/230 PROVIDE MERV 8 FILTER RACK, DUCTED INDOOR UNIT
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
IN x IN [mm x mm] IN [mm ] CFM [L/s] CFM [L/s]
IN WG
[Pa]
SD-1 DRUM LOUVER 2000 [ 940 ] 4500 [ 2100 ] 0.100 [ 25 ] DUCT MOUNTED 70 X 15 [ 600 x 600 ] N/A [152 ø] 32 NONE WHITE ADJUSTABLE
SD-2 SUPPLY REGISTER 2000 [ 940 ] 3000 [ 1400 ] 0.040 [ 10 ] DUCT MOUNTED 50 X 26 [ 600 x 600 ] 48x24 [203 ø] 19 OBD WHITE ALUMINUM, 22.5 DEG DOUBLE DEF.
SD-3 SUPPLY REGISTER 4000 [ 1900 ] 6500 [ 3100 ] 0.060 [ 15 ] DUCT MOUNTED 50 X 44 [ 600 x 600 ] 48x42 [254 ø] 26 OBD WHITE ALUMINUM, 22.5 DEG DOUBLE DEF.
SD-4 LOUVERED FACE 90 [ 42 ] 170 [ 80 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø [305 ø ] 19 NONE WHITE ALUMININUM, SQUARE, CEILING
SD-5 LOUVERED FACE 170 [ 80 ] 280 [ 130 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [356 ø ] 19 NONE WHITE ALUMINUM, SQUARE, CEILING
SD-6 SUPPLY REGISTER 80 [ 38 ] 120 [ 57 ] 0.060 [ 15 ] DUCT MOUNTED 7 X 7 [203 x 203] 6 x 6 [152 x 152] 15 OBD WHITE ALUMINUM, 22.5 DEG DOUBLE DEF.
SD-7 SUPPLY REGISTER 130 [ 61 ] 300 [ 140 ] 0.060 [ 15 ] DUCT MOUNTED 15 X 7 [356 x 254] 14 X 6 [305 x 203] 20 OBD WHITE ALUMINUM, 22.5 DEG DOUBLE DEF.
NOTES
1. SEE FLOOR PLAN FOR THROW PATTERN.
2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
3. PROVIDE SQUARE TO ROUND ADAPTER.
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
RG-1 RETURN GRILLE 4000 [ 1900 ] 4000 [ 1900 ] 0.030 7.500 DUCT MOUNTED 48x36 [ 600 x 600 ] N/A [ 152 DIAM ] 19 NONE WHITE ALUMINUM, 35 DEG DEFL, 3/4" SPACING
RG-2 RETURN GRILLE 3000 [ 1400 ] 3000 [ 1400 ] 0.022 5.500 DUCT MOUNTED 34x34 [ 600 x 600 ] N/A [ 203 DIAM ] 13 NONE WHITE ALUMINUM, 0 DEG DEFL, 3/4" SPACING
RG-3 EGG CRATE 200 [ 94 ] 500 [ 240 ] 0.030 7.500 CEILING 24 x 24 [ 600 x 600 ] 18 X 18 [ 254 DIAM ] 10 NONE WHITE ALUMINUM, FLUSH FACE
RG-4 RETURN GRILLE 100 [ 47 ] 210 [ 99 ] 0.050 13.000 WALL/DUCT 10 x 10 [ 254 x 254 ] 8 x 8 [ 203 x 203 ] 11 NONE WHITE ALUMNINUM, 0 DEG DEFL, 3/4" SPACING
RG-5 EGG CRATE 100 [ 47 ] 180 [ 85 ] 0.090 23.000 CEILING 24X24 [ 305 x 305 ] 8" [ 254 x 254 ] 13 NONE WHITE ALUMNINUM, FLUSH FACE
RG-6 RETURN GRILLE 270 [ 130 ] 500 [ 240 ] 0.022 5.500 WALL 16X16 [ 356 x 356 ] 14X14 [ 305 x 305 ] 10 NONE WHITE ALUMINUM, 0 DEG DEFL, 3/4" SPACING
NOTE
PROVIDE SQUARE TO ROUND ADAPTER.
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
MARK LOCATION
AREA AND/OR
ROOM
SERVED
SYSTEM AIR
HANDLING SIZE
AIR FLOW ADDITIONAL SOUND
ATTUNATION
REQUIRED
CONTROL
TYPE
CONTROL
SEQUENCE
REHEAT PERIMETER
SUPPLEMENTAL HEAT
LINK
REMARKSMAX MIN
CFM [L/s] CFM [L/s] HW ELEC NONE 14-TU-6-1 EB107 EB108 14-AHU-6 A 200 [ 94 ] 90 [ 42 ] NONE VAV 5 DEGREE DEADBAND X N/A ----
14-TU-6-2 EB107 EB105 14-AHU-6 D 600 [ 280 ] 280 [ 130 ] NONE VAV 6 DEGREE DEADBAND X N/A
14-TU-6-3 EB107 EB107 14-AHU-6 F 1000 [ 470 ] 500 [ 240 ] NONE VAV 7 DEGREE DEADBAND X N/A
14-TU-6-4 EB107 EB107 14-AHU-6 G 1200 [ 570 ] 500 [ 240 ] NONE VAV 8 DEGREE DEADBAND X N/A
AIR TERMINAL UNIT SIZING SCHEDULE
SIZE
MIN ALLOWABLE AIR
FLOW
MAX ALLOWABLE AIR
FLOW DUCT INLET SIZE MAX APD
MAXIMUM SOUND POWER LEVEL (Re: 10 -12 WATTS) FOR BOX
DISCHARGE AT MAXIMUM INLET DUCT STATIC HOT WATER HEATING COIL
REMARKSOCTAVE BANDS EAT EWT FLOW MAX WPD PIPE RUNOUT SIZE TO
COIL
CFM [L/s] CFM [L/s] IN [mm] IN WG [Pa] 2 3 4 5 6 7 °F [°C] °F [°C] GPM [L/m] FT [kPa] IN [mm] A 90 [ 42 ] 260 [ 120 ] 5 [ 130 ] 0.4 [ 100 ] 69 63 59 52 51 47 55 [ 13 ] 180 [ 82 ] 0.5 [ 2 ] 5 [ 15 ] 0.75 [ 19 ] ----
B 130 [ 61 ] 380 [ 180 ] 6 [ 150 ] 0.4 [ 100 ] 69 67 61 55 52 49 55 [ 13 ] 180 [ 82 ] 0.7 [ 3 ] 5 [ 15 ] 0.75 [ 19 ] ----
C 160 [ 76 ] 490 [ 230 ] 7 [ 180 ] 0.4 [ 100 ] 70 68 63 57 53 49 55 [ 13 ] 180 [ 82 ] 0.7 [ 3 ] 5 [ 15 ] 0.75 [ 19 ] ----
D 230 [ 110 ] 680 [ 320 ] 8 [ 200 ] 0.4 [ 100 ] 71 68 59 53 51 47 55 [ 13 ] 180 [ 82 ] 1 [ 4 ] 5 [ 15 ] 0.75 [ 19 ] ----
E 270 [ 130 ] 790 [ 370 ] 9 [ 230 ] 0.4 [ 100 ] 71 69 60 54 51 47 55 [ 13 ] 180 [ 82 ] 1.5 [ 6 ] 5 [ 15 ] 0.75 [ 19 ] ----
F 350 [ 170 ] 1050 [ 500 ] 10 [ 250 ] 0.4 [ 100 ] 74 68 61 57 54 52 55 [ 13 ] 180 [ 82 ] 1.5 [ 6 ] 5 [ 15 ] 0.75 [ 19 ] ----
G 500 [ 240 ] 1500 [ 710 ] 12 [ 300 ] 0.4 [ 100 ] 73 69 64 59 57 53 55 [ 13 ] 180 [ 82 ] 2.5 [ 10 ] 5 [ 15 ] 0.75 [ 19 ] ----
NOTES
1. INLET STATIC BASED ON ARI 885-98.
2. THIS SCHEDULE IS USED WITH THE TERMINAL UNIT SCHEDULE.
3. CONTROL SEQUENCE SHALL BE AS INDICATED ON THE AIR TERMINAL UNIT SCHEDULE.
4. PROVIDE SOUND ATTENUATION AFTER-SECTION AS REQUIRED TO MEET ROOM NC LEVEL.
GROUND FLOOR PLAN -
HVAC PIPING
CHILLER PLANT FLOOR
PLAN - HVAC PIPING
FIRST FLOOR PLAN
SECOND FLOOR PLAN
THIRD FLOOR PLAN
ROOF PLAN
A/C PREP
A/C PREP
BOILER ROOM LOWER LEVEL ENLARGED PLAN- PIPING
BOILER ROOM SINK
BOILER ROOM UPPER LEVEL ENLARGED PLAN - PIPING
D
D
EXPANSION TANK SCHEDULE
MARK LOCATION SYSTEM AND/OR
SERVICE TYPE
APPROX SYSTEM
VOLUME
SYSTEM TEMPERATURE RANGE INITIAL PRESSURE IN
TANK
MAX OPERATING
PRESSURE
FILL PRESSURE AT TANK
MIN VOLUME TANK MIN BLADDER
VOLUME PIPE SIZE TO TANK COLD WATER FILL
SIZE REMARKSMIN MAX RELIEF VALVE AT TANK
GAL [L] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] PSIG [kPa] PSIG [kPa] GAL [L] GAL [L] IN [mm] IN [mm] 14-ET1 E4101 GEN 1 HT COOLANT VERT DIAPHRAGM [ ] 100 [ 38 ] 180 [ 82 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 100 [ 380 ] 23 [ 87 ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET2 E4101 GEN 1 LT COOLANT VERT DIAPHRAGM [ ] 90 [ 32 ] 120 [ 49 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 60 [ 230 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET3 E4101 GEN 2 HT COOLANT VERT DIAPHRAGM [ ] 100 [ 38 ] 180 [ 82 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 100 [ 380 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET4 E4101 GEN 2 LT COOLANT VERT DIAPHRAGM [ ] 90 [ 32 ] 120 [ 49 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 60 [ 230 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET5 E4101 GEN 3 HT COOLANT VERT DIAPHRAGM [ ] 100 [ 38 ] 180 [ 82 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 100 [ 380 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET6 E4101 GEN 3 LT COOLANT VERT DIAPHRAGM [ ] 90 [ 32 ] 120 [ 49 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 60 [ 230 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
14-ET7 E4101 HEATING WATER LOOP VERT DIAPHRAGM [ ] 120 [ 49 ] 180 [ 82 ] 10 [ 69 ] 70 [ 480 ] 80 [ 550 ] 70 [ 480 ] 80 [ 300 ] [ ] 1 [ 25 ] 0.75 [ 19 ]
FLUID IS 377 GLYCOL SOLUTION
HOT WATER HEATING COIL SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
APPLICATION
AIR FLOW MAX FACE VELOCITY APD
TEMPERATURES
TOTAL MIN CAPACITY
HOT WATER
% GLYCOL REMARKSEAT LAT FLOW EWT LWT WPD
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [kPa]
14-HWHC-1 E2101 GEN ROOM 14-AHU-1 PREHEAT 30000 [ 14000 ] 900 [ 5 ] 0.74 [ 190 ] 6 [ -14 ] 55 [ 13 ] 1631 [ 5600 ] 163 [ 10 ] 180 [ 82 ] 160 [ 71 ] 4 [ 12 ] 37 IFB COIL, VELOCITIES PRESSURE DROP AT FULL AHU COOLING FLOW
14-HWHC-2 E2101 GEN ROOM 14-AHU-2 PREHEAT 30000 [ 14000 ] 900 [ 5 ] 0.74 [ 190 ] 6 [ -14 ] 55 [ 13 ] 1631 [ 5600 ] 163 [ 10 ] 180 [ 82 ] 160 [ 71 ] 4 [ 12 ] 37 IFB COIL, VELOCITIES PRESSURE DROP AT FULL AHU COOLING FLOW
14-HWHC-3 E2101 GEN ROOM 14-AHU-3 PREHEAT 30000 [ 14000 ] 900 [ 5 ] 0.74 [ 190 ] 6 [ -14 ] 55 [ 13 ] 1631 [ 5600 ] 163 [ 10 ] 180 [ 82 ] 160 [ 71 ] 4 [ 12 ] 37 IFB COIL, VELOCITIES PRESSURE DROP AT FULL AHU COOLING FLOW
14-HWHC-6 E2101 WORKROOM 14-AHU-6 PREHEAT 2000 [ 940 ] 400 [ 2 ] 0.04 [ 10 ] 46 [ 8 ] 65 [ 18 ] 41 [ 140 ] 4 [ ] 180 [ 82 ] 160 [ 71 ] 3 [ 9 ] 37
CHILLED WATER COOLING COIL SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW MAX FACE VELOCITY APD
EAT LAT
TOTAL CAPACITY SENSIBLE CAPACITY
CHILLED WATER
REMARKSDb Wb Db Wb FLOW EWT LWT WPD CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M]
14-CWCC-1 E2101 GEN ROOM 14-AHU-1 45,000 [ 21000 ] 571 [ 3 ] 0.24 [ 60 ] 93.5 [ 34 ] 73.4 [ 23 ] 78.5 [ 26 ] 69.1 [ 21 ] 1040 [ 300 ] 820 [ 240 ] 200 [ 13 ] 44 [ 7 ] 54 [ 12 ] 11.3 [ 3 ]
14-CWCC-2 E2101 GEN ROOM 14-AHU-2 45,000 [ 21000 ] 571 [ 3 ] 0.24 [ 60 ] 93.5 [ 34 ] 73.4 [ 23 ] 78.5 [ 26 ] 69.1 [ 21 ] 1040 [ 300 ] 820 [ 240 ] 200 [ 13 ] 44 [ 7 ] 54 [ 12 ] 11.3 [ 3 ]
14-CWCC-3 E2101 GEN ROOM 14-AHU-3 45,000 [ 21000 ] 571 [ 3 ] 0.24 [ 60 ] 93.5 [ 34 ] 73.4 [ 23 ] 78.5 [ 26 ] 69.1 [ 21 ] 750 [ 220 ] 748 [ 220 ] 200 [ 13 ] 44 [ 7 ] 54 [ 12 ] 9.3 [ 3 ]
14-CWCC-4 E2101 GEN ROOM 14-AHU-4 16,000 [ 7600 ] 460 [ 2 ] 0.37 [ 93 ] 78 [ 26 ] 63 [ 17 ] 55 [ 13 ] 54 [ 12 ] 434 [ 130 ] 404 [ 120 ] 87 [ 6 ] 44 [ 7 ] 54 [ 12 ] 7 [ 2 ]
14-CWCC-5 E2101 GEN ROOM 14-AHU-5 16,000 [ 7600 ] 460 [ 2 ] 0.37 [ 93 ] 78 [ 26 ] 63 [ 17 ] 55 [ 13 ] 54 [ 12 ] 434 [ 130 ] 404 [ 120 ] 87 [ 6 ] 44 [ 7 ] 54 [ 12 ] 7 [ 2 ]
14-CWCC-6 EB107 WORKROOM 14-AHU-6 3,000 [ 1400 ] 500 [ 3 ] 0.56 [ 140 ] 83 [ 28 ] 67 [ 19 ] 55 [ 13 ] 54 [ 12 ] 112 [ 33 ] 92 [ 27 ] 22 [ 1 ] 44 [ 7 ] 54 [ 12 ] 3.2 [ 1 ] -----
NOTE
THE COOLING COIL FIN SPACING SHALL NOT EXCEED 100 FINS PER FOOT.
AIR SEPARATOR SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
TYPE
AIR SEPARATOR
REMARKSSIZE IN FLOW WPD BUILT-IN
STRAINER
REQ'DIN [mm] GPM [L/s] FT [kPa]
1-AS1 01090 MER HEATING WATER FULL FLOW
TANGENTIAL 4 [ 100 ] 240 [ 15 ] 3.2 [ 10 ] YES ---
PUMP SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM AND/OR
SERVICE TYPE
CIRCULATING FLUID
MIN % EFF
ELECTRICAL MOTOR
FLUID
FLOW HEAD NPSH AVAILABLE TEMPERATURE SP GR NOMINAL POWER PHASE VOLT MAX RPM SPEED
CONTROL REMARKS
GPM [L/s] FT [kPa] FT [kPa] °F [°C] HP [kW]
14-P1 EB101 CHP HIGH TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 525 [ 33 ] 70 [ 1100 ] 16 [ 260 ] 180 [ 82 ] 1.01 72 15 [ 11 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P2 EB101 CHP HIGH TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 525 [ 33 ] 70 [ 1100 ] 16 N/A 180 [ 82 ] 1.01 72 15 [ 11 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P3 EB101 CHP HIGH TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 525 [ 33 ] 70 [ 1100 ] 16 N/A 180 [ 82 ] 1.01 72 15 [ 11 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P4 EB101 CHP LOW TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 135 [ 9 ] 50 [ 800 ] 6.3 N/A 115 [ 46 ] 1.01 61 5 [ 4 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P5 EB101 CHP LOW TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 135 [ 9 ] 50 [ 800 ] 6.3 N/A 115 [ 46 ] 1.01 61 5 [ 4 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P6 EB101 CHP LOW TEMP ENGINE
COOLING LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 135 [ 9 ] 50 [ 800 ] 6.3 N/A 115 [ 46 ] 1.01 61 5 [ 4 ] 3 460 1750 CONSTANT 37% ETHYLENE GLYCOL
14-P7 E4101 CHP &
WORKROOM
HYDRONIC HEATING
LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 370 [ 23 ] 38 [ 610 ] 6.5 N/A 180 [ 82 ] 1.01 75 7.5 [ 6 ] 3 460 1750 VARIABLE 37% ETHYLENE GLYCOL
14-P8 E4101 CHP &
WORKROOM
HYDRONIC HEATING
LOOP
VERTICAL
INLINE 37% ETHYLENE GLYCOL 370 [ 23 ] 38 [ 610 ] 6.5 N/A 180 [ 82 ] 1.01 75 7.5 [ 6 ] 3 460 1750 VARIABLE 37% ETHYLENE GLYCOL
HOT WATER
FLOW DIAGRAM
BOILER PLANT DIAGRAM
HEAT RECOVERY
STEAM GENERATOR DIAGRAM
FIRST
SECOND
GROUND
MEZZANINE
BOILER FLOW DIAGRAM
CHILLED WATER FLOW DIAGRAM
HOT WATER SYSTEM POINTS LIST
NAME TYPE
REMARKS
HEATING HOT WATER SYSTEM POINTS LIST (SEE MP-610 FOR SYSTEM DIAGRAM)
LEAD/LAG PUMP
SELECTION XSW BI
PUMP-1
START/STOP SW BO
PUMP-2
START/STOP SW BO
X X X
PUMP-1 STATUS HW BI
PUMP-2 STATUS HW BI
X X
X X
PUMP-1 FAILURE HW BI
PUMP-2 FAILURE HW BI
X X
X X
X
X
PUMP-1 SPEED SW AO
PUMP-2 SPEED SW AO
HEATING HOT
WATER PRESSURE SETPOINT XSW AI X
HEATING HOT
WATER SYSTEM PRESSURE HW AI X X
SEE MP610 FOR LOCATION
HEATING HOT
WATER SUPPLY TEMP. HW AI X XX
HEATING HOT
WATER RETURN TEMP. HW AI X XX
DG MO AL TR
NAME TYPE REMARKS
HEATING HOT WATER PUMP VFD POINTS
VFD ENABLE XHW BO XX
VFD SIGNAL XHW AO XX
SPEED FEEDBACK XSW AO X
DG MO AL TR SH
VFD FAULT XSW BI X
VFD OPERATION MODE (AUTO,
HAND, BYPASS) XSW BI X
SC
HOT WATER CONTROL POINTS LEGEND
COLUMN ABBREVIATIONS (MARKED WITH "X" WHERE REQUIRED):
DG - THE ASSOCIATED POINT SHALL BE DISPLAYED ON THE SYSTEM GRAPHICS.
MO - THE ASSOCIATED POINT CAN BE MODIFIED/OVERRIDDEN BY THE OPERATOR.
AL - THE ASSOCIATED POINT SHALL CREATE AN ALARM.
TR - THE ASSOCIATED POINT SHALL LOGGED/TRENDED
SC - THE ASSOCIATED POINT SHALL BE SCHEDULED THROUGH THE WORKSTATION
LEGEND
POINT "TYPE" IDENTIFICATION:
HW - HARDWARE (HARDWIRED) POINT
SW - SOFTWARE POINT
BI - BINARY (DIGITAL) CONTACT POINT (NO OR NC)
BO - BINARY (DIGITAL) CONTACT OUTPUT (NO OR NC)
AI - ANALOG INPUT
AO - ANALOG OUTPUT
PI - METER INPUT
"CONTROL POINT"
NAME SCTRALMODGTYPE
| Volume 2 cover VA ATL CHP - ARCHITECTURAL STAMPED |
| GI-100.2 COVER SHEET |
| GI-001.2-INDEX AND SYMBOLS |
| 2014-11-19_VA ATL CHP - Mechanical |
| VA ATL CHP - ELECTRICAL STAMPED 2014-11-21 |
| FIRE SUPPRESSION 2014-11-18.pdf |
| FX-001 General Notes & Abbreviations - Fire Suppression FX-001 (1) |
| FX-002 Symbols - Fire Suppression FX-002 (1) |
| FX-101 Ground Floor Plan - Fire Suppression FX-101 (1) |
| FX-102 First & Second Floor Plans - Fire Suppression FX-102 (1) |
| FX-103 Third Floor and Roof Plans - Fire Suppression FX-103 (1) |
| FX-601 Fire Suppression Diagram FX-601 (1) |