An evaluation report and related federal contract opportunity outline the need to assess, remove, replace, and recommission defective controllers, switches, and devices on the poultry ventilation system at a USDA Agricultural Research Service facility. The evaluation report details specific issues found with controllers, switches, relays, and fan speed controllers across nine rooms and two corridors requiring replacement of parts. It also identifies the need to replace light traps and shutters on exhaust fans, add time clock controls to cooling pumps, test and repair corridor preheaters, and lubricate a vent machine. The related federal contract opportunity solicits proposals to complete the work by the specified response date of February 10th, 2022, and holds a mandatory site visit for interested parties. The work is to be conducted for the USDA Agricultural Research Service Northeast Area according to the statement of work.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Room 101:
Control System Status:
ST1.6 controller: 18” fan runs on high speed only (Triac damaged), Replace back board of ST1.6 AeroSpeed con-troller
Heater does not run with Stage Hand in AUTO posi on, Replace Stage Hand relay card for heater
TC1-CD fan speed controller has a broken push bu on but the controller s ll works, no work needed
Parts Needed: 1—TW1277 controller back board, 1—FC4120 relay circuit board
Room 102:
Control System Status:
ST1.6 controller: 18” fan runs and speed varies but toggle switch will not stay in MANUAL posi on unless held, replace toggle switch for Stage 1 fan in Stage Hand box
Heater a empted to start but did not stay running, check room heater for malfunc on and repair
TC1-CD fan speed controller is working properly to control the circula on fans in the room
Parts Needed: 1—TC1300 DPDT toggle switch
Room 103:
Control System Status:
ST1.3 AeroSpeed controller has a broken Selector Dial so it could not be tested, at a minimum the controller’s front cover needs to be replaced, but replacing the complete controller is recommended
Only the MANUAL side of the Stage Hand switches and relays could be tested and all were okay
TC1-CD fan speed controller had a dark display and appeared to not be working, replace TC1-CD controller
Parts Needed: 1—ST5121 controller, 1—TC1-CD controller
Room 104:
Control System Status:
ST1.6 controller: 18” fan runs and speed varies
All Stage Hand switches and relays tested okay
TC1-CD fan speed controller would not run the circula on fans, signs of damage to a ribbon cable between the controller’s display and the back circuit board, replace TC1-CD controller
Parts Needed: 1—TC1-CD controller
USDA ARS BARC Poultry Research Facility—Scope of Work to be Performed
EVALUATION REPORT
Room 105:
Control System Status:
ST1.3 controller: 18” fan runs on high speed only (Triac damaged), replace back board of controller
Heater seems to be connected to a thermostat in the room, so it could not be tested with the room controller, re-connect room heater to Stage Hand relay and ST1.3 controller
TC1-CD fan speed controller does not have a front cover, replace TC1-CD controller
Stage Hand relay for cool cell pump receptacle not connected, replace Stage Hand relay card and reconnect
Stage Hand box missing one Stage Hand relay card (a spare relay) leaving a hole in the front cover of the box, re-place
Stage Hand relay card to close off hole, this spare relay card might be needed if the relay card for the heater is defec ve
Parts Needed: 1—TW1275 controller back board, 1—TC1-CD controller, 2—FC4120 relay circuit board
Preheat & Cooling Corridor for Rooms 101 ‐ 105:
AeroSentry Photohelic Control Status:
Neon indicator lights on AeroSentry not working, but controller does work for open and close func ons, replace neon indicator lights
Parts Needed (Apex Ag-Tek parts): 1— EP-2152QA5 green neon light, 2—EP-2150QA3 amber neon light
Aerotech BA4503-30 Vent Machine:
The vent machine was tested and found to be working in both open and close direc ons, the close limit stop was set to provide a 1/2” wide minimum opening for the corridor, provide lubrica on of the ball-screw and corner pulleys in the vent machine as needed (vent machine operates several sec ons of 30” tall Aerotech air intake vents for the corri-dor)
Cool Cell Systems (on outside of corridor wall):
Each cool cell pump is operated by a 120V receptacle on the outside of the corridor which is controlled by the last cooling stage of the room controller for each room. In order to prevent the cooling pumps from running during the night me hours, a 24hr me clock control should be added. This will require adding one 24hr me clock for each room (suitable item: Interma c T100 series Electromechanical Time Switch, model T101 or similar). The me clock can be installed next to the Stage Hand box for each room. The SPST relay in the me clock must be wired in series with the Stage Hand relay that controls the cool cell pump receptacle. The me clock can be powered by the same 120V circuit that feeds the Stage Hand relays. Set me clock to allow the cool cell pumps to run between the hours of 10am and 9pm. (Pump only runs if the cooling stage for the room is on.)
Corridor Preheaters:
Test all preheaters in the corridor and their respec ve thermostat. Perform any maintenance and repairs as necessary. Each room has a preheater mounted in the corridor which is controlled by a thermostat also in the corridor.
Room 135 (129):
Control System Status:
ST1.6 controller: 18” fan runs and speed varies
All Stage Hand switches and relays tested okay
TC1-CD fan speed controller display is dark and appears to not work, replace TC1-CD controller
Parts Needed: 1—TC1-CD controller
Room 136 (130):
Control System Status:
ST1.6 controller: 18” fan runs and speed varies
All Stage Hand switches and relays tested okay
TC1-CD fan speed controller appears to be okay, but the fans did not run, perhaps because switches at each fan were turned off, must verify that the controller will run the 14” circula on fans
Parts Needed: None (unless other items are found)
Room 137 (131):
Control System Status:
ST1.6 controller: 18” fan runs and speed varies
All Stage Hand switches and relays tested okay
TC1-CD fan speed controller appears to be okay, but the fans did not run, perhaps because switches at each fan were turned off, must verify that the controller will run the 14” circula on fans
Parts Needed: None (unless other items are found)
Room 138 (132):
Control System Status:
ST1.6 controller: 18” fan runs and speed varies
All Stage Hand switches and relays tested as okay except relay for cool cell pump does not have 120V power con-nected to the input to the relay, replace Stage Hand relay circuit board and reconnect 120V input power (if ex-is ng relay circuit board is s ll good then keep one as a spare)
Heater seems to be connectd to a thermostat in the room. Replace Stage Hand relay and reconnect heater to it.
Toggle switch for Stage 1 fan is damaged, replace toggle switch
TC1-CD fan speed controller appears to be okay, but the fans did not run, perhaps because switches at each fan were turned off, must verify that the controller will run the 14” circula on fans
Parts Needed: 2—FC4120 relay circuit board, 1—FC1110 selector knob for ST1.6 controller, 1—FC1300 switch
Room 139 (133):
Control System Status:
ST1.3 controller: 18” fan runs and speed varies
Cooling Stage on the ST1.3 controller does not func on properly to turn on the cooling pump receptacle at the ap-propriate temperature se ng, replace at least the front cover of the ST1.3 controller and possibly the complete con-troller (complete unit included in parts list).
All Stage Hand switches and relays tested okay
TC1-CD fan speed controller is working properly
Parts Needed: 1—ST5121 controller (ST1.3)
Preheat & Cooling Corridor for Rooms 135 ‐ 139:
AeroSentry Photohelic Control Status:
Neon indicator lights on AeroSentry not working, but controller does work for open and close func ons, replace neon indicator lights
Parts Needed (Apex Ag-Tek parts): 1— EP-2152QA5 green neon light, 2—EP-2150QA3 amber neon light
Aerotech BA4503-30 Vent Machine:
The vent machine was tested and found to be working in both open and close direc ons, the close limit stop was set to provide a 1/2” wide minimum opening for the corridor, provide lubrica on of the ball-screw and corner pulleys in the vent machine as needed (vent machine operates several sec ons of 30” tall Aerotech air intake vents for the corri-dor)
Cool Cell Systems (on outside of corridor wall):
Each cool cell pump is operated by a 120V receptacle on the outside of the corridor which is controlled by the last cooling stage of the room controller for each room. In order to prevent the cooling pumps from running during the night me hours, a 24hr me clock control should be added. This will require adding one 24hr me clock for each room (suitable item: Interma c T100 series Electromechanical Time Switch, model T101 or similar). The me clock can be installed next to the Stage Hand box for each room. The SPST relay in the me clock must be wired in series with the Stage Hand relay that controls the cool cell pump receptacle. The me clock can be powered by the same 120V circuit that feeds the Stage Hand relays. Set me clock to allow the cool cell pumps to run between the hours of 10am and 9pm. (Pump only runs if the cooling stage for the room is on.)
Corridor Preheaters:
Test all preheaters in the corridor and their respec ve thermostat. Perform any maintenance and repairs as necessary.
Each room has a preheater mounted in the corridor which is controlled by a thermostat also in the corridor.
Light Traps and Shutters Remove and Install new Light traps and shutters. Of the 27 exhaust fans in facility, 14 will recieve new light traps.
They will be identified to the contractor by the COR prior to starting work. Attachment 3 shows part details.
All of the PR26 shutters shall be replaced. Attachment 3 shows part details.
See Addendum for various photos of the ven la on equipment installed in the facility.
Disclaimer: The above descrip on of items is intended to convey a detailed list of all items with the ven la on systems that will need to be addressed to get things into working order. Some items as noted however, may need to be further inves gated to determine if any addi onal items need to be replaced. Those items can be quoted and delivered at a later me if needed.
Report date: 3/31/2021
USDA ARS BARC Poultry Research Facility—Scope of Work Addendum
Site visit by Nevin Wagner & Errol Moyer (Ag‐One Associates) on 3/2/2021
Rooms 101 to 105:
Rooms 135 to 139 as signs indicate at rooms (or 129‐133 on print):
Corridor Air Intake 30” Vents
Corridor Air Intake Vent Machine (AeroSentry SP Con-trol not shown but connected to this machine)
Corridor Cool Cells behind Air Intake Vents
Outside View: 1 Typical Cool Cell System Outside View: Cool Cell Systems along 1 Corridor, other Cor-ridor similar
Inside of a room: 14in circula on fan and MI4 air inlets that draw air from Corridor through light trap boxes (light trap boxes not shown)
Inside of room: (chicken side of facility)
Inside of room: A typical Large Room shown with 3 exhaust fans (1-18” fan and 2-26” fans, all have light trap boxes and all boxes are the same size
Report Addendum Date: 3-31-21