Attachment 1 - Renovate Bldg.62 AC Shop - Drawings.pdf
PDF 35 MB Posted
- Attached to
- Y1DZ--36C257-26-AP-0167 | NEW CON FY26 | 674-21-252 - Renovate Bldg. 62 AC Shop (VA-26-00003429)
- Solicitation number
- 36C25726R0010
About this file
This file is a comprehensive set of architectural and engineering drawings for renovating Building 62, an Air Conditioning (AC) Shop at the Central Texas Veterans Health Care System in Temple, Texas. The project encompasses a complete renovation of a 5,115 square foot facility, involving demolition and replacement of electrical, mechanical, plumbing, and structural systems. Key components include installing new VRF (Variable Refrigerant Flow) HVAC equipment with multiple indoor and outdoor units, new electrical distribution panels and transformers, updated lighting systems, plumbing fixtures, and structural modifications to the roof and interior spaces.
The design documents, prepared by O'Brien Engineering, Inc., detail renovations across multiple disciplines including electrical (new 225 kVA transformer, 800A main distribution panel), mechanical (installing ceiling-concealed and wall-mounted HVAC units), and plumbing (new water heater, water softener, and fixtures). The project follows VA construction standards, incorporating accessibility requirements, life safety considerations, and adherence to various building codes including the 2021 International Building Code and NFPA standards. The renovation aims to modernize the facility's infrastructure while maintaining functionality for the VA's air conditioning and refrigeration equipment repair operations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25726R0010 0003.docx | DOCX document | |
| Pre-Bid Renovation of Bldg. 62 - AC Shop - 12.29.2025.pdf | ||
| 36C25726R0010 0002.docx | DOCX document | |
| 36C25726R0010 0001.docx | DOCX document | |
| Solicitation - 36C25726R0010_1 - Renovation of Bldg. 62 AC Shop.pdf | ||
| Attachment 3 - Renovate Bldg.62 AC Shop - PCRA.pdf | ||
| Attachment 4 - Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 2 - Renovate Bldg. 62 AC Shop - Specs.pdf | ||
| 36C25726R0010_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI001
COVER SHEET RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
RENOVATE BLDG.62 - AC SHOP : 674-21-252
TEMPLE, TEXAS
CENTRAL TEXAS VA HEALTHCARE SYSTEM
SHEET INDEX
SHEET NUMBER SHEET NAME
00_GENERAL
GI001 COVER SHEET
GI002 VICINITY MAP, SYMBOLS AND NOTES
GI101 ACCESSIBILITY STANDARDS
GI103 LIFE SAFETY PLAN
GI201 EXISTING PHOTO - EXTERIOR
GI202 EXISTING PHOTO - INTERIOR
GI203 EXISTING PHOTO - MEP+S
07_STRUCTURAL
S100 ROOF FRAMING PLAN
S200 DETAILS
08_ARCHITECTURAL
AD101 DEMOLITION PLAN & NOTES
AE100 OVERALL FLOOR PLAN
AE111 FLOOR PLAN & ENLARGED PLAN
AF121 FINISH PLAN
AE131 EQUIPMENT PLAN & EQUIPMENT LIST
AC141 REFLECTED CEILING PLAN
AE151 ROOF PLAN
AE200 EXTERIOR ELEVATIONS
AE300 BUILDING SECTIONS
AE301 SECTION DETAILS
AI400 INTERIOR ELEVATIONS & MILLWORK DETAILS
AE410 STANDARD PARTITION TYPES
AE500 STAIR & RAMP DETAILS
AE600 DOOR & WINDOW SCHEDULE / WINDOW DETAILS
AE601 DOOR DETAILS
AE900 PERSPECTIVE VIEWS
SHEET INDEX
SHEET NUMBER SHEET NAME
11_PLUMBING
P001 COVER SHEET - SHEET LOG & GENERAL NOTES
P002 GENERAL NOTES, SYMBOLS & ABBREVIATIONS
PD101 PLUMBING DEMOLITION PLAN
PP101 PLUMBING WASTE & VENT PLAN
PP102 PLUMBING WATER SUPPLY PLAN
P501 PLUMBING DETAILS
P502 WATER SOFTENER DETAILS
P601 PLUMBING SCHEDULES
PP701 PLUMBING SITE PLAN
PP901 WASTE & VENT ISOMETRIC
PP902 WATER SUPPLY ISOMETRIC
13_MECHANICAL
M001 COVER SHEET
M002 GENERAL NOTES, SYMBOLS & LEGENDS
MD101 DUCT DEMOLITION PLAN - LEVEL 1
MH101 MECHANICAL HVAC PLAN
MH102 DUCT PLAN - ROOF
MP101 MECHANICAL HVAC PIPING PLAN
MH301 SECTIONS
MH401 DETAILS
MH501 SCHEDULES & DIAGRAMS
MH502 SCHEDULES & DIAGRAMS
MH503 SCHEDULES & DIAGRAMS
SHEET INDEX
SHEET NUMBER SHEET NAME
14_ELECTRICAL
E001 COVER SHEET - GENERAL NOTES & SHEET LOGS
E002 GENERAL NOTES
E003 SYMBOLS ABBREVIATIONS & LEGENDS
ED101 ELECTRICAL DEMOLITION PLAN - LEVEL 1
ED102 ELECTRICAL DEMOLITION PLAN - ROOF
ED701 ELECTRICAL SITE PLAN - DEMOLITION
EL101 ELECTRICAL LIGHTING PLAN - LEVEL 1
EP101 ELECTRICAL POWER PLAN - LEVEL 1
EP102 ELECTRICAL MECHANICAL POWER PLAN - LEVEL 1
EP103 ELECTRICAL MECHANICAL POWER PLAN - ROOF
EP501 ELECTRICAL POWER DETAILS
EP601 ELECTRICAL SINGLE LIN DIAGRAM - SITE
EP602 ELECTRICAL SINGLE LINE DIAGRAM - NEW
EP603 SCHEDULES & DIAGRAMS
EP701 ELECTRICAL SITE PLAN - NEW WORK
Revisions: Date:
T
TT
T
T
0 COLUMN GRID LINE
DOOR NUMBER
SYMBOL
DETAIL - SECTION
POSITION ON SHEET
SHEET NUMBER
DETAIL - PLAN/ RCP
POSITION ON SHEET
SHEET NUMBER
WALL SECTION
POSITION ON SHEET
SHEET NUMBER
EXTERIOR ELEVATION
POSITION ON SHEET
SHEET NUMBER
INTERIOR ELEVATION
POSITION ON SHEET
SHEET NUMBER
EXTERIOR WALL TYPE TAG
EXTERIOR WINDOW
SIGN TYPE, SEE SIGNAGE
SCHEDULE
DRAWING NUMBER
DRAWING SCALE
VIEW TITLE
NOTES BY NUMBER
DRAWING REVISION
LEVEL DATUM
LEVEL NAME
LEVEL ELEVATION
NORTH ARROW
INTERIOR WINDOW
GRAPHIC SCALE
0 4'-0" 8'-0" 16'-0"
XX
XX
XXXX
7'-0" R 3'-11"
100°
SIM
X
X-XXX
DIMENSION TO FACE OF
GYPSUM BOARD, FACE OF
CONCRETE, COLUMN
CENTERLINE, OR AS NOTED.
CENTERLINE
X
X X
X
A1
A101
SIM
A101
SIM
ROOM TAG (FOR SPECIALTY PLANS)
ROOM NAME
ROOM NUMBER
FLOOR FINISH
ROOM NAME
XXXX
FLOR
BASE
WALL
CEIL BASE TYPE
WALL FINISH
CEILING TYPE
A
A101
SIM
Name Elevation
1/8" = 1'-0"
AC1
INTERIOR PARTITION TYPE TAGA3
ROOM NAME
101101 ROOM NAME
ROOM NUMBER
ROOM AREA
ROOM TAG (FOR STANDARD PLANS)
N
BUILDING SECTION
POSITION ON SHEET
SHEET NUMBER
A101
SIM
BATT. INSULATION
CAST IN PLACE CONCRETE
CAST STONE
CONCRETE MASONRY/CMU
EARTH IN SECTION
FACE BRICK
GYP./GYPSUM BOARD
MARBLE
PARTICLE BOARD/PLYWOOD
ROOF INSULATION
STUCCO
CONTINUOUS WOOD BLOCKING
DISCONTINUOUS WOOD BLOCKING
FINISHED WOOD
OWNER
ARCHITECT
O'BRIEN ENGINEERING INC.
CONTRACTING OFFICER REPRESENTATIVE
MECHANICAL, PLUMBING, AND
ELECTRICAL ENGINEER
O'BRIEN ENGINEERING INC.
Mr. TYRONE BENNETT
CENTRAL TEXAS VA HEALTHCARE SYSTEM
STRUCTURAL ENGINEER
CDC STRUCTURAL ENGINEERS
VICINITY MAP
NOT TO SCALE
N
CODE INFORMATION
BUILDING: 2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
ACCESSIBILITY: ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
FIRE: 2021 INTERNATIONAL FIRE CODE
NFPA 101 LIFE SAFETY CODE 2024
PLUMBING: 2021 INTERNATIONAL PLUMBING CODE
MECHANICAL: 2021 INTERNATIONAL MECHANICAL CODE
ELECTRICAL: 2023 NATIONAL ELECTRICAL CODE
ENERGY: 2021 INTERNATIONAL ENERGY CODE
2022 ASHRAE 90.1
OCCUPANCY CLASSIFICATIONS
INDUSTRIAL OCCUPANCY (NFPA 101 LIFE SAFETY CODE 2021 6.1.12)
MIXED OCCUPANCY (NON-SEPERATED) OF LOW-HAZARD FACTORY INDUSTRIAL (F-2) AND
LOW-HAZARD STORAGE (S-2) (2021 INTERNATIONAL BUILDING CODE 508.2.3)
CONSTRUCTION TYPE
PROJECT AREA
5,115 SF
TYPE V - B
PROJECT TYPE
ALTERATIONS (2021 INTERNATIONAL ENERGY CONSERVATION CODE - SECTION C503, C503.1 - C503.2) ALTERATIONS - LEVEL 3 (2021 INTERNATIONAL EXISTING BUILDING CODE CHAPTER 9, 907.1)
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE 2024
SEPERATION & RATED WALL
WHERE TWO STORIES OR LESS IN HEIGHT AND THE TOTAL BUILDING SQUARE FOOTAGE IS LESS THAN 10,000 SQFT, NO SEPARATION IS REQUIRED. (2024 NFPA 6.1.14.1.4 SEPARATED OCCUPANCIES)
NO SEPARATION REQUIREMENT (2021 INTERNATIONAL BUILDING CODE, TABLE 508..4)
NO SPRINKLER REQUIREMENT (2024 NFPA 40.3.5 EXTINGUISHMENT REQUIREMENTS)
FIRE SPRINKLER IS NOT REQUIRED (2021 INTERNATIONAL BUILDING CODE, 506.1 & 506.2 WITH TABLE 506.2)
AUTOMATIC SPRINKLERS
GENERAL PROJECT DESCRIPTION
THIS PROJECT SHALL CONSIST OF INTERIOR RENOVATIONS TO AN EXISTING BUILDING AS DEFINED ON
THE CHART BELOW.
PROJECT TYPE YES NO
NEW CONSTRUCTION: (COMPLETELY NEW BUILDING AND SITE WORK)
ADDITION: (NEW CONSTRUCTION TO INCREASE SIZE OF EXISTING BUILDING)
RENOVATION: (REPLACEMENT OF EXISTING BUILDING COMPONENTS)
SYSTEM UPGRADES
ITEM YES NO
NEW STRUCTURAL SYSTEM (ROOF)
EXISTING STRUCTURAL SYSTEM AFFECTED
EXISTING EXTERIOR WALLS AFFECTED
EXISTING INTERIOR WALLS AFFECTED
EXISTING INTERIOR FINISHES AFFECTED
EXISTING ROOFING AFFECTED (DEMO)
HVAC SYSTEMS AFFECTED
ELECTRICAL SYSTEMS AFFECTED
B
LD
G
R A
IL
R
O A
D T
R A
C K
S
B
LD
G
BLDG 222
BLDG 147
BLDG 47
BLDG 146
BLDG 46
BLDG 45
BLDG 44
BLDG 220
B
LD
G
B
LD
G
ROAD 7 52
BLDG 59
B
LD
G
ROAD 8
TE
A
G U
E P
LA
C
E
R O
A D
B
LD
G
BLDG 20
BLDG 203
BLDG 204
R O
A D
A
ROAD 6A
R O
A D
A
R O
A D
A
R O
A D
ROAD 11
STATE VETERANS HOME
R O
A D
A
ROAD 6B
TE
A
G U
E P
LA
C
E
W. AVE R
W. AVE U
TE
A
G U
E P
LA
C
E
B
LD
G
ROAD 8B
ROAD 1A
ROAD 1B
VE
TE
R A
N M
EM
O
R
IA
L D
R
IV
E
BLDG 62
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI002
VICINITY MAP, SYMBOLS AND
NOTES
RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024
DRAWING LEGENDABBREVIATIONS
ACT. ACTUAL
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
A.F.S. ABOVE FINISH SLAB
AGG. AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
ALUM. ALUMINUM
BLDG. BUILDING
BK. BRICK
BM. BEAM
CAB. CABINET
CPT. CARPET
C.J. CONTROL JOINT
CENTERLINE
CG CORNER GUARD
CLG. CEILING
COL. COLUMN
CONC. CONCRETE
COND. CONDITION
CONT. CONTINUOUS
C.T. COUNTERTOP
DBL. DOUBLE
DEMO. DEMOLITION
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
DN. DOWN
DWG. DRAWING
E.W.C. ELECTRIC WATER COOLER
EA. EACH
E.J. EXPANSION JOINT
EXP. EXPANSION
E.W. EACH WAY
EXT. EXTERIOR
EXIST. EXISTING
F.E.C. FIRE EXTINGUISHER CABINET
F.D. FINISH DIMENSION
F.D.V.B. FIRE DEPARTMENT VALVE BOX
F.F. FINISH FLOOR
FIN. FINISH(ED)
FRT. FIRE RETARDANT TREATED
G.I. GALVANIZED IRON
G.B./GYP.BD. GYPSUM BOARD
GA. GAUGE
GALV. GALVANIZED
GL. GLASS
H.M. HOLLOW METAL
H.S. HORIZONTAL IN SPLASH
I.C.U. INTENSIVE CARE UNIT
INT. INTERIOR
INSUL. INSULATION
I.T.C. INSTALLED THIS CONTRACT
K.S. KNEE SPACE
LAM. LAMINATED
LAV. LAVATORY
L.L.V. LONG LEG VERTICAL
L.L.H. LONG LEG HORIZONTAL
MANUF. MANUFACTURER
MAX. MAXIMUM
MECH. MECHANICAL
MIN. MINIMUM
M.O. MASONRY OPENING
MTL./MET. METAL
MNT. MOUNTED
N/A NOT APPLICABLE
NOM. NOMINAL
N.T.S. NOT TO SCALE
N.I.C. NOT IN CONTRACT
O.C. ON CENTER
O.D. OVERFLOW DRAIN
O.H/OPP.H. OPPOSITE HAND
P.D. PLAN DIMENSION
PLAS. LAM. PLASTIC LAMINATE
P.T. PORCELAIN TILE
P.T.D. PAPER TOWEL DISPENSER
RB RUBBER BASE
R./REV. REVISED/REVERSE
R./RAD. RADIUS
REINF. REINFORCE
REF. REFERENCE/REFER TO
REQ'D REQUIRED
R.D. ROOF DRAIN
RM. ROOM
R.O. ROUGH OPENING
SCHED. SCHEDULED
SAB. SOUND ATTENUATION BATTS
SHT. SHEET
SIM. SIMILAR
SL. SLOPE
STL. STEEL
S.S. STAINLESS STEEL
S.S.V. SOLID SURFACE VENEER
SUSP. SUSPENDED
S.V. SHEET VINYL
T.A.S. TEXAS ACCESSIBILITY STANDARDS
T.B. TACK BOARD
T.D.H. TEXAS DEPARTMENT OF HEALTH
TEMP. OR (T.) TEMPERED GLASS
THK. THICK
TOIL. TOILET
TYP. TYPICAL
U.C. UNDER COUNTER
UCR UNDER COUNTER REFRIGERATOR
U.L. UNDERWRITERS LABORATORIES
U.N.O. UNLESS NOTED OTHERWISE
UR. NEW URINAL
VCT VINYL COMPOSITION TILE
V.T. VINYL TILE
VERT. VERTICAL
W.C. NEW WATER CLOSET
WDW. WINDOW
WD. WOOD
WH WATER HEATER
W/ WITH
W/O WITHOUT
MATERIALS LEGEND GENERAL NOTES
1. THE CONTRACT DRAWINGS AND THE PROJECT MANUAL COMPRISE THE CONTRACT
DOCUMENTS. CONTRACTOR(S) SHALL BE FAMILIAR WITH ALL ASPECTS OF THE CONTRACT
DOCUMENTS, AND SPECIFICALLY THE DRAWINGS AND SPECIFICATIONS WHICH PERTAIN TO THE
CONTRACTOR(S) SCOPE OF WORK, THE GENERAL CONDITIONS OF THE CONTRACT, DIVISION 1
OF THE SPECIFICATIONS, AND COORDINATION OF RELATED TRADES, BEFORE SUBMITTING A
BID.
2. THESE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. IN THE EVENT OF
OMISSION OF NECESSARY DIMENSIONS, CONTRACTOR SHALL NOTIFY THE COR.
3. VERIFY ALL DIMENSIONS, GRADES, AND EXISTING CONDITIONS AT JOB SITE. WHERE
DIMENSIONS ARE LABELED "VERIFY", THE CONTRACTOR SHALL NOTIFY THE COR IF DIMENSION
VARIES FROM DIMENSION SHOWN PRIOR TO CONSTRUCTING WALLS.
4. VERIFY SIZE AND LOCATIONS OF ALL OPENINGS WITH CONTRACTORS INVOLVED, INCLUDING
MECHANICAL AND ELECTRICAL AND PROVIDE OPENINGS AS REQUIRED. NO OPENINGS SHALL
BE MADE THROUGH STRUCTURAL COMPONENTS WITHOUT PRIOR APPROVAL FROM THE COR.
5. THE PROJECT SHALL BE CONSTRUCTED TO BE ACCESSIBLE TO PERSONS WITH DISABILITIES.
6. ERRORS AND/OR OMISSIONS IN ROOM, DOOR, OR WINDOW SCHEDULES DO NOT RELIEVE THE
CONTRACTOR FROM EXECUTING WORK SHOWN ON THE DRAWINGS OR DESCRIBED IN THE
SPECIFICATIONS.
7. ALL DIMENSIONS ON PLANS ARE TO THE FACE OF FINISHED WALL, CONCRETE STRUCTURE, OR
MASONRY UNLESS NOTED OTHERWISE.
8. ADD SUFFICIENT BLOCKING IN STUD WALLS TO SUPPORT ALL ITEMS OR EQUIPMENT SHOWN OR
SPECIFIED TO BE ATTACHED TO THE WALLS. PROVIDE ADDITIONAL STRUCTURAL SUPPORT
(ANGLES, CHANNELS, ETC.) WITHIN WALLS WHERE WEIGHT OF ATTACHED ITEMS IS TOO GREAT
TO BE SUPPORTED BY METAL STUDS.
9. LIGHT FIXTURES LOCATED IN CEILING SYSTEMS SHALL BE LOCATED ACCORDING TO THE
ARCHITECTURAL REFLECTED CEILING PLAN.
10. CEILING DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST FAN INTAKES LOCATED IN CEILING
SYSTEMS SHALL BE LOCATED ACCORDING TO THE ARCHITECTURAL REFLECTED CEILING PLAN.
11. IN ROOMS OR AREAS WITH EXPOSED STRUCTURE, ALL WIRING & CABLING TO BE IN CONDUIT.
3'-0"
3' -0
3'
-0
4'-0"
H.C. SEAT
GRAB BAR
SHOWER
HEAD
CLEAR
AREA
SHOWER PLAN
4' -0
" M
AX
3' 2"
M
IN
2' 9"
T O
'-0
3'-0"
CONTROL
AREA
RECESSED
SOAP TRAY
MTD. 40" A.F.F
CONTROL WALL
3'-0"
1' -5
/4
SEAT WALL
3'-0"
1' -5
/4
BACK WALL
1'-5 1/2"
2' -9
" T O
'-0
5'-0" OR 4'-0"
2' -6
3'
-0
O R
'-0
3' -0
5'-0"
GRAB BARS
SHOWER
HEAD
SECONDARY SHOWER HEAD & SLIDE
BAR (WHERE INDICATED)
CLEAR
AREA
SHOWER PLAN
5'-0"
4' -0
NURSE CALL WITH
PULL CORD
WHERE SPECIFIED
GRAB BAR
BACK WALL ELEVATION CONTROL WALL ELEVATION
2'-6", 3'-0", OR 4'-0"
2'-11 1/2"
2' -8
/4
2' -8
/4
1' -6
3"
3' 2"
T O
'-0
" M
AX
6"
TO
C
O N
TR
O
LS
VERTICAL
GRAB BARS
CONTROL
AREA
RECESSED
SOAP TRAY
MTD. 40" A.F.F
4"
2' -8
/2
6"
REMOVABLE BENCH
(WHERE INDICATED)
SECONDARY CONTROLS
(WHERE INDICATED)
SIDE WALL ELEVATION
ROLL-IN HDCP ACCESSIBLE SHOWER (ACCEPTABLE MINIMUM SIZES: 48" X 48", 30" X 60" OR 36" X 60") (VA REQ'D)
TRANSFER TYPE HDCP ACCESSIBLE SHOWER 36" X 36"
6'-0" MIN. (VA REQ'D)
1"
2'-10" MIN. (VA REQ'D)
1"
5' -6
" M
IN
VA
R
EQ
'D
1/
2" 3'
-0
1'-0" 3'-6"
FLUSH HANDLE TO
OPEN SIDE OF STALL/
ROOM. TYP.
STANDARD HDCP TOILET
STALL DIMENSIONS
(V A
R
EQ
'D
6' -0
" M
IN
(F
LO
O R
-M
TD
W .C
(V A
R
EQ
'D
6' -0
" M
IN
(W
AL
L- M
TD
W
.C
6" 3'-0"
1' -0
3'
-6
4" MAX.
(VA REQ'D)
2'-10" MIN.
STANDARD HDCP TOILET
STALL DIMENSIONS
1'-6"
1' -6
1' -6
/4
3'-0" MIN. 6" MAX.
2' -1
0"
FRONT OF TOILET
1' -3
" S
TA
N D
A R
D , T
O P
O F
S E
A T
1' -6
" H D
C P
, T O
P O
F S
E A
T
3' -8
" M
AX
. T O
F
LU
SH
C
TR
L
2' -1
0"
2'-0"
3'-0" MAX.
1' -9
/4
NAPKIN DISPOSAL
(WHERE SHOWN)
TOILET TISSUE
DISPENSER
WALL MOUNTED TOILET
2'-0"
3'-0 1/4"
1' -3
" S
TA
N D
A R
D , T
O P
O F
S E
A T
1' -6
" H D
C P
, T O
P O
F S
E A
T
3' -8
" M
AX
. T O
F
LU
SH
C
TR
L
2' -1
0"
NAPKIN DISPOSAL
(WHERE SHOWN)
TOILET TISSUE
DISPENSER
FLOOR MOUNTED TOILET
4" MAX.
3' -4
PAPER TOWEL
DISPENSER/
WASTE
RECEPTACLE
3' -4
PAPER TOWEL
DISPENSER
3' -8
/4
SOAP DISPENSER
2' -1
0" M
AX
3' -4
" M
AX
6' -8
" M
IN
TO REFLECTIVE
SURFACE
7" (VA REQ'D)
PAPER TOWEL
DISPENSER
1'-6" MIN.
1' -5
" M
IN
LAVATORY &
MIRROR
9" M
IN
2' -3
" M
IN
2' -5
" M
IN
2' -1
0" M
AX
2'-6" CLR.
1/
2" M
AX
2' -3
" C
LE
A R
K
IT
C H
E N
S 2'
-5 " T
O
IL
E T
R O
O M
S
1'-6"
SINK MOUNTED
COUNTER FRONT
ELEVATION
2'-6" 2'-6"
1' -8
" M
AX
SINK MOUNTED
COUNTER PLAN
COORDINATE W/ M.E.P.
ALL PIPES ARE TO BE
PROPERLY INSULATED
OR LOCATED TO
PREVENT CONTACT.
1' -5
" M
AX
2-6" MIN.
3' -8
" M
AX
IF X < 24",
Y= 2'-6"
IF X > 24",
Y= 3'-0"
Y
HDCP URINAL
1/ 2"
M
AX
NOTE: ALL DOORS IN ALCOVES MUST
COMPLY WITH THE CLEARANCE NOTED
FOR FRONT APPROACHES.
DOOR THRESHOLD
DETAIL
3"
5' -0
" C
EN
TE
R
MOUNTING LOCATION REQUIRED AT
STRIKE SIDE OF DOOR; SIDELITE
SIGNS TO BE DOUBLE, BLANK SIGN
ON BACK SIDE OF GLASS
5' -0
" C
EN
TE
R
LINE OF
NEAREST
DOOR SWING
OR
PROTRUDING
OBJECT
ALTERNATE MOUNTING LOCATION
WHERE STRIKE SIDE MOUNTING NOT
POSSIBLE. (NEAREST ADJACENT
WALL)
NOTE: A PERSON
MUST BE ABLE
TO APPROACH
WITHIN 3" OF
SIGN WITHOUT
ENCOUNTERING
ANY DOOR
SWING OR
PROTRUDING
OBJECT.
6' -8
" M
IN
LOBBY
OVERHEAD SIGN
CLEARANCE
A/C AIR CONDITIONING
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADB AUTOMATIC DOOR BUTTON
ADD ADDENDUM
ADDL ADDITIONAL
ADJ ADJUSTABLE/ ADJACENT
AFF ABOVE FINISH FLOOR
AGGR AGGREGATE
ALT ALTERNATE/ ALTERERATION
ALUM ALUMINUM
AMT AMOUNT
ANCH ANCHOR
ANDD ANODIZED
APPROX APPROXIMITE(LY)
ARCH ARCHITECTURAL
ARF ABOVE REFERENCE FLOOR
ASPH ASPHALT(IC)
ASST ASSISTANT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AVG AVERAGE
BAL BALANCE
BB BULLETIN BOARD
B/C BOTTOM OF CURB
BD BOARD
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK(ING)
BM BENCH MARK/BEAM
B.O. BOTTOM OF
BOT BOTTOM
BSMT BASEMENT
CAB CABINET
CB CATCH BASIN
C/C CENTER TO CENTER
CCTV CLOSED CIRCUIT TV
CEMPL CEMENT PLASTER
CER CERAMIC
CG CORNER GUARD
CH COAT HOOK
CHAN CHANNEL
CHKBD CHALKBOARD
CIP CAST-IN-PLACE (CONCRETE)
CJ CONTROL JOINT
CL CENTER LINE/ CLEARANCE
CLG CEILING
CLR CLEAR
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT
COL COLUMN
COMB COMBINATION/ COMBUSTIBLE
COMP COMPRESS(ED)/ COMPOSITE
CONC CONCRETE
COND CONDUIT/ CONDITION
CONF CONFERENCE
CONN CONNECT(ION)
CONST CONSTRUCTION
CONT CONTINUE/ CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATOR
CORR CORRIDOR
CPT CARPET
CSWK CASEWORK
CT CERAMIC TILE
CTR CENTER
CU CLEAN UTILITY ROOM
D DETENTION
D.A.F.S DIRECT APPLIED FINISH SYSTEM
DBL DOUBLE
DE DETENTION EQUIPMENT
DEG DEGREE(S)
DEMO DEMOLISH/ DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIV DIVISION/ DIVIDER
DN DOWN
D.D. DOUBLE OCCUPANCY CELL
D.U. DIRTY UTILITY ROOM
DWL DOWEL
DWR DRAWER
EA EACH
EB EXPANSION BOLT
EJ EXPANSION JOINT
ELEC ELECTRIC(AL)
ELEV ELEVATOR/ ELEVATION
ENAM ENAMEL(ED)
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENTR ENTRANCE
EPFL EPOXY FLOORING
EPNT EPOXY PAINT
EQ EQUAL
EQUIP EQUIPMENT
ES ELECTRONIC SECURITY
EST ESTIMATE(D)
ETC ET CETERA
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXAM EXAMINATION/ EXAMINING
EXC EXCAVATED/ EXCAVATION
EXH EXHAUST
EXIST(E) EXISTING
EXP EXPOSED/ EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAB FABRICATE/ FABRICATOR/ FABRIC
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDPR FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FDVC FIRE DEPT. VALVE CABINET
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CAB.
FH FIRE HYDRANT/ FUME HOOD/ FLAT HEAD
FHC FIRE HOSE CABINET
FHEC FIRE HOSE & EXTINGUISHER CAB.
FIN FINISH(ED)
FL FLOOR LINE/ FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLR FLOOR(ING)
FLUOR FLUORESCENT
FOS FACE OF STUD
FP FIREPROOF(ING)/ FULL PENETRATION
FRAM(G) FRAMING
FRT FIRE RETARDANT
FS FULL SIZE/ FLOOR SINK
FT FOOT/ FEET
FTG FOOTING
FURR FURRING
FXD FIXED
GA GAUGE/ GAGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL/ GENERATOR
GL GLASS/ GLAZING/ GLAZED
GLAM GLUE LAMINATED
GND GROUND
GWB GYPSUM WALLBOARD
GYP GYPSUM
HA HANDICAPPED ACCESSIBLE
HB HOSE BIBB
HC HOSE CABINET/ HANDICAP/ HOLLOW CORE
H.C.S.D. SINGLE OCCUPANT CELL
HCW HOLLOW CORE WOOD
H/C WTR HOT AND COLD WATER
HDBD HARDBOARD
HDCP HANDICAPPED (ACCESSIBLE)
HDR HEADER
HDWD HEADWOOD
HDWR HARDWARE
HGT(HT) HEIGHT
HM HOLLOW METAL
HR HOUR
HS HOOK STRIP/ HIGH STRENGTH
HSKG HOUSEKEEPING
HTR HEATER
HVAC HEATING/ VENTILATION/ AIR CONDITIONING
HWY HIGHWAY
HYD HYDRANT
ID INSIDE DIAMETER (DIM.)
IE THAT IS
IG INSULATING GLASS
IMP INSULATED METAL PANEL
IN INCH
INCAND INCANDESCENT
INCL INCLUDE(ING)
IND INDUSTRIAL
INFO INFORMATION
ING INSULATING GLASS
INSTIL INSTALLATION/ INSTALL
INSUL INSULATE(D) (ING)
INT INTERIOR
INTER INTERSECTION/ INTERMEDIATE
INV INVERT
ISO ISOLATION CELL
I.T. INMATE TOILET
JAN JANITOR
J.C. JANITOR CLOSET
JST JOIST
JT JOINT
KD KNOCK OUT
KP KICK PLATE
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LB(S) LAG BOLT(S)/ POUND(S)
LBL LABEL
LF LINEAL FOOT/ LINEAR FOOT
LH LEFT HAND
LHR LEFT HAND REVERSE
LIN LINEAR
LL LIVE LOAD
L&P LATH & PLASTER
LT(G) LIGHT(ING)
LW LIGHTWEIGHT
MACH MACHINE
MAINT MAINTENANCE
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MBR MEMBER
MC MEDICINE CABINET
MCW MINERAL CORE WOOD
MDFB MEDIUM DENSITY FIBER BOARD
MECH MECHANINCAL
MED MEDICAL/ MEDIUM
MED.S. MEDICAL STORAGE
MET METAL
MEZZ MEZZANINE
MFB MINERAL FIBER BOARD
MFR MANUFACTUR(ER) (ING)
MGR MANAGER
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML METAL LATH/ MATCH LINE
MLP METAL LATH AND PLASTER
MMB MEMBRANE
MO MASONRY OPENING
MOD MODULAR/ MODIFIED/ MODICATION
MP MOVABLE PARTITION/ METAL PANEL
MR MET RECESS, MOD RACK
M&S MIRROR & SHELF
MT MOUNT (ED) (ING)
MTR MOTOR
MTL METAL
MUL MULLION
N NORTH
NEG NEGATIVE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO or # NUMBER
NOM NOMINAL
NONCOM NONCOMBUSTIBLE
NRC NOISE REDUCTION COEFFICIENT
NS NON SLIP
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER (DIM.)
OFD OVERFLOW DRAIN
OFF OFFICE
OH OVERHEAD/ OVERHANG
OPER OPERATING
OPH OPPOSITE HAND
OPN(G) OPEN (ING)
OPP OPPOSITE
PA PUBLIC ADDRESS
PAR PARAGRAPH/ PARAPET
PTN PARTITION (S)
PB PANIC BOLT/ PUSH BUTTON
PBD PARTICLEBOARD
PC PRE-CAST
PED PEDESTAL
PERF PERFORATE (D)
PERIM PERIMETER
PERP PERPENDICULAR
PFB PREFABRICATE (D)
PG PLATE GLASS
PGBD PEGBOARD
PH PHASE/ PAN HEAD
PL PLATE/ PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNEU PNEUMATIC
PNL PANEL
PNT PAINT(ED)
POL POLISH(ED)
PORT PORTABLE
PP PUSH PLATE
PR PAIR, PRINTER, COMPUTER PRINTER
PREFAB PREFABRICATE(D)
PRELIM PRELIMARY
PRESS PRESSURE
PROJ PROJECT(ION)
PROP PROPERTY
PROT PROTECT (IVE) (ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PORCELIN TILE
PTD/R COMBINATRION PAPER TOWEL
DISPENSER & RECEPTACLE
PTR PAPER TOWL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
QTR QUARTER
QUAN QUANITITY
R RADIUS/ RISER/ RESILIENT
RAD RADIATOR/ RADIUS
RB RESILIENT BASE
RCWY RACEWAY
RD ROOF DRAIN/ ROAD
RE: REFER/ REFERENCE
RECEP RECEPTACLE/ RECEPTION
RECIRC RECIRCULATION
RECT RECTANGULAR
RECVD RECIEVED (ING)
REF REFERENCE
REFR REFRIGERATOR
REG REGULATOR/ REGLET/ REGISTER
REINF REINFORCE (D) (ING) (MENT)
REQ(D) REQUIRE (D)
RESIL RESILIENT
RET RETURN
REV REVERSE/ REVISED/ REVISION
RFG ROOFING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RS RESILIENT SHEET
R&S ROD AND SHELF
RT RESIDENT TILE
RTN RETURN
SAB SOUND ABSORPTION BATT
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SCN SCREEN
SCW SOLID CORE WOOD
SD SOAP DISPENSER/ SOAP DISH
SECT SECTION
SET SETTING
SF SQUARE FEET
SFC SPECIAL FLOOR COATING
SFP SPRAYED ON FIREPROOFING
SHR SHOWER
SHT SHEET
SK SINK/ SKETCH
SIM SIMILAR
SLR SEALER
SM SHEET METAL
SND SANITARY NAPKIN DISPENSER
SNT SEALANT
SNR SANITARY NAPKIN RECEPTACLE
S.O. SINGLE OCCUPANCY CELL
SP STANDPIPE/ SHEAR PLATE
SPEC SPECIFICATION/ SPECIFIED
SPK SPEAKER
SPL SPECIAL
SPR SPRINKLER
SPNT SPECIAL PAINT
SSK SERVICE SINK
S.T. STAFF TOILET
ST STREET/ STREAM
SST STAINLESS STEEL
STA STATION
STC SOUND TRANSMISSION COEFFICIENT
(CLASS)
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUBFL SUBFLOOR(ING)
SUP SUPPLY
SUPP SUPPORT/ SUPPLEMENT(AL)
SURF SURFACE
SUSP SUSPEND(ED)
S.V. SAFETY VESTIBULE
S&V STAIN & VARNISH
SWCG SPECIAL WALL COATING
SYM SYMMETRICAL
SYN SYNTHETIC
SYS SYSTEM
T TOP/ TREAD/ TOILET
T&B TOP & BOTTOM
TB TOWEL BAR
TBD TO BE DETERMINED
T/C TOP OF CURB/ TOP OF CONCRETE
TD TOWEL DISPENSER
TEL TELEPHONE
TEMP TEMPERATURE/ TEMPERED/
TEMPORARY
TERR TERRAZZO
TG TEMPERED GLASS
T&G TONGUE AND GROOVE
THB TEMPERED HARDBOARD
THERMO THERMOSTAT(IC)
THK THICK(NESS)
THRES THRESHOLD
THRU THROUGH
TJ TELEPHONE JACK
TKBD TACKBOARD
TOIL TOILET
T.O.M. TOP OF MASONRY
TOP TOPPING
TOS TOP OF STEEL
TPD TOILET PAPER DISPENSER
TR TREAD
TRK TRACK
T/S TOP OF SLAB
TV TELEVISION
T/W TOP OF WALL
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES, INC.
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
UTIL UTILITY
UV UNIT VENTILATOR
VAP VAPOR
VAR VARIABLE/ VARNISH/ VARIES
VB VAPOR BARRIER
V.C. VIOLENT CELL
VEH VEHICLE
VENT VENTILATION/ VENTILATE, VENTILATOR
VEN VENEER
VERT VERTICAL
VEST VESTIBULE
VG VERTICAL GRAIN
VOL VOLUME
VP VENEER PLASTER
W/ WITH
WAIN WAINSCOT
WB WHITE BOARD/ WOOD BASE
WC WATER CLOSET
WCG WALL COVERING
WD WOOD
WDW WINDOW
WF WIDE FLANGE (STEEL)
WG WIRE GLASS/ WALL GRILL
WL WATER LINE
W/O WITHOUT
WP WATERPROOF (ING)/ WORK POINT/ WEATHER
PROOF
WR WATER RESISTANT/ WASTE RECEPTACLE
WT WEIGHT
YD YARD DRAIN
HANDRAIL EXTENTIONS AT
TOP RUN
HANDRAIL EXTENTIONS AT
BOTTOM RUN
ONE TREAD
11" MIN. 1 1/2" MAX.
R 0' - 1 1/2"
MINIMUM USABLE AND
MAXIMUM NOSING
DIMENSIONS
(V A
R
EQ
'D
M
IN
. L A
N D
IN
G
'-0
A
T D
O O
R
S (VA REQ'D)
5'-0" MIN.
6'-0" MIN. AT DOORS
MAX. LENGTH= 40' FOR SLOPE LESS THAN 1:25 (VA REQ'D)
MAX. LENGTH= 35' FOR SLOPE OF 1:20 TO 1:25 (VA REQ'D)
(V A
R
EQ
'D
4' -0
" M
IN
VA
R
EQ
'T
HANDLE EXTENTION
1'-0" MIN.
(VA REQ'D)
5'-0" MIN.
6'0" MIN. AT DOORS
(VA REQ'D)
SLOPE: 1:20 (5%) TO 1:33 (3%)
RAMP DETAIL
1 1/2".
1 1/4" - 1 1/2"
ST
AI
R N
O
SI
N G
A N
D /O
R R
AM
P
SU
R
FA
C
E
(V A
R E
Q 'D
TO
P O
F H
A N
D R
A
IL
: 3 4"
A B
O V
E
HANDRAIL DETAIL
1 1/4" - 1 1/2"
GRAB BAR DETAIL
LOCKER ROOM
BENCH
2'-0" MIN. BY 4'-0" MIN.
1' -7
" M
AX
1' -6
" M
IN
PROTRUSION LIMITS -
PLAN
G R
EA
TE
R T
H
AN
'-3
4" MAX.
PROTRUSION LIMITS -
SECTION
EQ
U
AL
T
O
'-3
LE
SS
T H
AN
O
R
NO LIMITS
CHANGES IN LEVEL
1/ 2"
M
AX
1/
4" M
AX
HDCP ACCESSIBLE AND STANDARD DIMENSIONS
ABBREVIATONS (ARCHITECTURAL ONLY) HDCP ACCESSIBILITY GENERAL NOTES
1. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN THE
ARCHITECTURAL DRAWINGS AND THE INFORMATION GIVEN ON THIS
SHEET.
2. DO NOT SCALE THESE DRAWINGS.
3. DIMENSIONS INDICATED ARE THE MINIMUM CLEAR DIMENSIONS
REQUIRED BY THE UNIFORM FEDERAL ACCESSIBILITY STANDARDS
(UFAS) AND THE BARRIER FREE DESIGN GUIDE SUPPLEMENT BY THE
DEPARTMENT OF THE VA. THE CONTRACTOR IS RESPONSIBLE FOR
LAYOUT OF BUILDING ELEMENTS TO ASSURE THAT DIMENSIONS SHOWN
ARE PROVIDED.
4. NOT ALL CONDITIONS SHOWN ON THIS SHEET MAY BE REQUIRED BY
THIS PROJECT. COMPARE THE REQUIREMENTS OF THE ARCHITECTURAL
DRAWINGS WITH THIS SHEET FOR RELEVANCE OF INFORMATION.
5. REFERENCE ACCESSIBLE DIMENSIONS LEGEND FOR ACCESIBLE
MOUNTING HEIGHTS OF ALL FIXTURES & ACCESSORIES LOCATED
THROUGHOUT CONTRACT DOCUMENTS.
6. DIMENSIONS SHOWN ON INTERIOR ELEVATIONS AT WALLS ARE TO THE
FINISHED SURFACE.
7. HANDICAP ACCESSIBLE SHOWERS ARE TO BE RECESSED INTO
CONCRETE AT TRANSFER SHOWERS, WRAP AS REQUIRED TO HAVE NO
MORE THAN 1/2" LIP AT EDGE OF SHOWER ENTRY (NO LIP AT ROLL-IN
SHOWERS)
8. ALL EXPOSED PIPE UNDER SINKS ARE TO BE WRAPPED OR
PROTECTED
CLEAR FLOOR SPACE
FOR WHEELCHAIR
TURNING SPACE
REQUIREMENT
2'-6"
4' -0
"(VA REQ'D)
5'-6" MIN.
MANEUVERING CLEARANCES AT ALCOVES
2' -6
4'-0" 1'-0"
2' -6
4'-0"
1' -3
" M
AX
4' -0
2'-6"
2' -0
" M
AX
4' -0
2'-6" 1'-0"
1/ 2"
M
AX
CARPET PILE THICKNESS
VA REQ'D: CARPET
CUSHION NOT
PERMITTED
(VA REQ'D)
3'-10" MIN.
WIDE DOOR
PATIENT DOORS ONLY
(VA REQ'D)
5'-0" MIN.
(VA REQ'D)
2'-10" MIN.
2' -0
MAX. DOORWAY DEPTH
(VA REQ'D)
2'-10"
CLEAR
1'-6" MIN.5'
-0
" M
IN
2' -0
" M
IN
1'-0"
IF CLOSER
AND
LATCH
Y
X
NOTE:
X = 36" MIN.
IF Y = 60";
X = 42" MIN.
IF Y = 54"
5'-6"
3' -6
NOTE: 48" IF
DOOR HAS
BOTH LATCH
AND CLOSER
X: 24" MIN.
Y : 4
8" M
IN
NOTE:
Y = 54" MIN.
IF DOOR
HAS CLOSER
" M
IN
2'-0"
NOTE: Y = 48" MIN.
IF DOOR HAS A
CLOSER
MIN. OPENING WIDTH
4'-0"
4'-0"
MINIMUM PASSAGE WIDTH
(VA REQ'D)
5'-0" MIN.
CENTERED ON LOW
4'-0" MIN.
2' -6
" M
IN
HIGH
LOW
2'-0" MAX.
RECESS DEPTH
NOT TO EXCEED
FOUNTAIN DEPTH
C
EN
TE
R
ED
O
N L
O W
4' -0
" M
IN
2'-6" MIN.
17" - 19"
CLEAR FLOOR AREA
HIGH
LOW
RECESSED PLAN SURFACE PLAN
17" - 19"
SPOUT OUTLET
9" M
IN
2' -3
" M
IN
3' -0
" M
AX
6" MAX.8" MIN.
SKIRT REQ'D BELOW IF MTD ALONG PATH OF TRAVEL
SIDE ELEVATION
EQUIPMENT
ALLOWED
IN SHADED
AREA
ELECTRIC WATER COOLER STANDARDS
3' -9
" M
AX
9" M
IN
1'-9" MAX.
HIGH AND LOW REACH
(ADJUSTABLE SHELVES)
MAXIMUM SIDE REACH
OVER AN OBSTRUCTION
2'-6" MIN. 2'-0" MAX.
2' -1
0" M
IN
TO
P
O F
R
EA
C H
3' -1
0" M
AX
ADJUSTABLE
SHELVES
X: 4'-0" MAX.
Y : 4
'-0 " M
AX
1' -3
" M
IN
FORWARD REACH
2'-1" MAX.
R
EA
C H
'-8
3' -8
4'
-0 " F
O R
H O
R
IZ
O N
TA
L
MAXIMUM FRONT
REACH OVER AN
OBSTRUCTION
DOORWAY CLEARANCES: NOTE: PATIENT BEDROOM DOORS AT LEAST 44" WIDE ARE EXEMPT
FROM THE REQUIREMENTS FOR SPACE OF THE LATCH SIDE OF THE DOOR
OF URINAL RIM
DEPTH 2'-0" MAX.
MIN. TO FRONT
X
HAND-HELD
SHOWER
HEAD
8' -0
SECONDARY SHOWER HEAD & SLIDE
BAR (WHERE INDICATED)
EQ
EQ
1 1/2".
4' -0
VA
R
EQ
'T
1'-0" MIN.
EXPOSED PUPES TO BE WRAPPED
W/ INSULATION OR HAVE
PROTECTIVE ENCLOSURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI101
ACCESSIBILITY STANDARDS RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024Revisions: Date:
S S S S S
LIFE SAFETY SYMBOLS
XX PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES
REFER TO SCHEDULE)
REFER TO ELECTRICAL DRAWINGS FOR EXIT
LIGHTING, ILLUMINATION OF EXIT LIGHTING
INDICATED FOR REFERENCE
FIRE EXTINGUISHER CABINET
HANGING FIRE EXTINGUISHERS
EXIT DISCHARGE
FEC
FE
LIFE SAFETY PLANS GENERAL NOTES
A. ALL PENETRATIONS MADE THROUGH RATED WALLS SHALL BE CONSTRUCTED
AND SEALED AS REQUIRED TO MAINTAIN THE REQUIRED WALL RATING.
B. REFER TO PROJECT SPECIFICATION SHEETS FOR ADDITIONAL
REQUIREMENTS.
ONE HOUR FIRE RATED PARTITION
TWO HOUR FIRE RATED PARTITION
ONE HOUR FIRE/SMOKE RATED PARTITION
NO ANTICIPATED WORK IN THIS AREA EXCEPT
AS REQUIRED BY THAT IN ADJACENT AREAS.
AREA TO REMAIN IN OPERATION
THROUGHOUT PROJECT DURATION.
CODE INFORMATION
BUILDING: 2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
ACCESSIBILITY: ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
FIRE: 2021 INTERNATIONAL FIRE CODE
NFPA 101 LIFE SAFETY CODE 2024
PLUMBING: 2021 INTERNATIONAL PLUMBING CODE
MECHANICAL: 2021 INTERNATIONAL MECHANICAL CODE
ELECTRICAL: 2023 NATIONAL ELECTRICAL CODE
ENERGY: 2021 INTERNATIONAL ENERGY CODE
2022 ASHRAE 90.1
OCCUPANCY CLASSIFICATIONS
INDUSTRIAL OCCUPANCY (NFPA 101 LIFE SAFETY CODE 2021 6.1.12)
MIXED OCCUPANCY (NON-SEPERATED) OF LOW-HAZARD FACTORY INDUSTRIAL (F-2) AND
LOW-HAZARD STORAGE (S-2) (2021 INTERNATIONAL BUILDING CODE 508.2.3)
CONSTRUCTION TYPE
PROJECT AREA
5,115 SF
TYPE V - B
PROJECT TYPE
ALTERATIONS (2021 INTERNATIONAL ENERGY CONSERVATION CODE - SECTION C503, C503.1 - C503.2) ALTERATIONS - LEVEL 3 (2021 INTERNATIONAL EXISTING BUILDING CODE CHAPTER 9, 907.1)
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE 2024
SEPERATION & RATED WALL
WHERE TWO STORIES OR LESS IN HEIGHT AND THE TOTAL BUILDING SQUARE FOOTAGE IS LESS THAN 10,000 SQFT, NO SEPARATION IS REQUIRED. (2024 NFPA 6.1.14.1.4 SEPARATED OCCUPANCIES)
NO SEPARATION REQUIREMENT (2021 INTERNATIONAL BUILDING CODE, TABLE 508..4)
NO SPRINKLER REQUIREMENT (2024 NFPA 40.3.5 EXTINGUISHMENT REQUIREMENTS)
FIRE SPRINKLER IS NOT REQUIRED (2021 INTERNATIONAL BUILDING CODE, 506.1 & 506.2 WITH TABLE 506.2)
AUTOMATIC SPRINKLERS
870 SF
LARGE AC /
REFRIGERATION
EQUIPMENT
REPAIR
507 SF
WORK SHOP
499 SF
AC FILTER
STORAGE
507 SF
PARTS STORAGE
673 SF
AC WORK SPACE
476 SF
CORRIDOR
343 SF
BREAKROOM
NOT IN SCOPE
DOCKDOCK
92 SF
IDF
344 SF
PLUMBING SHOP
OFFICE
72 SF
CORRIDOR
58 SF
RESTROOM
29 SF
HAC
60 SF
RESTROOM
28 SF
SHOWER
EXIT #2 EXIT #3
EXIT #1
1A
1B
1C
1D
1E
PLUMBING SHOP / STORAGE
FE
FE
FE
FUNCTION OF SPACE LEGEND
INDUSTRIAL
STORAGE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI103
LIFE SAFETY PLAN RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024
3/16" = 1'-0"
LIFE SAFETY PLAN
ACTUAL NORTH
N N
PLAN NORTH
OCCUPANT LOAD - LEVEL 1
Function of Space Area Occupant Load Factor Occupant Load
INDUSTRIAL 3,553 SF 100 41
STORAGE 1,006 SF 500 3
Total Capacity 4,559 SF 44
TRAVEL DISTANCE SCHEDULE - LEVLE 1
TRAVEL PATH DISTANCE
1A 47'
1B 44'
1C 43'
1D 58'
1E 74'
39 OCCUPANTS X 0.2" PER OCCUPANT = 7.8" REQUIRED
(3) X 44" DOOR = 132" PROVIDED
BUILDING EGRESS DOORS
EXIT DOOR TYPE Egress Width Provided
EXIT #1 44"
EXIT #2 44"
EXIT #3 44"
TOTAL 132"
STORAGE 2
BG24
STORAGE 3
BG25
STORAGE 4
BG26
STORAGE 1
BG27
SHOP
BG28
LOCKER
BG29
RESTROOM
BG30
LOADING DOCK 2
BG31
LOADING DOCK 1
BG32
STORAGE 5
BG33
STORGE 6
BG34
STORAGE 6A
BG35
HALLWAY
BG36
PLUMBING SHOP
/ STORAGE
BG38
EXT 01
EXT 02 EXT 03
EXT 04
EXT 05
EXT 06
EXT 07
EXT 08
EXT 09
EXT 10
EXT 11
A/C STEAM VAULT
EXT 01 EXT 02 EXT 03 EXT 04
EXT 05
EXT 06
EXT 07EXT 08
EXT 09
EXT 10
EXT 11
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI201
EXISTING PHOTO - EXTERIOR RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024
1/8" = 1'-0"
FLOOR PLAN - EXISTING (W/ EXTERIOR PHOTOS)
NN
ACTUAL NORTH PLAN NORTH
STORAGE 3
BG25
STORAGE 4
BG26
STORAGE 1
BG27
SHOP
BG28
LOCKER
BG29
RESTROOM
BG30
LOADING DOCK 2
BG31
LOADING DOCK 1
BG32
STORAGE 5
BG33
STORGE 6
BG34
STORAGE 6A
BG35
HALLWAY
BG36
PLUMBING SHOP
/ STORAGE
BG38
INT 04
INT 01
INT 03
INT 07
INT 13
INT 014
INT 11
INT 02
INT 05
INT 06
INT 09
INT 08
INT 12
INT 10
INT 01 INT 02
INT 03
INT 12
INT 06INT 07 INT 09
INT 10
INT 14
INT 03
INT 04 INT 05
INT 08
INT 11
INT 13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI202
EXISTING PHOTO - INTERIOR RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024
1/8" = 1'-0"
FLOOR PLAN - EXISTING (W/ INTERIOR PHOTOS)
NN
STORAGE 3
BG25
STORAGE 4
BG26
STORAGE 1
BG27
SHOP
BG28
LOCKER
BG29
RESTROOM
BG30
LOADING DOCK 2
BG31
LOADING DOCK 1
BG32
STORAGE 5
BG33
STORGE 6
BG34
STORAGE 6A
BG35
HALLWAY
BG36
PLUMBING SHOP
/ STORAGE
BG38
MEPS 02
MEPS 03
MEPS 04
MEPS 05
MEPS 01
MEPS 08
MEPS 06
MEPS 07
MEPS 09
MEPS 02 MEPS 02
MEPS 03
MEPS 04 MEPS 05
MEPS 01 MEPS 01
MEPS 07
MEPS 06MEPS 06MEPS 06
MEPS 08 MEPS 09
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVAL OFFICIAL:
COR, Mr. TYRONE BENNETT
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
O'Brien Engineering, Inc., Managing Partner
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
OEI - LBL Joint Venture LLC O'Brien Engineering, Inc., Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
GI203
EXISTING PHOTO - MEP+S RENOVATE BLDG. 62 - AC SHOP
TEMPLE, TX
674-21-252
06/26/2024 JOW CH
ISSUE FOR BID
06/26/2024
1/8" = 1'-0"
FLOOR PLAN - EXISTING (W/ MECH. / ELEC. PHOTOS)
NN
NOT IN SCOPE
2X
R O
O F
JO
IS
TS
(J
3)
4"
O .C
A
B O
V E
D E
C K
(2 ) 2
X
R
ID
G E
W
X
S
TEEL B
EAM
W
12 X 14 STEEL BEAM
W
12 X 14 STEEL BEAM W
X
S
TEEL B
EAM
2X
R O
O F
JO
IS
TS
(J
1)
4"
O .C
A
B O
V E
B U
IL
D
IN
G
TY
P
2X
R O
O F
JO
IS
TS
(1
4" O
.C
A B
O V
E B
U
IL
D
IN
G
TY
P
2X12 ROOF JOISTS (J1) @ 24" O.C.
ABOVE BUILDING - TYP.
2X12 ROOF JOISTS (J1) @ 24" O.C.
ABOVE BUILDING - TYP.
2X
R O
O F
JO
IS
TS
(J
3)
4"
O .C
A
B O
V E
D E
C K
(3 ) 2
X
W
2)
/2
P
LY
W O
O D
S A
N W
IC
H
E D
B E
TW
E
E N
(3 ) 2
X
W
2)
/2
P
LY
W O
O D
S A
N W
IC
H
E D
B E
TW
E
E N
(3) 2X12 W/ (2) 1/2" PLYWOOD
SANWICHED BETWEEN
2X12 ROOF JOISTS (J1)
@ 24" O.C.
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2J2
J2
J2
J2J2
J2
J2
J2
J2
J2
J2
J2
J2
J2 J2
J2 J2
S200
S200
S200
S200
(4 ) 2
X
B O
LT
TO
G
E
TH
E R
(B 3)
B1
B1
B1
B1
B2
B1
B2
B1
S200
SIM
S200
SIM
S200
SIM
J2 J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
J2
TYP.
S200
SIM
DOUBLE ROOF JOISTS AT
MECH. DUCT UP TO ROOF
TO AVOID CONFLICTIONS
DOUBLE ROOF JOISTS AT
MECH. DUCT UP TO ROOF
TO AVOID CONFLICTIONS
DOUBLE ROOF JOISTS
AT SKYLIGHT
DOUBLE ROOF JOISTS
AT SKYLIGHT
DOUBLE ROOF JOISTS
AT SKYLIGHT
D O
U B
LE
R
O O
F
JO
IS
TS
A
T S
K Y
LI
G
H T
DOUBLE ROOF JOISTS
AT SKYLIGHT
(4 ) 2
X
B
LT
TO
G
E
TH
E R
(B 3)
S200
SIM
S200
SIM
S200
SIM
S200
S200
OH
T.O.BEAM
13'-5 1/4"
T.O.BEAM
13'-5 1/4"
I. GENERAL
1. PRIOR TO CONSTRUCTION, VERIFY STRUCTURAL ELEVATIONS AND DIMENSIONS WITH OTHER PROJECT DRAWINGS AND COORDINATE
LOCATION OF OPENINGS AND SLEEVES THROUGH THE STRUCTURE, SLAB DEPRESSIONS, FLOOR DRAINS, INSERTS, AND OTHER RELATED
ITEMS.
2. FRAME FOR OPENINGS THROUGH FLOORS, ROOFS, AND WALLS AS PER DETAILS. DO NOT INTERRUPT FRAMING MEMBERS FOR OPENINGS
EXCEPT WHERE SO INDICATED ON DRAWINGS.
3. VERIFY ALL DIMENSIONS IN FIELD BEFORE STARTING THE WORK.
4. BEFORE BEGINNING CONSTRUCTION, NOTIFY ENGINEER OF ANY DISCREPANCIES OR CONFLICTS FOUND IN DRAWINGS AND/OR FIELD
DIMENSIONS.
5. EXISTING STRUCTURES ARE SHOWN ON DRAWINGS FOR CLARITY ONLY. VERIFY ALL DIMENSIONS, ELEVATIONS AND TYPE OF
CONSTRUCTION OF THOSE STRUCTURES AND NOTIFY ENGINEER BEFORE BEGINNING NEW CONSTRUCTION OF ANY INTERFERENCES
AND/OR DISCREPANCIES THAT MIGHT EXIST.
6. CONSTRUCT PROJECT TO COMPLY WITH INTERNATIONAL BUILDING CODE CURERENT EDITION.
II. DESIGN CRITERIA FOR PRIMARY STRUCTURAL SYSTEM
1. THE STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.
2. DESIGN LOADS:
ROOF ......................................................... 20 PSF
INSULATION .............................................. 4 PSF
TWO LAYERS OF PLYWOOD ................... 4 PSF
ROOFING ................................................... 3 PSF
FUTURE CEILING AND MEP ..................... 7 PSF
III. SCOPE
1. THESE DRAWINGS ARE ISSUED TO INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF THE STRUCTURAL DESIGN CONCEPT
FOR THE TIMBER & STRUCTURAL STEEL PORTIONS OF THE ROOF FRAMING. CURTAIN WALL DESIGN & CONSULTING SCOPE OF DESIGN
SRVICES IS STRICTLY LIMITED TO NEW ROOF CONSTRUCTION FOR GRAVITY LOADS ONLY.
2. CONTRACTS, IF LET ON THE BASIS OF SUCH DOCUMENTS, MUST BE WITH THE UNDERSTANDING THAT THE CONTRACTOR IS TO FURNISH ALL ITEMS REQUIRED FOR PROPER COMPLETION OF THE WORK WITHOUT ADJUSTMENT TO THE CONTRACT PRICE. IT IS INTENDED THAT THE WORK BE OF SOUND AND QUALITY CONSTRUCTION AND THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE INCLUSION OF ADEQUATE AMOUNTS TO COVER INSTALLATION OF ALL ITEMS INDICATED, DESCRIBED OR IMPLIED, TO PERFORM THE INTENDED FUNDS
SPECIFIED ON THE ARCHITECTURAL DRAWINGS.
IV. SUBMITTALS
1. REVIEW OF SUBMITTAL INFORMATION SHALL BE FOR GENERAL REQUIREMENTS OF PROJECT AND SHALL NOT INCLUDE CHECKING OF
DETAILED DIMENSIONS OR DETAILED QUANTITIES NOR REVIEW OF THE CONTRACTOR’S SAFETY MEASURES IN, ON, OR NEAR THE WORK
SITE OR MEANS AND METHODS OF DOING WORK.
2. CONTRACTOR SHALL SUBMIT THE FOLLOWING:
• CONFIRMATION FOUNDATION UNDER BERAING WALL WHERE W12X14 INTERSECTS CLAY TILE WALL.
• SUBMIT A WALL BRACING PLAN, SEALED BY A PROFESSIONAL ENGINEER FOR PERIOD BETWEEN EXISTING ROOF REMOVAL AND
NEW ROOF.
• TIMBER SPECIFICATIONS AND DESIGN STRENGTH
• SIMPSON METAL CONNECTORS
3. CONTRACTOR SHALL CHECK ALL SHOP DRAWING SUBMITTALS FOR COMPLIANCE WITH CONTRACT DOCUMENTS.
4. CONTRACTOR SHALL INDICATE CHECKING AND APPROVAL OF SHOP DRAWINGS BY AFFIXING HIS SHOP DRAWING STAMP WITH THE DATE
OF APPROVAL AND NAME OF PERSON APPROVING SHOP DRAWINGS.
5. CONSTRUCTION SCHEDULE SHALL ALLOW 2 WEEKS FOR SHOP DRAWING REVIEW AND RETURN BY THE STRUCTURAL ENGINEER. REVIEW
BY THE DESIGN TEAM SHALL BE FOR GENERAL COMPLIANCE WITH THE COMPLIANCE WITH THE CONTRACT DOCUMENTS.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL QUANTITIES, DIMENSIONS, CONSTRUCTION MEANS, METHODS, AND JOB SITE SAFETY.
7. ACTIONS TAKEN ON THE SHOP DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY OF COMPLIANCE WITH
CONTRACT DOCUMENTS.
V. REINFORCED CONCRETE SUPPORTING ROOF STRUCTURE
1. CONSTRUCT ALL REINFORCED CONCRETE TO COMPLY WITH RECOMMENDATIONS OF ACI 318 AND ACI 301 UNLESS OTHERWISE NOTED OR
SPECIFIED.
2. DETAIL, FABRICATE AND PLACE ALL REINFORCING STEEL TO COMPLY WITH RECOMMENDATIONS OF ACI “MANUAL OF STANDARD PRACTICE
FOR DETAILING REINFORCED CONCRETE STRUCTURES” (ACI 315).
3. SHOW LOCATION OF ALL REQUIRED AND ADDITIONAL PROPOSED CONSTRUCTION JOINTS AND ADDITIONAL REINFORCING STEEL
REQUIRED THEREIN ON REINFORCING STEEL SHOP DRAWINGS.
4. CONCRETE SHALL CONFIRM TO THE FOLLOWING REQUIREMENTS:
LOCATION SLUMP TYPE MIN. 28-DAY COMPRESSIVE STRENGTH (PSI) MIN. CEMENT CONTENT
FOOTINGS 5" - 7" NW 3000 5 SACKS
5. INCLUDE AIR ENTRAINING ADMIXTURE AND WATER REDUCING ADMIXTURE IN ALL CONCRETE MIXES EXCEPT IN FOOTINGS AND
FOUNDATION PIERS.
6. CONCRETE THAT WILL BE EXPOSED TO WEATHER SHALL HAVE WATER CONTENT LIMITED TO A MAXIMUM OF SIX (6) GALLONS PER SACK OF
CEMENT.
7. REINFORCING BARS SHALL HAVE MINIMUM YIELD STRENGTH INDICATED BELOW AND SHALL COMPLY WITH ASTM A615 STANDARD AND
SHALL BE GRADE INDICATED BELOW:
ITEM GRADE YIELD STRENGTH
ALL REINFORCING U.O.N. ASTM-A615 GRADE 60 60000
8. USE WELDABLE ASTM A706 - GRADE 60 FOR ALL BARS THAT WILL BE WELDED (AWS D1.4).
9. BARS, OTHER THAN GRADE 40, SHALL BE MILL MARKED SO THAT TYPE, GRADE AND YIELD STRENGTH ARE VISIBLY IDENTIFIABLE.
10. UNLESS OTHERWISE NOTED, ALL INTERIOR SLABS SHALL BE 5” THICK REINFORCED WITH #3 @ 12” CONTINUOUS BOTH WAYS. SUPPORT
BARS TO A POSITION 2” CLEAR BELOW TOP OF SLAB.
11. REINFORCING BARS NOTED “CONT.” SHALL LAP 50 BAR DIAMETERS AT SPLICES AND SHALL HAVE MATCHING CORNER BARS. TOP BARS
NOTED “CONT.” IN BEAMS MAY BE SPLICED AT MID-SPAN ONLY. BOT BARS NOTED “CONT.” IN BEAMS MAY BE SPLICED AT SUPPORTS ONLY.
12. PROVIDE CORNER BARS AS PER TYPICAL DETAIL AT CORNERS AND INTERSECTIONS OF ALL GRADE BEAMS AND WALLS.
13. PROVIDE CONCRETE COVERAGE FOR REINFORCING STEEL AS FOLLOWS UNLESS OTHERWISE SHOWN:
FOOTINGS ......................................................... 3" CLEAR
SLABS-ON-GRADE AT TOP SURFACE ........... 2" CLEAR
14. SET ANCHOR BOLTS TO HAVE AT LEAST 3” CONCRETE COVER AND TO ALLOW REINFORCEMENT TO PASS OUTSIDE OF BOLTS.
15. DETAILING AND INSTALLATION OF REINFORCING BARS AND ACCESSORIES SHALL BE IN ACCORDANCE WITH RECOMMENDATIONS OF ACI
315.
16. WHEN CONCRETE WALLS SPAN VERTICALLY TO RETAIN EARTH BELOW GRADE, CONSTRUCT FLOORS AT TOP AND BOTTOM OF SUCH
WALLS BEFORE BACKFILL IS PLACED.
17. PROVIDE AND INSTALL REINFORCING BAR ACCESSORIES IN ACCORDANCE WITH ACI SP66 RECOMMENDATIONS.
18. SECURE APPROVAL OF ENGINEER FOR LOCATION OF ALL CONSTRUCTION JOINTS NOT SHOWN ON DRAWINGS FOR SPACING, ACCESSIBILITY, AND SHOULD ANY CONFLICTS OCCUR, NOTIFY ENGINEER PRIOR TO FABRICATION AND/OR CONSTRUCTION.
VI. STRUCTURAL STEEL
1. DETAIL, FABRICATE AND ERECT ALL STRUCTURAL STEEL IN ACCORDANCE WITH LATEST AISC "SPECIFICATION FOR DESIGN, FABRICATION
AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS".
2. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:
a. EXCEPT WHERE OTHERWISE NOTED, ALL CHANNELS, ANGLES, M & S SHAPES SHALL HAVE A MINIMUM YIELD STRENGTH OF 36 KSI
AND SHALL CONFORM TO ASTM A36.
b. STRUCTURAL STEEL FOR W & WT SHAPES SHALL BE GRADE 50 STEEL WITH A MINIMUM YIELD STRENGTH OF 50 KSI AND
CONFORMS TO ASTM A572 OR ASTM A588.
c. PLATES SHALL BE ASTM A36 EXCEPT PLATES USED IN MOMENT CONNECTIONS AND AS STIFFENERS SHALL BE THE SAME MATERIAL
AND GRADE AS THE MEMBERS CONNECTED TO THE PLATES.
d. ALL STRUCTURAL STEEL PIPE SHALL CONFORM TO ASTM A-501 OR A-53.
e. ALL STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A-500, GRADE B.
f. ANCHOR RODS (ANCHOR BOLTS) SHALL BE GRADE 36, ASTM A-307, UNLESS INDICATED OTHERWISE.
g. ALL FIELD-BOLTED CONNECTIONS SHALL BE MADE WITH H. T. BOLTS. H. T. BOLTS SHALL CONFORM TO ASTM A315 OR ASTM A490
AND SHALL BE DESIGNED TO INDICATE WHEN THEY HAVE BEEN TIGHTENED TO THE REQUIRED BOLT TENSION. (BOLTS SHALL BE
LOAD INDICATOR BOLT [LIB]). ONLY ONE TYPE PERMITTED IN A CONNECTION.
h. TEMPORARY ERECTION BOLTS SHALL CONFORM TO ASTM A307.
3. PERFORM WELDING WITH E70 XX ELECTRODE.
4. MAINTAIN STRUCTURAL STABILITY DURING ERECTION BY INSTALLATION OF TEMPORARY VERTICAL AND HORIZONTAL BRACING IN ALL
STORIES ABOVE COMPLETED FLOOR SLABS AND PERMANENT VERTICAL BRACING. LIMIT TEMPORARY BRACING TO TWO STORIES UNLESS
OTHERWISE APPROVED BY THE ENGINEER.
ROOF FRAMING GENERAL NOTES:
ROOF FRAMING PLAN LEGEND
2 X 12 ROOF JOIST (J1) W12 X 14 STEEL BEAM (B1 & B2)
2 X WOOD BLOCKING
VII. MASONRY
1. WORK THIS SECTION IN CONJUNCTION WITH THE MASONRY SECTION OF THE SPECIFICATIONS.
2. CONCRETE MASONRY UNITS:
a. HOLLOW LOAD BEARING CONCRETE MASONRY UNITS SHALL BE GRADE N-1 LIGHT-WEIGHT CONCRETE BLOCK CONFORMING TO
ASTM C-90.
b. MASONRY UNITS SHALL HAVE CURED FOR NOT LESS THAN 28 DAYS WHEN PLACED IN THE STRUCTURE.
c. F1M – 1350 PSI.
3. CEMENT FOR MORTAR AND GROUT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C-150.
4. MORTAR, TYPE “S”, FOR REINFORCED MASONRY SHALL CONFORM TO ASTM C-270-86B.
5. QUICK LIME SHALL CONFORM TO ASTM C-5; HYDRATED LIME SHALL CONFORM TO ASTM C-207.
6. SUBMIT ALL MIX DESIGNS FOR MORTAR AND GROUT TO THE ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION. ALSO SEE NOTE NO.
15.
7. ALL WALLS SHALL BE LAID UP IN STRAIGHT UNIFORM COURSES WITH REGULAR RUNNING BOND.
8. ADMIXTURES:
a. THE USE OF ADMIXTURES SHALL NOT BE PERMITTED IN MORTAR OR GROUT UNLESS APPROVED BY THE ENGINEER.
b. ANTI-FREEZE COMPOUNDS SHALL NOT BE USED IN MORTAR OR GROUT.
9. CELLS CONTAINING REINFORCEMENT SHALL BE SOLIDLY FILLED WITH GROUT AND POURS SHALL BE STOPPED 1 ½” FROM THE TOP OF A
COURSE TO FORM A KEY AT POUR JOINTS.
10. ALL BOLTS, ANCHORS, ETC. IN THE WALL SHALL BE ACCURATELY SET AND SOLID GROUTED WITH GROUT OR MORTAR.
11. THE STARTING JOINT OF MASONRY WALLS SHALL BE LAID WITH FULL MORTAR COVERAGE ON THE JOINT.
12. ALL MASONRY DESIGN AND CONSTRUCTION TO BE IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, 2021 EDITION.
13. AT LEAST 16 HOURS SHOULD ELAPSE AFTER COMPLETING CONSTRUCTION OF MASONRY WALLS BEFORE THE APPLICATION OF
UNIFORMLY DISTRIBUTED LOADS.
14. NO GROUT LIFT IS TO EXCEED FOUR (4) FEET WITHOUT CLEAN-OUT HOLES, MAXIMUM HEIGHT OF GROUT LIFT IS TO BE EIGHT (8) FEET.
15. GROUT MIX HALL BE ONE PART CEMENT, THREE PARTS SAND, TWO PARTS PEA GRAVEL AND ON-TENTH PART LIME. ADD SUFFICIENT
WATER TO PROVIDE CONSISTENCY WITHOUT CAUSING SEGREGATION. MINIMUM COMPRESSIVE STRENGTH OF GROUT SHALL BE 3,000 PSI.
16. MORTAR SHALL CONSIST OF ONE PART CEMENT TO THREE PARTS SAND AND ON-HALF PART HYDRATED LIME OR LIME PUTTY. MINIMUM
COMPRESSIVE STRENGTH OF MORTAR SHALL BE 2,500 PSI.
17. REINFORCING STEEL (MATERIAL):
a. ENFORCING BARS SHALL BE IN ACCORDANCE WITH ASTM A-615, GRADE 60.
b. REINFORCING STEEL SHALL BE SPLICED AS SHOWN ON THE DRAWINGS.
c. PRE-FABRICATED JOINT REINFORCEMENT SHALL CONFORM TO ASTM REQUIREMENTS.
18. MASONRY UNITS:
a. MASONRY UNITS SHALL BE SOUND, DRY, CLEAN, AND FREE FROM CRACKS WHEN PLACED IN THE STRUCTURE.
b. ALL MASONRY UNITS SHOULD BE STORED ON THE JOB SO THAT THEY ARE KEPT OFF THE GROUND AND PROTECTED FROM RAIN.
c. MASONRY UNITS SHOULD NOT BE WETTED BEFORE LAYING IN THE WALLS. FURTHERMORE, THE WALL SHOULD NOT BE
SATURATED WITH WATER FOR CURING OR ANY OTHER PURPOSE.
19. MORTAR AND GROUT:
a. MORTAR OR GROUT WHICH IS UNUSED AFTER ONE (1) HOUR AFTER THE INITIAL MIXING SHOULD BE DISCARDED.
b. ALL INGREDIENTS ARE TO BE MIXED IN A BATCH MIXER FOR NOT LESS THAN THREE (3) MINUTES.
c. THE CONSISTENCY OF MORTAR SHOULD BE ADJUSTED TO MAINTAIN HIGH PLASTICITY. IF THE MORTAR BEGINS TO STIFFEN, IT
SHOULD BE RESTORED TO WORKABLE CONSISTENCY BY ADDING WATER AND THOROUGHLY REMIXING.
d. ALL MORTAR “FINS”, “DROPPINGS” AND FOREIGN MATTER SHOULD BE REMOVED BEFORE PLACING GROUT.
e. ALL MASONRY UNITS SHOULD BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL CONTINUITY OF THE CORES TO BE FILLED.
f. WHERE POUR HEIGHTS ARE IN EXCESS OF 4’, GROUT SHOULD BE POURED IN LIFTS OF 4’ MAXIMUM FOR THE COMPLETE LENGTH
OF THE CONTINUOUS WALL. ALLOW THIRTY (30) MINUTES FOR SETTLEMENT OF GROUT BEFORE POURING THE NEXT LIFT.
g. REINFORCING STEEL SHALL BE TIED IN PLACE AND INSPECTED BEFORE GROUTING STARTS.
h. GROUT SHALL BE RODDED OR PUDDLE DURING PLACEMENT TO ENSURE COMPLETE FILLING OF THE CORE.
i. GROUTING OF BEAMS OVER OPENING SHALL BE DONE IN ONE CONTINUOUS POUR.
j. THE TOPS AND / OR BOTTOMS OF UNFILLED CELLS SHALL BE COVERED WITH METAL LATH TO CONFINE GROUT FILL TO THE BOND
BEAM.
k. SPACES AROUND METAL DOOR FRAMES AND OTHER BUILT-IN ITEMS SHALL BE FILLED SOLIDLY WITH GROUT OR MORTAR.
20. REINFORCING STEEL (PLACING):
a. ALL REINFORCING STEEL SHALL BE WIRED TOGETHER AND LAPPED FIFTY (50) BAR DIAMETERS, UNLESS OTHERWISE NOTED ON
THE DRAWINGS.
b. VERTICAL BARS SHALL BE HELD IN POSITION AT TOP AND BOTTOM AND AT INTERVALS NOT EXCEEDING ONE HUNDRED NINETY-
TWO (192) DIAMETERS OF THE REINFORCEMENT.
c. HORIZONTAL REINFORCING BARS SHALL BE LAID ON THE WEBS OF THE UNITS IN CONTINUOUS MASONRY COURSES CONSISTING O
BOND BEAM AND SHALL BE SOLIDLY GROUTED IN PLACE.
d. VERTICAL REINFORCING STEEL SHALL HAVE A MINIMUM CLEARANCE OF ¼” FROM THE MASONRY AND NOT LESS THAN ONE (1) BAR
DIAMETER BETWEEN BARS.
e. DOWELS SHALL NOT BE SLOPED MORE THAN ONE (1) HORIZONTAL IN SIX (6) VERTICAL.
21. JOINTS:
a. BED JOINT: THE STARTING JOINT SHALL BE LAID WITH FULL MORTAR COVERAGE ON THE BED JOINT, EXCEPT THAT MORTAR
“DROPPINGS” SHALL NOT PROTRUDE MORE THAN 3/8” INTO THE GROUT SPACE.
b. HEAD JOINT: ALL HEAD JOINTS SHALL BE FILLED SOLIDLY WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE WALL OF NOT
LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS.
c. INTERIOR CROSS JOINTS SURROUNDING CELLS WHICH ARE TO BE FILLED WITH GROUT SHOULD BE SOLIDLY FILLED WITH MORTAR.
d. JOINTS SHOULD BE TOOLED WITH A JOINTER COMPACTING THE MORTAR INTO THE JOINT AND AGAINST THE MASONRY UNIT WITH
FIRM PRESSURE.
22. CONSTRUCTION:
a. ALL MASONRY SHALL BE LAID TRUE, LEVEL AND PLUMB.
b. NO CONSTRUCTION SUPPORT SHALL BE ATTACHED TO THE WALLS, EXCEPT WHERE SPECIFICALLY PERMITTED BY THE ENGINEER.
c. BEFORE PLACING MASONRY, ALL FORMS AND EQUIPMENT SHALL BE CLEANED; ALL DEBRIS AND ICE SHALL BE REMOVED FROM
THE SPACES TO BE OCCUPIED BY THE MASONRY. ALL REINFORCING SHALL BE THOROUGHLY CLEANED OF ANY COATINGS.
23. FOR BONDING MASONRY TO CONCRETE BASE, THE TOP SURFACE OF THE CONCRETE SHALL BE CLEAN WITH LAITANCE REMOVED AND
AGGREGATE EXPOSED BEFORE STARTING MASONRY CONSTRUCTION.
24. NO PIPES OR CONDUIT SHALL BE EMBEDDED IN MASONRY WALLS, UNLESS AUTHORIZED BY THE ENGINEER.
VIII. WOOD FRAMING NOTES
1. EXCEPT AS NOTED DIMENSION LUMBER USED FOR STRUCTURAL FRAMING SHALL BE KILN DRIED, NO. 1 GRADE SOUTHERN PINE OR
DOUGLAS FIR WITH AN ALLOWABLE BENDING STRESS OF 1,800 PSI, MINIMUM; 90 PSI IN HORIZONTAL SHEAR; AND SHALL HAVE A MODULUS OF ELASTICITY OF 1,700,000 PSI AS DETERMINED BY AN APPROVED LUMBER GRADING AGENCY. THE 2X10 SPANNING 20 FEET SHALL BE KILN DRIED, STRUCTURAL SELECT NO. 1 GRADE SOUTHERN PINE OR DOUGLAS FIR WITH AN ALLOWABLE BENDING STRESS OF 2,200 PSI, MINIMUM; 90 PSI IN HORIZONTAL SHEAR; AND SHALL HAVE A MODULUS OF ELASTICITY OF 1,700,000 PSI AS DETERMINED BY AN APPROVED
LUMBER GRADING AGENCY.
POSTS AND/OR COLUMNS SHALL HAVE AN ALLOWABLE COMPRESSIVE STRESS PARALLEL TO GRAIN OF 1,650 PSI MINIMUM.
2. NON-STRUCTURAL DIMENSION LUMBER SHALL BE KILN DRIED, NO. 2 GRADE HEM-FIR OR BETTER WITH AN ALLOWABLE STRESS OF 1,000 PSI, MINIMUM; 75 PSI IN HORIZONTAL SHEAR; AND SHALL HAVE A MODULUS OF ELASTICITY OF 1,600,000 PSI AS DETERMINED BY AN
APPROVED LUMBER GRADING AGENCY.
3. NAILING OF FRAMING MEMBERS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE, U.N.O.
4. CONNECTORS FOR WOOD CONSTRUCTION SHALL BE “SIMPSON STRONG-TIE CONNECTORS” OR EQUAL. TYPE OF CONNECTORS AND
INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER, U.N.O.
5. MULTIPLE MEMBER WOOD BEAMS SHALL BE BOLTED TOGETHER WITH ONE ¾” DIAMETER BOLT TOP AND BOTTOM OVER ALL SUPPORTS
AND / OR AT ENDS OF BEAM IN ADDITION, PROVIDE ½” DIAMETER BOLTS AT 2’ – 0” ON CENTER STAGGERED (TOP AND BOTTOM) FULL
LENGTH OF BEAM.
6. MULTIPLE MEMBER WOOD COLUMNS SHALL BE BOLTED TOGETHER WITH TWO ¾” DIAMETER BOLTS TOP AND BOTTOM AND TWO ½”
DIAMETER BOLTS AT THIRD HEIGHT OF THE COLUMN, U.N.O.
7. PLYWOOD ROOF SHEATHING SHALL BE APA RATED SHEATHING EXPOSURE 1, 23/32” THICK, SPAN RATING 40/20. NAIL WITH 8d NAILS AT 4” O.
C. AT ALL EDGE SUPPORTS AND AT 12” O. C. AT ALL INTERMEDIATE SUPPORTS.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .