This document is a set of mechanical engineering drawings for the Joint Ambulatory Care Center, a joint VA/Department of Defense (Navy) project located at VA Gulf Coast Veterans Health Care System in Pensacola, Florida. The drawings depict ground and second floor mechanical plans organized by sectors, with detailed fire and smoke damper specifications, ductwork layouts, VAV (variable air volume) terminal units, and HVAC equipment locations.
The drawings specify extensive mechanical systems including multiple air handling units (AHU-1 through AHU-10), fan coil units (FCU-1 through FCU-6), exhaust fans, supply and return ductwork with pressure class designations (primarily 2" W.C. SMACNA pressure class), and terminal units with specific CFM (cubic feet per minute) airflow ratings. Key components include spin-in dampers with airflow ranges of 50-200 CFM, stainless steel exhaust ductwork for laboratory and surgical areas, make-up air units, and specialized equipment such as MRI chillers and biosafety cabinets. The specifications require 26-gauge minimum sheetmetal duct construction with 2-inch fiberglass wrap and FSK vapor barrier jackets. Fire and smoke dampers are distributed throughout the building at slab penetrations and duct transitions. The drawing set underwent multiple revision cycles between October 2005 and August 2008, with final submittal documentation dated February 2, 2006, indicating this represents a completed design for a fully sprinklered healthcare facility.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25626Q0376 0001.pdf | ||
| ATTACHMENT D VAAR 852.219-75 Certificate of Compliance.pdf | ||
| 36C25626Q0376.pdf | ||
| ATTACHMENT B LIST OF PAST PERF REF.docx | DOCX document | |
| Attachment C Past Performance Questionaire fillable.pdf | ||
| ATTACHMENT A Escambia County FL WD 2015-4561 R31 dtd 12-03-2025.pdf | ||
| 36C25626Q0376_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SERVED BY SUPPLY FAN NO.1
ITEM (TERMINAL UNIT SHOWN)
ITEM NUMBER (TERMINAL UNIT NO.1)
EQUIPMENT ABBREVIATION (SUPPLY FAN)
TYPICAL UNIT NO.
SECTION LETTER
DRAWING NUMBER WHERE SHOWN
DRAWING NUMBER WHERE DRAWN
DETAIL NUMBER
TU-I-I
A H7
DRAWING SYMBOLS
H4
R
INCLINED DROP, IN DIRECTION OF AIR FLOW
INCLINED RISE, IN DIRECTION OF AIR FLOW
D
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
EXHAUST OR RETURN REGISTER OR TOP GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
CEILING DIFFUSERS
DUCTWORK SYMBOLS
(WALL TYPE)
(WALL TYPE)
MANUAL VOLUME DAMPER
DUCT WITH SOUND LINING
VDF. DPR
FIRE DAMPER
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
STANDARD RADIUS ELBOW
VANED ELBOW (SHORT RADIUS)
SYMBOL IS MISSING)
RECTANGULAR ELBOWS WITH VANES EVEN IF
VANED ELBOW (PROVIDE ALL SQUARE OR
FLEXIBLE CONNECTION
10X8
FC
SECTION.)
BDD
BACK DRAFT DAMPER
STAINLESS STEEL DUCT
INDICATES NEGATIVE PRESSURE.
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
A
4 1/2
SMOKE DAMPER
ACCOMODATE MAXIMUM OPERATING PRESSURE
PRESSURE CLASS (IN. OF WATER) WHICH WILL
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
POINT OF CHANGE IN DUCT CONSTRUCTION BY
S. DPR
N
DOUBLE WALL CASING PANELOR
45^
MANUAL SPLITTER DAMPER
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45^TAP)
45^ RETURN
SUPPLY
DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)
DUCT MOUNTED COIL (ELECTRIC)
SF 3 SUPPLY FAN NO.3
FLEXIBLE DUCTWORK (SHOWN WITH DIFFUSER)
SYMBOLSINGLE LINE
NEW DUCT
R
D
VD
BDD
FD
SD
GENERAL SYMBOLS
FAN POWERED UNIT
DIFFUSER SYMBOLS
DUCT TURNING UP
UNIT HEATER (HORIZONTAL)
TERMINAL UNIT - REHEAT COIL,
VARIABLE VOLUME, VAV REHEAT,
SINGLE LINE SYMBOL
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES
WATER FLOW MEASURING DEVICE
STRAINER
THERMOMETER
PRESSURE GAGE
ORIFICE UNION
BLAST THERMOSTATIC TRAP
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
DIRECTION OF PIPE PITCH (DOWN)
TOP CONNECTION, 45^OR 90%%94
BOTTOM CONNECTION, 45^OR 90%%94
ECCENTRIC REDUCER
SIDE CONNECTION
DIRECTION OF FLOW
REDUCER OR INCREASER
ANCHOR
DUCT TURNING DOWN
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
MESH SCREENOEDOED
700 SIDEWALL GRILLE , REGISTER 700
DIFFUSER KEY:
100 AIR QUANTITY (CFM)
SYMBOLSINGLE LINE
CEILING GRILLE , REGISTER
CEILING SUPPLY DIFFUSER
SEE DIFFUSER/GRILLE SCHEDULE
SEE DIFFUSER/GRILLE SCHEDULE
TEST PLUG (PRESSURE/TEMPERATURE)
MANUAL AIR VENT
PRESSURE REDUCING VALVE
GATE VALVE
SAFETY OR PRESSURE RELIEF VALVE
AUTOMATIC FLOW CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
STRAIGHT-THRU TWO POSITION CONTROL VALVE
STRAIGHT-THRU MODULATING CONTROL VALVE
CIRCUIT SETTER
BALANCING VALVE
BUTTERFLY VALVE
ANGLE GLOBE VALVE
CHECK VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
GLOBE VALVE
BALL VALVE
VALVE SYMBOLS
PIPING RISER SYMBOLS
CONDENSER WATER FROM & TO TOWER
CHILLED WATER SUPPLY & RETURN
HOT WATER SUPPLY & RETURN
CWFT
CWTT
CH
CHR
HWH
HWHR
EQUIPMENT/TERMINAL UNIT SYMBOLS
HOSE CONNECTION (HC)
STRAINER WITH BLOWOFF AND
HWHR HOT WATER HEATING RETURN
CONDENSER WATER TO TOWERCWTT
D
CHR
CWFT
CH
CONDENSER WATER FROM TOWER
MAKE-UP WATER
DRAIN LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
RL
RHG
RS
AIR CONDITIONING
V
REFRIGERANT LIQUID
REFRIGERANT HOT GAS
REFRIGERANT SUCTION
VENT LINE
HWH
HEATING
HOT WATER HEATING SUPPLY
ALIGNMENT GUIDE
AUTOMATIC AIR VALVE
V
END CAP
BLIND FLANGE
PIPING SYMBOLS
MECHANICAL
LEGENDS AND
SYMBOLS
MH-0.02
K. MILNER
H. SHEINMAN
10 / 31 / 0510 / 31 / 05SUBMITTAL #3
OPEN END DUCT WITH 1/2" x 1/2" WIRE
COMBINATON FIRE/SMOKE DAMPER
(2) TYPICAL OF 2
"MARK", "REFERENCE" OR "ID"A
OR
OR
12 / 25 / 05SUBMITTAL #4
HWR
HWS
CWR
CHWR
CWS
CHWS
FINAL SUBMITTAL FULLY SPRINKLERED
SMOKE DETECTORS F
SD1
1 FINAL SUBMITTAL 02/02/06
AIRFLOW (CFM)
AIRFLOW (CFM)
SMACNA DUCTWORK PRESSURE
CLASS DESCRIPTORS
SMACNA PRESSURE CLASS, IN INCHES W.C.
2 3 3
RECORD DOCUMENTS 08/08/08
PROJECT NUMBER
DRAWING NUMBER
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
DRAWN
CHECKED
DATE
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
SCALE
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
PROJECT NUMBER
DRAWING NUMBER
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
Q
P
N
Q.8
1 2 3 4 5 6
M
L
Q.9
5.2 5.8
R
EXAM 13EXAM 14EXAM 15EXAM 16
EXAM 17EXAM 18EXAM 19EXAM 20
EXAM 21EXAM 22EXAM 23EXAM 24 MED.
VITALS
TRIAGE TRIAGE
GROUP CONSULT
ROI
COUNTER
ROI WORK
FILES / EQUIP
MAS SEC/
WAIT
WAIT
ELEC
MAS COPY/
MAIL / WORKCLERICAL
MAS
SUPV
CLERK
STOR
STOR
CLERK
HBA 1
HBA 2 HBA 3 HBA 4 HBA 5
INTERVIEW BOOTHS
INTERVIEW 1 TRAVEL 2 TRAVEL 1
CASHIER MAS RECEPTION
ROI SUPV.
VOL.
SEC.
VOL WORK RM
VOL. STOR.
STORVOL SPEC
MAS ASSIST
MAS TEAM LDR
MAS MED ASSIST
VOL SPEC
SEC
SERV ORG
REP 1
SERV ORG
REP 2
SERV ORG
REP 3
SERV ORG
REP 4
SERV ORG
REP 5
SERV ORG
REP 6
SERV ORG
REP 7
SERV ORG
REP 8
COMM
TLT.
TLT
BAR
EXAM
BAR
EXAM
DIETICIAN SOIL
HSKP
TLT.
SERV ORGAN
MED ADMIN SERV
TLT.
VOL SIGN-IN/
LOUNGE
1A100
1A1011A1021A1031A1041A1051A1061A1071A108
1A109 1A110 1A111 1A112 1A113
1A114
1A115
1A116
1A117
1A118
1A119 1A1201A1211A1221A1231A124
1A125
1A126
1A127
1A128 1A129 1A130 1A131 1A132
1A133
1A135
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
1G101
LOBBY
1G100
VEST
1C100
1C1011C102
1C103
1C104
1C105
1C106 1C107
1C108
1C109
1C110
1C111
1C112
1C113
1C114 1C1151C116
1C117 1C121 1C123 1C125 1C127 1C129 1C130
1C101A
WAIT
C1-08
C1-09C1-10
C1-11
C1-12
1A134
1A136
1A1371A138 1A139
1A140
1A141
1A142
1A143
1A144
1A145
1A146
1A147
1A148
1A149
1A150
PYXIS
REF.
PYXIS
PAT ADV
OFFICE
C1-05A
C1-03A
MAS
WAIT
FEE SVCS
SUPV.
MED COST
SUPV.
FAXCOPIER PRINT COMP
COPIER PRINT
FAX
COMP
COPIER PRINT FAX COMP
CART MAIL TABLE MAIL MACH.
REF
COFFE
RA
CK
CART
VAC
SH
EL
VG
PTS
PTS
VOLUNTEERS
COFFE
1G101A
MACHINE RM.
DEDICATION PLAQUE
(N.I.C.)
DIRECTORY
OPER
ROOM
1B100
1B111
1B112
1B107A
1B106A
STORAGE
STORAGE
GROUND FLOOR
MECHANICAL PLAN- SECTOR 1
FIRE/SMOKE DAMPERS ONLY
MH-1.01-1 FR & SMK DMPRS
08/29/05SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
KEYED NOTES:
MH-4.06
ESCUTCHEON IN CEILING PENETRATION. SEPARATELY HANG AUXILIARY DRAIN PAN FROM STRUCTURE.
MATCHLINE
SEE SHEET MH-1.01-3
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -2
FO
R
CO
NT
IN
UA
TI
ON
FAN COIL UNIT WITH DISCHARGE PLENUM (40" W X 28" D X 24" H). PROVIDE SUPPLY GRILLES
HANG FAN COIL UNIT FROM STRUCTURE ABOVE WITH (4) 1/4" THREADED RODS AND 1'4" MINIMUM-STATIC-DEFLECTION
SUBMITTAL #4 12 / 25 / 05
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
HOT WATER CABINET HEATER. MOUNTED LOW WALL.
SEE MH-1.02-1 FOR CONTINUATION.
AS SHOWN. MOUNT UNIT ON A 12" RAISED GALVANIZED STRUCTURAL STEEL ANGLE SUPPORT.
SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND COOLING COIL.
PIPE 3 4" DRAIN FROM DRAIN PAN THROUGH CEILING TO SPILL ONTO 1G100. PROVIDE CHROME
2 06/20/06REVISION #2
3 REVISION #3 09/11/06
4 REVISION #5 11/06/06
08/08/08RECORD DOCUMENTS
5 REVISION #11 06/23/08
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 110 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
PROVIDE A 5" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 8X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 150 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
X2
20X1416X1416X10
110110110110
110 110 110 110
150 130
90170
X2
100110110
110 110 110 110 110
90100
90X22
70100100100
100 100 100 60 160
X1
28X1618X14
18X14
MVD
880 880
14X14 10X10
12X12
10X10
8X
18X12
8X
X2
125125
310110
150 150
150120
170 120
130130130
130130130130
80 110
130130130
130130130130
110 110
90 90
48X18
S5
38X16
X1
18X1412X12
MVD
MVD
22X14
16X14
X1
X1
X1
16X16
18X10, UP18X6,
UP
UP
26X122, UP
36X122, UP
40X6
44X8
X1
X1
8X8
X2
R5
MVD 16
"Ø
90X22
MVD12X18MVD
10"Ø
"Ø
UP
9"
FCU-2.1
ABOVE CEILING
40X14
44X14
FCU-1
110 120
R68"Ø UP
R5
74X26
BOD=10'-9"
X1
BO
D= `1
0'- 9"
S9 (3)
S5
12X20 EA
DUCT, UP
20X14
EA DUCT
UP
CUH-1.1
2 3
2 3
8X 8 T T
20X16
8X8
16X16 16X12 10X10
T
8X8
T
8X8
T
8X8
X1
T
8X8
T
X1
T
8X8
T
8X8
T
8X 8 8X
T
T
T
T
8X8
DN
12X12 DN
T
8X8
T
8X8
T
8X8
T
8X8
T
T
14X12
T
12X12 8X8
T
12X12
T T
12X12
X1
12X26
T
8X8
T
20X14
10X10
MVD
UP
X1
DN
MVD
12X12
X1
12X12 8X8
8X8
T
14X18
X1
T
10X10
T
FD
T
12X10
(TYPICAL AT ALL
TERMINAL UNITS)
(TYPICAL FOR ALL
DUCTING UPSTREAM
OF TERMINAL
UNITS)
TYPICAL FOR
ALL EXHAUST
DUCT U.N.O.)
VAV-1-8 VAV-1-7
VAV-1-11
VAV-1-6
VAV-1-5
VAV-1-4 VAV-1-3 VAV-1-2 VAV-1-1
VAV-1-13
VAV-1-14
VAV-1-15
VAV-1-16
VAV-1-17
VAV-1-20
VAV-1-21
VAV-1-19
VAV-1-18
VAV-1-22
VAV-1-23
VAV-1-25VAV-1-24
VAV-1-80
VAV-1-72
VAV-1-71
106X36
X2
X2
74X
0X
FO
T
6X
VAV-1-79
10X8
X1
12X10
DN
UP
VAV-1-9
VAV-1-12
12X12
T
X1
X1
DN
T
VA
V-
1-
2,3
AutoCAD SHX Text Solar
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
7 8 9 10 11 12 13
R
Q
P
N
Q.8
M
L
Q.9
M.9
1G101
LOBBY
1G100
VEST
ED
U
C
AT
IO
N
A&MM
ENGINEERING
POLICE
EMS
DF
UNION
OFFICE
ELEC
TEL
DF
PHARMACY SERVICE
COVERED EXTERIOR SEATING AREA
PRESCRP
RECV
STAFF
BREAK RM
MALE
LOCKER
MECHANICAL
ROOM
FEMALE
LOCKER
PROCURE
SPECIAL.
ST
TLT
COMP.
BOOTH
DISPENS.
SUPV.
COMM
ELEC
EMS
STORAGE
LARGE
EQUIP
SOILED
LINEN
CLEAN
LINEN
REFRIG /
FREEZ.ACTIVE
STORAGE
ANTE
ROOM
RECEIV./
BREAKDOWN
UNIF
DIST
FILLING /
ASSEMBLY
ONCOL
PREPPROSTHETIC
STORAGE
HSK
OFFICE
OPER
ROOM
ARMO
SUPPLY
STAFF ED.
COORD STOR
SUPP MNGR
SUPV
OFFCIE
SUPP. SECUNPOST
STOCK
DISP ST.KP
MED
GAS
RECEIVE/
ISSUE
FLAM
STOR.
GENERAL / MED
STORAGEEQUIP
STOR.
COMPUTER
TRAINING
PAT. ED.
COORD
PAT. ED.
ADMIN
HR
HR
MEDIA
SVCS
SEC A/C ELECTRICALPLUMBING
CARPENTRY
INFECTED
WASTE
STORAGE
EMS
SUPV.CONF
CHIEF
ENG.
DRAFT
PLAN
FLAM
STORAGE
COVERED
WORK
GROUNDS
EQUIP
HSK
PNEUMATIC
TUBE CENTAL
STA.
PHARM WAIT
CONTROL SUB
SEC
TOIL./SHOWER
TOIL./SHOWER
DISPENSING
ADP
SAFTY SPEC
FLAM.
PICK-UP
CONSULT
PRE PKG.
CLERK
WORK RM
1B100
1B101 1B102
1B103
CANTEEN
(LAYOUT BY OTHERS)
1B104
1B105
1B106
1B107
1B108
1B109
1B110
1B111
1B112
1B113
1B114 1B115 1B116
1B117
1B118
1B119 1B120 1B121 1B122
1B123 1B124
1B125
1B126
1B127
1B128 1B129
1B1301B131
1B132
1B133
1B134 1B135
1B136 1B137
1B138
1B139
1B140 1B141
1B142
1B143
1B144
1B145
1B146 1B147
1B148
1B149
1B150
1B151 1B152
1B153
1B155
1B156
1B157 1B158
1B159
1B160
1B154
1B161
1B162
1B163 1B164 1B1651B166 1B167 1B168 1B169 1B170 1B171
1B172
1B173
1B174 1B175
1B176
1B177
1B178
1B179
1B180
1B181
1B182
1B183
1B185
CANTEEN SERVICE
C1-82 C1-83
C1-84
C1-85
C1-86
C1-87 C1-88 C1-89
C1-90C1-91
C1-92
C1-93
C1-94
C1-95
C1-87A
1B184
MED
VAC
FEC
PTS
PTS
TEAM LDR
PUBLIC TLT MALE
PUBLIC TLT
FEMALE
1B107A
1B106A
STORAGE
STORAGE
RECEIVING
1B180A
ELEC
EQUIP
1B200
AMBULANCE
VESTIBULE
CHAINLINK
FENCE
3'-0"(W) X 7'-0"(H)
CHAINLINK
SWING GATE
IV
ADMIXTURE
ANTE
ROOM
1B120A
PASS
THRU
GROUND FLOOR
MECHANICAL PLAN
SECTOR 2- FIRE/SMOKE DAMPERS ONLY
MH-1.01-2
K. MILNER
H. SHEINMAN
08/29/05
KEYED NOTES:
4 4 4 4
5 7
SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
MH-4.06
MH-3.01
MH-3.01
8X8, ABOVE LOADING DOCK SOFFIT, UP THROUGH ROOF TO FAN ON ROOF ABOVE.
MATCHLINE
SEE SHEET MH-1.01-4
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -1
FO
R
CO
NT
IN
UA
TI
ON
10 12 15
PROVIDE SHEETMETAL DISCHARGE TRANSITION, 3 SQUARE FEET.
EXHAUST FAN HUNG FROM STRUCTURE ABOVE BY (4) 1/4" THREADED RODS WITH 1/4"
MINIMUM-STATIC-DEFLECTION SPRING HANGERS.
HOT WATER UNIT HEATER WITH FACTORY-FURNISHED WALL BRACKET, MOUNTED HIGH ON WALL.
12"Ø CONSTANT-VOLUME EXHAUST AIR VALVE, SET FOR 800 CFM, EQUAL TO PHOENIX CONTROLS CVVAF12LACNHX .SEE FUME HOOD CONSTANT VOLUME CONTROLS DIAGRAM.
MOTORIZED CONTROL DAMPER SEE FUME HOOD CONSTANT VOLUME CONTROLS DIAGRAM.
LOCATION OF AHU-2'S DUCT STATIC PRESSURE SENSOR.
LOCATION OF AHU-6'S DUCT STATIC PRESSURE SENSOR.
HORIZONTAL BLADES. SEE SPECIFICATION 10200.
SUBMITTAL #4 12 / 25/ 05
SEE MH-1.02-2 FOR CONTINUATION.22
4 2
(TYPICAL AT ALL TERMINAL UNITS)
(TYPICAL FOR ALL DUCTING
UPSTREAM OF TERMINAL UNITS)
(TYPICAL OF ALL EXHAUST
DUCTING, U.N.O.)
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
(NOT USED.)
23 CLOSE MOTORIZED DAMPERS AND VAV PRIMARY DAMPER WHEN AHU-2 IS OFF.
1 1
MH-4.01
LOCATION OF ECC. SEE SPECIFICATION 15902.24
FAN COIL UNIT, HUNG FROM STRUCTURE ABOVE BY (4) 1/4" THREADED RODS WITH 1/2" MINIMUM-STATIC- DEFLECTION SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND COOLING COIL. PIPE DRAIN PAN TO SPILL INTO FLOOR DRAIN. SEPARATELY HANG AUXILIARY DRAIN PAN FROM
STRUCTURE.
PROVIDE A 9 INCH X 24 INCH CLEANOUT FABRICATED OF MINIMUM 16 GAUGE STEEL IN SIDE OF
WELDED STEEL KITCHEN GREASE DUCT, BOLTED TO CLEANOUT’S WELDED FRAME OPENING.
BOTTOM EDGE OF CLEANOUT SHALL BE NO LESS THAN 1.5 INCHES ABOVE BOTTOM OF DUCT.
INSULATE CLEANOUT FOR 0 INCHES CLEARANCE WITH UL LISTED FIRE-RATED DUCT WRAP IN
ACCORDANCE WITH UL LISTED INSTRUCTIONS. PROVIDE OUTER 16 GAUGE COMPRESSION
PLATE AND THROUGH BOLTS AS NEEDED. PROVIDE SIGNAGE WITH MINIMUM 1” TALL RED
LETTERS ON ACCESS PANELS’ INSULATION OR COMPRESSION PLATE STATING THE
FOLLOWING: “ACCESS PANEL – DO NOT OBSTRUCT”
WELDED STEEL KITCHEN GREASE DUCTING, FABRICATED OF MINIMUM 16 GAUGE WELDED
STEEL. SUPPORT DUCTING FROM STRUCTURE ABOVE SUFFICIENTLY TO SUPPORT THE
DUCT WEIGHT WITH ITS UL LISTED FIRE- RATED DUCT WRAP INSULATION WEIGHT AND 800
LBS ANYWHERE ALONG DUCT SYSTEM. WRAP DUCTING WITH DUCT WRAP EQUAL TO
VESUVIUS PYROSCAT DOUBLE-LAYER SYSTEM, UL LISTED USING UL 1978 FOR 0 INCH
CLEARANCE AND 2-HR FIRE-RATING. EACH LENGTH OF DUCTING SHALL BE CONTINUOUSLY
EXTERNALLY WELDED LIQUIDTIGHT USING BELL-TYPE CONNECTIONS WITH FILLET WELDS,
OR EDGED-WELDED FLANGES, OR FILLET-WELDED FLANGES.
BOTTOM OF DUCT = 9’-11”
BOTTOM OF DUCT = 12’-3”
PROVIDE A WELDED OR BOLTED DUCT-TO-HOOD CONNECTION. IF BOLTED, USE A 1 INCH X 1 INCH
MINIMUM 16 GAUGE STEEL WELD-ON FLANGE, 1/4 INCH BOLTS ON 4 INCH CENTERS AND AT
CORNERS, AND 1500 DEGREE F RATED GASKET OR SEALANT. SEE FIGURE 7.5.2.2 IN THE 2001 NFPA
96 STANDARD.
STAINLESS STEEL DUCTWORK HARD-CONNECTED TO BIOSAFETY CABINET.
48"X84" SHORT CIRCUIT MAKE-UP AIR KITCHEN EXHAUST HOOD.
WELDED STAINLESS STEEL EXHAUST DUCTING, WRAPPED WITH DUCT WRAP EQUAL TO VESUVIUS
PYROSCAT DOUBLE-LAYER SYSTEM, UL LISTED USING UL 1978 FOR 2-HR FIRE-RATING.
HOT WATER CABINET HEATER MOUNT LOW ON WALL.
MOUNT FAN COIL UNIT ON A 12" RAISED GALVANIZED ANGLE IRON SUPPORT.
REVISION #1 03/17/06
3 REVISION #2 06/20/06
4 REVISION #3 09/11/06
5 REVISION #5 11/06/06
6 REVISION #7 04/25/07
MH-4.0222
7"Ø
7 REVISION #8 08/27/07
6 46
4 4 6
LOCATION OF AHU-10'S DUCT STATIC PRESSURE SENSOR.25
8 REVISION #9 09/24/07
9 02/29/08MSK-11 AND MSK-12
WIRE MOTORIZED DAMPERS TO CLOSE WHEN FANS KEF-1 AND MUAF-1 ARE
STARTED, AND TO OPEN WHEN FANS ARE STOPPED.
08/08/08RECORD DOCUMENTS
10 REVISION #11
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 110 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
06/23/08
27 10
90X22
X1
MVD
UP TO MUAF-1
12X12
90 9060
50X20
X1
250 100
X1
160 140
22X1414X14
80 140
UP TO
KEF-1
X1
60 200 200
350 350
230230
160 160140
T
X2
190 160
200 170
110 760
X1
760 760
12" Ø
MVD
40X16
20X10
140 330
R5
X8
MVD
16X10 12X8
32X14
30X14
"Ø
180 450
16"Ø
16"Ø 14X1414X14
140 140
140 140
60X20
8X8
X1
S7
X1
X1
X1
"Ø
"Ø
MVD
MVD
X1
18X10
X1
500 500
X1
X1
180180
16X12
X1
UPUP
9"
8X8
12"Ø
44X8 44X14
ABOVE CEILING
EF-1
FCU-4
S7 (4)
S
T
EF-2
EF-3
EF-4
8X8
UH-1.1
PROVIDE 12" X 12"MESH HARDWARE CLOTH
OED
8X8
OED
8X8
OED
UH-1.2
OED
T
PROVIDE 12" X 12"MESH HARDWARE CLOTH
UH-1.3
UH-1.4 8X8
M
R6
X1
FCU-6
T
R6
12X10
BACKDRAFT
DAMPER
T
22X22
R7
12X10 R6
12X10 R6
12X10 2525 150
12X10 R690
12"Ø230 230
MVD
390 390
16"Ø
380 380
16"Ø
S5
S5
12X20 EA
DUCT, UP
R5
20X30 SA
DUCT, UP
30X18 EA LOUVER
AND SCREEN
CUH-1.2
12X10
OED
A/C
24X12 EA LOUVER AND
BIRDSCREEN
24X24 EA LOUVER AND
BIRDSCREEN
12X12 EA LOUVER
AND BIRDSCREEN
X1
16X12
340 340
X1
220 220
16X14
X1
14X14
200 200
200200
12X14
X1
X1
200 160
8X
12X12
16X10
X1
26X18
18X18
18X18
26X14
530 500
8"Ø
"Ø
"Ø
X1
T
T
T
T
T T
30X16 14X14
DN DN
DN
DN
X1
X1
DN
DN
FO
T
FO
T
UP
UP
BOD=13'-0"
DN
DN
MM
R2
R2
30X20
BOD=12'-9"
T
120T
T
44X14
22X14
X1
X1
UP TO MUAF-1UP TO MUAF-1
12X10
T
8X
T
T
T
16X14 12X10
R-7
8"Ø 10X10
T
T
8"Ø 8X8
18X12
T
12X12
DN
UP
X1
UP DN
X1
MVD
10X10
8X8
T
T
T
20X14
16X14 12X14
T
T
82X20
X1
12X10
T
10X10
T
16X14
T
10X10
T
8X 8 T
X1
T
10X10
T
10X10
10X8 10X8
VAV-6-1
VAV-6-2
VAV-6-3
VAV-2-12
VAV-2-13
VAV-2-14
VAV-2-15
VAV-2-16
VAV-2-17
VAV-2-8
VAV-2-9
VAV-2-10
VAV-2-11
VAV-2-19
VAV-2-20
VAV-2-21
VA
V-
2-
VAV-2-23
VAV-2-24
VAV-2-29
VAV-2-27
VAV-2-25
VAV-6-4
VAV-6-5
VAV-6-6
VAV-2-2
VAV-2-1
VA
V-
2-
106X36
8X8
12X12
X1
12X12
160180
12X12
T
12X12
VAV-2-18
14X14
X1
X1
VAV-2-4
14X12
X1
8" CHWS, UP
8" CHWR, UP
10X
20X20 32X20 190
14X14
"Ø
"Ø
8" Ø
"Ø
8" Ø
"Ø
"Ø
12X8
X6
T T T
T
DN 18X10,
BOD=11'-8"
18X10, BOD=10'-6"
18X10, BOD=11'-8"
UP 18X18
18X18, ABOVE LOADING
DOCK SOFFIT, UP THROUGH
ROOF TO FAN ON ROOF ABOVE
RHC-1
RHC-2
RHC-3
RHC-4
12"Ø
180 180
EAV-2A
SAV-1 SAV-2
SAV-3 EAV-3
EAV-4
EAV-1
EAV-2B
H H H
H
12X14, BOD=11'-11"14X12, BOD 13'-0"
DN
14X12, BOD=10'-8"
14X12
BOD=11'-1"UP 5"
12X14, UP TO EF-20
ON ROOF ABOVE
20X18 UP TO
AHU-10 ON
ROOF ABOVE
DN
UP
20X18
X1
R2
R2
R2
R2
28X16 24X10
24X8
AutoCAD SHX Text Solar
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
1 2 3 4 5 6
K
J
H
G
F
L
EXAM 5EXAM 6EXAM 7EXAM 8
EXAM 9EXAM 10EXAM 11EXAM 12
EXAM 13EXAM 14EXAM 15EXAM 16
EXAM 17EXAM 18EXAM 19EXAM 20
EXAM 21EXAM 22EXAM 23EXAM 24 TRIAGE GROUP CONSULT ELEC
VITALS
TRIAGE
VITALS
VITALS TRIAGE
CONSULTEXAM 1EXAM 2EXAM 3EXAM 4
EXAM 5EXAM 6EXAM 7EXAM 8
EXAM 9EXAM 10EXAM 11EXAM 12
EXAM 13EXAM 14EXAM 15EXAM 16
EXAM 17EXAM 18EXAM 19EXAM 20
OBSERVATION
EXAM 21EXAM 22EXAM 23EXAM 24 MED.
VITALS
VITALS
VITALS
TRIAGE TRIAGE
GROUP CONSULT
COMM.
1C100
1C1011C102
1C103
1C104
1C105
1C106 1C107
1C108
1C109
1C110
1C111
1C112
1C113
1C114 1C1151C116
1C117
1C118
1C119 1C120
1C121
1C122
1C123
1C124
1C125
1C126
1C127
1C128
1C129 1C130
1C131
1C132
1C133 1C134
1C1351C136 1C137
1C1381C139
1C140
1C141
1C142
1C143
1C144
1C145
1C146
1C147
1C148
1C149
1C150
1C151
1C152
1C153
1C154
1C155
1C156
1C157 1C158
1C159 1C160
1C161
1C162
1C163
1C164
1C165
1C166
1C167
1C168
1C169
1C170
1C171
1C172 1C173
1C174
1C175
1C176
1C1771C178
1C179
1C180
1C181
1C182
1C183
1C184
1C185 1C186
1C187
1C188
1C189 1C190
1C191
1C192 1C193
1C194 1C195
1C196
1C197
1C198
1C199
1C200
1C201
1C202
1C203
1C204
1C205
1C206 1C207 1C208
1C209 1C210
1C211
1C101A
TRIAGE
RECEPTION
RECEPTION
C1-08
C1-09C1-10
C1-11
C1-12
C1-13
C1-14
C1-15
C1-16
C1-17
C1-18
C1-19
C1-20
C1-21
C1-22
C1-23
C1-24
C1-25
C1-26
C1-27
C1-28
C1-29
C1-30
C1-31
C1-25A
C1-25B
C1-17A
1G102
COMP.
BOOTH
1D160
GROUND FLOOR
MECHANICAL PLAN
SECTOR 3- FIRE/SMOKE DAMPERS ONLY
MH-1.01-3 FR & SMK DMPRS
K.MILNER
H. SHEINMAN
08/29/05
MATCHLINE
SEE SHEET MH-1.01-1
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -4
FO
R
CO
NT
IN
UA
TI
ON
MATCHLINE
SEE SHEET MH-1.01-5
FOR CONTINUATION
SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
KEYED NOTES:
MH-4.04
MH-4.06
SUBMITTAL #4 12 / 25 / 05
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
1HOT WATER CABINET HEATER MOUNTED LOW WALL.
SEE MH-1.02-3 FOR CONTINUATION. 1
2 06/20/06REVISION #2
3 REVISION #3 09/11/06
4 REVISION #5 11/06/06
08/08/08RECORD DOCUMENTS
5 REVISION #11 06/23/08
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 140 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 110 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
X2
X2
X2
X2
X2
X2
X2
22X14 110
110110110110
120210
14X12 14X10
8X
18X14
110110110110
110 110 110
110110110
110110110110
110 110 110 160
110 110 110 110
14X12 10X10
20X14
110 110 110
110 110 110
110110110
110 110 110 110 110 160
110180 510
90 90
18X14
100 120
110110110110
160 160 130130
110 110 110
110 110 110
100 100 100 100 120 90 90
190190
14X1412X12
20X1416X1416X10
110 110
110110110110
110 110 110 110
10X10
10X10
14X14
150 130
90170
X2
100110110
110 110 110 110 110
90100
X2
255 255
270 270
70100100100
100 100 100 60 160
X1
X1
18X14
18X14
880 880
14X14 10X10
12X12
10X10
8X
20X20 EAD, UP
18X18
X1
16X16
X1
10X10
10X10
8X
18X12
8X
UP
26X122, UP
36X122, UP
X2
90X22
12X18
UP
DN
UP
S5
74X26
BOD=10'-9"
X1
BO
D= `1
0'- 9"
R5
S5
R5
20X14
EA DUCT
UP
CUH-1.1
ECCENTRIC ELBOW,
WITH SINGLE-THICKNESS
TURNING VANES
2 3
T T
12X12 8X8
T
12X12
T T
12X12
12X26
T
12X12
T
8X8
X1
T
8X8
8X8
T
10X10
T
12X12
T
12X12
T 8X10
T
T
T
12X10
12X12
T
T
10X108"Ø
T
12X12
T
14X18
X1
T 28X14
X1
14X12
T
X1
210X10 20X16
18X14
T
T
X1
8X8
T
8X8
T
10X10
T
T
12X12
T T
12X12
T
8"Ø
T
12X12
TT
8X8 T
T
T
8X10
T
12X12
(TYPICAL FOR ALL
DUCTING UPSTREAM
OF TERMINAL
UNITS)
S4
R4
(TYPICAL FOR ALL
EXHAUST DUCTING
U.N.O.)
VAV-1-22
VAV-1-23
VAV-1-25VAV-1-24
VAV-1-71
VAV-1-70
VAV-1-69
VAV-1-68
VAV-1-67
VAV-1-66
VAV-1-65
VAV-1-64
VAV-1-62
VAV-1-61
VAV-1-60
VAV-1-59
VAV-1-57
VAV-1-58
VAV-1-56
VAV-1-54
VAV-1-53
VAV-1-52
VAV-1-51
VAV-1-50
VAV-1-55
106X36
X2
X2
74X
0X
FO
T
6X
X30
136X33
6X
33X136, UP
30x114, UP
FOT136X33
8X8
10X10
VAV-1-79
X1
X8
12X12
12X10
UP
160 160
VAV-1-78
14X12
VAV-1-63
10X10 VAV-1-77
VAV1-75
VAV-1-76
R4
S4
2,3
9,10
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
L
K
J
H
G
F
K.5
10.8
1G102
LOBBY
HSK
DF
ULTRASOUND
STOR
DRESS
DRESS DRESS
DRESS
DRESS DRESS
CHEST
GRINDWORK ROOMSTORSECWAIT
RECEPT. COMM
VITALS
CAST
WAIT
RECEPT
MRI GANTRY
CLEAN LINEN
WAIT
1B112 1B114 1B115 1B116
1B132
1B133
1B134 1B135
1D100
1D102
1D103
1D104
1D105 1D106 1D107 1D108 1D109
1D110
1D111
1D112
1D113
1D114
1D115
1D116
1D117
1D118
1D119
1D120 1D121
1D122
1D123
1D124
1D125
1D126
1D127
1D128
1D129
1D130
1D131 1D132 1D133 1D134
1D135
1D136
1D139
1D1401D141
1D1421D143
1D144
1D145
1D146
1D148
1D150
1D1511D1521D1531D1541D1551D1561D157 1D158 1D159
1D160
1D162
1D163 1D164
1D165
1D166
1D167
1D168
1D169
1D170
1D171
1D172
1D173
1D174
1D175
1D176
1D177 1D178
1D179
1F100
1F101
1F103 1F104 1F105 1F106
1F107 1F109 1F110 1F111
C1-69
C1-70
C1-71
C1-72
C1-73 C1-74
C1-75
C1-76
C1-77
C1-78
C1-79
C1-80
C1-81
C1-82 C1-83
PEGBD
PE
GB
D
C1-79A
1D109A 1D109B 1D109C 1D109D 1D109E
1D109F 1D109G 1D109H
1D137
LCKRS
SH
EL
VG
SS
CABINET
C1-81A
1B200
1D130A
7 8 9 10 11 12 136
GROUND FLOOR
MECHANICAL PLAN
SECTOR 4- FIRE/SMOKE DAMPERS ONLY
MH-1.01-4 FR & SMK DMPRS
K. MILNER
H. SHEINMAN
SUBMITTAL #3
KEYED NOTES:
10 / 31 / 05 10 / 31 / 05
MH-3.01
MH-3.02
MATCHLINE
SEE SHEET MH-1.01-2
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -3
FO
R
CO
NT
IN
UA
TI
ON
MATCHLINE
SEE SHEET MH-1.01-6
FOR CONTINUATION
M 12
SUBMITTAL #4 12 / 25 / 05
3 2
(TYPICAL FOR ALL
DUCTING UPSTREAM
OF TERMINAL UNITS)
4 3
4 2
(TYPICAL AT ALL
TERMINAL UNITS)
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
EXHAUST FAN WITH SUCTION GRILLE, HUNG FROM CEILING WITH (4)1/4" THREADED RODS AND
1/4" MINIMUM -STATIC-DEFLECTION SPRING HANGERS.
HANG AIR CONDITIONING UNIT ROM STRUCTURE WITH (6)1/4" THREADED RODS AND 1/2" MINIMUM-STATIC-DEFLECTION SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND COOLING COIL. PIPE 3/4" DRAIN FROM AUXILIARY PAN, THROUGH CEILING PENETRATION. SEPARATELY HANG DRAIN PAN FROM STRUCTURE.
ALL MECHANICAL WITHIN THE BOUNDRIES SHALL BE ALUMINUM.
AIR COOLED PROCESS CHILLER FOR MRI EQUIPMENT , ON 12" CONCRETE PAD.
PROVIDE WAVE GUIDE AT EVERY WALL PENETRATION.
HOT WATER CABINET HEATER MOUNTED LOW ON WALL.
HANG FAN COIL UNIT FROM STRUCTURE WITH (4) 1/4" THREADED RODS WITH 1/2" MINIMUM-STATIC DEFLECTION VIBRATION ISOLATORS. PROVIDE 1/2" X 1/2" MESH HARDWARE CLOTH ON FAN OUTLET. PROVIDE SEPARATELY-HUNG
DRIP PAN BENEATH UNIT AND VALVE PACKAGES.
HANG FAN COIL UNIT FROM STRUCTURE ABOVE WITH (4) 1/4" THREADED RODS AND 1/4" MINIMUM-STATIC- DEFLECTION SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND EVAPORATOR COIL. PIPE 3/4" DRAIN FROM AUXILIARY DRAIN PAN, THROUGH CEILING PENETRATION. SEPARATELY HANG
AUXILIARY DRAIN PAN FROM STRUCTURE.
OUTDOOR AIR-COOLED CONDENSER FOR CRACU, ON 12" THICK CONCRETE PAD.
PROVIDE WALL MOUNTED SPEED SWITCH, ON WALL AT LOCATION SHOWN. PROVIDE LOCKED-BOX COVER OVER SWITCH.
EXHAUST FAN, HUNG FROM CEILING WITH (4) 1/4" THREADED RODS AND 1/4" MINIMUM-STATIC-DEFLECTION
SPRING HANGERS AND FLEXIBLE FABRIC DUCT CONNECTORS.
INTERLOCK MOTORIZED DAMPER WITH EF-10 TO CLOSE DAMPER WHEN FAN IS STARTED AND TO OPEN WHEN FAN IS STOPPED.
7"Ø FLEXIBLE NON-METAL HOSES, TO MRI MAGNET.
SEE MH-1.02-4 FOR CONTINUATION.
MOUNT DIFFUSER/GRILLE IN SUSPENDED CEILING, 8'-3" ABOVE FLOOR.15
2 REVISION #1 03/17/06
3 REVISION #2 06/20/06
4 REVISION #3 09/11/06
08/08/08RECORD DOCUMENTS
5 REVISION #11 06/23/08
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 110 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
90X22
100 100
60X20
16X12 10X10 8X8110
100 100 80
120 150 90
50X20
X1
250 100
X2
190 160
140 140
114X30
X3
X2
X1
60X24
X2
110 110 110 80
110110
500120130130
X1
80X24
12X10
X1
130 130
16X10
66X20
120 500 12X12
180 180
555555
60X20
18X12
R5
X1
X1
500 500
X1
X1
UP
12X10
X2
90 90 90 90
38X18
8X8
X1
X1
X1
X1
X1
DN
UP
DN
UP
DN
X1
114X30
8X8
DN
60X24
DN
60X24
BOD=10'-6"
UP
60X30
BOD=10'-0"
DN
UP
60X20
BOD=13'-0"
DN
40X6
44X8
40X14
44X14
FCU-2.2
ABOVE CEILING
EF-1
CUH-1.3
FCU-3.1
X2
X1
CRACU-3
R5
FD6"Ø
10X10
X1
380 380
16"Ø
DN
UP
DN
6" Ø
S5
S5
R5
42X30 EA
DUCT, UP
54X30
BOD=10'-0"
30X18 EA LOUVER
AND SCREEN
12X12
EXHAUST AIR
LOUVER AND SCREEN
(2)
48X12
EXHAUST LOUVER
AND SCREEN
R5
AIR-COOLED
CONDENSER
FOR CRACU-3
MRI EQUIPMENT
DEDICATED CHILLER
AIR-COOLED
CONDENSER FOR
CRACU-2
X1
120T
T
82X20
X1
12X10
10X10
T
T
X1
14X12
T
18X14
T
12X12
900 900 900 900
X1
T
210 210
210210
T
T
T
130 140
T
10X10
8X8
X1
8X8
X1
X1
X1
BO
D=
9'- 0"
27X14
EF-17
20X8
"Ø
"Ø
S
EF-10
EF-18
EF-9
12X12 DN
X3
X1
T
T
X1
T
42014 X1
X2
TT
UP
DN
BOD=11'-9"
BOD=11'-0"
UP
UP
X2
BO
D=
'-0
CRACU-2
8X8 T
T
10X10
T
16X14
X1
T
24X12
12X10
DN
UP
T
14X12
T
X1
T
12X10
T
X812X12
T
T
X1
4 UP
DN
X1
T
14X12
X1
20X16
14X14
FD
8X8
T
T
560550
T
55014 X1
VA
V-
2-
VAV-2-23
VAV-2-24
VAV-2-29
VAV-2-27
VAV-2-25
VAV-2-26
VAV-2-28
VAV-2-30
VAV-2-31
VAV-2-33
VAV-2-32
VAV-2-34
VAV-2-35
VAV-2-36
VAV-2-37
VAV-2-38
VAV-2-66
VAV-2-65
VAV-2-64 VAV-2-63
VAV-2-62
VAV-2-61
VAV-2-60
VAV-2-59
VAV-2-58
VAV-2-57
33X136, UP
30x114, UP
T
X1
T
X8
14"Ø
10"Ø
14X12
X1
14"Ø
X1
X1
VAV-2-69
6"Ø
DN
DN UP
VAV-2-70
10X12
VAV-2-67
UP
UP
UP
DN
DN
UP
UPDN
DN
DN
8" Ø
20X20 32X20 190
14X12
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
1 2 3 4 5 6
F
E
D
C
B
A.9
5.2
CHIEF SEC./ WAIT PHYS LCPO PA OFFICE PA OFFICE PHYS / WAIT DOC. OFFICE
PSYCH TESTPSYCH LCPO
EXAM 3
EXAM 8
EXAM 9
PA OFFICE
STOR
EXAM 1EXAM 2EXAM 3EXAM 4EXAM 26 EXAM 25
AUDIO BOOTH
EYE SCREEN
EXAM 1
EXAM 5EXAM 4 EXAM 6
EXAM 2
AMIC TREAT PREV MED
IMMUN
EXAM 7
IDC OFFICE
1G103
1G104
1G105
1C192 1C193 1C196 1C198 1C200 1C202 1C204 1C206 1C207 1C208
1C209 1C210
C1-29
C1-30
C1-31
C1-32
C1-33
C1-34
C1-35 C1-36
C1-37 C1-38C1-39
C1-40
C1-41
C1-42
C1-40A C1-41A
C1-41B
C1-41C
C1-36A
OFFICE
1E100 1E101
1E102
1E103
1E104
1E105
1E106
1E107
1E108
1E109
1E110
1E111
1E1121E1131E1141E115
1E116 1E117
1E118
1E119
1E120
1E121
1E122
1E123
1E124
1E125
1E126
1E127
1E128
1E129
1E130
1E131
1E132
1E133
1E134
1E135
1E1361E137
1E138
1E139
1E140
1E1411E142
1E143
1E144
1E145
1E146
1E147
1E148
1E149
1E1501E151
1E152
1E153
1E154
1E155
TREAT. 11
TREAT. 1
ELEC
WAIT
1F143
1F144
1F147
GROUND FLOOR
MECHANICAL PLAN
SECTOR 5- FIRE/SMOKE DAMPERS ONLY
MH-1.01-5 FR & SMK DMPRS
K. MILNER
H. SHEINMAN
08/29/05SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
KEYED NOTES:
HOT WATER CABINET HEATER MOUNTED LOW ON WALL.
ESCUTCHEON IN CEILING PENETRATION. SEPARATELY HANG AUXILIARY DRAIN PAN FROM STRUCTURE.
HANG FAN COIL UNIT FROM STRUCTURE ABOVE WITH (4) 14" THREADED RODS AND 1'4" MINIMUM-STATIC-DEFLECTION
LOCATION OF AHU-1 DUCT STATIC PRESSURE SENSOR.3
SUBMITTAL #4 12 / 25 / 05
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -6
FO
R
CO
NT
IN
UA
TI
ON
MATCHLINE
SEE SHEET MH-1.01-3
FOR CONTINUATION
SEE MH-1.02-5 FOR CONTINUATION.4
(TYPICAL FOR ALL DUCTING UPSTREAM
OF TERMINAL UNITS)
(TYPICAL FOR ALL
RETURN DUCTING)
(TYPICAL FOR ALL
EXHAUST DUCTING
U.N.O.)
2 4
(TYPICAL FOR ALL TERMINAL UNITS)
FINAL SUBMITTAL FULLY SPRINKLERED
1SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND COOLING COIL.
PIPE 3 4" DRAIN FROM AUXILIARY DRAIN PAN THROUGH CEILING TO SPILL ONTO 1G100. PROVIDE CHROME
1 1
2 REVISION #2 06 / 20 / 06
3 REVISION #3
FINAL SUBMITTAL 02/02/061
09/11/06
4 REVISION #5 11/06/06
08/08/08RECORD DOCUMENTS
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 8X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 100 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
5 REVISION #11 06/23/08
X1
X1
22X1614X1412X12
16X14
X1
12X12
16X14 10X10
X1
X1
X1
160 140140140160
110110110110110
110170
140 140
110 110 110 110
100 110
110110
110110
140140 140140
100110 110110
110 110 110 110 110
7060110110110100
275275 110 110110110
110 110 120 120
160190
150150
22X14 110
110110
110110 110
110110 120210
14X12 14X10
8X
110110110110
16X14
6" Ø
6" Ø
14X14
12X
10X10
90 90
110110
26X12
X1
X1
S5
DN
X1
200 200
40X6
44X8
40X14
44X14
FCU-2.3
ABOVE CEILING
UP
DN
X1
DN
6"Ø
500 500
18X18
EAD, UP
S5
R5
S5
R5
R5
CUH-1.4
T
8"Ø
T
12X12
TT
8X8
12X12
T
12X10
T
12X10
X1
X1
T
24X12
T
X1
X1
20X10
X1
X1
10X10
T
12X12
T
T
10X10 16X14
T
12X10
T
DN
X1
X1
T
12X10
T
8X8
8X8
T
T
8X8
8X8
T
T
8X
T T
8X
T
8X
T
T
8X
T
8X
T
8X
T
8X
T
X1
X1
T
T
T
12X12 AP
12X12
T
8X
VAV-1-51
VAV-1-50
VAV-1-49
VAV-1-47
VAV-1-46
VAV-1-74
VAV-1-73
VAV-1-44
VAV-1-43
VAV-1-41
VAV-1-39
VAV-1-38
VAV-1-30
VAV-1-48
VAV-1-45
VAV-1-40
VAV-1-42
VAV-1-37
VAV-1-35
VAV-1-34
VAV-1-33 VAV-1-32 VAV-1-29
VAV-1-28 VAV-1-27
VAV-1-26VAV-1-31
VAV-1-36
10X10
UP
12X10
UP
UP
10X10
10X8
VAV-2-68
DN UP
VAV-2-70
X1
UP
UP
120 200
T
GROUND FLOOR
MECHANICAL PLAN
SECTOR 6- FIRE/SMOKE DAMPERS ONLY
MH-1.01-6 FR & SMK DMPRS
K. MILNER
H. SHEINMAN
08/29/05SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
MATCHLINE
SEE SHEET MH-1.01-4
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.01 -5
FO
R
CO
NT
IN
UA
TI
ON
SUBMITTAL #4 12 / 25 / 05
(TYPICAL FOR ALL EXHAUST
DUCTING, U.N.O.)
(TYPICAL FOR ALL DUCTING
UPSTREAM OF TERMINAL UNITS)
4 2 (TYPICAL OF ALL TERMINAL UNITS)
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
06/20/062 REVISION #2
3 REVISION #3 09/11/06
4 REVISION #5 11/06/06
08/08/08RECORD DOCUMENTS
REVISION #11 06/23/08
PROJECT NUMBER
DRAWING NUMBER
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
SEC 1
SEC 3
SEC 2
SEC 4
SEC 5 SEC 6
1ST FLOOR PLAN
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
F
E
D
C
A
7 8 9 10 11 12 136
1G103
LOBBY
1G104
LOBBY
1G105
VEST
DF
TREAT. 2
TREAT. 3 TREAT. 4 TREAT. 5
TREAT. 6 TREAT. 7 TREAT. 8 TREAT. 9 TREAT. 10
TREAT. 11 TREAT. 12 TREAT. 13 TREAT. 14 TREAT. 15 TREAT. 16
WHL / LIT
LCPO
STORAGE
TRAINING AIDS
EMGEXAM
ELEC
EXAM EXAM
EXERCISE
WAIT
VA CLINIC OFFICENAVY TECH OFFICE
STOR
GRINDWORK ROOMSTORSECWAIT
RECEPT. COMM
CLEAN LINEN1D162 1D167 1D178
1F100
1F101
1F102
1F103 1F104 1F105 1F106
1F107
1F108
1F109 1F110 1F111
1F112
1F113
1F114
1F115
1F116
1F117
1F118
1F119 1F120
1F121
1F122
1F123
1F124
1F1251F126
1F127
1F128
1F129
1F130
1F131
1F132
1F133
1F134
1F135
1F136
1F137
1F138
1F1391F140 1F141
1F142
1F143
1F144
1F145 1F146
1F147
1F148 1F149
1F150
1F151
1F152
1F153
1F154
1F155
1F156
1F157
C1-60
C1-61
C1-62
C1-63
C1-64
C1-65
C1-66
C1-67
C1-68 C1-69
C1-70
C1-60A
WHL / LIT
C1-64A
EXAM
1F150A
X1
X1
X1
20X16
110110110110
110 110 110 110 110 70
90 90 90 90
120 120 120
120 120 120
100 100
60X20
16X12 10X10 8X8110
100 80
120 150 90
X2
X2
110 110
14X10
X1
895 895
895 160
X1
110 110 110 80
110 180
26X12
X1
X1
X1
12X10
DN
UP
DN
DN
40X6
44X8
40X14
44X14
UP
6"Ø
32X20
BOD=13'-0"
36X18
DN
UP
DN
X2
S5
S5
R5
CUH-1.5FCU-3.2
R5
20X10
X1
X1
X812X12
T
X1
T
X1
X1
325325
325325325
X1
X1
16X12
X1
X1
UP DN
8X8
UP
T
DN
16X14
20X16
T
14X14
T
8X8
T
8X
T
12X10
T
8X8
T
8X8 T
8X8
8X8
8X
T
12X10
T
T
10X1010X10
T
T
10X10
14X12
T
T
X1
X1
X1
T
FD
8X8
VAV-2-57
VAV-2-71
VAV-2-39
VAV-2-40
VAV-2-41
VAV-2-42 VAV-2-44
VAV-2-43
VAV-2-45
VAV-2-47
VAV-2-46
VAV-2-48
VAV-2-49
VAV-2-50
VAV-2-51
VAV-2-52
VAV-2-53
VAV-2-54
VAV-2-56
16X14
T
T
10X8
X1
X1
X1
VAV-2-69
VAV-2-68
6"Ø
DN
DN UP UPDN
VAV-2-55
T
T
SECOND FLOOR
SECTOR 1- FIRE/SMOKE DAMPERS ONLY
MH-1.02-1 FR & SMK DMPRS
K. MILNER
H. SHEINMAN
08/29/05
KEYED NOTES:
SUBMITTAL #3 10 / 31 / 0510 / 31 / 05
WELDED STAINLESS STEEL EXHAUST DUCT.
REFER TO MH-4.05 FOR CONTINUATION.
14X14 AP, LOW TO FLOOR.
8X8 AP, LOW TO FLOOR.
(2) 24X24 AP, LOW TO FLOOR.
SUBMITTAL #4 12 / 25 / 05
MATCHLINE
SEE SHEET MH-1.02-3
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.02 -2
FO
R
CO
NT
IN
UA
TI
ON
WELDED STAINLESS STEEL DUCTING.
SEE MH-1.01-1 FOR CONTINUATION.
2 4
2 3
44 4
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/061
LOCATION OF AHU-3'S DUCT STATIC PRESSURE SENSOR.
06/20/06REVISION #22
3 REVISION #3
09/11/06
08/08/08RECORD DOCUMENTS
4 06/23/08
(TYPICAL AT ALL
TERMINAL UNITS)
(EXHAUST
DUCT)
(EXHAUST DUCT)
(RETURN DUCT)
(TYPICAL FOR ALL DUCTING
UPSTEAM OF TERMINAL UNITS)
(TYPICAL FOR ALL
DUCTING UPSTREAM
OF TERMINAL UNITS)
PROVIDE A 4" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 6X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 110 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
PROVIDE A 5" Ø SPIN-IN IN TRUNK DUCT EQUAL TO FLEXMASTER FLD/B03 AND 4"Ø
SHEETMETAL DUCT TRANSITIONING TO 8X6 AIR GRILLE BOOT. PROVIDE A 6X6 SUPPLY AIR
REGISTER EQUAL TO TITUS 272-FS. SHEETMETAL DUCT SHALL BE MIN. 26 GAUGE, CONSTRUCTED TO 2" W.C. SMACNA PRESSURE CLASS. WRAP DUCT WITH 2" THICK, 3/4 PCF FIBERGLASS DUCT WRAP WITH FSK VAPOR BARRIER JACKET. SET SPIN-IN'S DAMPER TO ALLOW 180 CFM AIR. SEAL SPIN-IN AND A DUCT JOINTS WITH SHEETMETAL SCREWS AND MASTIC. ALLOW MASTIC TO SET IN
UNPRESSURED DUCT FOR A MIN. 12 HOURS.
REVISION #11
PROJECT NUMBER
DRAWING NUMBER
Office of Facilities
Management
SHEET TITLE
HEERY INTERNATIONAL, INC.
999 PEACHTREE STREET, NE
ATLANTA, GEORGIA 30309
CONSULTANTS: PROJECT NAME
COPYRIGHT 2005 BY HEERY
INTERNATIONAL, INC. ALL RIGHTS
RESERVED.THIS DOCUMENT IS
THE PROPERTY OF HEERY
INTERNATIONAL, INC. IT IS TO BE
USED ONLY FOR THE SPECIFIC
PROJECT IDENTIFIED OR REFERRED
TO HEREIN AND IS NOT TO BE USED
ON OTHER PROJECTS OR EXTENSIONS
TO THIS PROJECT, IN WHOLE OR PART,
EXCEPT BY EXPRESS WRITTEN
AGREEMENT WITH AND COMPENSATION
TO HEERY INTERNATIONAL, INC.
JOINT AMBULATORY CARE CENTER
A JOINT/SHARED VA/DoD (NAVY) PROJECT
REVISIONS DATE KEY PLAN STAMP
05090-00
BUILDING NUMBER
N/A
TRUE
NORTH
DRAWN
CHECKED
DATE
0 8' 16'
VA GULF COAST VETERANS HEALTH CARE SYSTEM
6425 OFFICE PARK PLAZA
NORTH PENSACOLA BLVD.
PENSACOLA, FL 32503
1/8" = 1'-0"
SCALE
2ND FLOOR PLAN
SEC 1
SEC 3 SEC 4
SEC 5
PROJECT
NORTH
VA FORM 08-6231, OCT 1978
6"
6"
6"
6"A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
987654321 on e e igh th inc h = on e f oo t ( for a sh ee t p lot ted at
"x on e q ua rte r in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee ei gh ths in ch on e f oo t ( for a sh ee t p lot ted at
"x on e h alf in ch on e f oo t ( for a sh ee t p lot ted at
"x thr ee qu ar ter s i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e i nc h = on e f oo t ( for a sh ee t p lot ted at
"x on e a nd on e h alf in ch es on e f oo t ( for a sh ee t p lot ted at
"x thr ee in ch es on e f oo t ( for a sh ee t p lot ted at
"x
$$DATE$$
$$TIME$$
$$$$$$$$$$$$FILENAME_LONG$$$$$$$$$$$$
$$$$$$PLOTTER$$$$$$
$$$$$$$$$$$$PENTABLE$$$$$$$$$$$$
user:
date plotted:
time plotted:
file name & path:
pen table:
plotter:
$$USER$$
US
ER
_F
ILE
AL
L_
PL
OT
_IN
FO
SEC 2
SEC 6
Q
P
N
Q.8
1 2 3 4 5 6
M
L
Q.9
5.2 5.8
R
2A100
C2-01
2A101
2A102
2A103
2A104
2A105
2A106
2A107
2A108
2A109
2A110
2A1112A112
2A113
2A114
2A115 2A1162A1172A118
2A119 2A120
2A121
2A122 2A123 2A124
2A125
2A126 2A127 2A128 2A129
2A130
2A131 2A132
2A133
2A134
2A135
2A136
2A137
2A138
2A1392A140
2A141
2A142
2A1432A144
2A145
2A146
2A147
2A148
2A149
2A150
2A1512A152
2A153
2A154
2A155
2C100
2C101
2C102
2C103
2C104
2C105
2C106
2C1072C108
2C109
2C110
2C111
2C112
2C113
2C114
2C115 2C119 2C122
2C125
C2-02
C2-03
C2-04
C2-05
C2-06
C2-07
2A100A
C2-08C2-09
C2-10
C2-11
C2-12C2-13C2-14
C2-15 C2-16
C2-15A
C2-03A
2G100
2G101
2G102
2G103
2G104 2G105
2G106
1G101
IMMIT
WAIT
WAIT
X2
215 215
110110110
175 175
450 450
110110
X2
12X12
600 600
215 215
160 160
120 120 120
150 120
100100100100
120 120 120 120
150 150 150 150 140
270 160
50100
90 90
120 120 120
120 120 120
210 160 160
100 100 100 100
200130
150150 150 150 140 270
16X12
8X
8X8
12X12 S5
X1
16X16
16X12 10X10
14X12
14X12 12X10
16X12
20X12
12X12
X1
10X10
22X12 16X12
X1
12X12 10X10
155 155
60X20
60X20
S6
S6
S6
S6
S6
S6
X1
X1
X2
4, HI
GH
18X6, DN
26X122, DN
10"Ø
14"Ø
"Ø
18X10
X1
18X24
18X14
UP
UP
X1
20X12
0X
FD
UP
450450
14X14 AP
16X16, AP
FD FD
36X120, UP
14"Ø M M
22X22
R5
R5
S5
24X24 AP
(TYP. 2)
24X24 AP
(TYP. 2)
20X14 EA
DUCT, DN
S6
S610X10
T
8X8
T
8X
T
8X
T
8X
T
8X
8X
TTT
14X14
X1
12X12
8X8
T
T
8X
T
8X8
TT
8X8
DN
10X10
T
12X10
T
12X10
14X14
T
12X12 10X10
12X12
UP DN
12X10
8X8 10X8
T
12X12
12X10
T
8X8
T
14X18
T
12X12
8"Ø UP
T
8X8
T
14X12
12X10
T 14"Ø
10"Ø 14X18
T
14X18
T
X1
T
X2
12X12115
T
S6
S6
S6
S6
S6
S6
16X16 AP
20X12
12X20 DN
S6
X1
X1
S6
S6
X1
S6
X1
S6
S6
X1
X1
20X12
12X20 DN
T
X1
X2
SILENCER S-1
IN RISER
VAV-3-1
VAV-3-2
VAV-3-3
X1
T
10X8
10X8
X1
VAV-3-10
VAV-3-12
VAV-3-13
T
VAV-3-14
VAV-3-15
VAV-3-16
VAV-3-17
VAV-3-18
X1
T
VAV-3-19
VAV-3-20 VAV-3-21
10X10VAV-3-22
VAV-3-23
VAV-3-24
VAV-3-25100
VAV-3-26
VAV-3-28
VAV-3-29
VAV-3-27
VAV-3-30
VAV-3-31
VAV-3-32
VAV-3-33
VAV-4-15
42X120, UP
TRANSITION 36X120 AT
SILENCER BOTTOM TO
33X106 ABOVE 2ND
FLOOR SLAB
36X120, DN
VAV-3-4VAV-3-5VAV-3-6VAV-3-7VAV-3-8
VAV-3-9
VAV-3-11
12X12
TT
8X
8X
T
X1
17,18,19,20,21
22,23
25,26
SECOND FLOOR
SECTOR 2- FIRE/SMOKE DAMPERS ONLY
MH-1.02-2 FR & SMK DMPRS
K. MILNER
H. SHEINMAN
08/29/05
KEYED NOTES:
SUBMITTAL #3 10 / 31 / 05 10 / 31 / 05
MATCHLINE
SEE SHEET MH-1.02-4
FOR CONTINUATION
MA
TC
HL
IN
E
SE
E
SH
EE
T
MH
-1
.02 -1
FO
R
CO
NT
IN
UA
TI
ON
8"Ø FLEXIBLE DUCT DRD W/MVD, TO CONNECT TO AUDIO BOOTH SILENCER.
38X14 EXHAUST AIR DUCT TO MECHANICAL ROOM ON THIRD FLOOR. SEE THIRD
FLOOR FOR CONTINUATION.
CONTINUED ON MH-4.05.
12X12 KITCHEN EXHAUST DUCT FROM FIRST FLOOR TO KEF-1.
12X12 MAKE UP AIR DUCT FROM FILTERED SUPPLY AIR CHAMBER.
AIR COOLED CONDENSER TO BE MOUNTED ON FLASHED EQUIPMENT RAILS.
SUSPEND FAN COIL UNIT FROM THE STRUCTURE ABOVE WITH (4) 1/4" THREADED RODS WITH
1/4" MINIMUM-STATIC-DEFLECTION SPRING HANGERS .
SUPPORT AIR CONDITIONER ON A 12" TALL FLOOR STAND.
HANG FAN COIL UNIT FROM STRUCTURE ABOVE WITH (4) 1/4" THREADED RODS AND 1/4" MINIMUM- STATIC-DEFLECTION SPRING HANGERS. PROVIDE AN AUXILIARY DRAIN PAN BENEATH VALVE SET AND EVAPORATOR COIL. PIPE 3/4" DRAIN FROM AUXILIARY DRAIN PAN THROUGH CEILING TO SPILL
ONTO 1G100. PROVIDE CHROME ESCUTCHEON IN CEILING PENETRATION. SEPARATELY HANG
AUXILIARY DRAIN PAN FROM STRUCTURE.
WELD STAINLESS STEEL EXHAUST DUCT FROM ROOM 1B120. WRAP DUCT WITH DUCT WRAP EQUAL TO VESUVIUS PYROSCAT DOUBLE-LAYER SYSTEM, UL LISTING USING UL 1978 FOR 2-HOUR FIRE RATING.
SUBMITTAL #4 12 / 25 / 05
4 2
(TYPICAL AT ALL
TERMINAL UNITS)
(RETURN)
3 2
2 2
(TYPICAL AT ALL
DUCT UPSTREAM OF
TERMINAL UNITS)
FINAL SUBMITTAL FULLY SPRINKLERED
FINAL SUBMITTAL 02/02/06
2 06/20/06REVISION #2
3 REVISION #3 09/11/06
4 REVISION #5 11/06/06
REVISION #7 04/25/07
6 REVISION #8 08/27/07
PARTIAL PLAN
SCALE:1/4"=1'-0"
MH-102-2
12X14, DOWN
14"Ø FLANGE (TYP.)
14"Ø
ROOF EQUIPMENT RALI
WIT RESTRAINT STRAP
(TYP.)
PRESSURE SENSOR
6"X6" MOTORIZED CONTROL
DAMPER
FAN EF-20
DISCHARGE CONE, 16"X16" OUTLET
WITH 1/2" X 1/2" S/S MESH
PROVIDE A 16X16 AP, LOW TO FLOOR.
PROVIDE A 24X24 AP, LOW TO FLOOR.
SEE MH-1.01-2 FOR CONTINUATION.
RESTRAIN AHU FROM WIND LOADS WITH MINIMUM FOUR (4) STAINLESS STEEL CABLES, MIN. 3/16 INCH
DIAMETER, TIED TO ROOF ANCHORS. SUPPORT AHU ON ROOF CURB, 18" ABOVE ROOF SKIN.
KEYED NOTES: ( APPLIES TO 2/MH-1.02-2 ONLY)
PROVIDE STRUCTURAL FLASHABLE DUCT CURB, FABRICATED ON MINIMUM 14 GAGE WELDED GALVANIZED STEEL AND ATTACHED TO ROOF DECK WITH EXPANSION ANCHORS ON 12” CENTERS (TWO PER SIDE), MINIMUM 3” EMBED. PROVIDE STAINLESS STEEL CURB CAP, ATTACHED TO CURB WITH CADMIUM-PLATED FASTENERS ON 12 INCH CENTERS (MINIMUM 2 PER SIDE). FILLET WELD EXHAUST DUCT PENETRATION THROUGH CURB CAP. PAINT ALL WELDS ON GALVANIZED METAL WITH GALVANIZING PAINT, MINIMUM 2 COATS.
FABRICATE DUCTING ABOVE ROOF OF WELDED 14 GAUGE TYPE 304 STAINLESS STEEL.
SE…