Attachment 1 - Salient Characteristics - HELAMS.pdf

PDF 108 KB Posted

Attached to
4 EWS HELAMS
Solicitation number
FA251726Q0025
Issued by

About this file

This document is an attachment specifying the salient characteristics and technical requirements for HELAMS (Highly Expeditionary Lightweight Agile Modular System).

The HELAMS is a deployable facility requiring 16-inch ducts (minimum of 4 each) for Military specification ECUs. The facility must include Sensitive Compartmented Information Facility (SCIF) capability with an integrated intrusion detection system, corner leveling jacks rated at 4x5,000 lbs, and input power specifications of 120/208 VAC, 3-phase, 60Hz at 60 amps with two MIL-C-22992 Class L power connectors. Environmental controls include lighting with dimming options, emergency backup lighting, and cooling with temperature control capabilities. Access security is provided through both CDX-10 and Cypher personnel door locks. The facility accommodates six 19-inch server racks center-mounted side by side. Physical dimensions are specified for both stowed and deployed configurations: exterior stowed at 96"W x 178"L x 96.25"H (interior stowed 79.7"W x 174.3"L x 87"H) and exterior deployed at 258"W x 178"L x 96.25"H (interior deployed 256"W x 174.3"L x 87"H).

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 – Salient Characteristics - HELAMS

• 16in 4ea min, ducts for Mil spec ECUs to be used.

• Sensitive Compartmented Information Facility (SCIF) (including intrusion detection system) capability

• Corner leveling jacks (4x5,000lbs)

• Input Power (120/208 VAC, 3PH, 60Hz)

• Current (60 amp)

• 2ea Power Connector (MIL-C-22992, Class L)

• Lighting (with dimming options)

• Emergency Backup Lighting

• Cooling / temperature control

• CDX-10 Personnel Door Locks

• Cypher Personnel Door Locks

• EXTERIOR STOWED 96"W X 178"L X 96.25"H

INTERIOR STOWED 79.7.W X 174.3.L X 87"H

EXTERIOR DEPLOYED 258.W X 178.L X 96.25.H

INTERIOR DEPLOYED 256.W X 174.3.L X 87"H

• 6ea 19 in Server Racks center mounted side by side.

File details come from the government source that posted it. Updated .