This document is the Unified Facilities Criteria (UFC) 3-201-01 Civil Engineering document, dated 20 December 2022, developed and authorized by multiple Department of Defense (DoD) agencies including the U.S. Army Corps of Engineers, Naval Facilities Engineering Systems Command, Air Force Civil Engineer Center, and the Office of the Secretary of Defense. The document provides comprehensive civil engineering requirements and guidelines for planning, design, and construction of permanent DoD facilities worldwide, applicable to all service elements and contractors involved in project delivery across all construction levels. It covers a wide range of site design considerations including flood hazard planning, environmental policy, site analysis, geotechnical investigations, vehicle circulation, utilities, storm drainage systems, and pavement design for roads, parking areas, and airfields.

The UFC serves as a standardized technical reference that integrates multiple design disciplines and government unique criteria, addressing critical aspects such as accessibility, antiterrorism, security, high-performance sustainability requirements, and safety. It references and incorporates various federal regulations, executive orders, and national building codes, with provisions for adapting to international agreements and location-specific environmental conditions. The document is a living document that will be periodically reviewed and updated, and it is distributed electronically through the Whole Building Design Guide web site. The criteria are designed to ensure consistent, high-quality engineering standards across DoD construction projects, with specific attention to emerging challenges like climate change, flood risk management, and resilient infrastructure design.

View the file

Other versions and copies of UFC 3-201-01

File Revision Posted Attached to
13 - UFC 3-201-01 Civil Engineering.pdf Revision not stated Relocate Kirtland Sunshades

Who attaches UFC 3-201-01

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UFC 3-201-01

20 December 2022

UNIFIED FACILITIES CRITERIA (UFC)

APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED

CIVIL ENGINEERING

This Page Intentionally Left Blank

UNIFIED FACILITIES CRITERIA (UFC)

CIVIL ENGINEERING

Any copyrighted material included in this UFC is identified at its point of use.

Use of the copyrighted material apart from this UFC must have the permission of the copyright holder.

Indicate the preparing activity beside the Service responsible for preparing the document.

U.S. ARMY CORPS OF ENGINEERS

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND (Preparing Activity)

AIR FORCE CIVIL ENGINEER CENTER

Record of Changes (changes are indicated by \1\ ... /1/)

Change No. Date Location

This UFC supersedes UFC 3-201-01, dated 01 April 2018.

FOREWORD

The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides planning, design, construction, sustainment, restoration, and modernization criteria, and applies to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance with USD (AT&L) Memorandum dated 29 May 2002. UFC will be used for all DoD projects and work for other customers where appropriate. All construction outside of the United States is also governed by Status of Forces Agreements (SOFA), Host Nation Funded Construction Agreements (HNFA), and in some instances, Bilateral Infrastructure Agreements (BIA).

Therefore, the acquisition team must ensure compliance with the most stringent of the UFC, the SOFA, the HNFA, and the BIA, as applicable.

UFC are living documents and will be periodically reviewed, updated, and made available to users as part of the Services’ responsibility for providing technical criteria for military construction. Headquarters, U.S. Army Corps of Engineers (HQUSACE), Naval Facilities Engineering Systems Command (NAVFAC), and Air Force Civil Engineer Center (AFCEC) are responsible for administration of the UFC system. Defense agencies should contact the preparing service for document interpretation and improvements. Technical content of UFC is the responsibility of the cognizant DoD working group. Recommended changes with supporting rationale may be sent to the respective DoD working group by submitting a Criteria Change Request (CCR) via the Internet site listed below.

UFC are effective upon issuance and are distributed only in electronic media from the following source:

• Whole Building Design Guide web site http://www.wbdg.org/ffc/dod.

Refer to UFC 1-200-01, DoD Building Code, for implementation of new issuances on projects.

AUTHORIZED BY:

PETE G. PEREZ, P.E., SES

Chief, Engineering and Construction U.S. Army Corps of Engineers

R. DAVID CURFMAN, P.E., SES

Chief Engineer Naval Facilities Engineering Systems Command

DAVID H. DENTINO, SES

Deputy Director of Civil Engineers DCS/Logistics, Engineering & Force Protection (HAF/A4C) HQ United States Air Force

MICHAEL McANDREW, SES Deputy Assistant Secretary of Defense (Construction) Office of the Secretary of Defense http://www.wbdg.org/pdfs/ufc_implementation.pdf http://www.wbdg.org/ffc/dod i

TABLE OF CONTENTS

CHAPTER 1 INTRODUCTION

1-1 REISSUES AND CANCELS

1-2 PURPOSE AND SCOPE

1-3 APPLICABILITY

1-3.1 Foreign Countries

1-4 GENERAL BUILDING REQUIREMENTS

1-4.1 Low Impact Development

1-5 CYBERSECURITY

1-6 BEST PRACTICES

1-7 GLOSSARY

1-8 REFERENCES

1-9 COMMENTARY

CHAPTER 2 SITE DESIGN

2-1 PLANNING

2-1.1 Wetlands

2-1.2 Flood Hazard Planning

2-2 NATIONAL ENVIRONMENTAL POLICY ACT

2-3 PRELIMINARY SITE ANALYSIS

2-4 EXISTING CONDITIONS

2-4.1 Geotechnical Site Investigation

2-4.2 Surveying

2-4.3 Environmental Considerations

2-4.4 Existing Sewers

2-5 APPROVALS AND PERMITS

2-6 CLEARING AND DEMOLITION

2-7 SITE DEVELOPMENT

2-7.1 Accessibility

2-7.2 Petroleum, Oil and Lubrication (POL)

2-8 FLOOD RESISTANT DESIGN

2-8.1 Non-Tidally Influenced Locations

2-8.2 Tidally Influenced Locations

2-8.3 Flood Resistant Design Options ii

2-8.4 Flood Protection Systems

2-8.5 Mission Critical Roads

2-9 GRADING

2-9.1 Transverse and Longitudinal Slopes

2-9.2 Finished Floor Elevations

2-9.3 Airfields

2-10 VEHICLE CIRCULATION

2-10.1 Special Circulation Areas

2-10.2 Traffic Studies

2-10.3 Design Vehicles

2-10.4 Design Traffic

2-10.5 Roads

2-10.6 Parking Areas

2-10.7 Bicycle Facilities

2-11 SITE APPURTENANCES

2-11.1 Pedestrian Circulation

2-11.2 Curb or Curb and Gutter

2-11.3 Wheelstops

2-11.4 Bollards

2-11.5 Signage and Markings

2-11.6 Dumpster Enclosures

2-12 UTILITIES

2-12.1 Water Distribution Systems

2-12.2 Wastewater Collection Systems

2-12.3 Lighting

2-13 STORM DRAINAGE SYSTEMS

2-14 ENTRY CONTROL FACILITIES

2-15 BRIDGES, OVERPASSES AND UNDERPASSES

CHAPTER 3 STORM DRAINAGE SYSTEMS

3-1 DESIGN CRITERIA

3-1.1 Approved Methodologies

3-1.2 Design Storm Frequency

3-1.3 Maximum Spread iii

3-1.4 Inlet Design

3-1.5 Erosion and Sediment Control

3-1.6 Pollution Prevention

3-2 MATERIAL SELECTION FOR AIRFIELDS

3-3 ROOF DRAINAGE

3-4 SURFACE DRAINAGE

3-4.1 Open Channels

3-5 UNDERGROUND GRAVITY STORM DRAINAGE SYSTEM

3-5.2 Minimum Pipe Size

3-5.3 Minimum and Maximum Cover

3-5.4 Design Velocity

3-5.5 Manning’s Roughness Coefficient

3-5.6 Material Selection

3-5.7 Culverts and Outfalls

3-5.8 Storm Structures

3-6 STORMWATER MANAGEMENT FACILITIES

3-6.1 Safety and Storm Drainage System Components

3-6.2 Airfields

3-7 STORMWATER PUMP STATIONS

3-7.1 Existing Pump Stations: Upgrades and Additional Flow

CHAPTER 4 PAVEMENTS

4-1 SURFACED AND UNSURFACED ROADS AND SITE PAVEMENTS. .. 35

4-1.1 Frost Conditions

4-1.2 Recycled Materials

4-1.3 Flexible Pavements

4-1.4 Rigid Pavements

4-1.5 Permeable Pavements

4-1.6 Aggregate Pavements

4-2 AIRFIELD PAVEMENTS AND MARKINGS

APPENDIX A BEST PRACTICES

A-1 WHOLE BUILDING DESIGN GUIDE

A-2 BEST PRACTICES CIVIL ENGINEERING RELATED GUIDANCE

A-2.1 Building Location and Orientation iv

A-2.2 Flood Hazard Areas

A-2.3 Flood Protection Systems

A-2.4 Roads

A-2.5 Vehicle Circulation

A-2.6 Parking Areas

A-2.7 Rational Formula

A-2.8 Airfield Pavements

APPENDIX B GLOSSARY

B-1 ACRONYMS

B-2 DEFINITION OF TERMS

APPENDIX C REFERENCES

C-1 FEDERAL GOVERNMENT

C-2 NON-GOVERNMENT

C-3 INDUSTRY PUBLICATIONS

FIGURES

Figure 3-1 Deflection at Structures

TABLES

Table 2-1 Design Flood Elevation (DFE)

Table 2-2 Grading

Table 3-1 Storm Structure Spacing Criteria

Table 3-2 Minimum Invert Elevations

Table 3-3 Design Velocity

Table A-1 Essential and Non-Essential Guidance

Table A-2 Parking Space Guidelines for Non-Organizational Vehicles

CHAPTER 1 INTRODUCTION

1-1 REISSUES AND CANCELS.

This UFC supersedes UFC 3-201-01 with Change 5 dated 1 April 2021.

1-2 PURPOSE AND SCOPE.

This UFC provides civil engineering requirements for all new and renovated Government facilities for the Department of Defense (DoD). Where other criteria, statutory or regulatory requirements, are referenced, the more stringent requirement must be met.

1-3 APPLICABILITY.

This UFC applies to all service elements and contractors involved in the planning, design and construction of permanent DoD facilities worldwide. It is applicable to all methods of project delivery and levels of construction.

1-3.1 Foreign Countries.

All design and construction outside of the United States and United States territories is governed by international agreements, such as the Status of Forces Agreements (SOFA), Host Nation-Funded Construction Agreements (HNFA), and in some instances, Bilateral Infrastructure Agreements (BIA), and country-specific Final Environmental Governing Standards (FGS) or DoDI 4715.05. DoDI 4715.05 is commonly referred to as the Overseas Environmental Baseline Guidance Document (OEBGD). The OEBGD applies when there are no international agreements in place. Therefore, in foreign countries this UFC will be used for DoD projects to the extent that it is allowed by and does not conflict with the applicable international agreements.

1-4 GENERAL BUILDING REQUIREMENTS.

Comply with UFC 1-200-01, DoD Building Code. UFC 1-200-01 provides applicability of model building codes and government unique criteria for typical design disciplines and building systems, as well as for accessibility, antiterrorism, security, high performance and sustainability requirements, and safety. Use this UFC in addition to UFC 1-200-01 and the UFCs and government criteria referenced therein.

1-4.1 Low Impact Development.

Use UFC 3-210-10 for Low Impact Development (LID) criteria. UFC 3-210-10 was developed to comply with the DoD Memorandum implementing Section 438 of the Energy Independence and Security Act (EISA).

1-5 CYBERSECURITY.

All control systems (including systems separate from an energy management control system) must be planned, designed, acquired, executed, and maintained in accordance with UFC 4-010-06, and as required by individual Service Implementation Policy.

1-6 BEST PRACTICES.

APPENDIX A provides guidance for accomplishing certain civil design and engineering services. The Designer of Record (DoR) is expected to review and interpret this guidance as it conforms to criteria and contract requirements and apply the information according to the needs of the project. If a Best Practices document has guidelines or requirements that differ from any UFC or the Unified Facilities Guide Specifications (UFGS), the UFC and the UFGS must be given a higher order of precedence.

1-7 GLOSSARY.

APPENDIX B contains acronyms, abbreviations, and terms.

1-8 REFERENCES.

APPENDIX C contains a list of references used in this document. The publication date of the code or standard is not included in this document. Unless otherwise specified, the most recent edition of the referenced publication applies.

1-9 COMMENTARY.

Limited commentary has been added to the chapters. Section designations for such commentary are preceded by a “[C]” and the commentary narrative is highlighted with light gray.

CHAPTER 2 SITE DESIGN

2-1 PLANNING.

Site selection and planning require knowledge of environmental requirements, land use restrictions, building setbacks, flood hazard areas, utility connections, utility offsets, vehicle circulation, buffers from natural and manmade features and other similar requirements. Use this UFC prior to starting design to determine specific project requirements including but not limited to demolition, site development, water distribution, and wastewater collection.

2-1.1 Wetlands.

Executive Order (EO) 11990 directs all Federal agencies to avoid wetlands development wherever there is a practicable alternative.

2-1.2 Flood Hazard Planning.

EO 11988 directs all Federal agencies to comply with the minimum requirements of the National Flood Insurance Program. DTM 22-003 directs DoD to avoid development within a flood hazard area to the maximum extent practicable. When mission needs require siting a building within or partially within a flood hazard area, evaluate alternative site locations to avoid or minimize adverse impacts to the floodplain. When no practicable alternative exists, use section 2-1.2.3 to develop a flood risk reduction plan and use section 2-8 to determine the appropriate flood risk reduction criteria.

2-1.2.1 Assessment of Flood Vulnerability.

Provide an assessment of flood vulnerability that integrates: current flood hazard mapping; increases in projected sea level rise; when available, the climate-informed science approach; and future forecasted land use changes over the service life of the facility.

2-1.2.1.1 Non-Tidally Influenced Locations.

Use paragraph 2-8.1.1 Flood Hazard Areas.

2-1.2.1.2 Tidally Influenced Locations.

Use paragraph 2-8.2.1 DoD Regional Sea Level Database.

2-1.2.2 Design Flood Event.

The design flood event is the 100 year or greater flood event used to establish the design flood. The design flood event may include events that exceed the 100-year event, such as areas that may be impacted by projected sea level rise over the service life of the facility, the 500-year flood event, or when available, the Climate-Informed Science Approach.

2-1.2.3 Flood Risk Reduction Plan.

A project-specific Basis for Flood Risk Reduction is required for all facilities sited within a flood hazard area. When developing the Basis for Flood Risk Reduction, fully consider all flood risk reduction measures included in ASCE 24-14 such as breakaway walls, non-engineered and engineered openings, dry proofing and wet proofing. The Basis for Flood Risk Reduction may include temporary flood protection systems.

2-1.2.3.1 Department of Defense Form 1391 Disclosure Requirements.

When mission needs require siting a building within or partially within a flood hazard area, indicate the following information on DoD Form 1391:

1. Identify the type of flood hazard area: 1 percent annual chance event (ACE), 0.2 percent ACE, Climate-Informed Science Approach; or projected sea level rise over the service life of the facility; and

2. For the Climate-Informed Science Approach, the climate informed science flood elevation as the base flood elevation (BFE) and the design flood elevation (DFE);

3. For the Freeboard Approach, the design flood event, BFE and the DFE; or

4. For the DRSL Approach, sea level rise scenario and timeframe used to establish the DFE.

2-1.2.3.2 Flood Risk Reduction Documentation.

In accordance with PL 115-232, Section 2805(a)(3), as amended by PL 116-92, evaluate all applicable flood risk reduction measures and document in the Basis for Flood Risk Reduction. Store the Basis for Flood Risk Reduction in project file during the 1391 development process and retain the Basis for Flood Risk Reduction in the project historical file. In tidally influenced locations, the Basis for Flood Risk Reduction must incorporate DoD component direction, when available. DoD component direction may include scenarios and timeframes that are less than or greater than the default values shown in the DRSL Approach column in Table 2-1. The Basis for Flood Risk Reduction must include:

• A description of the site location and rationale for the project’s site selection, including if the site is non-tidally or tidally influenced;

• Information concerning alternative sites that were considered and an explanation of why those sites did not satisfy mission requirements;

• A description of the flood hazard area, such as a high velocity V zone, coastal A zone, X zone, area inundated by projected sea level rise, or the Climate-Informed Science Approach, and an assessment of the flood vulnerability;

• A description of the design flood event, such as the 1 percent ACE, 0.2 percent ACE, Climate-Informed Science Approach, or the projected sea level rise scenario and timeframe;

• If using the Climate–Informed Science Approach, the climate-informed science flood elevation, an assessment of the flood vulnerability (risk of flooding), the BFE and the DFE;

• If the project is in a non-tidally influenced location, an assessment of the flood vulnerability (risk of flooding), the BFE and the DFE;

• If the project is in a tidally influenced location, a description of the approach used, Freeboard Approach or DRSL Approach; whichever is more stringent. For the Freeboard Approach, include an assessment of the flood vulnerability (risk of flooding), BFE and the DFE. For the DRSL Approach, include an assessment of the flood vulnerability (risk of flooding), and the sea level rise scenario and timeframe used to establish the DFE; and

• A description of planned flood risk reduction measures.

2-2 NATIONAL ENVIRONMENTAL POLICY ACT.

National Environmental Policy Act (NEPA) actions should be completed prior to starting design. Obtain NEPA documentation prepared for the project from the Installation environmental staff. Comply with the identified measures and include them as contract requirements.

2-3 PRELIMINARY SITE ANALYSIS.

Use UFC 2-100-01 to develop a preliminary approach appropriate to the site and adjacent facilities, integrate sustainable strategies, and utilizing a holistic design approach. Conduct a preliminary site visit and obtain photographs of the site.

Research and obtain Installation’s master plan, utility maps, and as-built record drawings for information related to topography, utility, and storm drainage availability, including design approaches used in the project vicinity. Evaluate the potential for abandoned or unmapped utilities. Research and review available subsurface investigation data and reports in order to evaluate subsurface conditions. Identify flood hazard areas in accordance with the International Building Code (IBC) Section 1612 and sections 2-1.2 and 2-8 of this UFC. Research and obtain explosive safety requirements. Consult with the Government Project Manager to establish contact with the Installation’s Environmental personnel to determine if the site has environmental concerns, such as radon, pesticides, or known contamination. If required, provide radon mitigation system design in accordance with UFC 3-101-01. Evaluate the need for additional analysis based on project requirements and site conditions.

Conduct detailed consultations with the Government in order to clearly define requirements and preferences.

2-4 EXISTING CONDITIONS.

2-4.1 Geotechnical Site Investigation.

Obtain soil exploration, testing, and evaluation from a professional geotechnical engineer. Determine the extent of exploration and testing based on recommendations with the geotechnical engineer, structural engineer (for foundations), civil engineer (for site elements such as LID, pavements, wells, and septic systems), local stormwater permitting agency (for detention ponds), and Government reviewers. Soils investigation (sampling, testing, and evaluation) must be in accordance with UFC 3-220-01, UFC 3- 250-01, and UFC 3-260-02.

Indicate the results of the subsurface investigation, including boring locations, boring logs, groundwater observations, a summary of laboratory test results, and any details required to convey requirements for site preparation on the contract documents.

2-4.1.1 Soil Corrosivity.

Require geotechnical site investigation for soil corrosivity, when existing operating records, visual observations, inspections, or testing indicate corrosive soil conditions.

Provide an evaluation of existing soils at the proposed depths and locations of piping in accordance with AWWA M27, chapter titled Evaluating the Potential for Corrosion.

2-4.2 Surveying.

Unless provided by Government personnel, a licensed or certified professional must seal all surveys in accordance with the applicable requirements of the local regulatory agency or overseas equivalent having jurisdiction over the Installation. Where overseas equivalent requirements do not include an accuracy standard, provide surveys at a minimum third order in accordance with National Oceanic and Atmospheric Administration (NOAA), Federal Geodetic Control Committee, Standards and Specifications for Geodetic Control Networks.

Prior to entering property not owned by the Government, consult with the Government Project Manager to establish contact with the Installation’s real estate personnel. Notify and obtain authorization for a right of entry over, across, or through all lands public or private landowners necessary to perform required field survey work. Coordinate with the Installation’s Security section for approval to enter controlled or restricted areas including but not limited to airfields, ranges, and munition storage. Consult with Government Project Manager to establish contact with the Installation’s Environmental personnel before entering the area with regards to any restrictions such as cutting or clearing vegetation, natural resources, or species.

2-4.2.1 Topographic Surveys.

Provide a topographic survey of the project site in accordance with each service’s requirements as well as the requirements of the state or Host nation equivalent in which the site is located. If state or Host nation equivalent requirements are not available, use Model Standards for Topographic Surveys.

2-4.3 Environmental Considerations.

Coordinate with the Installation EV Staff during preliminary site investigation, review existing records and evaluate site for environmental concerns or known contamination such as soil or groundwater contamination. If known contamination or environmental concerns are identified, notify the Government Project Manager and evaluate impacts to project cost to ensure adequate funding for current project.

2-4.4 Existing Sewers.

Use WEF MOP FD-6 for guidance when evaluating and rehabilitating existing sewers.

2-5 APPROVALS AND PERMITS.

The DoR must identify, assist, and provide, as applicable, all permits, approvals, and fees required for the design and construction of the new project from Federal, state, and local regulatory authorities or overseas equivalent. The Civil Engineering DoR must be a Professional Civil Engineer experienced and licensed. Licensure in the location of the project may be required to obtain permits and approvals. In the United States and its territories and possessions the Government will review permits for acceptability. In locations outside of the United States and its territories and possessions with Host nation agreements, follow permit approval procedure as directed in project scope and by the Government Project Manager. In locations outside of the United States and its territories and possessions without Host nation agreements, the Government will review and approve site improvement plans for compliance.

Consult with the Government Project Manager to determine the appropriate signatories for permit applications.

2-6 CLEARING AND DEMOLITION.

Identify the following in the construction documents: limits of disturbance; limits of demolition; limits of clearing and grubbing; isolated trees and shrubs to remain or to be removed. Describe size, density, and type of trees to be cleared and grubbed, items to be salvaged or relocated, staging area, temporary storage area and location.

Coordinate with the Installation concerning clearing options to remove merchantable timber from the project site.

During site demolition and preparation, remove existing and abandoned utilities under or within 10 feet (3.0 m) of the foundation of any new facility or building foundation.

Reroute existing utilities to remain in accordance with paragraph titled “UTILITIES” in Chapter 2.

2-7 SITE DEVELOPMENT.

Location and orientation of facilities must be based on an analysis of activities to be accommodated and on specific requirements for each project, to include all functional, technical, and economic factors. Use UFC 3-101-01 for building function, size, and orientation criteria.

Incorporate the following into site design, as applicable:

a. Land use restrictions and setbacks (existing and future).

b. Circulation (vehicle and pedestrian).

c. Orientation and Location to integrate green space. Provide adequate grading and drainage while preserving natural topographic features to minimize cut and fill, impact on existing drainage patterns and tree removal.

d. Operational and natural constraints.

1. Maintain mandated buffers:

(a) Airfield and helipad clearances.

(b) Explosives safety clearances.

(c) Noise abatement.

(d) Antiterrorism and physical security clearances.

(e) Storage and handling hazardous material clearances.

(f) Separation of incompatible land use or functions.

(g) Building setbacks (if established).

(h) Fire separation zones per building and fire codes.

2. Eliminate or minimize construction activities requiring permits for areas such as archaeological sites, wetlands, utilities, and stormwater management.

3. Minimize site or utility maintenance and operating costs.

4. Accommodate site constructability and security requirements.

5. Minimize distance to existing utility connections.

2-7.1 Accessibility.

Use UFC 1-200-01 to determine accessibility requirements.

2-7.2 Petroleum, Oil and Lubrication (POL).

Use UFC 3-460-01 for POL criteria.

2-8 FLOOD RESISTANT DESIGN.

Facilities sited within or partially within a flood hazard area must be designed in accordance with UFC 1-200-01 and this UFC. For flood resistant design, UFC 1-200-01 implements the IBC and the IBC implements ASCE 24-14. This UFC modifies the IBC and ASCE 24-14. The term facilities applies to buildings and structures and the terms buildings and structures are used interchangeably for flood resistant design criteria. To minimize impacts to the existing floodplain, EO 11988 directs all Federal agencies to elevate buildings rather than filling in land, wherever practicable. Use UFC 4-152-01 for waterfront construction.

When mission needs require siting a building within or partially within a flood hazard area, obtain the project specific Basis for Flood Risk Reduction, when available. When the Basis for Flood Risk Reduction is not available, the DoR is responsible for preparing the Basis for Flood Risk Reduction, consistent with section 2-1.2. Use the Basis for Flood Risk Reduction and Table 2-1 when computing the minimum DFE. Table 2-1 modifies ASCE 24-14, Table 1-1 Flood Design Class of Buildings and Structures and provides DFEs. Ensure proper correlation between vertical datums and submit flood design calculations, including the governing criteria used, to the Government Civil Engineer.

Table 2-1 Design Flood Elevation (DFE)

ASCE 24-14 Flood Design Class

Freeboard Approach 1

DRSL

Approach 2,3,4

Climate-Informed Science Approach

(minimal risk; non-essential facilities)

BFE Lowest 2065 BFE

(moderate risk; non-essential facilities)

BFE + 2 ft (600 mm) Low 2065 BFE +1 ft (300 mm)

Subcategory 3a (high risk; non-essential facilities)

BFE + 2 ft (600 mm) Medium 2065 BFE +1 ft (300 mm)

Subcategory 3b5

(high risk; essential facilities)

BFE + 3 ft (900 mm) High 2065 BFE + 2 ft (600 mm)

(high risk; essential facilities) BFE + 3 ft (900 mm) Highest 2065 BFE + 2 ft (600 mm)

1. The freeboard approach complies with PL 115-232, Section 2805(a)(4)(A) and (B).

2. The default sea level rise scenario complies with USD (A&S) DTM 22-003, “Flood Hazard Area Management for DoD Installations,” dated June 7, 2022.

3. Use the site-specific value from the DoD Regional Sea Level (DRSL) database corresponding to the designated scenario (lowest/low/medium/high/highest) for the 1 percent ACE for year 2065. The DRSL database is publicly available at https://drsl.serdp-estcp.org/Site. The FOUO DRSL database is available at https://sealevelscenarios.serdp-estcp.org.

4. These are default values in the absence of a Basis for Flood Risk Reduction. When provided, use the component’s sea level rise scenario and timeframe in lieu of the value provided in this column.

5. Essential facilities that would not need to remain operational during the design flood event but would need to be fully operational immediately following a storm event.

6. Essential facilities that would need to remain operational during the design flood event.

https://drsl.serdp-estcp.org/Site https://sealevelscenarios.serdp-estcp.org/

2-8.1 Non-Tidally Influenced Locations.

2-8.1.1 Flood Hazard Areas.

The boundaries of the flood hazard area for the design flood event must be designated by:

a. When available, the Climate-Informed Science Approach,

b. The applicable Flood Insurance Study (FIS) with the accompanying Flood

Insurance Rate Map (FIRM) or Flood Boundary and Floodway Map (FBFM) issued by Federal Emergency Management Agency (FEMA), when available,

c. Past flooding events, storm of significant impact,

d. A flood hazard map adopted by the Installation; or

e. A flood study performed to determine flood hazard areas in accordance with FEMA accepted hydrologic and hydraulic engineering practices used to define flood hazard areas.

When a new project site occupies two or more flood hazard areas, site the buildings or most vulnerable buildings to avoid the flood hazard area that presents the highest risk to the extent practicable.

2-8.1.1.1 Base Flood Elevation.

Determine the BFE for the design flood event in accordance with the following order of precedence:

1. When available, the Climate-Informed Science Approach;

2. As indicated on the applicable FIS and accompanying FIRM;

3. When regulation promulgated by a state or other government source is greater than the BFE identified in the Basis for Flood Risk Reduction, use the BFE established by the state or other government source;

4. A flood study performed to determine the BFE in accordance with FEMA;

or

5. A flood elevation established by the Installation using documented historical flood data from previous extreme flood events.

When a building is sited within or partially within one or more flood hazard areas or BFE contours, use the flood hazard area or BFE that presents the highest risk to the buildings. In some cases, it may be acceptable to design portions of buildings that are structurally independent.

2-8.1.1.2 Design Flood Elevation.

Determine the DFE in accordance with the following order of precedence:

1. Use Table 2-1 to determine the DFE using the Freeboard Approach or, when available, the Climate-Informed Science Approach.

2. When regulation promulgated by a state or other government source is greater than the DFE computed in the first order of precedence, use the DFE established by the state or other government source.

2-8.2 Tidally Influenced Locations.

2-8.2.1 DoD Regional Sea Level Database.

The DRSL Database provides five global and site-specific sea level change scenarios for three discrete time periods, 2035, 2065, and 2100. These scenarios are bound by the lowest scenario which is based on the 95% confidence interval for sea level trends developed by NOAA and the highest scenario which is based on the highest projection from the United Nations Framework Convention on Climate Change produced by the Intergovernmental Panel on Climate Change. The three intermediate scenarios are based on equally proportional 0.5 m increment subdivisions of the upper bound for the 2100 time period which deviates from the United Nations Framework Convention on climate change scenarios. For the 2100 time period, the five global scenarios from the DRSL Database are lowest 0.7 ft (0.2 m), low 1.6 ft (0.5 m), medium 3.3 ft (1 m), high

4.9 ft (1.5 m), and highest 6.6 ft (2.0 m).

In accordance with PL 116-92, Section 2804 and DTM 22-003 on Flood Hazard Area Management for DoD Installations, use the DRSL Database to determine site-specific mean sea level rise when the tidal record is a minimum of 50 years or two National Tidal Datum Epochs. Use the following order of precedence to select the appropriate sea level rise scenario and timeframe:

1. Basis of Flood Risk Design retained in the project file.

2. The DRSL Approach column in Table 2-1.

For the lowest scenario, the NOAA relative sea level trend from the 95% confidence interval may be interpolated or extrapolated to estimate future sea level rise increases for time periods not provided in the DRSL Database. The low, medium, high and highest scenarios may be graphically interpolated to estimate sea level rise between the time periods provided in the DRSL Database. Do not extrapolate the low, medium, high and highest scenarios in the DRSL Database.

2-8.2.2 Flood Hazard Areas.

Determine the flood hazard area in accordance with the most stringent of the following requirements:

1. Paragraph 2-8.1.1, or

2. The 1 percent ACE EWL elevation from the DRSL Database.

2-8.2.3 Base Flood Elevation.

When using the DRSL approach, set the BFE equal to the EWL for the 1 percent ACE from the DRSL Database.

2-8.2.4 Design Flood Elevation.

Use the following procedure to account for projected current and future mean sea level rise over the service life of the facility. Procedure for determining the DFE in tidally influenced locations:

1. Use paragraph 2-8.1.1.2 to determine DFEfreeboard.

2. Use paragraph 2-8.2.1 to determine the sea level rise scenario and timeframe.

3. Use Equation 2-1 to determine DFESL.

4. DFE equals DFEfreeboard or DFESL, whichever is more stringent.

Equation 2-1. Design Flood Elevation

𝑫𝑫𝑫𝑫𝑫𝑫𝑺𝑺𝑺𝑺 = 𝑬𝑬𝑬𝑬𝑬𝑬 + 𝑺𝑺𝑺𝑺𝑺𝑺

Where:

DFESL = Sea level rise impacted design flood elevation EWL = 1 percent ACE EWL from the DRSL Database SLR = Increases to site-specific mean sea level from the DRSL Database

2-8.3 Flood Resistant Design Options.

ASCE 24-14 does not require elevating all building types as a minimum standard.

ASCE 24-14 allows additional flood resistant design standards to be used when constructing flood resistant buildings and minimizing damage from the design flood event. Flood resistant design standards include flood risk reduction measures such as:

[C] 2-8.2.3 Base Flood Elevation

The EWL is the historical extreme water level value from the DRSL Database, not including wave height, having a 1 percent chance of being equal or exceeded in any given year. When using the DRSL Approach, the 1 percent ACE EWL from the DRSL Database is used as the 1 percent ACE flood event to consistently apply flood design criteria between the Freeboard Approach and the DRSL Approach.

[C] 2-8.2.4 Design Flood Elevation

Equation 2-1 is equivalent to using the combined tab in the DRSL Database.

• Design of openings (see ASCE 24-14, paragraph 2.7.2),

• Openings in breakaway walls (see ASCE 24-14, paragraph 2.7.1.1),

• Non-engineered openings (see ASCE 24-14, paragraph 2.7.2.1),

• Engineered openings (see ASCE 24-14, paragraph 2.7.2.2),

• Dry floodproofing (see ASCE 24-14, paragraph 6.2), or

• Wet floodproofing (see ASCE 24-14, paragraph 6.3).

Fully investigate flood resistant design standards, including temporary flood protection systems, and evaluate the impact of their use based on level of risk, non-essential or essential status, level of protection provided, user impacts and cost.

2-8.4 Flood Protection Systems.

When the design flood event cannot be mitigated using the flood risk reduction measures identified in ASCE 24-14, use a flood protection system to protect the building or buildings. A flood protection system may also be used when an engineering and cost analysis indicates that a flood protection system is advantageous to the intent of the project or master development plan. Flood protection systems may consist of dams, levees, floodwalls, and other types of flood protective works.

2-8.4.1 Establishing Flood Protection System Design Criteria.

Flood protection systems meeting the minimum design requirements in 44 CFR 65.10 may be accredited by FEMA for protection against the 1 percent ACE. FEMA accreditation of flood protection systems is encouraged but not required. Use 44 CFR Section 65.10 for the design of flood protection systems providing protection to the 1% ACE. Design flood protection systems to protect the building or buildings to the minimum DFE. When the design flood event exceeds the 1 percent ACE, the DoR must modify the minimum height of wall and associated criteria provided in 44 CFR Section

65.10 to account for the minimum DFE and submit the revised criteria to the Government Civil Engineer for review and approval prior to beginning design. In accordance with 44 CFR Section 65.10, the flood protection system is required to be certified by the DoR. Refer to FEMA GD34 for guidance on FEMA accreditation.

[C] 2-8.4.1 Establishing Flood Protection System Design Criteria

A registered professional engineer is responsible for certifying flood protection systems.

Flood protection system accreditation may be received from FEMA once a registered professional engineer has completed the certification process and all of the required documentation has been submitted to FEMA for review.

2-8.5 Mission Critical Roads.

Design mission critical roads and roads used for evacuation to be above the BFE plus freeboard or in accordance with the Installation’s emergency management plan.

Determine freeboard based on the reliability of available flood hazard area maps and supporting data, flood elevation and floodway data, increases in projected sea level rise, climate-informed science approach, or in accordance with FEMA accepted hydrologic and hydraulic engineering practices used to define flood hazard areas.

2-9 GRADING.

UFC 1-200-01 implements grading requirements from the IBC and provides supplements to IBC criteria. Use UFC 1-200-01, paragraph titled “Soils and Foundations”, to determine the appropriate requirements for site grading. Grading must direct water towards new or existing drainage features and away from impervious site features such as buildings, structures, runways, and roads. Grading must not result in low spots that hold water or that direct water towards new or existing site features.

Conform to existing topography to the greatest extent possible.

Crowned sections are the standard cross sections for roads, runways, taxiways, and safety areas. Crowned sections are generally symmetrical and slope away from the center line of the pavement.

2-9.1 Transverse and Longitudinal Slopes.

Acceptable ranges of transverse and longitudinal slopes are indicated in Table 2-2.

Grading criteria is also indicated in AASHTO GDHS.

[C] 2-8.5 Mission Critical Roads

Mission critical roads provide at least one route of travel to mission critical buildings.

Freeboard is used to provide a factor of safety. A minimum freeboard of 1 foot (300

mm) is recommended.

Table 2-2 Grading

Item Item Description Requirement Best Practices 1 Longitudinal grades of roads Min. 0.3% Min. 0.5% 2 Transverse grades of roads Min. 2.0%

3 Concrete pavement in parking areas Min. 1.0%

Min. 1.5% Max. 5.0%

4 Curb & Gutter or Valley Gutter Min. 0.3% Min. 0.5%

5 Bituminous pavement in parking areas Min. 1.5%

Min. 2.0% Max. 5.0%

6 Permeable Pavements in parking areas* Min. 1.0% Max. 5.0%

7 Walks, Transverse Max. 2.0% 8 Walks, Longitudinal Max. 5.0% 9 Concrete Landings Max. 2.0%

10 Paved Concrete Ditches, longitudinal Min. 0.3%

11 Unpaved Ditches, longitudinal* Min. 0.5%

12 Pervious Surfaces (Grass, Turf, or Landscape)* Min 2.0%

* Regulatory agency’s stormwater management criteria may govern for items used as stormwater management features.

2-9.2 Finished Floor Elevations.

Establish minimum finished floor elevations in accordance with this UFC, UFC 1-200-01 paragraph titled “Structural Design”, or UFC 3-101-01, whichever is more stringent.

2-9.3 Airfields.

Use the airfield grading criteria in UFC 3-260-01.

[C] 2-9.2 Finished Floor Elevations

The referenced criteria is included for projects that many or may not be in a flood hazard area. For example, if a project is not in a flood hazard area, UFC 3-101-01 may provide the more stringent criteria.

2-10 VEHICLE CIRCULATION.

The DoR must address unique aspects of military facilities when designing roads and parking. For example, roads on military installations are typically designed for lower speeds while also addressing the movement of specialized military vehicles. Roads, parking areas and structures must conform to current antiterrorism and accessibility requirements.

2-10.1 Special Circulation Areas.

Circulation areas for vehicles other than normal passenger cars have special requirements to maintain traffic safety. These areas require additional space to accommodate unusual traffic patterns and greater turning radii for maneuverability.

Special circulation areas include areas such as drop off areas, delivery and service zones, garbage collection areas (dumpsters), drive-in facilities, emergency vehicle access, and entry control facilities. The design must also address the turning and reverse movements for the largest vehicle including but not limited to deliveries, emergencies, and garbage collection that will use the facility and discourage through traffic.

2-10.1.1 Dumpster Pads.

Consider site circulation, building location, and distance to service doors. Coordinate the location of dumpster pads with Government personnel. Provide access to dumpster pads that is fully coordinated with the operation of the facility and facilities waste collection plan. When wheeled trash cans or carts are used as part of the facilities waste collection plan, provide sidewalks and ramps for access to and from the facility.

Size dumpster pads in accordance with the Installation waste collection service.

Provide site circulation and reverse turning area that allows dumpster trucks to maintain a forward movement to and from the dumpster pads. For frontloading dumpster trucks, provide a straight approach for dumpster trucks to access and align with the dumpster, reverse away, and exit forward. For rear-loading dumpster or roll off trucks, provide a reverse turning area that allows for a straight approach for dumpster trucks to access and align with the dumpster after reversing, and exit forward. For side-loading dumpster trucks, provide a straight approach for dumpster trucks to access and align with the dumpster, reverse away if needed, and exit forward. The concrete dumpster pad must be large enough to accommodate the:

• Front wheels of frontloading dumpster trucks;

• Rear wheels of rear-loading and roll-off dumpster trucks; or

• Front and rear wheels of side-loading dumpster trucks.

2-10.1.1.1 Airfields.

Locate dumpsters in locations approved by Airfield Operations (AIROPS) to avoid a Bird/Animal Aircraft Strike Hazard (BASH) issue.

2-10.2 Traffic Studies.

Provide traffic studies and analysis in accordance with Surface Deployment and Distribution Command Transportation Engineering Agency (SDDCTEA) Pamphlet 55-17 and SDDCTEA Pamphlet 55-8.

2-10.3 Design Vehicles.

Design vehicle types include:

a. Passenger car, truck, light-delivery truck, bus, and truck combinations are as defined by AASHTO (moving vans, refuse trucks and school buses, snow-clearing trucks).

b. Emergency vehicles.

c. Specialized military vehicles such as tracked vehicles.

Obtain design information for emergency vehicles and specialized military vehicles from the Government Project Manager.

2-10.4 Design Traffic.

Use ITE LP-674B to evaluate average daily traffic (ADT) and peak hourly traffic, as applicable. Adjust for vehicles other than passenger cars. In addition to the vehicles indicated in ITE LP-674B (trucks, RV’s, buses), add specialized military vehicles as a vehicle type and determine the nearest equivalent AASHTO vehicle type.

2-10.5 Roads.

Design roads in accordance with SDDCTEA Pamphlet 55-17, AASHTO GDHS, AASHTO RSDG-4, and AASHTO VLVLR as applicable.

Single-lane roads may be provided for fire lanes and approach drives to buildings within built-up areas. Access roads to unmanned facilities may also be single-lane roads.

Where shoulders are not sufficiently stable to permit all-weather use and the distance between intersections is greater than ½-mile (805 m), turnouts must be provided at 1/4-mile (402 m) intervals along single lane roads for use by occasional passing or meeting vehicles.

2-10.5.1 Fire Lane and Emergency Vehicle Access.

Fire lanes and emergency vehicle access must comply with UFC 3-600-01.

2-10.6 Parking Areas.

Design parking areas in accordance with SDDCTEA Pamphlet 55-17, Chapter titled “Parking”. Parking areas include on-street parking, off-street parking lots, and parking structures. Refer to scope of work to determine the gross area or number of parking spaces. If the number of parking spaces is not identified in the project scope of work, use Table A-2 for guidance. Provide parking spaces primarily by off-street parking areas or structures.

For Flood Design Class IV facilities, design parking supporting essential personnel that would need to remain at the facility during the design flood event to be above the BFE plus freeboard. Determine freeboard based on the reliability of available flood hazard area maps and supporting data, flood elevation and floodway data, increases in projected sea level rise, climate-informed science approach, or in accordance with FEMA accepted hydrologic and hydraulic engineering practices used to define flood hazard areas.

2-10.6.1 On-Street Parking.

The use of on-street parking is discouraged. On-street parking will not be allowed within 20 feet (6.1 m) of an intersection. The minimum length for the first and last stall is 20 feet (6.1 m). The minimum length for each interior stall is 22 feet (6.7 m).

Exception to SDDCTEA Pamphlet 55-17: The minimum width for all passenger vehicle stalls is 8 feet (2.4 m).

2-10.6.2 Off-Street Parking.

Typically, 90 degree parking is preferred for off-street parking for ease of traffic flow. If 90 degree parking is not used, the designer must be able to justify by showing that the minimum functional and technical requirements are met while providing an economic benefit to the Government. Provide minimum 9 feet (2.7 m) wide and 18.5 feet (5.6 m) long parking spaces for 90 degree parking. The design must discourage through traffic.

Exception to SDDCTEA Pamphlet 55-17: In areas of limited space, provide a minimum buffer strip of 8 feet (2.4 m) when sufficient space is available.

2-10.6.3 Compact Cars.

Compact spaces may be used when there will be a consistent number of compact size vehicles accessing the facility on a regular basis. Do not use compact spaces when sufficient space is available for standard size passenger vehicles.

2-10.6.4 Motorcycles.

When motorcycle spaces are subtracted from the required regular spaces a parking study must be performed to determine the consistent number of motorcycles regularly parking at the facility throughout the year. When performing the traffic study, take into

[C] 2-10.6 Parking Areas

Freeboard is used to provide a factor of safety. A minimum freeboard of 1 foot (300

mm) is recommended.

account adverse weather (winter in northern climates). Do not subtract motorcycle spaces from required regular spaces unless supported by a traffic study.

Motorcycle parking surfaces are typically designed as rigid pavements to prevent kickstands from penetrating bituminous pavement in warm weather. The minimum size for motorcycle spaces is 9 feet (2.7 m) long and 4.5 feet (1.3 m) wide.

2-10.6.5 Parking Areas Outside of the United States.

Use UFC 1-200-01 and refer to the “Forward” at the beginning of this UFC to determine accessibility requirements for areas outside of the United States. When standard passenger car dimensions, as indicated in SDDCTEA Pamphlet 55-17, are not used, a traffic engineering study (parking study, parking design vehicle study) must be performed to determine the predominant vehicle size and parking layout. Perform traffic engineering studies in accordance with SDDCTEA Pamphlet 55-8. The minimum parking size for all cars is 8 feet (2.4 m) x 16 feet (4.8 m).

During the parking study, take into account the following at a minimum:

• Requirements for each project.

• An analysis of activities to be accommodated.

• Government vehicle use.

• Standard vehicles from the United States.

• Current and future parking demand.

• Variety of parking areas needed.

• Truck traffic, including deliveries- and garbage collection.

• Emergency vehicles.

• Minimum entrance widths.

• Number of entrances.

• AT setbacks.

• Parking (on-street, off-street, parking orientation, aisle widths, minimum stall size and orientation, accessible spaces).

2-10.7 Bicycle Facilities.

Use AASHTO GDHS and SDDCTEA Pamphlet 55-17 for the design of bicycle facilities.

Use Best Practices document, AASHTO GBF for additional design guidance.

2-11 SITE APPURTENANCES.

Provide site appurtenances in accordance with state or local standards where project is located.

2-11.1 Pedestrian Circulation.

Allow for pedestrian circulation between various new and existing facilities by providing a network of new sidewalks that connect new pedestrian circulation systems with existing pedestrian circulation systems. Use UFC 1-200-01 to determine accessibility requirements. Use AASHTO GDHS and SDDCTEA Pamphlet 55-17 for the design of pedestrian circulation systems. Use Best Practices document, AASHTO GPF for additional design guidance.

Sidewalks may consist of portland cement concrete, bituminous concrete (asphalt), solid pavers, permeable pavers, or pervious concrete. The minimum thickness of PCC concrete sidewalks is 4 inches (100 mm). Provide bituminous sidewalks with a minimum 4 inches (100 mm) thick base and a 1 inch (25 mm) thick bituminous surfacing. The minimum width for all sidewalks is 4 feet (1.2 m). In high volume or urban areas, the minimum width for sidewalks is 6 feet (1.8 m). Where the sidewalk is adjacent to the curb, increase the minimum width to account for obstacles such as signs and fire hydrants. Consult with the Government Project Manager for special sidewalk requirements for facilities with high pedestrian volumes such as barracks, medical facilities, where extra wide walks may be required.

2-11.2 Curb or Curb and Gutter.

Use concrete curb and gutter when overland flow cannot be achieved; to extend curb or curb and gutter from an adjacent facility; or to confine traffic. Asphalt-type curbs are only allowed in remote areas where approved by the Installation.

2-11.2.1 Airfields.

Curbs and gutters are not permitted to interrupt surface runoff along a runway, taxiway, heliport, or apron. The runoff must be allowed unimpeded travel transversely off the runway and then directed to the inlets.

2-11.3 Wheelstops.

Provide 6 feet (1.8 m) long wheelstops anchored to the pavement at parking spaces adjacent to sidewalks, buildings, stormwater management facilities, areas of extreme slope, and other areas without curb where a vehicle would likely cause property damage. Locate the front face of the wheelstop 30 inches (750 mm) from the edge of the pavement or sidewalk.

Where snow removal equipment is used, wheelstops may not be allowed by the Installation; coordinate with Government Project Manager.

2-11.4 Bollards.

2-11.4.1 Bollards around Structures.

Provide bollards around any structures subject to damage from vehicular traffic by incidental contact; such bollards must be at minimum 4 feet (1.2 m) high. For steel bollards, provide minimum 4 inch (100 mm) diameter filled with concrete and painted.

Bollards on aircraft aprons protecting fire hydrants must not exceed 30 inches (750 mm) aboveground and 24 inches (600 mm) above load bearing paving.

2-11.4.2 Bollards for Security.

For vehicular barrier and crash rated applications, use UFC 4-022-02.

2-11.5 Signage and Markings.

Provide signs and associated pavement markings to facilitate proper utilization of the project site. Provide new traffic control devices such as signs and markings in accordance with SDDCTEA Pamphlet 55-17.