This notice describes a forthcoming solicitation for a design-build project. The Department of Veterans Affairs intends to issue a Request for Proposal to renovate approximately 60 telecommunications rooms and one data center at the VA Palo Alto Health Care System facility to meet Electronic Health Records Modernization infrastructure standards. The project scope involves relocating or remodeling the rooms while maintaining ongoing IT services. Offerors must be a Service-Disabled Veteran-Owned Small Business. The solicitation will use a two-phase selection process and be evaluated as described within. The period of performance is approximately 555 days from notice to proceed. The magnitude of construction is estimated between $20-50 million. Questions must be submitted in writing by the specified date.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VISN 21 CM/PM Electronic Health

Records Modernization (EHRM) PHASE I Support Task

PO# 612C209

Palo Alto Health Care System Palo Alto VA Medical Center

Capitola VA Clinic

Fremont VA Clinic

San Jose VA Clinic

Sonora VA Clinic

Stockton VA Clinic

Modesto VA Clinic

Major General Will iam H. Gourley VA-DOD Outpatient Clinic

(Monterey Clinic)

Sunnyvale Research Center

Mountain View Human Resources

VHAPALPrasaS1 Cross-Out

Ta b l e o f C o n t e n t s

Project TeamContributors

Vicinity Map/Building Addresses

Campus Map / Building Information

VAMC Fiber Distances

VAMC Fiber Distances

VAMC Fiber Distances

VAMC Fiber Distances

Door Security Requirements

Palo Alto VAMC - Bldg. 4

First Floor Plan

Second Floor Plan

Third Floor Plan

Palo Alto VAMC – Bldg. 5

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Palo Alto VAMC – Bldg. 6

First Floor Plan

Second Floor Plan

Third Floor Plan

Palo Alto VAMC – Bldg. 7

First Floor Plan

Palo Alto VAMC – Bldg. 40

First Floor Plan

Palo Alto VAMC – Bldg. 50

First Floor Plan

Palo Alto VAMC – Bldg. 100

Basement Plan

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Palo Alto VAMC – Bldg. 100 (G-Wing)

Second Floor Plan

Identification of Network Spaces

Network Spaces: (cont’d)

Palo Alto VAMC - Bldg. 101

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Palo Alto VAMC – Bldg. 102

First Floor Plan

Palo Alto VAMC – Bldg. 103

First Floor Plan

Palo Alto VAMC – Bldg. 105

First Floor Plan

Second Floor Plan

Palo Alto VAMC – Bldg. 500

First Floor Plan – Area A

First Floor Plan – Area C

Second Floor Plan – Area A

Second Floor Plan – Area D

Third Floor Plan – Area A

Palo Alto VAMC – Bldg. 520

First Floor Plan

Palo Alto VAMC – Bldg. 520A

First Floor Plan

Second Floor Plan

Palo Alto VAMC – Bldg. 530

First Floor Plan

Second Floor Plan

Palo Alto VAMC – MB-1

First Floor Plan

Palo Alto VAMC – MB-2

First Floor Plan

Palo Alto VAMC – MB-3

First Floor Plan

Palo Alto VAMC – MB-4

First Floor Plan

Struck out buildings are not in scope of work

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

Ta b l e o f C o n t e n t s

Palo Alto VAMC – PS-1

First Floor Plan

Palo Alto VAMC – PS-2

Second Floor Plan

Fifth Floor Plan

Palo Alto VAMC – Bldg. T6A

First Floor Plan

Palo Alto VAMC – Bldg. T6B

First Floor Plan

Palo Alto VAMC – Bldg. T7A

First Floor Plan

Palo Alto VAMC – Bldg. T7B

First Floor Plan

Palo Alto VAMC – Bldg. T7C

First Floor Plan

Palo Alto VAMC – Bldg. T7D

Second Floor Plan

Palo Alto VAMC – Bldg. T-50

First Floor Plan

Palo Alto VAMC – Bldg. T601

First Floor Plan – N/A

Identification of Network Spaces

(cont’d)

Off Campus Locations:

San Jose VA Clinic

First Floor Plan

Second Floor Plan

Third Floor Plan

Sonora VA Clinic

First Floor Plan

Stockton VA Clinic

First Floor Plan – N/A

Sunnyvale Research Center

First Floor Plan

Second Floor Plan

Capitola VA Clinic

First Floor Plan

Second Floor Plan

Freemont VA Clinic

First Floor Plan

Modesto VA Clinic

First Floor Plan

Monterey VA Clinic

First Floor Plan

Second Floor Plan

Second Floor Plan (cont’d)

Third Floor Plan

Third Floor Plan (cont’d)

Mountain View Human Resource Center

Second Floor Plan

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Cross-Out

Network Space Design

Bldg. 4:

A201 & A202

Design Matrix

Enlarged Plan – Existing

Bldg. 4:

B311

Design Matrix

Enlarged Plan - Existing

Bldg. 5:

A-187

Design Matrix

Enlarged Plan - Existing

Bldg. 5:

A-402 & A-402A

Design Matrix

Enlarged Plan – Existing

Bldg. 6:

A-123A

Design Matrix

Enlarged Plan – Existing

Bldg. 6:

A-277 & A-278

Design Matrix

Enlarged Plan - Existing

Bldg. 7:

D-101

Design Matrix

Enlarged Plan - Existing

Bldg. 7:

F-144A

Design Matrix

Enlarged Plan - Existing

Bldg. 7:

H-126A

Design Matrix

Enlarged Plan – Existing

Bldg. 40:

Servers in Fenced Area

Design Matrix

Enlarged Plan – None

Bldg. 50:

SP12

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

FB-333

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

FB-370

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

EB-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

EB-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

A1-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

A1-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

E1-TC4

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

C1-TC3

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

E1-TC5

Design Matrix

Enlarged Plan - Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Network Space Design (cont’d)

Bldg. 100:

F1-TC6

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

F2-TC6

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

E2-TC5

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

E2-TC4

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

B2-TC2

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

C2-TC3

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

A2-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

A3-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

B3-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

C3-TC3

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

E3-TC4

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

E3-TC5

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

F3-TC6

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

A4-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

B4-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

C4-TC3

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

E4-TC5

Design Matrix

Enlarged Plan - Existing

Bldg. 100:

E4-TC4

Design Matrix

Enlarged Plan – Existing

Bldg. 100:

F4-TC6

Design Matrix

Enlarged Plan - Existing

Bldg. 100 (G-WING):

T1.7

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

A1-TC1

Design Matrix

Enlarged Plan - Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Bldg. 101:

C1-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

A2-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

C2-TC2

Design Matrix

Enlarged Plan – Existing

Bldg. 101:

A3-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

C3-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

C4-TC2

Design Matrix

Enlarged Plan - Existing

Bldg. 101:

A4-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 102:

Design Matrix

Enlarged Plan – Existing

Bldg. 103:

Design Matrix

Enlarged Plan - Existing

Bldg. 105:

1A-120

Design Matrix

Enlarged Plan - Existing

Bldg. 105:

2A-220

Design Matrix

Enlarged Plan - Existing

Bldg. 500:

A1-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 500:

A2-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 500:

A3-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 500:

B1-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 500:

B2-TC1

Design Matrix

Enlarged Plan – Existing

Bldg. 520:

C-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 520:

A-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. 520A:

F-SC1

Design Matrix

Enlarged Plan - Existing

Bldg. 520A:

F-SC2

Design Matrix

Enlarged Plan - Existing

Bldg. 530:

TC1A

Design Matrix

Enlarged Plan – N/A

Bldg. 530:

Design Matrix

Enlarged Plan – N/A

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Bldg. MB-1:

Design Matrix

Enlarged Plan - Existing

Bldg. MB-2:

Design Matrix

Enlarged Plan - Existing

Bldg. MB-3:

Design Matrix

Enlarged Plan – Existing

Bldg. MB-4:

Design Matrix

Enlarged Plan - Existing

Bldg. PS-1:

1-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. PS-2:

SP2B-TC1

Design Matrix

Enlarged Plan - Existing

Bldg. PS-2:

SP5A-TC2

Design Matrix

Enlarged Plan – Existing

Bldg. T-6A:

TC1

Design Matrix

Enlarged Plan – Existing

Bldg. T-6B:

Elec/Tele

Design Matrix

Enlarged Plan - Existing

Bldg. T-7A:

TC1

Design Matrix

Enlarged Plan – N/A

Bldg. T-7B:

TC1

Design Matrix

Enlarged Plan – N/A

Bldg. T-7C:

Elec/Data

Design Matrix

Enlarged Plan – Existing

Bldg. T-7D:

Elec/Data

Design Matrix

Enlarged Plan – Existing

Bldg. T-50:

Design Matrix

Enlarged Plan – Existing

Bldg. T-600:

T-600

Design Matrix

Enlarged Plan - N/A

San Jose:

1019A

Design Matrix

Enlarged Plan – Existing

San Jose:

Design Matrix

Enlarged Plan – Existing

San Jose:

Design Matrix

Enlarged Plan – Existing

Sonora:

Design Matrix

Enlarged Plan – Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Identification of Off Campus

Network Spaces

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

Sunnyvale:

Design Matrix

Enlarged Plan – Existing

Sunnyvale:

M201

Design Matrix

Enlarged Plan - Existing

Capitola:

Design Matrix

Enlarged Plan – Existing

Capitola:

Open Office TR Rack

Design Matrix

Enlarged Plan – Existing

Freemont:

Design Matrix

Enlarged Plan - Existing

Modesto:

C159

Design Matrix

Enlarged Plan - Existing

Monterey:

1G010

Design Matrix

Enlarged Plan – Existing

Monterey:

2B001

Design Matrix

Enlarged Plan – Existing

Monterey:

2G005

Design Matrix

Enlarged Plan - Existing

Monterey:

3B001

Design Matrix

Enlarged Plan – Existing

Monterey:

3G005

Design Matrix

Enlarged Plan – Existing

Stockton:

Design Matrix

Enlarged Plan – N/A

Stockton:

Trailer 1 IT Closet

Design Matrix

Enlarged Plan – N/A

Stockton:

Trailer 2 IT Closet

Design Matrix

Enlarged Plan – N/A

Stockton:

Trailer 3 IT Closet

Design Matrix

Enlarged Plan – N/A

Stockton:

Trailer 4 IT Closet

Design Matrix

Enlarged Plan – N/A

Stockton:

Trailer 5 IT Closet

Design Matrix

Enlarged Plan – N/A

Mountain View:

Design Matrix

Enlarged Plan – Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Appendix A – Power Installation Example

Appendix B – Compliance Requirements

Appendix C – Rack Labeling Standard

Appendix

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

P R O J E C T C O N TA C T D I R E C T O R Y

Concourse Federal Group

123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, Project Manager ........................................................................................thower@concousefederal.com

Lorena Alvarez................................................................................................................IaIvarez@concousefederaI.com

Mike Olson ................................................................................................................... molson@concousefederal.com

Marshall Contino, Concourse A|E Vice President ....................................................... mcontino@concousefederal.com

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com

Kory Young, EIT, Senior Mechanical Engineer................................................................kyoung@dheeng.com

VA Palo Alto Health Care System

Jay Kim, Chief Engineer & Acting AD.............................................................................Jay.Kim@va.gov

Tammie Ridder, Palo Alto, OI&T Area Manager.............................................................Tammie.Ridder@va.gov

James Crowe……Associate Chief Engineering……………..................................................James.Crowe2@va.gov

Frank Quiles, Chief of Facilities Planning and Development..........................................Frank.Quiles@va.gov

V i c i n i t y M a p B u i l d i n g A d d r e s s e s

P a l o A l t o V A M e d i c a l C e n t e r ( V A M C )

3 8 0 1 M i r a n d a A v e n u e

P a l o A l t o , C A 9 4 3 0 4

M o u n t a i n V i e w H u m a n R e s o u r c e s

C e n t e r

1 7 7 6 O l d M i d d l e f i e l d W a y

M o u n t a i n V i e w , C A 9 4 0 4 3

C S P C C ( N O T I N S C O P E )

7 0 1 - B N . S h o r e l i n e B l v d

M o u n t a i n V i e w , C A

9 4 0 4 3 - 3 2 0 8

S u n n y v a l e R e s e a r c h C e n t e r

1 0 8 0 I n n o v a t i o n W a y

S u n n y v a l e , C A 9 4 0 8 9

F r e m o n t V A C l i n i c

3 9 1 9 9 L i b e r t y S t r e e t , B u i l d i n g B

F r e m o n t , C A 9 4 5 3 8 - 1 5 0 1

3 4

S a n J o s e V A C l i n i c

5 8 5 5 S i l v e r C r e e k V a l l e y P l a c e

S a n J o s e , C A 9 5 1 3 8 - 1 0 5 9

C a p i t o l a V A C l i n i c

1 3 5 0 4 1 s t A v e n u e , S u i t e 1 0 2

C a p i t o l a , C A 9 5 0 1 0 - 3 9 0 6

M a j o r G e n e r a l W i l l i a m H .

G o u r l e y V A - D o D O u t p a t i e n t

C l i n i c ( M o n t e r e y C l i n i c )

2 0 1 9 t h S t r e e t

M a r i n a , C A 9 3 9 3 3 - 6 0 3 9

S t o c k t o n V A C l i n i c

7 7 7 7 S o u t h F r e e d o m R o a d

F r e n c h C a m p , C A 9 5 2 3 1 - 9 6 9 4

M o d e s t o V A C l i n i c

1 2 2 5 O a k d a l e R o a d

M o d e s t o , C A 9 5 3 5 5 - 3 3 5 7

S o n o r a V A C l i n i c

1 3 6 6 3 M o n o W a y

S o n o r a , C A 9 5 3 7 0 - 2 8 1 1

1 0

1 1

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

C a m p u s M a p – PA L O A LT O V A M e d i c a l C e n t e r

B u i l d i n g I n f o r m a t i o n

LO

O

P R

O A

D

FOOTHILL EXPY

Bldg. # Bldg. Name TR Qty Levels

4 Research 3 3

5 Primary Care Clinic 4 4

6 Research & Administration Building 3 3

7 Spinal Cord Injury Center 6 1

40 Boiler Building 1 1

50 Logistics 1 1

100 Main Hospital 26 4

100 (G-WING)

Centers For Ambulatory Care, Polytrauma and Blind Rehabilitation 1 1

101 Administration 8 4

102 Diagnostics & Radiology Center 1 1

103 Emergency Generators 1 1

105 Education Training Center 2 2

500 Polytrauma and Blind Rehabilitation Center 5 3

520 Mental Health Center 3 1

520A Mental Health Administration 2 2

530 Wellness Center 2 2

MB1 Compensation & Pension 1 1

MB2 Polytrauma 1 1

MB3 Administration 1 1

MB4 Research Annex 1 1

PS1 Parking Structure 1 1 4

PS2 Parking Structure 2 1 5

T-50 Contractor Trailer 2 1

T600 Engineering Trailer 1 1

T6A Research 1 1

T6B Whistle Stop 1 1

T7A Brain Injury Center 1 1

T7B Driver Rehabilitation 1 1

T7C PSA Administration 1 1

T7D Call Center 1 1

Bldg. # Bldg. Name Data Ctr Levels

100 Main Hospital 1 4

VAMC FIBER DISTANCES

PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

4 1 A-103

Room to be abandoned and relocated to TR room A202

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

4 2 A-201

Fibre to serve A-201 and new room A-202 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

4 3 A-311

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

VAMC Palo Alto Division

Building Floor Room Distance From Existing

Server Room (Ft.)

Notes Fiber type Conduit Type

5 1 187

New TR Room

5 1 A-185

Room to be abandoned and relocated to TR room A187 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

5 2 A-243

Room to be abandoned and relocated to Fiber TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

5 3 A-308

Room to be abandoned and relocated to Fiber TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

5 4 A-403

Room to be abandoned and relocated to TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

5 4 A402/402A

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

6 1 A-123-A

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

6 2 A-278

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

6 3 A-377 1159

Abandon and to be served by A-278 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 F144A 1522 New TR Room 24 strand single mode Interior - 4" EMT

7 1 D101 1522 New TR Room 25 strand single mode Interior - 4" EMT

7 1 A-129 1522 Room to be abandoned and relocated to TR room D-101 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 B-104B 1522 Room to be abandoned and relocated to TR room H-126A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 D-122 1522 Room to be abandoned and relocated to TR room D-101 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 E-140 1522 Room to be abandoned and relocated to TR room F144A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 F-116 1522 Room to be abandoned and relocated to TR room F144A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 H-126A 1522 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

Note: New redundant fibre runs to the campus required. Runs and lengths TBD.

40 1

120 (Cage) in

Plumbing Shop

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

50 1 SP12

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

50 1 Outside Cage

TR to be abandoned 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

EXISTING TO REMAIN AND UPGRADED

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Typewritten Text

EXISTING TR TO REMAIN AND UPGRADED

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Typewritten Text Have to re-assess

VHAPALPrasaS1 Typewritten Text Only 1st lvl has Psychology

VHAPALPrasaS1 Typewritten Text Admin

VHAPALPrasaS1 Typewritten Text Admin

VHAPALPrasaS1 Typewritten Text Maintenance Shop

VHAPALPrasaS1 Typewritten Text Warehouse

VHAPALPrasaS1 Typewritten Text Warehouse

VHAPALPrasaS1 Typewritten Text Demarc & MDF move can be very difficult. Space planning needs to approve use of another room

VHAPALPrasaS1 Typewritten Text Every floor shall have TR

VHAPALPrasaS1 Typewritten Text Same 24 SM as redundant backbone is questionable

PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VAMC Palo Alto Division

Building Floor Room Distance From Existing

Server Room (Ft.)

Notes Fiber type Conduit Type

100 Bsmt FB370 100 Fibre main point of entry 24 strand single mode Interior - 4" EMT

100 Bsmt FB333 N/A Server Room 25 strand single mode Interior - 4" EMT

100 1 A1-TC1 (T16) 95 24 strand single mode Interior - 4" EMT

100 1 A1-TC2 (T14) 146 24 strand single mode Interior - 4" EMT

100 2 A2-TC1 (T26) 109 24 strand single mode Interior - 4" EMT

100 3 A3-TC1 (T36) 125 24 strand single mode Interior - 4" EMT

100 4 A4-TC1 (T46) 138 24 strand single mode Interior - 4" EMT

100 2 B2-TC2 (T24) 168 24 strand single mode Interior - 4" EMT

100 3 B3-TC2 (T34) 183 24 strand single mode Interior - 4" EMT

100 4 B4-TC2 (T44) 199 24 strand single mode Interior - 4" EMT

100 1 C1-TC3 (T15) 343 24 strand single mode Interior - 4" EMT

100 2 C2-TC3 (T25) 343 24 strand single mode Interior - 4" EMT

100 3 C3-TC3 (T35) 360 24 strand single mode Interior - 4" EMT

100 4 C4-TC3 (T45) 453 24 strand single mode Interior - 4" EMT

100 1 E1-TC4 (T13) 354 24 strand single mode Interior - 4" EMT

100 1 E1-TC5 (T12) 368 24 strand single mode Interior - 4" EMT

100 2 E2-TC4 (T23) 366 24 strand single mode Interior - 4" EMT

100 2 E2-TC5 (T22) 381 24 strand single mode Interior - 4" EMT

100 3 E3-TC4 (T33) 381 24 strand single mode Interior - 4" EMT

100 3 E3-TC5 (T32) 397 24 strand single mode Interior - 4" EMT

100 4 E4-TC4 (T43) 399 24 strand single mode Interior - 4" EMT

100 4 E4-TC5 (T42) 410 24 strand single mode Interior - 4" EMT

100 Bsmt EB-TC1 (T03) 176 24 strand single mode Interior - 4" EMT

100 Bsmt EB-TC2 (T02) 140 24 strand single mode Interior - 4" EMT

100 1 F1-TC6 (T11) 216 24 strand single mode Interior - 4" EMT

100 2 F2-TC6 (T21) 229 24 strand single mode Interior - 4" EMT

100 3 F3-TC6 (T31) 165 24 strand single mode Interior - 4" EMT

100 4 F4-TC6 (T41) 257 24 strand single mode Interior - 4" EMT

100 1 G1-T1.7 400

101 1 A1-TC1 (T11) 570 24 strand single mode Interior - 4" EMT

101 2 A2-TC1 (T21) 586 24 strand single mode Interior - 4" EMT

101 3 A3-TC1 (T31) 603 24 strand single mode Interior - 4" EMT

101 4 A4-TC1 (T41) 638 24 strand single mode Interior - 4" EMT

101 1 C1-TC2 (T12) 777 24 strand single mode Interior - 4" EMT

101 2 C2-TC2 (T22) 796 24 strand single mode Interior - 4" EMT

101 3 C3-TC2 (T32) 790 24 strand single mode Interior - 4" EMT

101 4 C4-TC2 (T42) 825 24 strand single mode Interior - 4" EMT

Note: New redundant fibre runs to the campus required. Runs and lengths TBD.

VHAPALPrasaS1

Not all buildings on Campus are Patient Care spaces. Some are slated for demolition. Some have completed construction and ready for Activation in near future. Built to OIT standards based on Mission Control or CBOC or other.

PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VAMC Palo Alto Division

Building Floor Room Distance From Existing

Server Room (Ft.)

Notes Fiber type Conduit Type

102 1 154 Outside

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

103 1 Outside

New TR Room 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

103 1

Mechanical room

(Only Voice)

TR to be abandoned

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

105 1 120

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

105 2 220

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

500 A1TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

500 A2TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

500 A3TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

500 B1TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

500 B2TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

520A 1 F-SC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

520A 2 F-SC2

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

520 1 A-TC1 2199

520 1 C-TC1 2199 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

520 Admin 1st floor T-4 2200 Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

520 Admin 2nd floor T-5 2215 Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

530 1 116 (Aquartics)

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

530 2

TC1, TC1A

(Recreation Therapy

Bldg)

Unable to find in drawings. Used longest run from data center to building

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

Note: New redundant fibre runs to the campus required. Runs and lengths TBD.

VHAPALPrasaS1 Line

VHAPALPrasaS1 Cross-Out

PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

MB1 106

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

MB2 106

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

MB3 330

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

MB4 408

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

PS1 1st floor Not found on Site plan or existing drawings

PS2 1st floor Not found on Site plan or existing drawings

PS2 5th floor Not found on Site plan or existing drawings

VAMC Palo Alto Division

Building Floor Room Distance From Existing

Server Room (Ft.)

Notes Fiber type Conduit Type

T6A TC1 Not found on Site plan or existing drawings

T6B

Whistle Stop Inside

Hallway

Unable to find in drawings. Used longest run from data center to building

24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T7A

TC1:wall mounted rack Not found on Site plan or existing drawings

T7B

TC1:wall mounted rack Not found on Site plan or existing drawings

T7C

TC1:Wall mounted rack Not found on Site plan or existing drawings

T7D TC1 Not found on Site plan or existing drawings

T-50 TC1

Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T600

RE's Trailer :wall mount inside copy room Not found on Site plan or existing drawings

Note: New redundant fibre runs to the campus required. Runs and lengths TBD.

VHAPALPrasaS1 Typewritten Text Garage

VHAPALPrasaS1 Typewritten Text Garage

VHAPALPrasaS1 Typewritten Text Garage

VHAPALPrasaS1 Typewritten Text Temporary leased trailers

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

Line

DOOR SECURITY REQUIREMENTS

PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S

BLDG: 4

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

ABANDON TR A-103

RELOCATE TO NEW TR

ROOM A202

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

VHAPALPrasaS1

EVERY FLOOR TO HAVE TR. REMEDIATE IN PLACE

LEVEL: 2

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

EXPAND IN PLACE

TELE/DATA

A-201

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NEW TR ROOM A202 TO

SERVE FIRST & SECOND

FLOOR

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE/DATA

A-311

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

BLDG: 5

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

NEW TR ROOM 187

ABANDON TR A185

RELOCATE TO A187

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Typewritten Text Relocation of Demarc & MDF location to be analyzed There are few projects in B7 that are concurrently being done. Patient rooms, exam rooms can't be converted to MDF without approval from Planning.

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON TR A243

RELOCATE TO A402 & A402A

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1

Every floor shall have a TR room per TDDM standards

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON MECH A308

RELOCATE TO A402 & A402A

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Cross-Out

VHAPALPrasaS1 Typewritten Text Every floor to have a TR room

VHAPALPrasaS1 Line

LEVEL: 4

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON MECH A403

RELOCATE TO A402 & A402A

VHAPALPrasaS1 Typewritten Text Relocation of TR to be approved by Planning. TRs should be stacked.

How to re-route vertical backbone & Conduit penetrations

BLDG: 6

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE OP

A-123A

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

EXPAND IN PLACE

TELE OP

A-278

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VHAPALPrasaS1 Typewritten Text SCS storage in adjoining room.

Until alternate space is provided, not sure if this works.

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON IT ROOM A-378

TO BE SERVED BY A-278

VHAPALPrasaS1 every floor should have TR. Not allowed.

BLDG: 7

SCALE: 1/64” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON

TELE/DATA

A-129

RELOCATE TO NEW TR

ROOM D-101

ABANDON

TELE/DATA

B-104B

TO BE SERVED BY H-126A

ABANDON

TELE/DATA

F-116

RELOCATE TO NEW TR ROOM

F144A

REMEDIATE IN PLACE

IT ROOM

H-126A

ABANDON

TELE/DATA

D-122

RELOCATE D-122 TO

NEW TR ROOM D-101

ABANDON

ELEC/FIRE/DATA

E-140

RELOCATE TO NEW TR

ROOM F144A

NEW TR ROOM F144A

NEW TR ROOM D101

VHAPALPrasaS1 Typewritten Text MDFs and IDFs remain in location and upgraded.

Demarc can't be moved easily and existing patient rooms and exam rooms can't be converted to TRs. Needs coordination with other projects that are concurrently being planned. DB contractor needs to work with Planning dept and take above mentioned comments, OEHRM & OIT standards into consideration and how it can be executed based on existing backbone pathways and relocation.

BLDG: 4 0

SCALE: 3/32” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

SERVERS LOCATED IN FENCED AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Typewritten Text Not in Scope

VHAPALPrasaS1 Typewritten Text

VHAPALPrasaS1

This is maintenance shop area has wall mtd cabinet that can't be cooled as the entire shop is an unconditioned space.

BLDG: 5 0

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

ELEC.

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

ABANDON

3A-50 (7A)

RELOCATE TO ROOM 12

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

TR room being moved to Main Electrical room that has Transformers and ATSs? Really?

BLDG: 1 0 0

LEVEL: BASEMENT

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE/DATA

EB-TC2

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

MPOE & MDF

FB-370

REMEDIATE IN PLACE

TELE/DATA

EB-TC1

REMEDIATE IN PLACE

SERVER ROOM

FB-333

SCALE: 1/64” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE/DATA

E1-TC5

T12

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

F1-TC6

T11

REMEDIATE IN PLACE

TELE/DATA

A1-TC2

T14

REMEDIATE IN PLACE

TELE/DATA

E1-TC4

T13

REMEDIATE IN PLACE

TELE/DATA

A1-TC1

T16

REMEDIATE IN PLACE

TELE/DATA

C1-TC3

T15

SCALE: 1/64” = 1’-0”

DATE: 10/15/2020

N

EXPAND IN PLACE

TELE/DATA

E2-TC5

T22

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

F2-TC6

T21

REMEDIATE IN PLACE

TELE/DATA

B2-TC2

T24

REMEDIATE IN PLACE

TELE/DATA

E2-TC4

T23

REMEDIATE IN PLACE

TELE/DATA

A2-TC1

T26

REMEDIATE IN PLACE

TELE/DATA

C2-TC3

T25

SCALE: 1/64” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE/DATA

E3-TC5

T32

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

F3-TC6

T31

REMEDIATE IN PLACE

TELE/DATA

B3-TC2

T34

REMEDIATE IN PLACE

TELE/DATA

E3-TC4

T33

REMEDIATE IN PLACE

TELE/DATA

A3-TC1

T36

REMEDIATE IN PLACE

TELE/DATA

C3-TC3

T35

SCALE: 1/64” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

TELE/DATA

E4-TC5

T42

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

F4-TC6

T41

REMEDIATE IN PLACE

TELE/DATA

B4-TC2

T44

REMEDIATE IN PLACE

TELE/DATA

E4-TC4

T43

REMEDIATE IN PLACE

TELE/DATA

A4-TC1

T36

REMEDIATE IN PLACE

TELE/DATA

C4-TC3

T45

BLDG: 1 0 0 ( G - W I N G )

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

T-1.7

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

NEW FACILITY UNDER CONSTRUCTION. OEHRM COMPLIANT.

BLDG: 1 0 1

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

A1-TC1

T11

REMEDIATE IN PLACE

TELE/DATA

C1—TC2

T12

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

A2-TC1

T21

REMEDIATE IN PLACE

TELE/DATA

C2—TC2

T22

NOTE: REMOVE ALL FIBER AND

INFRASTRUCTURE FROM ROOM C2100A

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

A3-TC1

T31

REMEDIATE IN PLACE

TELE/DATA

C3—TC2

T32

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

A4-TC1

T41

REMEDIATE IN PLACE

TELE/DATA

C4—TC2

T42

BLDG: 1 0 2

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELE/DATA

N

VHAPALPrasaS1

WILL BE DEMOLISHED IN 2021

BLDG: 1 0 3

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

NEW 4’x 8’ ROOM ON OUTSIDE OF

BUILDING TO PROVIDE FOR NEW

EQUIPMENT.

VERIFY LOCATION OF NEW TR CLOSET

N

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1 Typewritten Text Provides main emergency power to the Hospital.

Disruption of service requires monumental effort.

Polygon

BLDG: 1 0 5

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

IRMS

N

VHAPALPrasaS1 Typewritten Text Wellness Center, CAT6, UPS, 72 SM, VHAPALPrasaS1 Line

BLDG: 1 0 5

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

AMMS/EMS STORAGE

N

VHAPALPrasaS1 Line

BLDG: 5 0 0

LEVEL: 1 (AREA A)

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TCOM

A1-TC1

VHAPALPrasaS1 Typewritten Text STATE OF THE ART FACILITY ALMOST READY TO BE ACTIVATED, LOT OF OTHER PROJECTS ARE FOLLOWING THE OPENING OF THIS PLACE. READINESS CAN'T BE DELAYED.

ONLY ITEM MISSING MAY BE UPS IN THIS TR/MDF.

LEVEL: 1 (AREA C)

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TCOM

B1-TC1

VHAPALPrasaS1

MAY REQUIRE ONLY MINI SPLIT DEDICATED COOLING, ALL OTHER CRITERIA OEHRM COMPLIANT.

LEVEL: 2 (AREA A)

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

A2-TC1

VHAPALPrasaS1

SAME AS PREVIOUS

LEVEL: 2 (AREA D)

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

B2-TC1

VHAPALPrasaS1

LEVEL: 3 (AREA A)

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

A3-TC1

VHAPALPrasaS1

BLDG: 5 2 0

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

DATA

A-TC1

REMEDIATE IN PLACE

DATA

C-TC1

520A

VHAPALPrasaS1 Typewritten Text

OIT COMPLAINT, CAT 6, 24SM, EM POWER, 71DEG, 41%RH, 2T DEDICATED COOLING.

CONCOURSE FEDERAL'S MATRIX NEEDS TO BE RE-EVALUATED. NO NEED TO DISRUPT THE FUNCTIONS OF FACILITY IF IT MEETS EHRM REQUIREMENTS.

BLDG: 5 2 0 A

SCALE: 1/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

DATA

F-SC1

VHAPALPrasaS1

BLDG: 5 2 0 A

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

DATA

F-SC2

F-226

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VHAPALPrasaS1

BLDG: 5 3 0

SCALE: NTS

DATE: 10/15/2020

N

REMEDIATE IN PLACE

ROOM 116

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

VHAPALPrasaS1

Wellness center, New, CAT6, 12SM, no patient care, plenty of EM power, has 2T dedicated cooling

BLDG: 5 3 0

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TR

TC-1

VHAPALPrasaS1

MAY REQUIRE UPS & MINI SPLIT

BLDG: M B - 1

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

ELEC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

BLDG: M B - 2

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

REMEDIATE IN PLACE

ELEC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

BLDG: M B - 3

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

EXPAND IN PLACE

TEL

NO ROOM #

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

BLDG: M B - 4

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

EXPAND IN PLACE

TEL

BLDG: P S - 1

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

1-TC1

VHAPALPrasaS1 Line

BLDG: P S - 2

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM ROOM

SP2B-TC1

VHAPALPrasaS1 Line

BLDG: P S - 2

LEVEL: 5

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM ROOM

SP5A-TC2

VHAPALPrasaS1 Line

BLDG: T 6 A

SCALE: 1/8” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

IT CLOSET

TC1

VHAPALPrasaS1 Line

BLDG: T 6 B

SCALE: 1/8” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

ELEC/TELE

VHAPALPrasaS1 Line

BLDG: T 7 A

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

WALL MOUNTED RACK

TC1

ELEC/TELE

(VERIFY HALLWAY LOCATION)

VHAPALPrasaS1 Line

BLDG: T 7 B

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

WALL MOUNTED RACK

TC1

ELEC/TELE

(VERIFY HALLWAY LOCATION)

VHAPALPrasaS1 Line

BLDG: T 7 C

SCALE: 1/4” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

ELEC/TELE

TC1

VHAPALPrasaS1 Line

BLDG: T 7 D

SCALE: 3/32” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

ELEC/TELE

TC1

VHAPALPrasaS1 Line

BLDG: T - 5 0

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TR ROOM

VHAPALPrasaS1 Line

BLDG: T 6 0 1

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

DRAWING NOT AVAILABLE

VHAPALPrasaS1 Line

O F F C A M P U S LO C AT I O N S

BLDG: S A N J O S E

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TEL/DATA

(VA ROOM NUMBER 1019A)

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

COMMUNITY BASED CLINICS ARE NOT INCLUDED IN THIS CONTRACT

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TEL/DATA

2076B

(VA ROOM NUMBER 2103)

VHAPALPrasaS1 Line

SCALE: NTS

DATE: 10/15/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TEL/DATA

3076B

(VA ROOM NUMBER 3103)

VHAPALPrasaS1 Line

BLDG: S O N O R A C B O C

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

L.A.N.

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Line

BLDG: S T O C K T O N C B O C

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NO DRAWING AVAILABLE

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Typewritten Text IT upgrade of Stockton CBOC trailers in not in scope as the VA clinic is moving to a new facility.

VHAPALPrasaS1 Line

BLDG: SUNNYVALE RESEARCH

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

Not a patient care space & this is new under construction. This is not in contract..

BLDG: SUNNYVALE RESEARCH

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

REMEDIATE IN PLACE

TELECOM

M201

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Line

BLDG: CAPITOLA

SCALE: 3/32” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMEDIATE IN PLACE

OIT CLOSET

(UNMARKED ROOM)

VHAPALPrasaS1 Typewritten Text Lease is expiring soon before 2024.

It will no longer be VA space.

VHAPALPrasaS1 Line

BLDG: CAPITOLA

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMEDIATE IN PLACE

VHAPALPrasaS1 Line

BLDG: FREMONT

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMEDIATE IN PLACE

I.T. ROOM

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

Fremont CBOC not included in this contract

BLDG: MODESTO

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMEDIATE IN PLACE

I.T. ROOM

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

Modesto CBOC not included in this contract

BLDG: MONTEREY

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

REMEDIATE IN PLACE

TEL/DATA

1G010

VHAPALPrasaS1 Line

VHAPALPrasaS1 Line

VHAPALPrasaS1

Monterey CBOC not included in this contract.

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

REMEDIATE IN PLACE

TEL/DATA

2B001

VHAPALPrasaS1 Line

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

REMEDIATE IN PLACE

TEL/DATA

2G005

VHAPALPrasaS1 Line

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

REMEDIATE IN PLACE

TEL/DATA

3B001

VHAPALPrasaS1 Line

SCALE: NTS

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

REMEDIATE IN PLACE

TEL/DATA

3G005

VHAPALPrasaS1 Line

BLDG: MOUNTAIN VIEW HR

SCALE: 1/16” = 1’-0”

DATE: 10/15/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMEDIATE IN PLACE

ELEC

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

N E T WO R K S PAC E D E S I G N

SCALE: 1/4” = 1’-0”

DATE: 10/15/2020

NEW TR ROOM A201 & A202

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

REMOVE EXISTING

DOOR AND INFILL

DOOR OPENING

REMOVE EXISTING WALL

PROVIDE WINDOW

INSULATION IN ORDER

TO KEEP THE TR ROOM

TEMPERATURE COOL.

EXISTING TR ROOM A-103 TO

RELOCATE TO A-201 & A-202

Building 4, NEW Room A-201 & 202

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Room A-201 to expand into room A-202.

Room A-103 to be relocated to new TR room

A-202. Provide insulation on window to reduce heat transfer. Provide 3 ton ductless mini-split. Condenser to be located on roof.

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Rack Temperature/Humidity

Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to BMS X Missing grounding bus bar Install copper grounding bus bar

Piping over equipment Relocate piping or install pipe trough with floor tape-type leak detector X

Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X Remote Controlled battery thermostat Wired thermostat X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special

Telecommunications Systems Design

Manual

X Micro condensate pump Commercial condensate pump

C A

B

LI

N G

X Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 342

Approximate total cable length = 56430'

X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment provide two new racks.

VHAPALPrasaS1 Typewritten Text In spaces where mini-split is neither required nor feasible, exhaust fan and undecut door should be considered. Relative humidity is never a problem at VAPAHCS. This comment is general for all spaces.

VHAPALPrasaS1 Polygon

Polygon

SCALE: 1/4” = 1’-0”

DATE: 10/15/2020

B311

VA PALO ALTO HEALTHCARE SYSTEM

PALO ALTO VAMC

N

TEL/DATA

B311

Building 4, Room B311

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide insulation on window to reduce heat transfer. Provide 3 ton ductless mini-split.

Condenser to be located on roof.

Insufficient…