Attachment 1 - Salient Characteristics - 100 Ton Portable Chiller (2).pdf
PDF 146 KB Posted
- Attached to
- 100 Ton Portable Chiller Federal contract opportunity
- Solicitation number
- FA303025Q0010
About this file
This document contains the minimum salient characteristics for a 100-ton Trane air-cooled scroll packaged chiller with required accessories and transportation equipment. The specifications detail a high-efficiency unit operating on R-454B refrigerant, requiring 460V/60Hz/3-phase power, with features including factory-installed freeze protection, refrigerant isolation valves, ETL listing, ASHRAE 90.1/CSA C743-2019 compliance, and AHRI certification.
The package includes detailed requirements for a low-profile flatbed trailer (24' x 102" with 10,000 lb tandem axles), a 10 hp pump system (235 GPM @ 87 ft head), and extensive accessories including 4" chilled water piping, isolation valves, pressure gauges, and thermometers. Additional components include multiple Camlock connectors, ANSI 150 flange adapters, and fourteen 50-foot sections of 4/0 power cable with specific color coding. The unit must be started by Trane Service for warranty validation and includes a first-year warranty covering parts, labor, and refrigerant loss.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 3 - Amendment for Questions and Answers.pdf | ||
| Solicitation Amendment FA303025Q00100001 SF 30.pdf | ||
| Solicitation - FA303025Q0010.pdf | ||
| Attachment 2 - 2024 HVAC Chiller JA - AQ Signed 10 Sep 24.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Minimum Salient Characteristics
100 Ton Trane Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored.
100 nominal tons
460/60/3
High efficiency/performance
Refrigerant Charge R-454B
With factory installed freeze protec�on
Refrigerant isola�on valves (discharge valve)
ETL Listed to US/Canadian Safety Standard
ASHRAE 90.1/CSA C743 - 2019 Compliance
AHRI cer�fied.
Standard cooling applica�on (leaving water temperature greater than 42°F)
Grooved pipe connec�on
Factory insula�on 0.75"
Performance based on water.
Wide ambient opera�ng capability
Lanced aluminum fins
Across the line starter/direct online
Single point connec�on main line unit power – ancillary items require separate 110v power connec�on(s)
Circuit breaker
10,000-amp SCCR
Enclosure Type UL 60335 Rated for Outdoor Applica�ons
BACnet MS/TP Interface
Programmable quad relay alarm board
No Wireless Op�ons
Factory installed IFM Efector flow switch.
: (Three phase electrical connection/capability)
Factory installed water strainer.
Standard low noise fans
Architectural louvered panels – hail guards covering upper and lower sec�ons.
1st year en�re chiller parts labor, and refrigerant loss warranty
Factory start up and prestart inspec�on.
Low Profile Flatbed Trailer
3” Pintle Eye Hitch
Deck over approximately 24’ long x 102” wide
Straight deck with no ramps or pockets
10,000 lb. tandem axels
Primer + powder coat
Tool compartment
Spare �re and mount
10 hp pump with suc�on diffuser
TEFC NEMA Premium efficient motor
235 GPM @ 87 � head
Variable frequency drive
Furnish and install new transformer 208v /480v.
Weathershield to convert to type 3R enclosure.
4” chilled water piping from chiller to pump with bypass
Isola�on valves will be installed at the piping connec�ons to protect piping interior during transport.
Piping will include associated pressure gauges and thermometers.
120VAC connec�on for energizing oil heaters
DLO Camlock power connector for connec�on of temporary field wire
Accessories furnished:
(2) 50 � hose, 4” with Camlock connectors
(2) 4” male Camlock to ANSI 150 flange adapter
(2) 4” female Camlock to ANSI 150 flange adapter
(Quantity is in Parenthesis)
(14) 50 � sec�on of 4/0 power cable with Camlocs (3x Black, 3x Red, 3x Blue, 2x Green, 1x Brown, 1x Orange, 1x Yellow)
File details come from the government source that posted it. Updated .