This file is a Performance Work Statement (PWS) for elevator maintenance and repair services at the U.S. Army DEVCOM Soldier Center in Natick, MA. The contractor must inspect, test, repair, and maintain all elevators and lifts at the facilities, including performing monthly preventive maintenance, annual inspections/testing, and emergency services. Key requirements include responding to routine service calls within one hour during regular working hours, providing 24/7 emergency services with a one-hour response time during business hours and 1.5-hour response time after hours, maintaining logbooks for each elevator, and ensuring elevators are not out of service for more than 24 hours without approval.
The PWS specifies that all work must be performed by Massachusetts-licensed elevator mechanics in accordance with ASME standards, NFPA codes, and state regulations. The contractor must obtain annual elevator certificates of operation, provide third-party certified inspections, and submit detailed service reports within 3 days of all maintenance work. The period of performance is up to 60 months including options. The contractor is responsible for all parts, supplies, cleaning materials, and waste removal. Emergency situations like trapped passengers or fire hazards require immediate response, and detailed documentation of all maintenance, repairs, and inspections must be maintained in logbooks stored in each elevator machine room.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Performance Work Statement
Facility Maintenance - Vertical Elevator Maintenance and Service
USAG-Natick November 2024
Table of Contents
| 1.0 | General Information | 1 |
| 1.1 | Overview | 1 |
| 1.1.1 Workload Requirement | 1 | |
| 1.1.3 Diagnosis and Analysis | 1 | |
| 1.2 | Components | 1 |
| 1.3 | Work Management and Control | 2 |
| 1.3.1 Reporting Requirements, | 2 | |
| 1.3.1.1 Service Plans | 2 | |
| 1.3.2 | Publications and Forms | 2 |
| 1.3.3 | Facilities Maintenance Instruction | 2 |
| 2.0 Description of Services | 2 | |
| 2.1 Facility Workload | 2 | |
| 2.2 Natural Gas Appliance and Equipment | 2 | |
| 2.3 Heating, Ventilation, and Air Conditioning (HVAC) | 2 | |
| 2.3.1 General. l | 2 | |
| 2.3.2 | Seasonal Changeover Requirements | 3 |
| 2.3.5 Related Components and Accessories | 3 | |
| 2.4 Eye Washes and Safety Showers | 3 | |
| 2.5 Roof Gutters, Drains, and Downspouts | 3 | |
| 2.6 Automatic Doors. | 3 | |
| 2.7 Overhead Doors | 3 | |
| 2.8 Gates, Fences, Barriers and Dock Levelers | 3 | |
| 2.9 Air Compressors/Unfired Pressure Vessels | 4 | |
| 2.10 Plumbing | 4 | |
| 2.10.1 Components | 4 | |
| 2.10.2 Leaks | 4 | |
| 2.10.3 Sump Pumps and Septic Tanks | 4 | |
| 2.10.4 Water Heaters | 4 | |
| 2.10.5 Backflow Preventors | 4 | |
| 2.10.6 Grease Traps. | 4 | |
| 2.10.7 | 4 | |
| 2.10.8 Wash Facilities/Racks | 4 | |
| 2.10.9 Oil Water Separators | 4 | |
| 2.11 Sanitary Wastewater Treatment and Collection System (Septic Tanks) | 4 | |
| 2.12 Industrial Wastewater Treatment Plant (IWTP) | 4 | |
| 2.12.1 Components | 4 | |
| 2.12.2 Compliance | 4 | |
| 2.12.3 Reporting Requirements | 4 | |
| 2.13 Heating/Cooling Plants | 4 | |
| 2.13.1 Central Boiler Plants. | 4 | |
| 2.13.2 | Maintenance of Heating Plants. | 4 |
| 2.13.3 Chiller Units. N/A | 4 | |
| 2.13.4 Air Handlers. N/A | 4 | |
| 2.13.5 Condensers. N/A | 4 | |
| 2.13.6 Cooling Towers. | 4 | |
| 2.13.7 Ventilation Systems. N/A | 4 | |
| 2.13.8 Fan Coil Units. N/A | 4 | |
| 2.13.9 HVAC Controls. N/A | 4 | |
| 2.13.10 | Scheduled System Outages. | 4 |
| 2.13.11 | N/A | 4 |
| 2.13.12 | Freeze Protection. | 5 |
| 2.14 | Winterization and De-Winterization (Mothballed Buildings) | 5 |
| 2.15 Reserved. | 6 | |
| 2.16 | Lift Stations | 6 |
| 2.17 | Sedimentation Tanks Maintenance | 6 |
| 2.18 | Electrical. | 6 |
| 2.18.1 | Emergency Fixtures | 6 |
| 2.19 Auxiliary Generators | 6 | |
| 2.19.1 Perform PM of Auxiliary Generators. | 6 | |
| 2.20 Grounding Points, Lightning Protection, and Cathodic Protection Maintenance | 6 | |
| 2.20.1 General | 6 | |
| 2.20.3 Grounding Protection System (GPS) | 6 | |
| 2.20.4 Lightning Protection System (LPS) | 6 | |
| 2.20.5 Cathodic Protection System (CPS) | 6 | |
| 2.20.6 N/A | 6 | |
| 2.21 Security Systems | 7 | |
| 2.22 Fire Alarm, Fire Suppression and building Mass Notification Systems | 7 | |
| 2.22.1 Fire Alarm Systems | 7 | |
| 2.22.2 | Sprinkler and Hood Suppression Systems | 7 |
| 2.23 Reserved | 6 | |
| 2.24 | PM for Barracks Buildings | 6 |
| 2.24.1 Unscheduled Tasks | 6 | |
| 2.24.2 Scheduled Tasks/Scheduled Inspections | 6 | |
| 2.25 | Elevator Maintenance. | 6 |
| 2.25.1 Elevator Inspection and Certification | 6 | |
| 2.25.2 | Out of Service Time | 7 |
| 2.25.3 | Preventive Maintenance Requirements and Scheduled Maintenance Requirements | 7 |
| 2.25.4 | Regular Cleaning. | 8 |
| 2.25.5 | Workmanship/Qualifications of Employees. | 8 |
| 2.25.6 | Unscheduled Service Calls. | 9 |
| 2.25.7 | Out of Service Time | 9 |
| 2.25.8 | Emergency Calls. | 9 |
| 2.25.9 | Schedules. | 9 |
| 2.25.10 | Service Reports. | 9 |
| 2.25.11 | Additional Provisions. | 9 |
| 2.25.12 | Calculation of Deductions. | 9 |
| 2.25.13 | Determination of Deduction Amounts. | 10 |
| 2.25.14 | Withholding Monies for Failure to Maintain and/or Provide Parts. | 10 |
| 2.25.15 | Removal of Elevator(s) from Service. | 10 |
| 2.25.16 | Withholding Monies for Equipment Outages. | 10 |
| 2.25.17 | Inspection and Acceptance. | 10 |
| 2.25.18 | Compliance. | 10 |
| 2.26 | Swimming Pools and Hot Tubs | 11 |
| 2.26.1 | Circulation, Heating, and Filtration Systems | 11 |
| 2.27 | Keys and Locks | 11 |
| 2.27.1 Key Control in Contractor Occupied Facilities | 11 | |
| 2.27.3 Lock Combinations | 11 | |
| 2.28 | Food Service Equipment (FSE) | 11 |
| 2.29 | Dining Facility (DFAC) Maintenance | 11 |
| 2.29.1 | General | 11 |
| 2.29.1.9 | Pest Control | 11 |
| 2.30 | Crane and Load Scales Maintenance and Load Testing. N/A | 12 |
| 2.30.1 | General | 12 |
| 2.30.2 | Preventive Maintenance Plan | 12 |
| 2.30.3 | Crane Operator Training | 12 |
| 2.30.4 | Load scales | 12 |
| 2.31 | Glass and Glazing | 12 |
| 3.0 | Work Capability Levels. N/A | 12 |
| 4.0 | Self-Help Program | 12 |
| 5.0 | Operation and Maintenance of Energy Conservation Systems N/A | 12 |
| 6.0 | Sign Shop Operations | 12 |
| 7.0 | Utility Systems | 12 |
| 8.0 | Uninterruptible Power Supply (UPS) Systems | 12 |
| 9.0 | Area Lighting | 12 |
| 10.0 | Utility Marking | 12 |
| 11.0 | Pumps and Pumping Stations | 12 |
| 12.0 | Natural Gas and Propane Distribution System | 12 |
| 13.0 | Propane Tanks and Distribution Systems | 12 |
| 14.0 | Water Distribution Systems | 12 |
| 15.0 | Storm Water Collection System | 12 |
| 16.0 | Preventive Maintenance of Storm Water Systems | 12 |
| 17.0 | Reporting Requirements of Storm Water Systems. | 12 |
| 18.0 | Training. N/A | 12 |
| 19.0 | Certification. N/A | 12 |
| 20.0 | Other Utility Systems. N/A | 12 |
| 21.0 | Fuel Storage and Distribution Systems | 12 |
| 22.0 | Fuel-Powered Pump Maintenance | 12 |
| 23.0 | Emergency/Backup Generators (not attached to building) | 12 |
| 25.0 | Water Standpipes | 13 |
| 26.0 | Other Sanitary Wastewater Collection Systems | 13 |
| 27.0 | Fire Loop System Hydrants | 13 |
| 28.0 | Training of Personnel N/A | 13 |
| 29.0 | Deliverables | 13 |
| 30.0 | Period of Performance | 13 |
| 31.0 | Place of Performance | 13 |
| 32.0 | Invoicing | 13 |
1.0 General Information.
1.1 Overview. The Contractor shall inspect, repair and maintain all existing buildings, structures, and their components listed in Facilities List (Technical Exhibit TE-01 Base Map and Elevator Inventory), Real Property per Category Code (CATCODE) Unit of Measure). The Contractor shall provide sustainment of vertical facilities such as buildings and all utilities plant structures within the five (5) foot demarcation line, excluding Army Family Housing.
1.1.1 Workload Requirement. The following paragraphs describe all facets involved in the management of building and structure maintenance; they include terms used to classify work; provide information on the level of effort that will be required at Natick Soldier Systems Center in terms of workload and trade distributions; and describe the way in which work will be received, managed, and documented. The Contractor is responsible for the maintenance and repair of all building elevators, lifts, and equipment rooms under this contract. This Contract shall provide the addition of new facilities and for removal of existing ones without having to issue a formal modification.
1.1.2 Installed Building Equipment (IBE). N/A
1.1.3 Diagnosis and Analysis. N/A
1.1.3.1. N/A
1.1.3.2 N/A
1.2 Components. The Contractor shall perform preventive maintenance (PM) and repairs. Facilities and components covered under this Common Level of Support (SERVICE) include, but are not limited to, the following:
a. Administrative Buildings
b. Training Facilities
c. Maintenance Shops
d. Warehouses
e. Medical Facilities and Clinics (alarm/fire systems)
f. Schools, Chapels, and Recreational Facilities
g. Childcare Facilities
h. Barracks
i. Billeting
j. Dining Facilities
k. Range Facilities
l. HVAC Systems
m. Fire Alarms
n. Roofs, Flashing, and Fascia
o. Installed building equipment
p. Caulking around windows and doors
q. Touch up paint exterior building surfaces
1.3 Work Management and Control.
1.3.1 Reporting Requirements, General Fund Enterprise Business System (GFEBS). N/A
1.3.1.1 Service Plans. N/A
1.3.1.1.1 High Risk Utilities Plan. N/A
1.3.1.1.2 Snow and Ice Removal. N/A
1.3.1.2 Emergency Operating Plan. N/A
1.3.1.3 Other Emergency Services N/A
1.3.2 Publications and Forms. N/A
1.3.3 Facilities Maintenance Instruction. N/A
2.0 Description of Services. The Contractor shall develop and implement (after KO approval) a Comprehensive PM and Repair Program. PM consists primarily of inspection, cleaning, lubrication, adjustment, calibration, parts and component replacement on building and structures, its component equipment and other systems included at facilities which are listed in Annex A, 7.3 Technical Exhibits. The Contractor shall submit the Comprehensive PM, Repair Program and monthly mainenatance schedule for this service within 10 days after receipt of approval to start.
2.1 Facility Workload. N/A
2.1.1 BUILDER. N/A
2.1.2 Work Orders. N/A
2.1.3 Work Order Component Index N/A
2.1.4 N/A
2.2 Natural Gas Appliance and Equipment. N/A
2.3 Heating, Ventilation, and Air Conditioning (HVAC). N/A
2.3.1 General. lN/A
2.3.1.1 Work Area/System Description. N/A
2.3.1.2 Inventory List. N/A
2.3.1.3 Work Performance. N/A
2.3.1.4 Priorities Facilities. N/A
2.3.1.4.1 Priority 1 DMOs. N/A
2.3.2 Seasonal Changeover Requirements. N/A
2.3.2.1 Schedule. N/A
2.3.2.2 Spring Changeover. N/A
2.3.2.3 Fall Changeover. N/A
2.3.3 Chemical Treatment. N/A
2.3.4 Building Operations Control Center (BOCC). N/A
2.3.4.1 System Controls. N/A
2.3.4.1.1 Monitoring Controls. N/A
2.3.4.1.2 Controls Technicians. N/A
2.3.4.1.3 Access Card. N/A
2.3.5 Related Components and Accessories. N/A
2.3.5.1 N/A
2.3.5.2 N/A
2.3.5.3 Equipment/Accessories inside of Ductwork. N/A
2.4 Eye Washes and Safety Showers. N/A
2.5 Roof Gutters, Drains, and Downspouts. N/A
2.6 Automatic Doors. N/A
2.7 Overhead Doors. N/A
2.8 Gates, Fences, Barriers and Dock Levelers. N/A
2.9 Air Compressors/Unfired Pressure Vessels. N/A
2.9.1 Refrigerated Air Dryer. N/A
2.9.2 Compressor Storage Tanks. N/A
2.10 Plumbing. N/A
2.10.1 Components. N/A
2.10.2 Leaks. N/A
2.10.2.1 Gas Leaks. N/A
2.10.3 Sump Pumps and Septic Tanks. N/A
2.10.4 Water Heaters. N/A
2.10.5 Backflow Preventors. N/A
2.10.6 Grease Traps. N/A
2.10.6.1 Blockages. N/A
2.10.6.2 Inspection Records. N/A
2.10.6.3 N/A
2.10.6.4 DPW Environmental Division Approval. N/A
2.10.6.5 Grease traps and solid waste interceptors. N/A
2.10.7 Restroom Fixtures. N/A
2.10.8 Wash Facilities/Racks. N/A
2.10.8.1 Central Vehicle Wash Facilities. N/A
2.10.8.1.1 Confined Space Entry. N/A
2.10.8.1.2 Operating the CVWF. N/A
2.10.8.1.3 CVWF. N/A
2.10.8.2 N/A
2.10.9 Oil Water Separators. N/A
2.11 Sanitary Wastewater Treatment and Collection System (Septic Tanks). N/A
2.11.1 STP Maintenance. N/A
2.11.2 Components. N/A
2.11.3 Compliance. N/A
2.11.4 Reporting Requirements. N/A
2.12 Industrial Wastewater Treatment Plant (IWTP). N/A
2.12.1 Components. N/A
2.12.2 Compliance. N/A
2.12.3 Reporting Requirements. N/A
2.13 Heating/Cooling Plants. N/A
2.13.1 Central Boiler Plants. N/A
2.13.1.2 General Maintenance Considerations. N/A
2.13.2 Maintenance of Heating Plants. N/A
2.13.2.1 N/A
2.13.3 Chiller Units. N/A
2.13.4 Air Handlers. N/A
2.13.5 Condensers. N/A
2.13.6 Cooling Towers. N/A
2.13.7 Ventilation Systems. N/A
2.13.8 Fan Coil Units. N/A
2.13.9 HVAC Controls. N/A
2.13.10 Scheduled System Outages. N/A
2.13.11 N/A
2.13.12 Freeze Protection. N/A
2.14 Winterization and De-Winterization (Mothballed Buildings). N/A
2.14.1 Maintain a log of vacant facilities. N/A
2.14.1.1 N/A
2.14.2 Identify different levels of mothballing. N/A
2.14.3 Specific tasks related to systems. N/A
2.15 Reserved.
2.16 Lift Stations. N/A
2.17 Sedimentation Tanks Maintenance. N/A
2.18 Electrical. N/A
2.18.1 Emergency Fixtures. N/A
2.19 Auxiliary Generators. N/A
2.19.1 Perform PM of Auxiliary Generators. N/A
2.19.1.1 Temporary Generator. N/A
2.20 Grounding Points, Lightning Protection, and Cathodic Protection Maintenance. N/A
2.20.1 General. N/A
2.20.2 Grounding Point Checks. N/A
2.20.3 Grounding Protection System (GPS). N/A
2.20.4 Lightning Protection System (LPS). N/A
2.20.5 Cathodic Protection System (CPS). N/A
2.20.6 N/A
2.21 Security Systems. N/A
2.22 Fire Alarm, Fire Suppression and building Mass Notification Systems. N/A
2.22.1 Fire Alarm Systems. N/A
2.22.1.1 Turnover/Fire Testing Schedule. N/A
2.22.1.2 Preventive Maintenance Requirements. N/A
2.22.2 Sprinkler and Hood Suppression Systems. N/A
2.22.3 N/A
2.23 Reserved.
2.24 PM for Barracks Buildings. N/A
2.24.1 Unscheduled Tasks. N/A
2.24.1.1 Between Occupancy Maintenance (BOM). N/A
2.24.1.2 Interior Structure and Surfaces. N/A
2.24.1.4 Building Systems and Equipment. N/A
2.24.1.5 Quality Assurance. N/A
2.24.2 Scheduled Tasks/Scheduled Inspections. N/A
2.24.2.1 Key Card Systems. N/A
2.24.2.2 Reports. N/A
2.25 Elevator Maintenance. The Contractor shall inspect, test, repair and maintain elevators and lifts at the facilities at US Army Soldier Systems Center, Natick Massachusetts. A list of facilities with elevators and lifts is on Technical Exhibit TE-01. The Contractor shall coordinate directly with the facility users for scheduling of all work and access to the buildings and elevators. The COR shall assist only when the Contractor cannot gain reasonable access.
2.25.1 Elevator Inspection and Certification. Inspection and testing shall be performed with a Contractor-provided Certified Inspector. Inspection and testing shall be IAW the following:
a. Local requirement Technical Exhibit TE-01
b. ASME A17.1, A17.2, A17.3,
c. NFPA standards
d. National Electrical Codes (NEC)
e. Certificate of Elevator Inspection GSA Form 55 and Acknowledgment of Elevator Inspection Certificate GSA Form 55A or a form approved by KO/COR Certificate of Elevator Inspection GSA Form 55.)
2.25.1.1 The Contractor shall obtain an Annual Elevator certificate of operation. The Contractor shall post a notice inside each elevator noting the date of the completed annual certification and note that certificates are on file and available upon request. The Contractor shall create a schedule of inspection, testing, maintenance, repair and certification within thirty (30) days of the contract start date and submit to the KO/COR for approval (Deliverable). The Contractor shall coordinate any scheduled shutdown with the affected building occupants after written approval is provided by the KO/COR. In the event that an unscheduled shutdown of an elevator occurs, the Contractor shall notify the KO/COR within two (2) hours.
Inspections and Testing. The Contractor shall provide yearly inspection of the elevator systems. All inspections shall be performed in accordance with the current edition of ASME A17.1, ASME A17.2, and A17.3 and all subsequent updates NFPA standards, and the National Electric Codes. The Contractor shall prepare and submit a written report within one (1) week after the inspection/test is completed in accordance with CDRL A003. The report shall include the date and time of the inspection/test, the location of the elevator, the inspection/test performed, and the name of the technician performing the inspection/test. The Contractor shall supply a signed certificate of operation within one week of acceptance. The Contractor shall post a notice inside each elevator noting the date of the completed annual certification and note that certificates are on file and available upon request.
Elevators provided with fire service, derailment devices, seismic switches, pre-torque motor control, or other special circuitries shall be checked one time every year to ensure that these devices are operating correctly and as designed.
Fire related elevator controls, including monthly firefighters’ recall operation of all Elevators shall be tested and adjusted monthly for proper operation and properly annotated on the Elevator Firefighter’s service test record. Requirements of the latest edition of ASME A17.1 standard shall be followed as appropriate.
Special Provision. When the State of Massachusetts does not allow testing on federal facilities:
The Contractor shall be responsible for full compliance under the NFPA and ASME elevator code, to provide all labor and materials for a third party certified elevator inspection of all elevators and chair lifts located on post. The Contractor shall conduct a full category 5 load test/inspection and category 1 inspections as required by the NFPA/ASME regulation periods. All results will be documented on forms 00347CAT1 and 00348CAT5 attached for each elevator and chair lift in accordance with CDRL A003. The Contractor shall have technicians and Inspectors trained and knowledgeable of all updates and changes to the NFPA/ASME elevator code.
The Contractor shall prepare applications for inspections for each elevator and lift shown on the Elevator and Lift Inventory TE-01. The Contractor shall pay for all fees associated with these applications. The Contractor shall include the cost of application, arrangement, and site assistance to the independent inspection agency while performing the service, in the contract price. The Contractor shall prepare all elevators & lifts maintained under this contract for inspections and shall accompany the inspector(s) during the inspections. The Contractor shall correct any discrepancies, deficiencies and/or needed repairs or adjustments needed to prepare for inspections or needed as a result of inspections. Upon notification of the inspection and testing dates from the independent elevator inspector, the Contractor: Shall notify, in writing, the Contracting Officers Representative (COR) of these inspection and testing dates and shall have their inspection personnel perform preliminary inspections and tests that would include procedures that would be done by certified elevator inspectors, on all elevators and lifts that are scheduled one week prior to the inspection. The Contractor shall replace or repair all parts or components that were found, during preliminary Inspection, which would cause the certified elevator inspector to cite an elevator or lift for non compliance or unsafe condition.
2.25.1.2 For any elevators located in Massachusetts, licensing and regulatory requirements apply.
2.25.2 Out of Service Time. Elevators shall not be out of service for more than twenty-four (24) hours at any one time without approval from KO/COR. When parts are ordered, the KO/COR will be notified on the status and due delivery date. If the Contractor knows that the elevator is going to be down more than seven (7) calendar days, the KO/COR shall be informed in writing/email detailing the specific problem and indicating why the elevator will be down for more than seven (7) days. The Contractor shall post a Status of Repairs on the elevator door indicating the “repair by” date.
2.25.3 Preventive Maintenance Requirements and Scheduled Maintenance Requirements. Includes monthly preventative maintenance; shop parts and supplies; inspections and reports. Monthly preventative maintenance includes but is not limited to the following: lubricate equipment, adjust parts and components, re-lamp signals, and examine all elevator equipment for optimum operation. All maintenance and work shall be performed IAW industry standards.
2.25.3.1 Periodic Inspections, Testing, and Reports. The Contractor shall perform annual inspection/testing and make a formal report IAW industry standards. Schedule for Annual inspections shall be submitted for approval to the KO/COR within thirty (30) calendar days of the start of the contract. The Contractor shall also fill out DA Form 7485-R and submit the completed form to the KO/COR within ten (10) calendar days after completion of each Annual test. The Contractor shall perform Annual Testing and Certification of elevators IAW paragraph 2.25.1.
2.25.3.2 General PM Requirements. The following items shall be provided by the Contractor to support the maintenance and repair services.
The Contractor shall keep each logbook in the machine room of each elevator, maintain logbook to include records of scheduled maintenance services, annual service, testing, service calls, repairs and parts replaced. Information shall contain description of work, dates, problems, and corrective measures taken, persons requesting services/repairs, time completed, and the name of the mechanics performing the work. The logbook shall be hard bound. Existing logbook may be continued if the book is in good condition. Retain previous log books and records in a binder or other suitable document container. Logbooks will become Government Property.
Work covering routine cleaning and refinishing of the interior of cars and the exterior of hoist way doors and frames is not included in this contract. However, cleaning of equipment spaces, hoist ways, and daily cleanup of job sites in conjunction with preventative maintenance, inspection services, and repairs is included in this contract. Provide a metal waste can with cover in each elevator machine room.
Monthy PM Maintennce. Contractor shall inspect each elevator at least once each month, not including service calls. During monthly maintenance visits, the Contractor shall include the following services:
Adjustments. Adjust machinery and equipment as required. Circuit breakers or main line switches, together with fuses for same are excluded. Contractor shall maintain the performance times as outlined in the modernization specification for each unit. These times include door open & close times, door open duration times, car speeds and floor to floor performance times. In addition to the performance times the supplier shall maintain a smooth quiet ride and stopping accuracy for each unit.
Cleaning. Remove accumulated dirt, dust, and rubbish from machine rooms, hoist ways, and pits. Furnish cleaning supplies and tools. Cleaning and refinishing of interiors of cars and exteriors of hoist way doors and frames are excluded. Complete hoist way clean downs shall be performed no less than annually, car tops and car door equipment shall be cleaned no less than quarterly and machine rooms and pits monthly as a minmum.
Lubrication. Lubricate machinery and equipment with materials recommended by the manufacturer of the specific machinery and equipment. Contractor shall furnish all lubricants.
Traction Elevator Repairs. The Contractor shall furnish and install or repair as required machine motors, motor generator, controllers, hoist cables, selectors, worms, gears,thrusts, bearings, brake magnet coils, brake shoes, magnet frames, cams, car door and hoist way door hangers tracks and guides, door operating devices, interlocks, and contacts, car gates, safety devices, governors, push buttons, enunciators, shell lanterns and indicators, lamps replacements in systems, and other elevator signal and accessory equipment complete.
Hydraulic Elevator Repairs. The Contractor shall furnish and install or repair as required power units, pump motor and controller including valves, including relief valve, pilot, lowering, leveling, and check valves; or any of the parts thereof; V-belts, strainers, spring and gaskets; controller relays, solid state control components, contacts, coils, timers, magnet frames and controller wiring, traveling cable and components for entire operating circuit; plunger, guide bearings, packing gland; guide rails and guide shoes. Maintain hydraulic fluid at proper operating level, push buttons, enunciators, shell lanterns and indicators, lamps replacements in systems, and other elevator signal and accessory equipment complete.
2.25.4 Regular Cleaning. The Contractor shall thoroughly clean all elevator hoist ways, pits, car tops, controller interiors including filters and machine rooms. Work covering routine cleaning and refinishing of the interior of cars and the exterior of hoist way doors and frames is not included in this contract. However, cleaning of equipment spaces, hoist ways, and daily cleanup of job sites in conjunction with preventative maintenance, inspection services, and repairs is included in this contract. Provide a metal waste can with cover in each elevator machine room.
2.25.5 Workmanship/Qualifications of Employees. The workmanship shall be of highest quality in every detail. The quality of any repaired section of the elevator or lift systems shall be good as or better than the original installation. All work shall be performed by elevator mechanics licensed in the Commonwealth of Massachusetts.
2.25.6 Unscheduled Service Calls. Service Calls will be classified as routine when the work does not qualify as an emergency call. The Contractor shall respond to and begin work on routine service calls within one hour after receipt of the call. Routine service call work will normally be performed during the Government’s regular working hours. The contracting officer or the COR will notify the contractor of repairs to be made from the service call. The Contractor shall report to the work location, survey the repair, and provide to the COR an estimated time to repair and cost of repairs not covered in the basic service contract. The Contractor shall commence repair work after notification from the Contracting Officer or the COR. All repair work shall be in accordance with normal commercial practices using parts specified by the elevator manufacturer or items of equal or better quality. Downtime of the elevator will be kept to an absolute minimum. The Contractor shall notify the COR of all projected downtime and estimated time for repair.
2.25.7 Out of Service Time. Elevators shall not be out of service for more than twenty-four (24) hours at any one time without approval from KO/COR. When parts are ordered, the KO/COR will be notified on the status and due delivery date. If the Contractor knows that the elevator is going to be down more than seven (7) calendar days, the KO/COR shall be informed in writing/email detailing the specific problem and indicating why the elevator will be down for more than seven (7) days. The Contractor shall post a Status of Repairs on the elevator door indicating the “repair by” date.
2.25.8 Emergency Calls. Service calls will be classified as an emergency when system failures constitute a danger to personnel, threaten to damage property, or threaten to disrupt activity operations or mission. Examples include personnel “trapped” inside an elevator, a fire or electrical defect which could cause fire or shock, and two elevators out of service in the same building. In the event an elevator is shut down with trapped passengers, the Contractor shall respond within one hour between 8:00 A.M. and 5:00 P.M., Monday-Friday (regular weekday hours), and a one and one half hour response time from 5:00 P.M. to 8:00 A.M., Monday-Friday, Saturdays, Sundays, and holidays. Emergency Services shall be available Seven (7) days a week, 24 hours a day, including Federal holidays. The Contractor shall be on call twenty-four hours/seven days per week, including weekends and holidays, throughout the life of the contract.
2.25.9 Other Service. If repairs are needed due to malicious damage, damage from accident, or damage from emergency extrication, the Contractor shall give full details in writing regarding the extent of such damages, and the repairs necessary to return the elevator(s) to normal operation in accordance with CDRL A004. Any costs incurred under this section must be approved by the KO prior to performing any work.
2.25.9 Schedules. The Contractor shall establish a monthly Elevator maintenance program including a work schedule for each Elevator machine room. The work schedules shall be designed for each type of equipment to be serviced, such as geared elevators, hydraulic elevators, etc., and shall conform to the manufacturer’s recommended practice for the particular equipment concerned. All inspections, lubrication, adjustments, tests, cleaning, routine repairing, and other preventative maintenance activities shall be performed and documented in accordance with schedules submitted by the Contractor in accordance with CDRL A001.
2.25.10 Service Reports. The Contractor shall prepare and submit a report in accordance with Contract Data Requirements List (CDRL) A005 within 3 days of the all elevator and elevator machine room service performed and any findings. The report shall identify each elevator, the location, maintenance work performed, repairs needed, date of inspection/service, name of technician, and overall condition of the elevator. The Contractor shall submit all invoices for any items replaced on equipment.
2.25.11 Additional Provisions. It is the objective of the Government to obtain complete and satisfactory performance in accordance with the terms of the specifications and requirements in this contract. To this end, the Government is contracting for the complete performance of each task identified in the specifications, and deductions may therefore, be made as stipulated in this Section. Deductions for work performed improperly may be made as though the work had not been performed.
2.25.12 Calculation of Deductions. The deduction criteria in this Section will be used by the Government in determining monetary deductions for nonperformance of work under this contract or for deficiencies in the work performed, and supplements the default clause contained in the CONTRACT CLAUSES, but does not reduce or limit the Government’s rights there under.
2.25.13 Determination of Deduction Amounts. Inadequate performance is just as undesirable as nonperformance and the cost of correcting inadequate performance may equal or exceed the cost of initial performance. Therefore, the deduction criteria shall control in determining equitable holdbacks.
2.25.14 Withholding Monies for Failure to Maintain and/or Provide Parts. If the Contractor fails to provide the parts specified in this PWS, within 24 hours of establishment of the need for such parts, the Government may withhold all payments until the required parts are provided and are deemed satisfactory to the COR.
2.25.15 Removal of Elevator(s) from Service. When the Government removes one or more elevators & lifts listed in this contract from service for any reason, the monthly payments due the Contractor may be reduced. The Contractor shall be notified, in writing by e-mail or letter, at least 3 full work days in advance of the elevator(s) or lift(s) being removed from, or returned to, service. If the elevator(s) or lift(s) is to be removed from service for 30 consecutive calendar days or less, the contracting officer (CO) will issue a modification to the contract and negotiate an equitable adjustment in the contract price in accordance with the Changes clause. The period for reducing payments will begin on the effective date specified in the notice and will continue through the day before the elevator(s) or lift(s) is returned to service.
2.25.16 Withholding Monies for Equipment Outages. The Government reserves the right to take a deduction for any piece(s) of equipment which remains out of service in excess of three (3) consecutive calendar days commencing the first day notification was given the contractor of the outage. The deduction shall be determined on a daily rate calculated by dividing the number of days in the respective month(s) into the monthly price for the related piece(s) of equipment. The number of days shall be computed from the first day after the fifth consecutive calendar day after notification through the last day prior to service being restored.
2.25.17 Inspection and Acceptance. The Government reserves the right to have a representative observe the Contractor’s performance to confirm compliance with all the requirements of this contract. In the event that the Contracting Officer determines that the terms of this contract have not been complied with, the Government reserves the right to issue partial acceptance of the work performed and to withhold a portion of the payment pending disbursement adjustment. The Government reserves the right to perform such inspection and tests as are deemed necessary to insure contract compliance. Should it be determined that the standards herein are not being maintained the Government may immediately demand that the Contractor place the elevators & lifts in a condition that meets the requirements.
2.25.18 Compliance. If the Contractor fails to comply and complete the requirements within seven business days, the Government may by written notice terminate the right to proceed with the work. In such an event the Government may unilaterally take over management of the work and process it to completion with another Contractor if deemed appropriate.
Applicable Publications.
Testing, maintenance, inspection and certification shall be in accordance with:
A17.1-96 Safety Code for Elevators & lifts and Escalators (or current revision).
A17.2.1-96 Inspector's Manual for Electric Elevators & lifts (or current revision).
A17.2.2-97 Inspector's Manual for Hydraulic Elevators & lifts (or current revision).
A17.3-96 Safety Code for Existing Elevators & lifts and Escalators (or current revision).
A17.5-96 Elevator and Escalator Electrical Equipment (or current revision).
A18.1-99 Safety Standard for Platform Lifts and Stairway Chair-lifts (or current revision).
Commonwealth of Massachusetts Code, Elevator Regulations, Board of - 524; CMR, 524 CMR 1.00 – 35.00 (or current version).
Army Regulation, AR 420-5.
Maintenance and repair shall also be in accordance with:
Each Elevator Manufacturers’ Operation and Maintenance Manuals.
Current Editions. The Contractor shall abide by all applicable regulations, publications, manuals, and local policies and procedures. Any Contractor provided publications are to be procured and maintained at Contractor’s expense.
American Society of Mechanical Engineers (ASME):
ASME A17.1 (2000) Safety Code for elevators and escalators.
ASME A17.3 (2000) Safety Code for elevators and escalators.
American Society for Testing and Materials (ASTM):
ASTM A 167 (1989A) Stainless heat resistant Chromium-Stainless Steel plate, sheet, and strip.
ASTM A 366 (1985) Steel, Carbon, Cold-Rolled Sheet, Commercial Quality.
Americans with Disabilities Act (ADA).
National Electric Code (NEC).
Uniform Building Code (UBC).
National Fire Protection Association (NFPA) 101 Life Safety Code, 2009 Edition or lat-est edition.
2.26 Swimming Pools and Hot Tubs. N/A
2.26.1 Circulation, Heating, and Filtration Systems. N/A
2.27 Keys and Locks. N/A
2.27.1 Key Control in Contractor Occupied Facilities. N/A
2.27.2 N/A
2.27.2.1 N/A
2.27.3 Lock Combinations. N/A
2.28 Food Service Equipment (FSE). N/A
2.29 Dining Facility (DFAC) Maintenance. N/A
2.29.1 General. N/A
2.29.1.1 N/A
2.29.1.2 N/A
2.29.1.3 N/A
2.29.1.4 N/A
2.29.1.5 N/A
2.29.1.6 N/A
2.29.1.7 N/A
2.29.1.8 N/A
2.29.1.9 Pest Control. N/A
2.30 Crane and Load Scales Maintenance and Load Testing. N/A
2.30.1 General. N/A
2.30.2 Preventive Maintenance Plan. N/A
2.30.3 Crane Operator Training. N/A
2.30.4 Load scales. N/A
2.31 Glass and Glazing. N/A
3.0 Work Capability Levels. N/A
4.0 Self-Help Program. N/A
5.0 Operation and Maintenance of Energy Conservation Systems N/A
6.0 Sign Shop Operations
7.0 Utility Systems. N/A
8.0 Uninterruptible Power Supply (UPS) Systems. N/A
9.0 Area Lighting. N/A
10.0 Utility Marking. N/A
11.0 Pumps and Pumping Stations. N/A
12.0 Natural Gas and Propane Distribution System. N/A
13.0 Propane Tanks and Distribution Systems. N/A
14.0 Water Distribution Systems. N/A
15.0 Storm Water Collection System. N/A
16.0 Preventive Maintenance of Storm Water Systems. N/A
17.0 Reporting Requirements of Storm Water Systems. N/A
18.0 Training. N/A
19.0 Certification. N/A
20.0 Other Utility Systems. N/A
21.0 Fuel Storage and Distribution Systems. N/A
22.0 Fuel-Powered Pump Maintenance. N/A
23.0 Emergency/Backup Generators (not attached to building). N/A
24.0 Other Water Distribution Systems. N/A
25.0 Water Standpipes. N/A
26.0 Other Sanitary Wastewater Collection Systems. N/A
27.0 Fire Loop System Hydrants. N/A
28.0 Training of Personnel N/A
29.0 Deliverables: See Section 6.0 of Annex A.
30.0 Period of Performance: The total period of performance is up to 60 months, inclusive of all options.
31.0 Place of Performance: The primary place of performance for this work will be U.S. Army DEVCOM Soldier Center, Natick, MA.
32.0 Invoicing: The Contractor shall submit an invoice on a monthly basis via Wide Area Workflow (WAWF) in accordance with DFARS 252.232-7006 (see full-text clauses below for instruction).