STATEMENT OF WORK

See below for: TECHNICAL CAPABILITY/CONTRACTOR/RESPONSIBILITY CERTIFICATION

STATEMENT

Vendor shall certify that equipment being quoted meets the capabilities listed below and that vendor can assume all contractor responsibilities stated below by initialing at the bottom. In order to be considered for award, this must be completed and submitted with the vendor quote.

PURPOSE OF REQUEST: Service rental from vendor to provide one (1) trailer mounted 1,000 kW minimum Standby Power, 700kW Continuous Power (COP) Diesel Generator.

LOCATION: Norfolk Naval Shipyard (NNSY), Bldg. 298, Portsmouth, VA 23709

PERIOD OF PERFORMANCE: 04 May 2022 to 31 January 2023 with clause to extend month to month for 3 months if needed.

GOVERNMENT POINTS OF CONTACT: will be provided upon contract award

Table A

TECHNICAL CAPABILITES STATEMENT

Item #0001 General Specification for 1,000 kW Standby Diesel Generator.

Shall be provided with the following capabilities, features and specifications: Yes No

Output: 450volts, 3 phase, 3 wire ungrounded.

Standby Rating of 1,000kW (minimum), Continuous Power (COP) of 750kW (minimum), 1600 Amps (minimum)

Must be equipped with a block heater and battery charging circuit and suitable pigtails for mating with NNSY 120V distribution services cans.

Diesel generator shall be capable of parallel operation with ship’s electric plant.

Diesel generator shall be capable of paralleling with a shipboard diesel generator, diesel to be ungrounded with neutral lifted.

Safety Devices: Output circuit breaker Long Time Overcurrent trip set to 150% of Base Load

COP current rating.

Diesel generator unit dimensions shall not exceed 20’ L x 8’ W. Weight not to exceed 50,000 lbs.

Diesel fuel capacity must be capable of twenty-four (24) hour minimum run time prior to refueling at full Continuous Base Load. (onboard and/or external fuel tank included)

External fuel tank shall be 1240 gallons maximum, if utilized. Unit dimensions shall not exceed 10’ L by 8’ W, fully fueled weight not to exceed 10,000lbs. In lieu of one (1) tank, two (2) tanks can be used with dimensions not to exceed 5’-5 3/8” by 7’-8 5/8” max weight per tank 6200lbs (fully fueled). Fuel cell lifting points shall have current capacity certifications.

Onboard/External fuel tank(s) shall allow for refueling while diesel generator is operating.

Self-contained cooling system.

Shall be provided with the following capabilities, features and specifications: (Cont.) Yes No

Trailer mounted. Lifting points shall have current capacity certifications.

Outdoor enclosure. Unit shall be equipped with rain-tight enclosure & block heater.

The Diesel generator shall be of recent vintage (not more than ten years old), clean, and well maintained. The generator winding shall be a minimum of 5MΩ above ground with neutral disconnected. The unit shall have been tested within two weeks of delivery and applicable test data sent with unit.

All neutral connections shall be disconnected and isolated from generator windings and any additional equipment as necessary.

Unit shall have posted operating instructions in the vicinity of the control panel that clearly state how to start, stop and operate the diesel generator and output circuit breaker. The posted instructions shall include any necessary steps for proper operation of the diesel generator in parallel with shipboard diesel generator. Operating instructions may require clarification at ship’s request after delivery, and vendor is to clarify instructions as necessary.

Unit shall be compatible with Shipyard furnished “THOF-500E”-T-500 lugged output cables

(4 per phase). If mechanical lug connections are provided, they shall be sized for 500MCM

(4 per phase).

Table B

Rating (kW) Rating (Amps)

Standby Power

Prime Power

Base Load Continuous Operating

Power (COP)

Table C

Load (kW) Burn Rate (Gallons/HR) Run Time (Hours)

Standby Power

Prime Power

Base Load Continuous Operating

Power (COP)

TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBILITY CERTIFICATION

Vendor hereby certifies that vendor’s service meets or exceeds all specifications and contractor responsibilities stated in this solicitation, in their entirety, with no exceptions.__________ (initials)

CONTRACTOR RESPONSIBILITY:

1. Equipment delivery transportation shall be door to door by Contractor. Please deliver on 04 May 2022.

2. Provide all parts requiring repair or replacement under circumstances of normal equipment wear and tear at no additional charge.

3. Contractor is responsible for ensuring that all preventative maintenance is performed on equipment prior to delivery to the government as well as performing preventative maintenance as specified by the equipment’s manufacturer preventative maintenance schedule during the term of the rental period with the government.

3a. Contractor is responsible for all travel associated with preventative maintenance.

4. Contractor is responsible for providing contracted personnel and truck drivers that are able to meet the badging and security requirements of Norfolk Naval Shipyard/NOB. Contracted personnel must be United States Citizens. Foreign

Nationals will not be allowed on job site.

5. Post contact information for service/repair of equipment directly on the rental equipment. Contact information must be packaged to withstand being located in an outdoor environment.

6. The Contractor shall dispatch a representative in response to a service request to repair and/or replace a diesel generator within four (4) hours of notification by NNSY at no additional charge whether request is placed during normal business hours or outside of normal business hours.

6a. Contractor is responsible for travel associated with repair/replacement of equipment.

6b. Contractor is responsible to replace the diesel generator within 12 hours of initial notification if repairs cannot be made to the existing unit.

7. Contractor to provide training to Shop 99 in the proper operation of the generator set utilizing Contractor written operation instructions.

7a. Contractor is responsible for travel associated with training of diesel generator with Shop 99.

8. Contractor is to validate that the rental diesel generator is in accordance with the Statement of Work requirements at delivery.

9. Contractor to provide written documentation of the operational parameters of diesel generator set prior to awarding of the contract. Written documentation to include Technical Manual, allowable hours of operation, e.g. 100 hours, 250 hours, unlimited, etc., at specified ratings, e.g. Standby Power Rating, Prime Power Rating, Continuous Power Rating, etc. Also, written documentation to include Fuel Consumption and Running Hour data. Tables A, B and C must be completed and forwarded to C275 for review prior to awarding of the contract.

10. Contractor to provide assistance with electrically connecting output cables and providing for disconnect/reconnect of any electrical components that require access into equipment cabinets. Voltage and Phase Rotation checks must be taken on site to verify proper connection of output cabling.

11. Contractor to provide the option of contract extension past 31 January 2023 with three 1-month duration option to extend if needed up to 3 months.

12. Per FAR 22.102-1(a) entitled "Safety", s are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard cognizance must follow Federal and State OSHA requirements and Norfolk

Naval Shipyard OSHE Program Manual, NAVSHIPYDNORINST P5090.2 requirements or safety requirements for site specific location of the contract.

12a. Contractors and Non-NNSY Government Agencies (NNGAs) are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard (NNSY) cognizance must adhere to Federal

OSHA requirements for hazardous energy control IAW 29 CFR 1915.89 and must follow Hazardous Energy

Control (HEC) procedures as identified in NAVSEA’s Occupational Safety, Health, and Environment Corporate

Manual (OSHECM) Chapter 250 (latest revision), when performing work under NNSY contract. All HEC work to be performed by Contractors and NNGAs requires that NNSY Technical Points of Contact (TPOCs) and/or

Contracting Officer’s Representatives (CORs) be notified of the HEC scope of work prior to starting work. Any changes or deviations in the initial scope of HEC work requires the NNSY TPOCs and/or CORs be informed of the change/deviation. Appendix 250.B-1 through B-3 of OSHECM Chapter 250 for multiple employer work identifies when Contractors and NNGAs are required to assign their Lockout/Tags-Plus Coordinator (LOTC) to coordinate

HEC work with the cognizant NNSY LOTC. HEC locks shall be provided by the Contractor or NNGA for their employees use. The HEC locks shall have red bodies with name labels or name tags affixed, identifying who installed the HEC lock(s) and a point of contact telephone number. HEC lock name labels and tags must be made of materials that will hold up to the environment to which they are exposed. HEC tags used for Tags-Plus HEC work shall be provided by the cognizant NNSY LOTC to the contractor or NNGA for their use if machinery, equipment, or systems (MES) cannot be locked out. OSHECM Chapter 250 Tags-Plus procedures will be strictly followed.

12b. Contractors and NNGA’s may obtain electronic copies of OSHECM Chapter 250 (latest revision) and access the OSHA 1915.89 web site by using the following link to NNSY’s public access web site.

https://www.navsea.navy.mil/shipyards/norfolk/default.aspx

12c. Names and contact information for NNSY LOTCs and/or the Facility Custodian will be provided by NNSY

TPOC and/or CORs set forth elsewhere in this award document.

NNSY RESPONSIBILITY:

1. Security clearance and access for all personnel will be managed by the project Work Integration Leader (WIL).

2. Provide pier location.

3. Perform basic maintenance.

3a. Monitor all gauges.

4. Lost items and equipment damage beyond normal wear and tear.

https://www.navsea.navy.mil/shipyards/norfolk/default.aspx

ADDITIONAL DETAILS:

1. New or used equipment may be provided. NNSY reserves the right to inspect the proposed equipment prior to contract award.

2. The Diesel Generator will be exposed to everyday weather, and saltwater air. It is the contractor’s responsibility to provide any protective coverings for the unit.

3. The government reserves the right to return one or all units at any time prior to the expiration of the rental period.

The Contractor agrees to prorate costs for the time the units are in use by NNSY only. The government agrees to give the contractor forty-eight (48) hours-notice for return of the Diesel Generator prior to expiration of rental period.

4. After Hours Base Access – Contractors are to go to Gate 15 and let the guards know they are to provide services/support via contract ______________________. It would be helpful to have a copy of the contract. The guards at the gate will then call the Base Precinct and subsequently be escorted to Bldg. 1618 to have a badge made.

Requirements for Lifting of Equipment

1. The equipment shall be outfitted with suitable attachments for overhead lifting.

1.1. For multiple point lifts each lifting attachment shall be capable of supporting one half the gross weight of the equipment with a design factor of five to one based on ultimate strength. For single point lifts the lifting attachment shall be capable of supporting the gross weight of the equipment with a design factor of five to one based on ultimate strength.

1.2. For multiple point lifts each lifting attachment shall be designed to accept a standard anchor shackle (Federal

Specification RR-C-271G, type IVA) which is capable of supporting one half the gross weight of the equipment. For single point lifts the lifting attachment shall be designed to accept a standard anchor shackle

(Federal Specification RR-C-271G, type IVA) which is capable of supporting the gross weight of the equipment.

1.3. Design of the lifting attachments shall be such that the attachments and shackles are not side loaded more than

10° out of the plane. Lifting attachments shall be located such that the lifting slings do not contact the equipment, or alternatively a spreader beam certified to NAVFAC P-307 shall be provided. Whenever practical, the lifting attachments shall be located above the center of gravity, and such that the lifting slings do not contact the equipment housings.

1.4. Each lifting attachment shall be conspicuously marked in a contrasting color “Lift Here”. Letters shall have a minimum height of 1”.

2. The equipment shall be marked in a prominent location with the gross weight. Fuel tanks shall be marked with the empty and full weight (or alternatively the empty weight and working load limit). Marking shall be upper case letters of a contrasting color, with a minimum height of 1”. Marking shall include the units (i.e.

“Gallons”).

3. The equipment shall be provided with a lifting sketch / rigging diagram that meets the requirements below.

3.1. The lifting sketch shall detail any specific requirements and / or configurations that shall be meet prior to lifting

(i.e. “engage swing lock”, “Tilt mast back fully”, “Rotate lifting basket over side”, “Utilize 10’ minimum length slings”, “Spreader beam required”, etc.).

3.2. The lifting sketch shall include the location of the center of gravity of the equipment (full fuel, hydraulic tanks, etc.), equipment model/manufacturer, and gross weight.

3.3. A copy of the lifting sketch shall be permanently posted on the equipment, and a copy shall be forwarded to

Code 714, David Washbourne (757-396-7001).

4. If specialized handling gear other than shackles, standard slings, or chainfalls (i.e. spreader beams, special lift rigs, etc.) is required, the contractor shall furnish it. This handling gear shall be provided certified in accordance with NAVFAC P-307, with written documentation of proof testing.

Rigging Sketch Requirements

-Rigging sketches, as a minimum, shall identify the following:

1. The weight of the load.

2. The location of the center of gravity.

3. The minimum crane capacity.

4. The minimum capacity / length of slings.

5. The minimum capacity of other standard rigging gear.

6. The attachment (lifting) points for the load.

(a) The attachment points for multiple leg lifts shall be sized such that each attachment point can support half the load’s weight at the anticipated lift angle.

(b) The attachment point for single leg lifts shall be sized such that the attachment point can support the entire load’s weight.

7. Limitations on allowable orientations for any parts making up the lifting assembly.

8. For single leg vertical lifts using twisted rope (wire or synthetic), two parallel ropes each capable of supporting the entire load alone shall be required unless a method is used to prevent unlaying the rope.

9. A minimum D/d ratio of one shall be required where wire rope slings pass over any object, or in the eyes of wire rope slings. A minimum D/d ratio of one shall be required where synthetic rope slings pass over any object, or in the eyes of synthetic rope slings.

(a) "D" represents the diameter of the object the sling passes over.

(b) "d" represents the diameter of the sling.

(c) Table 14-3 of NAVFAC P-307 lists efficiency factors at various D/d ratios.

10. Components in each handling assembly shall be sized based on the worst case distribution of loads.

(a) When making a two, three, or four point lift, the handling gear shall be sized so that two legs can support the load without exceeding the safe working load (SWL) at the lift angle expected, unless an equalizing method is used.

11. When nonstandard gear is required (i.e. round stock lifting bars) written instructions shall be provided that ensure:

(a) The proper material is being used,

(b) The item is certified IAW NAVFAC P-307,

(c) Any special requirements or dimensions are followed to ensure that engineering assumptions are met (i.e.

eccentricity of the bearing points).

PORTABLE ELECTRONIC DEVICES (PEDs).

"In accordance with COMSUBLANT/COMSUBPACINST 2075.1C, the use of Portable Electronic Devices (PEDs) while in or on Department of Navy Submarine spaces are prohibited. A portable electronic device (PED) is defined as any non-stationary electronic apparatus with singular or multiple capabilities of, but not limited to recording, storing, and/or transmitting data, voice, video, or photo images (e.g., cell phones, laptops, tablets and wearable devices such as fitness bands and smart watches)."

IDENTIFICATION BADGES AND INSTALLATION ACCESS.

DBIDS

• Any new contractor, vendor or supplier requesting base access AFTER 31 May 2017 will be required to obtain a

DBIDS credential. NCACS credentials will no longer be issued.

• Only DBIDS credentials will be issued to ALL contractors, vendors and suppliers seeking base access AFTER

14 August 2017.

Defense Biometric Identification System (DBIDS) increases installation security and communications by receiving frequent database updates on changes to personnel/credential status, law enforcement warrants, lost/stolen cards, and force protection conditions. The system provides a continuous vetting anytime the DBIDS card is scanned at an installation entry point.

If you currently have a Navy Commercial Access Control System (NCACS) card, the following is required to get a DBIDS credential:

Present your NCACS Card and a completed copy of the SECNAV FORM 5512/1 to the base Visitor

Control Center representative.

The VCC will pull up your information in the computer, ensuring all information is current and correct.

Once your information is validated, a temporary DBIDS credential is provided.

Your temporary credential will have an expiration date, prior to which you will need to obtain your permanent DBIDS credential (~ 90 days).

For each additional U.S. Navy installation to which you need access, the first time you visit you only need to bring your DBIDS credential and statement of purpose for base access when arriving at the Visitor

Control Center.

The representative will enter base access authorization and then you may proceed to work.

If you do NOT have an NCACS Card, the following is required to obtain a DBIDS credential:

Present a letter or official document from my government sponsoring organization that provides the purpose for your access.

Present valid identification, such as a passport or Real ID Act-compliant state driver's license.

Present a completed copy of the SECNAV 5512/1 form to obtain your background check.

Upon completion of the background check, the Visitor Control Center representative will complete the

DBIDS enrollment process, which includes your photo, finger prints, base restrictions, and several other assessments; after all this is done, you will be provided with your new DBIDS credential.

You may now proceed to work.

FOR ADDITIONAL QUESTIONS ABOUT OBTAINING A DBIDS CARD, CONTACT YOUR LOCAL

BASE VISITOR CONTROL CENTER. INFORMATION IS ALSO PROVIDED AT:

www.cnic.navy.mil/om/dbids.html

One-Day Passes. Participation in the DBIDS is not mandatory, and if the Contractor chooses to not participate, the

Contractor's personnel will have to obtain daily passes, be subject to daily mandatory vehicle inspection, and will have limited access to the installation. The Government will not be responsible for any cost or lost time associated with obtaining daily passes or added vehicle inspections incurred by non-participants in the DBIDS.

SAFETY.

"Per FAR 22.102-1(a) entitled "Safety", Contractors are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard cognizance must follow Federal and State OSHA requirements and Norfolk Naval Shipyard OSHE Program Manual, NAVSHIPYDNORINST P5090.2 requirements or safety requirements for site specific location of the contract.

a. Contractors and Non-NNSY Government Agencies (NNGAs) are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard (NNSY) cognizance must adhere to

Federal OSHA requirements for hazardous energy control IAW 29 CFR 1915.89 and must follow

Hazardous Energy Control (HEC) procedures as identified in NAVSEA’s Occupational Safety, Health, and

Environment Corporate Manual (OSHECM) Chapter 250 (latest revision), when performing work under

NNSY contract. All HEC work to be performed by Contractors and NNGAs requires that NNSY Technical

Points of Contact (TPOCs) and/or Contracting Officer’s Representatives (CORs) be notified of the HEC scope of work prior to starting work. Any changes or deviations in the initial scope of HEC work requires the NNSY TPOCs and/or CORs be informed of the change/deviation. Appendix 250.B-1 through B-3 of

OSHECM Chapter 250 for multiple employer work identifies when Contractors and NNGAs are required to assign their Lockout/Tags-Plus Coordinator (LOTC) to coordinate HEC work with the cognizant NNSY

LOTC. HEC locks shall be provided by the contractor or NNGA for their employees use. The HEC locks shall have red bodies with name labels or name tags affixed, identifying who installed the HEC lock(s) and a point of contact telephone number. HEC lock name labels and tags must be made of materials that will hold up to the environment to which they are exposed. HEC tags used for Tags-Plus HEC work shall be provided by the cognizant NNSY LOTC to the contractor or NNGA for their use if machinery, equipment, or systems (MES) cannot be locked out. OSHECM Chapter 250 Tags-Plus procedures will be strictly followed.

b. Contractors and NNGA’s may obtain electronic copies of OSHECM Chapter 250 (latest revision) and access the OSHA 1915.89 web site by using the following link to NNSY’s public access web site:

http://www.navsea.navy.mil/shipyards/norfolk/default.aspx

Names and contact information for NNSY LOTCs and/or the Facility Custodian will be provided by NNSY TPOC and/or CORs set forth elsewhere in this award document.”

5252.204-9400 Contractor Unclassified Access to Federally Controlled Facilities, Sensitive Information, Information Technology (IT) Systems or Protected Health Information

(July 2013)

Homeland Security Presidential Directive (HSPD)-12, requires government agencies to develop and implement

Federal security standards for Federal employees and contractors. The Deputy Secretary of Defense Directive-

Type Memorandum (DTM) 08-006 – “DoD Implementation of Homeland Security Presidential Directive – 12

(HSPD-12)” dated November 26, 2008 (or its subsequent DoD instruction) directs implementation of HSPD-12.

This clause is in accordance with HSPD-12 and its implementing directives.

APPLICABILITY

This clause applies to contractor employees requiring physical access to any area of a federally controlled base, facility or activity and/or requiring access to a DoN or DoD computer/network/system to perform certain unclassified sensitive duties. This clause also applies to contractor employees who access Privacy Act and

Protected Health Information, provide support associated with fiduciary duties, or perform duties that have been identified by DON as National Security Position, as advised by the command security manager. It is the responsibility of the responsible security officer of the command/facility where the work is performed to ensure compliance.

Each contractor employee providing services at a Navy Command under this contract is required to obtain a

Department of Defense Common Access Card (DoD CAC). Additionally, depending on the level of computer/network access, the contract employee will require a successful investigation as detailed below.

ACCESS TO FEDERAL FACILITIES

Per HSPD-12 and implementing guidance, all contractor employees working at a federally controlled base, facility or activity under this clause will require a DoD CAC. When access to a base, facility or activity is required http://www.navsea.navy.mil/shipyards/norfolk/default.aspx contractor employees shall in-process with the Navy Command’s Security Manager upon arrival to the Navy

Command and shall out-process prior to their departure at the completion of the individual’s performance under the contract.

ACCESS TO DOD IT SYSTEMS

In accordance with SECNAV M-5510.30, contractor employees who require access to DoN or DoD networks are categorized as IT-I, IT-II, or IT-III. The IT-II level, defined in detail in SECNAV M-5510.30, includes positions which require access to information protected under the Privacy Act, to include Protected Health

Information (PHI). All contractor employees under this contract who require access to Privacy Act protected information are therefore categorized no lower than IT-II. IT Levels are determined by the requiring activity’s

Command Information Assurance Manager. Contractor employees requiring privileged or IT-I level access, (when specified by the terms of the contract) require a Single Scope Background Investigation (SSBI) which is a higher level investigation than the National Agency Check with Law and Credit (NACLC) described below.

Due to the privileged system access, a SSBI suitable for High Risk public trusts positions is required.

Individuals who have access to system control, monitoring, or administration functions (e.g. system administrator, database administrator) require training and certification to Information Assurance Technical

Level 1, and must be trained and certified on the Operating System or Computing Environment they are required to maintain.

Access to sensitive IT systems is contingent upon a favorably adjudicated background investigation. When access to IT systems is required for performance of the contractor employee’s duties, such employees shall in-process with the Navy Command’s Security Manager and Information Assurance Manager upon arrival to the Navy command and shall out-process prior to their departure at the completion of the individual’s performance under the contract. Completion and approval of a System Authorization Access Request Navy (SAAR-N) form is required for all individuals accessing Navy Information Technology resources. The decision to authorize access to a government IT system/network is inherently governmental. The contractor supervisor is not authorized to sign the SAAR-N; therefore, the government employee with knowledge of the system/network access required or the COR shall sign the SAAR-N as the “supervisor”.

The SAAR-N shall be forwarded to the Navy Command’s Security Manager at least 30 days prior to the individual’s start date. Failure to provide the required documentation at least 30 days prior to the individual’s start date may result in delaying the individual’s start date.

When required to maintain access to required IT systems or networks, the contractor shall ensure that all employees requiring access complete annual Information Assurance (IA) training, and maintain a current requisite background investigation. The Contractor’s Security Representative shall contact the Command Security

Manager for guidance when reinvestigations are required.

INTERIM ACCESS

The Navy Command's Security Manager may authorize issuance of a DoD CAC and interim access to a DoN 05or

DoD unclassified computer/network upon a favorable review of the investigative questionnaire and advance favorable fingerprint results. When the results of the investigation are received and a favorable determination is not made, the contractor employee working on the contract under interim access will be denied access to the computer network and this denial will not relieve the contractor of his/her responsibility to perform.

DENIAL OR TERMINATION OF ACCESS

The potential consequences of any requirement under this clause including denial or termination of physical or system access in no way relieves the contractor from the requirement to execute performance under the contract within the timeframes specified in the contract. Contractors shall plan ahead in processing their employees and subcontractor employees. The contractor shall insert this clause in all subcontracts when the subcontractor is permitted to have unclassified access to a federally controlled facility, federally-controlled information system/network and/or to government information, meaning information not authorized for public release.

CONTRACTOR’S SECURITY REPRESENTATIVE

The contractor shall designate an employee to serve as the Contractor’s Security Representative. Within three work days after contract award, the contractor shall provide to the requiring activity’s Security Manager and the

Contracting Officer, in writing, the name, title, address and phone number for the Contractor’s Security

Representative. The Contractor’s Security Representative shall be the primary point of contact on any security matter. The Contractor’s Security Representative shall not be replaced or removed without prior notice to the

Contracting Officer and Command Security Manager.

BACKGROUND INVESTIGATION REQUIREMENTS AND SECURITY APPROVAL PROCESS FOR

CONTRACTORS ASSIGNED TO NATIONAL SECURITY POSITIONS OR PERFORMING

SENSITIVE DUTIES

Navy security policy requires that all positions be given a sensitivity value based on level of risk factors to ensure appropriate protective measures are applied. Navy recognizes contractor employees under this contract as Non-

Critical Sensitive [ADP/IT-II] when the contract scope of work require physical access to a federally controlled base, facility or activity and/or requiring access to a DoD computer/network, to perform unclassified sensitive duties. This designation is also applied to contractor employees who access Privacy Act and Protected Health

Information (PHI), provide support associated with fiduciary duties, or perform duties that have been identified by DON as National Security Positions. At a minimum, each contractor employee must be a US citizen and have a favorably completed NACLC to obtain a favorable determination for assignment to a non-critical sensitive or IT-II position. The NACLC consists of a standard NAC and a FBI fingerprint check plus law enforcement checks and credit check. Each contractor employee filling a non-critical sensitive or IT-II position is required to complete:

SF-86 Questionnaire for National Security Positions (or equivalent OPM investigative product)

Two FD-258 Applicant Fingerprint Cards (or an electronic fingerprint submission)

Original Signed Release Statements

Failure to provide the required documentation at least 30 days prior to the individual’s start date shall result in delaying the individual’s start date. Background investigations shall be reinitiated as required to ensure investigations remain current (not older than 10 years) throughout the contract performance period. The

Contractor’s Security Representative shall contact the Command Security Manager for guidance when reinvestigations are required.

Regardless of their duties or IT access requirements ALL contractor employees shall in-process with the Navy

Command’s Security Manager upon arrival to the Navy command and shall out-process prior to their departure at the completion of the individual’s performance under the contract. Employees requiring IT access shall also check-in and check-out with the Navy Command’s Information Assurance Manager. Completion and approval of a System Authorization Access Request Navy (SAAR-N) form is required for all individuals accessing Navy

Information Technology resources. The SAAR-N shall be forwarded to the Navy Command’s Security Manager at least 30 days prior to the individual’s start date. Failure to provide the required documentation at least 30 days prior to the individual’s start date shall result in delaying the individual’s start date.

The contractor shall ensure that each contract employee requiring access to IT systems or networks complete annual

Information Assurance (IA) training, and maintain a current requisite background investigation. Contractor employees shall accurately complete the required investigative forms prior to submission to the Navy Command

Security Manager. The Navy Command’s Security Manager will review the submitted documentation for completeness prior to submitting it to the Office of Personnel Management (OPM). Suitability/security issues identified by the Navy may render the contractor employee ineligible for the assignment. An unfavorable determination made by the Navy is final (subject to SF-86 appeal procedures) and such a determination does not relieve the contractor from meeting any contractual obligation under the contract. The Navy Command’s

Security Manager will forward the required forms to OPM for processing. Once the investigation is complete, the results will be forwarded by OPM to the DON Central Adjudication Facility (CAF) for a determination.

If the contractor employee already possesses a current favorably adjudicated investigation, the contractor shall submit a Visit Authorization Request (VAR) via the Joint Personnel Adjudication System (JPAS) or a hard copy VAR directly from the contractor’s Security Representative. Although the contractor will take JPAS

“Owning” role over the contractor employee, the Navy Command will take JPAS "Servicing" role over the contractor employee during the hiring process and for the duration of assignment under that contract. The contractor shall include the IT Position Category per SECNAV M-5510.30 for each employee designated on a

VAR. The VAR requires annual renewal for the duration of the employee’s performance under the contract.

BACKGROUND INVESTIGATION REQUIREMENTS AND SECURITY APPROVAL PROCESS FOR

CONTRACTORS ASSIGNED TO OR PERFORMING NON-SENSITIVE DUTIES

Contractor employee whose work is unclassified and non-sensitive (e.g., performing certain duties such as lawn maintenance, vendor services, etc ...) and who require physical access to publicly accessible areas to perform those duties shall meet the following minimum requirements:

Must be either a US citizen or a US permanent resident with a minimum of 3 years legal residency in the

United States (as required by The Deputy Secretary of Defense DTM 08-006 or its subsequent DoD instruction) and

Must have a favorably completed National Agency Check with Written Inquiries (NACI) including a FBI fingerprint check prior to installation access.

To be considered for a favorable trustworthiness determination, the Contractor’s Security Representative must submit for all employees each of the following:

SF-85 Questionnaire for Non-Sensitive Positions

Two FD-258 Applicant Fingerprint Cards (or an electronic fingerprint submission)

Original Signed Release Statements

The contractor shall ensure each individual employee has a current favorably completed National Agency Check with Written Inquiries (NACI) or ensure successful FBI fingerprint results have been gained and investigation has been processed with OPM

Failure to provide the required documentation at least 30 days prior to the individual’s start date may result in delaying the individual’s start date.

* Consult with your Command Security Manager and Information Assurance Manager for local policy when IT-III

(non-sensitive) access is required for non-US citizens outside the United States.

NAVAL SEA SYSTEMS COMMAND - NORFOLK NAVAL SHIPYARD

SERVICE CONTRACTS DIVISION

No instructions, either verbal or written, deviating from the terms and conditions of this order are effective or binding upon the Government unless authorized and formalized by contractual documents issued by the

Contracting Officer. On any problems concerning the order, please contact Contract Specialist, Victoria C.

Buela, Code 451, NAVSEA, Norfolk Naval Shipyard, Submarine Services, Bldg. 65, 2ND Floor, Portsmouth, VA 23709-5000, Telephone: (757) 967-3034.

HAZARDOUS CHEMICAL EXPOSURE

Contractors are informed that their employees present on property under Norfolk Naval Shipyard cognizance may be exposed to hazardous chemicals as a result of shipyard operations. Information on the materials may be obtained from the Shipyard Safety and Health Office, Code 106.1, phone number (757) 396-3702 or 396-7912.

Ref. NAVSHIPYDNORINST PS100.56 VOL VI CHAPTER II PARA. 7-J(3)

REQUIREMENTS FOR ACCESS TO NNSY

Commander, Navy Installations Command (CNIC), has established the Defense Biometric Identification System, (DBIDS), a standardized process for granting unescorted access privileges to vendors, contractors, suppliers and service providers not otherwise entitled to the issuance of a Common Access Card (CAC) who seek access to and can provide justification to enter Navy installations and facilities. Participation in the DBIDS is not mandatory, and if the Contractor chooses to not participate, the Contractor's personnel will have to obtain daily passes, be subject to daily mandatory vehicle inspection, and will have limited access to the installation. The

Government will not be responsible for any cost or lost time associated with obtaining daily passes or added vehicle inspections incurred by non-participants in the DBIDS. Alternatively, if the vendor so chooses, it may voluntarily elect to obtain long-term credentials through enrollment, registration, background vetting, screening, issuance of credentials, and electronic validation of credentials. Further information regarding DBIDS can be found at www.cnic.navy.mil/om/dbids.html.

NOTE: Bldg 276, Phone#: (757) 396-5815 / (757) 396-5095

ACCESS TO NNSY BY DELIVERY PERSONNEL

Delivery personnel requesting access to NNSY must adhere to the requirements set forth in the Clause entitled

“REQUIREMENTS FOR ACCESS TO NNSY” herein.

INSPECTION AND ACCEPTANCE

Inspection and acceptance will be at destination, unless otherwise provided. Until delivery and acceptance, and after rejections, risk of loss will be on the Contractor unless loss results from negligence of the United States

Government. Notwithstanding the requirements for any Government inspection and test contained in specifications applicable to this contract, except where specialized inspections or tests are specified for performance solely by the Government, the Contractor shall perform or have performed, the inspections and tests required to substantiate that the supplies and services provided under the contract conform to the drawings, specifications and contract requirements listed herein, including, if applicable, the technical requirements for the manufacturer's part numbers specified herein.

http://www.cnic.navy.mil/om/dbids.html

CONTRACTOR'S VEHICLE REQUIREMENTS

Controlled Industrial Area (CIA) access of contractor vehicles requires that the company name be displayed on both sides of all company vehicles including privately owned vehicles being utilized in performance of a contract or purchase order. Cardboard or paper signs taped to a vehicle or placed in the window will not be acceptable to meet this requirement. Temporary vehicle passes (TVP) will be issued and must be displayed on the left front dash at all times. Failure to comply will result in the contractor being denied access to Norfolk Naval Shipyard

CIA.

The contractor's failure to comply with this requirement relieves the Norfolk Naval Shipyard of any liability regarding demurrage and/or detention costs associated with delays to gain access.

PERSONAL PROTECTIVE EQUIPMENT

Contractors are responsible for all personal protective equipment required by their employees in the performance of this requirement.

PUBLIC RELEASE AND FOREIGN DISCLOSURE OF INFORMATION OR PHOTOGRAPHS

There shall be no public release of information or photographs concerning any aspect of the materials or services related to this information, bid, contract, purchase order or other document resulting therefrom, regardless of their classifications, without prior approval of the Contracting Officer, Norfolk Naval Shipyard, NAVSEA

Submarine Services Division, Bldg. 65, 2nd Floor, Portsmouth, VA 23709-5000.