This notice describes a forthcoming solicitation for a design-build project. The Department of Veterans Affairs intends to issue a Request for Proposal to renovate approximately 60 telecommunications rooms and one data center at the VA Palo Alto Health Care System facility to meet Electronic Health Records Modernization infrastructure standards. The project scope involves relocating or remodeling the rooms while maintaining ongoing IT services. Offerors must be a Service-Disabled Veteran-Owned Small Business. The solicitation will use a two-phase selection process and be evaluated as described within. The period of performance is approximately 555 days from notice to proceed. The magnitude of construction is estimated between $20-50 million. Questions must be submitted in writing by the specified date.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VISN 21 CM/PM Electronic Health
Records Modernization (EHRM) PHASE I Support Task
PO# 612C209
Palo Alto Health Care System Palo Alto VA Medical Center
Capitola VA Clinic
Fremont VA Clinic
San Jose VA Clinic
Sonora VA Clinic
Stockton VA Clinic
Modesto VA Clinic
Major General Will iam H. Gourley VA-DOD Outpatient Clinic
(Monterey Clinic)
Sunnyvale Research Center
Mountain View Human Resources
VHAPALPrasaS1 Cross-Out
Ta b l e o f C o n t e n t s
Project TeamContributors
Vicinity Map/Building Addresses
Campus Map / Building Information
VAMC Fiber Distances
VAMC Fiber Distances
VAMC Fiber Distances
VAMC Fiber Distances
Door Security Requirements
Palo Alto VAMC - Bldg. 4
First Floor Plan
Second Floor Plan
Third Floor Plan
Palo Alto VAMC – Bldg. 5
First Floor Plan
Second Floor Plan
Third Floor Plan
Fourth Floor Plan
Palo Alto VAMC – Bldg. 6
First Floor Plan
Second Floor Plan
Third Floor Plan
Palo Alto VAMC – Bldg. 7
First Floor Plan
Palo Alto VAMC – Bldg. 40
First Floor Plan
Palo Alto VAMC – Bldg. 50
First Floor Plan
Palo Alto VAMC – Bldg. 100
Basement Plan
First Floor Plan
Second Floor Plan
Third Floor Plan
Fourth Floor Plan
Palo Alto VAMC – Bldg. 100 (G-Wing)
Second Floor Plan
Identification of Network Spaces
Network Spaces: (cont’d)
Palo Alto VAMC - Bldg. 101
First Floor Plan
Second Floor Plan
Third Floor Plan
Fourth Floor Plan
Palo Alto VAMC – Bldg. 102
First Floor Plan
Palo Alto VAMC – Bldg. 103
First Floor Plan
Palo Alto VAMC – Bldg. 105
First Floor Plan
Second Floor Plan
Palo Alto VAMC – Bldg. 500
First Floor Plan – Area A
First Floor Plan – Area C
Second Floor Plan – Area A
Second Floor Plan – Area D
Third Floor Plan – Area A
Palo Alto VAMC – Bldg. 520
First Floor Plan
Palo Alto VAMC – Bldg. 520A
First Floor Plan
Second Floor Plan
Palo Alto VAMC – Bldg. 530
First Floor Plan
Second Floor Plan
Palo Alto VAMC – MB-1
First Floor Plan
Palo Alto VAMC – MB-2
First Floor Plan
Palo Alto VAMC – MB-3
First Floor Plan
Palo Alto VAMC – MB-4
First Floor Plan
Struck out buildings are not in scope of work
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
Ta b l e o f C o n t e n t s
Palo Alto VAMC – PS-1
First Floor Plan
Palo Alto VAMC – PS-2
Second Floor Plan
Fifth Floor Plan
Palo Alto VAMC – Bldg. T6A
First Floor Plan
Palo Alto VAMC – Bldg. T6B
First Floor Plan
Palo Alto VAMC – Bldg. T7A
First Floor Plan
Palo Alto VAMC – Bldg. T7B
First Floor Plan
Palo Alto VAMC – Bldg. T7C
First Floor Plan
Palo Alto VAMC – Bldg. T7D
Second Floor Plan
Palo Alto VAMC – Bldg. T-50
First Floor Plan
Palo Alto VAMC – Bldg. T601
First Floor Plan – N/A
Identification of Network Spaces
(cont’d)
Off Campus Locations:
San Jose VA Clinic
First Floor Plan
Second Floor Plan
Third Floor Plan
Sonora VA Clinic
First Floor Plan
Stockton VA Clinic
First Floor Plan – N/A
Sunnyvale Research Center
First Floor Plan
Second Floor Plan
Capitola VA Clinic
First Floor Plan
Second Floor Plan
Freemont VA Clinic
First Floor Plan
Modesto VA Clinic
First Floor Plan
Monterey VA Clinic
First Floor Plan
Second Floor Plan
Second Floor Plan (cont’d)
Third Floor Plan
Third Floor Plan (cont’d)
Mountain View Human Resource Center
Second Floor Plan
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Cross-Out
Network Space Design
Bldg. 4:
A201 & A202
Design Matrix
Enlarged Plan – Existing
Bldg. 4:
B311
Design Matrix
Enlarged Plan - Existing
Bldg. 5:
A-187
Design Matrix
Enlarged Plan - Existing
Bldg. 5:
A-402 & A-402A
Design Matrix
Enlarged Plan – Existing
Bldg. 6:
A-123A
Design Matrix
Enlarged Plan – Existing
Bldg. 6:
A-277 & A-278
Design Matrix
Enlarged Plan - Existing
Bldg. 7:
D-101
Design Matrix
Enlarged Plan - Existing
Bldg. 7:
F-144A
Design Matrix
Enlarged Plan - Existing
Bldg. 7:
H-126A
Design Matrix
Enlarged Plan – Existing
Bldg. 40:
Servers in Fenced Area
Design Matrix
Enlarged Plan – None
Bldg. 50:
SP12
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
FB-333
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
FB-370
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
EB-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
EB-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
A1-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
A1-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
E1-TC4
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
C1-TC3
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
E1-TC5
Design Matrix
Enlarged Plan - Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Network Space Design (cont’d)
Bldg. 100:
F1-TC6
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
F2-TC6
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
E2-TC5
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
E2-TC4
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
B2-TC2
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
C2-TC3
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
A2-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
A3-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
B3-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
C3-TC3
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
E3-TC4
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
E3-TC5
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
F3-TC6
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
A4-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
B4-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
C4-TC3
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
E4-TC5
Design Matrix
Enlarged Plan - Existing
Bldg. 100:
E4-TC4
Design Matrix
Enlarged Plan – Existing
Bldg. 100:
F4-TC6
Design Matrix
Enlarged Plan - Existing
Bldg. 100 (G-WING):
T1.7
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
A1-TC1
Design Matrix
Enlarged Plan - Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Bldg. 101:
C1-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
A2-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
C2-TC2
Design Matrix
Enlarged Plan – Existing
Bldg. 101:
A3-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
C3-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
C4-TC2
Design Matrix
Enlarged Plan - Existing
Bldg. 101:
A4-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 102:
Design Matrix
Enlarged Plan – Existing
Bldg. 103:
Design Matrix
Enlarged Plan - Existing
Bldg. 105:
1A-120
Design Matrix
Enlarged Plan - Existing
Bldg. 105:
2A-220
Design Matrix
Enlarged Plan - Existing
Bldg. 500:
A1-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 500:
A2-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 500:
A3-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 500:
B1-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 500:
B2-TC1
Design Matrix
Enlarged Plan – Existing
Bldg. 520:
C-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 520:
A-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. 520A:
F-SC1
Design Matrix
Enlarged Plan - Existing
Bldg. 520A:
F-SC2
Design Matrix
Enlarged Plan - Existing
Bldg. 530:
TC1A
Design Matrix
Enlarged Plan – N/A
Bldg. 530:
Design Matrix
Enlarged Plan – N/A
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Bldg. MB-1:
Design Matrix
Enlarged Plan - Existing
Bldg. MB-2:
Design Matrix
Enlarged Plan - Existing
Bldg. MB-3:
Design Matrix
Enlarged Plan – Existing
Bldg. MB-4:
Design Matrix
Enlarged Plan - Existing
Bldg. PS-1:
1-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. PS-2:
SP2B-TC1
Design Matrix
Enlarged Plan - Existing
Bldg. PS-2:
SP5A-TC2
Design Matrix
Enlarged Plan – Existing
Bldg. T-6A:
TC1
Design Matrix
Enlarged Plan – Existing
Bldg. T-6B:
Elec/Tele
Design Matrix
Enlarged Plan - Existing
Bldg. T-7A:
TC1
Design Matrix
Enlarged Plan – N/A
Bldg. T-7B:
TC1
Design Matrix
Enlarged Plan – N/A
Bldg. T-7C:
Elec/Data
Design Matrix
Enlarged Plan – Existing
Bldg. T-7D:
Elec/Data
Design Matrix
Enlarged Plan – Existing
Bldg. T-50:
Design Matrix
Enlarged Plan – Existing
Bldg. T-600:
T-600
Design Matrix
Enlarged Plan - N/A
San Jose:
1019A
Design Matrix
Enlarged Plan – Existing
San Jose:
Design Matrix
Enlarged Plan – Existing
San Jose:
Design Matrix
Enlarged Plan – Existing
Sonora:
Design Matrix
Enlarged Plan – Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Identification of Off Campus
Network Spaces
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
Sunnyvale:
Design Matrix
Enlarged Plan – Existing
Sunnyvale:
M201
Design Matrix
Enlarged Plan - Existing
Capitola:
Design Matrix
Enlarged Plan – Existing
Capitola:
Open Office TR Rack
Design Matrix
Enlarged Plan – Existing
Freemont:
Design Matrix
Enlarged Plan - Existing
Modesto:
C159
Design Matrix
Enlarged Plan - Existing
Monterey:
1G010
Design Matrix
Enlarged Plan – Existing
Monterey:
2B001
Design Matrix
Enlarged Plan – Existing
Monterey:
2G005
Design Matrix
Enlarged Plan - Existing
Monterey:
3B001
Design Matrix
Enlarged Plan – Existing
Monterey:
3G005
Design Matrix
Enlarged Plan – Existing
Stockton:
Design Matrix
Enlarged Plan – N/A
Stockton:
Trailer 1 IT Closet
Design Matrix
Enlarged Plan – N/A
Stockton:
Trailer 2 IT Closet
Design Matrix
Enlarged Plan – N/A
Stockton:
Trailer 3 IT Closet
Design Matrix
Enlarged Plan – N/A
Stockton:
Trailer 4 IT Closet
Design Matrix
Enlarged Plan – N/A
Stockton:
Trailer 5 IT Closet
Design Matrix
Enlarged Plan – N/A
Mountain View:
Design Matrix
Enlarged Plan – Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Appendix A – Power Installation Example
Appendix B – Compliance Requirements
Appendix C – Rack Labeling Standard
Appendix
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
P R O J E C T C O N TA C T D I R E C T O R Y
Concourse Federal Group
123 S. Royal Street Alexandria, Virginia 22314
Tim Hower, Project Manager ........................................................................................thower@concousefederal.com
Lorena Alvarez................................................................................................................IaIvarez@concousefederaI.com
Mike Olson ................................................................................................................... molson@concousefederal.com
Marshall Contino, Concourse A|E Vice President ....................................................... mcontino@concousefederal.com
DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012
Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com
Kory Young, EIT, Senior Mechanical Engineer................................................................kyoung@dheeng.com
VA Palo Alto Health Care System
Jay Kim, Chief Engineer & Acting AD.............................................................................Jay.Kim@va.gov
Tammie Ridder, Palo Alto, OI&T Area Manager.............................................................Tammie.Ridder@va.gov
James Crowe……Associate Chief Engineering……………..................................................James.Crowe2@va.gov
Frank Quiles, Chief of Facilities Planning and Development..........................................Frank.Quiles@va.gov
V i c i n i t y M a p B u i l d i n g A d d r e s s e s
P a l o A l t o V A M e d i c a l C e n t e r ( V A M C )
3 8 0 1 M i r a n d a A v e n u e
P a l o A l t o , C A 9 4 3 0 4
M o u n t a i n V i e w H u m a n R e s o u r c e s
C e n t e r
1 7 7 6 O l d M i d d l e f i e l d W a y
M o u n t a i n V i e w , C A 9 4 0 4 3
C S P C C ( N O T I N S C O P E )
7 0 1 - B N . S h o r e l i n e B l v d
M o u n t a i n V i e w , C A
9 4 0 4 3 - 3 2 0 8
S u n n y v a l e R e s e a r c h C e n t e r
1 0 8 0 I n n o v a t i o n W a y
S u n n y v a l e , C A 9 4 0 8 9
F r e m o n t V A C l i n i c
3 9 1 9 9 L i b e r t y S t r e e t , B u i l d i n g B
F r e m o n t , C A 9 4 5 3 8 - 1 5 0 1
3 4
S a n J o s e V A C l i n i c
5 8 5 5 S i l v e r C r e e k V a l l e y P l a c e
S a n J o s e , C A 9 5 1 3 8 - 1 0 5 9
C a p i t o l a V A C l i n i c
1 3 5 0 4 1 s t A v e n u e , S u i t e 1 0 2
C a p i t o l a , C A 9 5 0 1 0 - 3 9 0 6
M a j o r G e n e r a l W i l l i a m H .
G o u r l e y V A - D o D O u t p a t i e n t
C l i n i c ( M o n t e r e y C l i n i c )
2 0 1 9 t h S t r e e t
M a r i n a , C A 9 3 9 3 3 - 6 0 3 9
S t o c k t o n V A C l i n i c
7 7 7 7 S o u t h F r e e d o m R o a d
F r e n c h C a m p , C A 9 5 2 3 1 - 9 6 9 4
M o d e s t o V A C l i n i c
1 2 2 5 O a k d a l e R o a d
M o d e s t o , C A 9 5 3 5 5 - 3 3 5 7
S o n o r a V A C l i n i c
1 3 6 6 3 M o n o W a y
S o n o r a , C A 9 5 3 7 0 - 2 8 1 1
1 0
1 1
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
C a m p u s M a p – PA L O A LT O V A M e d i c a l C e n t e r
B u i l d i n g I n f o r m a t i o n
LO
O
P R
O A
D
FOOTHILL EXPY
Bldg. # Bldg. Name TR Qty Levels
4 Research 3 3
5 Primary Care Clinic 4 4
6 Research & Administration Building 3 3
7 Spinal Cord Injury Center 6 1
40 Boiler Building 1 1
50 Logistics 1 1
100 Main Hospital 26 4
100 (G-WING)
Centers For Ambulatory Care, Polytrauma and Blind Rehabilitation 1 1
101 Administration 8 4
102 Diagnostics & Radiology Center 1 1
103 Emergency Generators 1 1
105 Education Training Center 2 2
500 Polytrauma and Blind Rehabilitation Center 5 3
520 Mental Health Center 3 1
520A Mental Health Administration 2 2
530 Wellness Center 2 2
MB1 Compensation & Pension 1 1
MB2 Polytrauma 1 1
MB3 Administration 1 1
MB4 Research Annex 1 1
PS1 Parking Structure 1 1 4
PS2 Parking Structure 2 1 5
T-50 Contractor Trailer 2 1
T600 Engineering Trailer 1 1
T6A Research 1 1
T6B Whistle Stop 1 1
T7A Brain Injury Center 1 1
T7B Driver Rehabilitation 1 1
T7C PSA Administration 1 1
T7D Call Center 1 1
Bldg. # Bldg. Name Data Ctr Levels
100 Main Hospital 1 4
VAMC FIBER DISTANCES
PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
4 1 A-103
Room to be abandoned and relocated to TR room A202
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
4 2 A-201
Fibre to serve A-201 and new room A-202 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
4 3 A-311
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
VAMC Palo Alto Division
Building Floor Room Distance From Existing
Server Room (Ft.)
Notes Fiber type Conduit Type
5 1 187
New TR Room
5 1 A-185
Room to be abandoned and relocated to TR room A187 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
5 2 A-243
Room to be abandoned and relocated to Fiber TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
5 3 A-308
Room to be abandoned and relocated to Fiber TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
5 4 A-403
Room to be abandoned and relocated to TR room A402 & A402A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
5 4 A402/402A
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
6 1 A-123-A
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
6 2 A-278
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
6 3 A-377 1159
Abandon and to be served by A-278 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 F144A 1522 New TR Room 24 strand single mode Interior - 4" EMT
7 1 D101 1522 New TR Room 25 strand single mode Interior - 4" EMT
7 1 A-129 1522 Room to be abandoned and relocated to TR room D-101 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 B-104B 1522 Room to be abandoned and relocated to TR room H-126A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 D-122 1522 Room to be abandoned and relocated to TR room D-101 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 E-140 1522 Room to be abandoned and relocated to TR room F144A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 F-116 1522 Room to be abandoned and relocated to TR room F144A 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 H-126A 1522 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
Note: New redundant fibre runs to the campus required. Runs and lengths TBD.
40 1
120 (Cage) in
Plumbing Shop
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
50 1 SP12
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
50 1 Outside Cage
TR to be abandoned 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
EXISTING TO REMAIN AND UPGRADED
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Typewritten Text
EXISTING TR TO REMAIN AND UPGRADED
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Typewritten Text Have to re-assess
VHAPALPrasaS1 Typewritten Text Only 1st lvl has Psychology
VHAPALPrasaS1 Typewritten Text Admin
VHAPALPrasaS1 Typewritten Text Admin
VHAPALPrasaS1 Typewritten Text Maintenance Shop
VHAPALPrasaS1 Typewritten Text Warehouse
VHAPALPrasaS1 Typewritten Text Warehouse
VHAPALPrasaS1 Typewritten Text Demarc & MDF move can be very difficult. Space planning needs to approve use of another room
VHAPALPrasaS1 Typewritten Text Every floor shall have TR
VHAPALPrasaS1 Typewritten Text Same 24 SM as redundant backbone is questionable
PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VAMC Palo Alto Division
Building Floor Room Distance From Existing
Server Room (Ft.)
Notes Fiber type Conduit Type
100 Bsmt FB370 100 Fibre main point of entry 24 strand single mode Interior - 4" EMT
100 Bsmt FB333 N/A Server Room 25 strand single mode Interior - 4" EMT
100 1 A1-TC1 (T16) 95 24 strand single mode Interior - 4" EMT
100 1 A1-TC2 (T14) 146 24 strand single mode Interior - 4" EMT
100 2 A2-TC1 (T26) 109 24 strand single mode Interior - 4" EMT
100 3 A3-TC1 (T36) 125 24 strand single mode Interior - 4" EMT
100 4 A4-TC1 (T46) 138 24 strand single mode Interior - 4" EMT
100 2 B2-TC2 (T24) 168 24 strand single mode Interior - 4" EMT
100 3 B3-TC2 (T34) 183 24 strand single mode Interior - 4" EMT
100 4 B4-TC2 (T44) 199 24 strand single mode Interior - 4" EMT
100 1 C1-TC3 (T15) 343 24 strand single mode Interior - 4" EMT
100 2 C2-TC3 (T25) 343 24 strand single mode Interior - 4" EMT
100 3 C3-TC3 (T35) 360 24 strand single mode Interior - 4" EMT
100 4 C4-TC3 (T45) 453 24 strand single mode Interior - 4" EMT
100 1 E1-TC4 (T13) 354 24 strand single mode Interior - 4" EMT
100 1 E1-TC5 (T12) 368 24 strand single mode Interior - 4" EMT
100 2 E2-TC4 (T23) 366 24 strand single mode Interior - 4" EMT
100 2 E2-TC5 (T22) 381 24 strand single mode Interior - 4" EMT
100 3 E3-TC4 (T33) 381 24 strand single mode Interior - 4" EMT
100 3 E3-TC5 (T32) 397 24 strand single mode Interior - 4" EMT
100 4 E4-TC4 (T43) 399 24 strand single mode Interior - 4" EMT
100 4 E4-TC5 (T42) 410 24 strand single mode Interior - 4" EMT
100 Bsmt EB-TC1 (T03) 176 24 strand single mode Interior - 4" EMT
100 Bsmt EB-TC2 (T02) 140 24 strand single mode Interior - 4" EMT
100 1 F1-TC6 (T11) 216 24 strand single mode Interior - 4" EMT
100 2 F2-TC6 (T21) 229 24 strand single mode Interior - 4" EMT
100 3 F3-TC6 (T31) 165 24 strand single mode Interior - 4" EMT
100 4 F4-TC6 (T41) 257 24 strand single mode Interior - 4" EMT
100 1 G1-T1.7 400
101 1 A1-TC1 (T11) 570 24 strand single mode Interior - 4" EMT
101 2 A2-TC1 (T21) 586 24 strand single mode Interior - 4" EMT
101 3 A3-TC1 (T31) 603 24 strand single mode Interior - 4" EMT
101 4 A4-TC1 (T41) 638 24 strand single mode Interior - 4" EMT
101 1 C1-TC2 (T12) 777 24 strand single mode Interior - 4" EMT
101 2 C2-TC2 (T22) 796 24 strand single mode Interior - 4" EMT
101 3 C3-TC2 (T32) 790 24 strand single mode Interior - 4" EMT
101 4 C4-TC2 (T42) 825 24 strand single mode Interior - 4" EMT
Note: New redundant fibre runs to the campus required. Runs and lengths TBD.
VHAPALPrasaS1
Not all buildings on Campus are Patient Care spaces. Some are slated for demolition. Some have completed construction and ready for Activation in near future. Built to OIT standards based on Mission Control or CBOC or other.
PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VAMC Palo Alto Division
Building Floor Room Distance From Existing
Server Room (Ft.)
Notes Fiber type Conduit Type
102 1 154 Outside
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
103 1 Outside
New TR Room 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
103 1
Mechanical room
(Only Voice)
TR to be abandoned
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
105 1 120
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
105 2 220
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
500 A1TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
500 A2TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
500 A3TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
500 B1TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
500 B2TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
520A 1 F-SC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
520A 2 F-SC2
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
520 1 A-TC1 2199
520 1 C-TC1 2199 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
520 Admin 1st floor T-4 2200 Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
520 Admin 2nd floor T-5 2215 Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
530 1 116 (Aquartics)
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
530 2
TC1, TC1A
(Recreation Therapy
Bldg)
Unable to find in drawings. Used longest run from data center to building
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
Note: New redundant fibre runs to the campus required. Runs and lengths TBD.
VHAPALPrasaS1 Line
VHAPALPrasaS1 Cross-Out
PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
MB1 106
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
MB2 106
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
MB3 330
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
MB4 408
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
PS1 1st floor Not found on Site plan or existing drawings
PS2 1st floor Not found on Site plan or existing drawings
PS2 5th floor Not found on Site plan or existing drawings
VAMC Palo Alto Division
Building Floor Room Distance From Existing
Server Room (Ft.)
Notes Fiber type Conduit Type
T6A TC1 Not found on Site plan or existing drawings
T6B
Whistle Stop Inside
Hallway
Unable to find in drawings. Used longest run from data center to building
24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T7A
TC1:wall mounted rack Not found on Site plan or existing drawings
T7B
TC1:wall mounted rack Not found on Site plan or existing drawings
T7C
TC1:Wall mounted rack Not found on Site plan or existing drawings
T7D TC1 Not found on Site plan or existing drawings
T-50 TC1
Unable to find in drawings. Used longest run from data center to building 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T600
RE's Trailer :wall mount inside copy room Not found on Site plan or existing drawings
Note: New redundant fibre runs to the campus required. Runs and lengths TBD.
VHAPALPrasaS1 Typewritten Text Garage
VHAPALPrasaS1 Typewritten Text Garage
VHAPALPrasaS1 Typewritten Text Garage
VHAPALPrasaS1 Typewritten Text Temporary leased trailers
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
Line
DOOR SECURITY REQUIREMENTS
PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
I D E N T I F I C AT I O N O F N E T WO R K S PAC E S
BLDG: 4
LEVEL: 1
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
ABANDON TR A-103
RELOCATE TO NEW TR
ROOM A202
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
VHAPALPrasaS1
EVERY FLOOR TO HAVE TR. REMEDIATE IN PLACE
LEVEL: 2
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
EXPAND IN PLACE
TELE/DATA
A-201
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NEW TR ROOM A202 TO
SERVE FIRST & SECOND
FLOOR
LEVEL: 3
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE/DATA
A-311
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
BLDG: 5
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
NEW TR ROOM 187
ABANDON TR A185
RELOCATE TO A187
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Typewritten Text Relocation of Demarc & MDF location to be analyzed There are few projects in B7 that are concurrently being done. Patient rooms, exam rooms can't be converted to MDF without approval from Planning.
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON TR A243
RELOCATE TO A402 & A402A
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1
Every floor shall have a TR room per TDDM standards
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON MECH A308
RELOCATE TO A402 & A402A
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Cross-Out
VHAPALPrasaS1 Typewritten Text Every floor to have a TR room
VHAPALPrasaS1 Line
LEVEL: 4
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON MECH A403
RELOCATE TO A402 & A402A
VHAPALPrasaS1 Typewritten Text Relocation of TR to be approved by Planning. TRs should be stacked.
How to re-route vertical backbone & Conduit penetrations
BLDG: 6
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE OP
A-123A
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
EXPAND IN PLACE
TELE OP
A-278
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VHAPALPrasaS1 Typewritten Text SCS storage in adjoining room.
Until alternate space is provided, not sure if this works.
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON IT ROOM A-378
TO BE SERVED BY A-278
VHAPALPrasaS1 every floor should have TR. Not allowed.
BLDG: 7
SCALE: 1/64” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON
TELE/DATA
A-129
RELOCATE TO NEW TR
ROOM D-101
ABANDON
TELE/DATA
B-104B
TO BE SERVED BY H-126A
ABANDON
TELE/DATA
F-116
RELOCATE TO NEW TR ROOM
F144A
REMEDIATE IN PLACE
IT ROOM
H-126A
ABANDON
TELE/DATA
D-122
RELOCATE D-122 TO
NEW TR ROOM D-101
ABANDON
ELEC/FIRE/DATA
E-140
RELOCATE TO NEW TR
ROOM F144A
NEW TR ROOM F144A
NEW TR ROOM D101
VHAPALPrasaS1 Typewritten Text MDFs and IDFs remain in location and upgraded.
Demarc can't be moved easily and existing patient rooms and exam rooms can't be converted to TRs. Needs coordination with other projects that are concurrently being planned. DB contractor needs to work with Planning dept and take above mentioned comments, OEHRM & OIT standards into consideration and how it can be executed based on existing backbone pathways and relocation.
BLDG: 4 0
SCALE: 3/32” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
SERVERS LOCATED IN FENCED AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Typewritten Text Not in Scope
VHAPALPrasaS1 Typewritten Text
VHAPALPrasaS1
This is maintenance shop area has wall mtd cabinet that can't be cooled as the entire shop is an unconditioned space.
BLDG: 5 0
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
ELEC.
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
ABANDON
3A-50 (7A)
RELOCATE TO ROOM 12
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
TR room being moved to Main Electrical room that has Transformers and ATSs? Really?
BLDG: 1 0 0
LEVEL: BASEMENT
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE/DATA
EB-TC2
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
MPOE & MDF
FB-370
REMEDIATE IN PLACE
TELE/DATA
EB-TC1
REMEDIATE IN PLACE
SERVER ROOM
FB-333
SCALE: 1/64” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE/DATA
E1-TC5
T12
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
F1-TC6
T11
REMEDIATE IN PLACE
TELE/DATA
A1-TC2
T14
REMEDIATE IN PLACE
TELE/DATA
E1-TC4
T13
REMEDIATE IN PLACE
TELE/DATA
A1-TC1
T16
REMEDIATE IN PLACE
TELE/DATA
C1-TC3
T15
SCALE: 1/64” = 1’-0”
DATE: 10/15/2020
N
EXPAND IN PLACE
TELE/DATA
E2-TC5
T22
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
F2-TC6
T21
REMEDIATE IN PLACE
TELE/DATA
B2-TC2
T24
REMEDIATE IN PLACE
TELE/DATA
E2-TC4
T23
REMEDIATE IN PLACE
TELE/DATA
A2-TC1
T26
REMEDIATE IN PLACE
TELE/DATA
C2-TC3
T25
SCALE: 1/64” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE/DATA
E3-TC5
T32
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
F3-TC6
T31
REMEDIATE IN PLACE
TELE/DATA
B3-TC2
T34
REMEDIATE IN PLACE
TELE/DATA
E3-TC4
T33
REMEDIATE IN PLACE
TELE/DATA
A3-TC1
T36
REMEDIATE IN PLACE
TELE/DATA
C3-TC3
T35
SCALE: 1/64” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
TELE/DATA
E4-TC5
T42
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
F4-TC6
T41
REMEDIATE IN PLACE
TELE/DATA
B4-TC2
T44
REMEDIATE IN PLACE
TELE/DATA
E4-TC4
T43
REMEDIATE IN PLACE
TELE/DATA
A4-TC1
T36
REMEDIATE IN PLACE
TELE/DATA
C4-TC3
T45
BLDG: 1 0 0 ( G - W I N G )
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
T-1.7
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
NEW FACILITY UNDER CONSTRUCTION. OEHRM COMPLIANT.
BLDG: 1 0 1
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
A1-TC1
T11
REMEDIATE IN PLACE
TELE/DATA
C1—TC2
T12
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
A2-TC1
T21
REMEDIATE IN PLACE
TELE/DATA
C2—TC2
T22
NOTE: REMOVE ALL FIBER AND
INFRASTRUCTURE FROM ROOM C2100A
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
A3-TC1
T31
REMEDIATE IN PLACE
TELE/DATA
C3—TC2
T32
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
A4-TC1
T41
REMEDIATE IN PLACE
TELE/DATA
C4—TC2
T42
BLDG: 1 0 2
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELE/DATA
N
VHAPALPrasaS1
WILL BE DEMOLISHED IN 2021
BLDG: 1 0 3
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
NEW 4’x 8’ ROOM ON OUTSIDE OF
BUILDING TO PROVIDE FOR NEW
EQUIPMENT.
VERIFY LOCATION OF NEW TR CLOSET
N
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1 Typewritten Text Provides main emergency power to the Hospital.
Disruption of service requires monumental effort.
Polygon
BLDG: 1 0 5
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
IRMS
N
VHAPALPrasaS1 Typewritten Text Wellness Center, CAT6, UPS, 72 SM, VHAPALPrasaS1 Line
BLDG: 1 0 5
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
AMMS/EMS STORAGE
N
VHAPALPrasaS1 Line
BLDG: 5 0 0
LEVEL: 1 (AREA A)
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TCOM
A1-TC1
VHAPALPrasaS1 Typewritten Text STATE OF THE ART FACILITY ALMOST READY TO BE ACTIVATED, LOT OF OTHER PROJECTS ARE FOLLOWING THE OPENING OF THIS PLACE. READINESS CAN'T BE DELAYED.
ONLY ITEM MISSING MAY BE UPS IN THIS TR/MDF.
LEVEL: 1 (AREA C)
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TCOM
B1-TC1
VHAPALPrasaS1
MAY REQUIRE ONLY MINI SPLIT DEDICATED COOLING, ALL OTHER CRITERIA OEHRM COMPLIANT.
LEVEL: 2 (AREA A)
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
A2-TC1
VHAPALPrasaS1
SAME AS PREVIOUS
LEVEL: 2 (AREA D)
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
B2-TC1
VHAPALPrasaS1
LEVEL: 3 (AREA A)
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
A3-TC1
VHAPALPrasaS1
BLDG: 5 2 0
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
DATA
A-TC1
REMEDIATE IN PLACE
DATA
C-TC1
520A
VHAPALPrasaS1 Typewritten Text
OIT COMPLAINT, CAT 6, 24SM, EM POWER, 71DEG, 41%RH, 2T DEDICATED COOLING.
CONCOURSE FEDERAL'S MATRIX NEEDS TO BE RE-EVALUATED. NO NEED TO DISRUPT THE FUNCTIONS OF FACILITY IF IT MEETS EHRM REQUIREMENTS.
BLDG: 5 2 0 A
SCALE: 1/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
DATA
F-SC1
VHAPALPrasaS1
BLDG: 5 2 0 A
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
DATA
F-SC2
F-226
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VHAPALPrasaS1
BLDG: 5 3 0
SCALE: NTS
DATE: 10/15/2020
N
REMEDIATE IN PLACE
ROOM 116
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
VHAPALPrasaS1
Wellness center, New, CAT6, 12SM, no patient care, plenty of EM power, has 2T dedicated cooling
BLDG: 5 3 0
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TR
TC-1
VHAPALPrasaS1
MAY REQUIRE UPS & MINI SPLIT
BLDG: M B - 1
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
ELEC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
BLDG: M B - 2
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
REMEDIATE IN PLACE
ELEC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
BLDG: M B - 3
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
EXPAND IN PLACE
TEL
NO ROOM #
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
BLDG: M B - 4
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
EXPAND IN PLACE
TEL
BLDG: P S - 1
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
1-TC1
VHAPALPrasaS1 Line
BLDG: P S - 2
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM ROOM
SP2B-TC1
VHAPALPrasaS1 Line
BLDG: P S - 2
LEVEL: 5
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM ROOM
SP5A-TC2
VHAPALPrasaS1 Line
BLDG: T 6 A
SCALE: 1/8” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
IT CLOSET
TC1
VHAPALPrasaS1 Line
BLDG: T 6 B
SCALE: 1/8” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
ELEC/TELE
VHAPALPrasaS1 Line
BLDG: T 7 A
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
WALL MOUNTED RACK
TC1
ELEC/TELE
(VERIFY HALLWAY LOCATION)
VHAPALPrasaS1 Line
BLDG: T 7 B
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
WALL MOUNTED RACK
TC1
ELEC/TELE
(VERIFY HALLWAY LOCATION)
VHAPALPrasaS1 Line
BLDG: T 7 C
SCALE: 1/4” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
ELEC/TELE
TC1
VHAPALPrasaS1 Line
BLDG: T 7 D
SCALE: 3/32” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
ELEC/TELE
TC1
VHAPALPrasaS1 Line
BLDG: T - 5 0
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TR ROOM
VHAPALPrasaS1 Line
BLDG: T 6 0 1
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
DRAWING NOT AVAILABLE
VHAPALPrasaS1 Line
O F F C A M P U S LO C AT I O N S
BLDG: S A N J O S E
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TEL/DATA
(VA ROOM NUMBER 1019A)
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
COMMUNITY BASED CLINICS ARE NOT INCLUDED IN THIS CONTRACT
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TEL/DATA
2076B
(VA ROOM NUMBER 2103)
VHAPALPrasaS1 Line
SCALE: NTS
DATE: 10/15/2020
N
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TEL/DATA
3076B
(VA ROOM NUMBER 3103)
VHAPALPrasaS1 Line
BLDG: S O N O R A C B O C
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
L.A.N.
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Line
BLDG: S T O C K T O N C B O C
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NO DRAWING AVAILABLE
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Typewritten Text IT upgrade of Stockton CBOC trailers in not in scope as the VA clinic is moving to a new facility.
VHAPALPrasaS1 Line
BLDG: SUNNYVALE RESEARCH
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
Not a patient care space & this is new under construction. This is not in contract..
BLDG: SUNNYVALE RESEARCH
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
REMEDIATE IN PLACE
TELECOM
M201
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Line
BLDG: CAPITOLA
SCALE: 3/32” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMEDIATE IN PLACE
OIT CLOSET
(UNMARKED ROOM)
VHAPALPrasaS1 Typewritten Text Lease is expiring soon before 2024.
It will no longer be VA space.
VHAPALPrasaS1 Line
BLDG: CAPITOLA
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMEDIATE IN PLACE
VHAPALPrasaS1 Line
BLDG: FREMONT
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMEDIATE IN PLACE
I.T. ROOM
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
Fremont CBOC not included in this contract
BLDG: MODESTO
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMEDIATE IN PLACE
I.T. ROOM
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
Modesto CBOC not included in this contract
BLDG: MONTEREY
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
REMEDIATE IN PLACE
TEL/DATA
1G010
VHAPALPrasaS1 Line
VHAPALPrasaS1 Line
VHAPALPrasaS1
Monterey CBOC not included in this contract.
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
REMEDIATE IN PLACE
TEL/DATA
2B001
VHAPALPrasaS1 Line
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
REMEDIATE IN PLACE
TEL/DATA
2G005
VHAPALPrasaS1 Line
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
REMEDIATE IN PLACE
TEL/DATA
3B001
VHAPALPrasaS1 Line
SCALE: NTS
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
REMEDIATE IN PLACE
TEL/DATA
3G005
VHAPALPrasaS1 Line
BLDG: MOUNTAIN VIEW HR
SCALE: 1/16” = 1’-0”
DATE: 10/15/2020
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMEDIATE IN PLACE
ELEC
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
N E T WO R K S PAC E D E S I G N
SCALE: 1/4” = 1’-0”
DATE: 10/15/2020
NEW TR ROOM A201 & A202
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
REMOVE EXISTING
DOOR AND INFILL
DOOR OPENING
REMOVE EXISTING WALL
PROVIDE WINDOW
INSULATION IN ORDER
TO KEEP THE TR ROOM
TEMPERATURE COOL.
EXISTING TR ROOM A-103 TO
RELOCATE TO A-201 & A-202
Building 4, NEW Room A-201 & 202
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Room A-201 to expand into room A-202.
Room A-103 to be relocated to new TR room
A-202. Provide insulation on window to reduce heat transfer. Provide 3 ton ductless mini-split. Condenser to be located on roof.
X
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Rack Temperature/Humidity
Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to BMS X Missing grounding bus bar Install copper grounding bus bar
Piping over equipment Relocate piping or install pipe trough with floor tape-type leak detector X
Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X Remote Controlled battery thermostat Wired thermostat X
No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special
Telecommunications Systems Design
Manual
X Micro condensate pump Commercial condensate pump
C A
B
LI
N G
X Inadequate fiber optic cabling to
TR
Install new as required
X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 342
Approximate total cable length = 56430'
X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new equipment provide two new racks.
VHAPALPrasaS1 Typewritten Text In spaces where mini-split is neither required nor feasible, exhaust fan and undecut door should be considered. Relative humidity is never a problem at VAPAHCS. This comment is general for all spaces.
VHAPALPrasaS1 Polygon
Polygon
SCALE: 1/4” = 1’-0”
DATE: 10/15/2020
B311
VA PALO ALTO HEALTHCARE SYSTEM
PALO ALTO VAMC
N
TEL/DATA
B311
Building 4, Room B311
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide insulation on window to reduce heat transfer. Provide 3 ton ductless mini-split.
Condenser to be located on roof.
Insufficient…