Attachment 1 -IFC-DESIGN-ANALYSIS - Replace Pump Station and Controls SA.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24224B0026
About this file
This document is a Design Analysis Report for the "Replace Pump Station and Controls, Building 176" project (Contract No. 36C24219C0179) at the VA Community Living Center St Albans Campus in Jamaica, NY.
The report provides the technical basis of design for the project, which involves replacing six water booster pumps, associated valves and controls, and electrical switchgear in the existing pump station. The project also includes installing a new controls conduit between Buildings 176 and 92 on the campus. Key details covered include the existing pump station configuration and operations, applicable codes and standards, architectural/structural/civil/plumbing/electrical design scopes, and equipment details. The report was prepared by D2X Associates, a Service-Disabled Veteran-Owned Small Business (SDVOSB), in partnership with several engineering firms. It was submitted as the Issued for Construction (IFC) design package on September 29, 2023.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24224B0026 0009.docx | DOCX document | |
| 36C24224B0026 0008.docx | DOCX document | |
| 36C24224B0026 0007.docx | DOCX document | |
| Attachment C - Responses to RFI.pdf | ||
| 36C24224B0026 0006.docx | DOCX document | |
| Attachment B - Responses to RFI.pdf | ||
| 36C24224B0026 0005.docx | DOCX document | |
| 36C24224B0026 0004.docx | DOCX document | |
| Attachment A - Responses to RFI.pdf | ||
| 36C24224B0026 0003.docx | DOCX document | |
| 36C24224B0026 0002.docx | DOCX document | |
| 36C24224B0026 0001.docx | DOCX document | |
| S04 - Sign In Site Visit - 36C24224B0026 Replace Pump Station and Controls.pdf | ||
| Attachment 5 FAR 52.225-2 BUY AMERICAN CERTIFICATE.pdf | ||
| Attachment 4 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING Certificate of Compliance.pdf | ||
| 36C24224B0026_1.docx | DOCX document | |
| 013200 Construction Documentation.docx | DOCX document | |
| Attachment 2 -IFC-Drawings Replace Pump Station and Controls SA.pdf | ||
| Attachment 3 - IFC MASTER SPECS SA Pump 360A4-17-520 092823 R3.pdf |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Replace Pump Station and Controls Project No. 630A4-17-520
Contract No.: 36C24219C0179
Department of Veterans Affair
Design Analysis Rev 0 Issued for Construction 09/28/23
Place of Performance VA Community Living Center St Albans Campus
179-00 Linden Ave & 79 Street Jamaica, NY 11425
Contract ing Off icer Representat ive Azhar.Hogue@va.gov
D2X Associates a dba of D2XConstruction LLC a SDVOSB
259 St. Ives Drive, Talent, OR 97540, Headquarters 442 Chelsea Avenue, West Babylon, NY 11704, Branch Office
541-944-8768 bdxinfo@gmail.com Daniel Davis, President
Partners O’Brien & Gere Engineers, Inc. (OBG)
163 North Wellwood Avenue, Suite 6, Lindenhurst, NY 11757 18 Link Drive, Binghamton, NY 13904
333 West Washington Street, Syracuse, NY 13221
Tolman Engineering, Architecture & Surveying, PLLC 3610 Lawson Road, Jamestown, NY 14701
Trophy Point, LLC 4588 South Park Avenue, Blasdell, NY 14219 mailto:bdxinfo@gmail.com
Intended for
Department of Veterans Affairs
Document type
Final Design Analysis Report IFC Submission
Date
September 29, 2023
[Text - If no optional text is needed then remember to delete the fields.]
REPLACE PUMP STATION
AND CONTROLS,
BUILDING 176
ST. ALBANS, VA
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
ISSUED FOR CONSTRUCTION REV 0
REPLACE PUMP STATION AND CONTROLS, BUILDING 176
ST. ALBANS, VA
Project name Replace Pump Station and Controls, Building 176 Project no. 25806/74526 Recipient Department of Veterans Affairs Document type Preliminary Design Analysis Report Version 5 Date September 29, 2023 Prepared by Todd M. Farr, PE, LEED AP BD+C, CIPE, CEM Checked by Todd M. Farr, PE, LEED AP BD+C, CIPE, CEM Approved by Todd M. Farr, PE, LEED AP BD+C, CIPE, CEM Description IFC Submission
This copyrighted material represents the proprietary work product of Ramboll. This material was prepared for the specific purpose of securing a contract with the above client. No other use, reproduction, or distribution of this material or of the approaches it contains, is authorized without the prior express written consent of Ramboll. However, the recipient may make as many copies of this document as deemed necessary for the sole purpose of evaluating this document for final selection and award.
© 2020 All Rights Reserved
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
CONTENTS
1. Introduction 3
2. Background 4
3. Environmental Basis of Design 5
4. Architectural Basis of Design 6
4.1 Scope of Work 6
4.2 Applicable Codes and Standards 6
4.3 Code Review 6
4.4 Masonry Work 6
5. Structural Basis of Design 7
5.1 Scope of Work 7
5.2 Applicable Codes and Standards 7
6. Civil Basis of Design 8
6.1 Scope of Work 8
6.2 VA Design Manuals and Guides 8
6.3 Site Phasing 8
7. Plumbing Basis of Design 9
7.1 Background 9
7.1.1 Building 176 – Existing Water Booster Pump Station 9
7.2 Scope of Work 11
7.2.1 Building 176 – Pump Station Booster Pump Area 12
7.2.2 Building 176 – Pump Station Shallow Pipe Trench Area 12
7.2.3 Building 176 – Pump Station Deep Pipe Trench Area 12
7.3 Applicable Codes and Standards 12
8. Electrical Basis of Design 13
8.1 General Demolition 13
8.2 Electric Service 13
8.3 Power Distribution System and Devices 13
8.4 Branch Circuits 14
8.5 Grounding Systems 14
8.6 Lighting System 14
8.7 Fire Alarm System 14
8.8 Applicable Codes and Standards 15
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
TABLE OF TABLES
Table 1. Existing Water Booster Pumps Description 9 Table 2. Existing Pump Operation Pressure Set Points 11
TABLE OF FIGURES
Figure 1. Missing Dry Pit Vertical Turbine Pump (P1) 10 Figure 2. Missing Reducer Connection to Surge Valve (P2) 10
APPENDICES
Appendix 1 Plumbing Manufacturers’ Data/Cut Sheets
Appendix 2 Lighting Simulations
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
1. INTRODUCTION
The purpose of this design analysis is to present the basis of design information for review by the Department of Veterans Affairs (VA) personnel. This design analysis has been separated into sections as follows:
• Section 1 – Introduction
• Section 2 – Background
• Section 3 – Environmental Basis of Design
• Section 4 – Architectural Basis of Design
• Section 5 – Structural Basis of Design
• Section 6 – Civil Basis of Design
• Section 7 – Plumbing Basis of Design
• Section 8 – Electrical Basis of Design
D2X ASSOCIATES 09/28/23
2. BACKGROUND
The VA desires to replace the existing pump station and controls in Building 176. The project includes:
• Replace six pumps, valves, accessories and controls. Reuse majority of the existing piping.
• Replace electrical switchgear for the six pumps.
• Connect the meter bypass valve, surge valves, flow meters, tank level sensors, pump VFDs and pressure switches pump to new DDC system and connect to existing BMS systems.
• Install control conduit from Building 176 to Building 89.
D2X ASSOCIATES 09/28/23
3. ENVIRONMENTAL HEALTH AND SAFETY BASIS OF
DESIGN
The VA stated that within our area of work there is no asbestos-containing materials (ACMs).
If ACM is found during construction, the contractor shall notify the VA contracting officer.
Tank cleaning and entry shall follow OSHA CFR 1910.146 and Veteran Affairs design standards for confined space entry.
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
4. ARCHITECTURAL BASIS OF DESIGN
4.1 Scope of Work
Architectural work includes clean up, patching and finish repair work as associated with the new control conduit in the Building 176 pump room. New self-closing safety gates will be added to existing trench access opening guardrails. New fire extinguisher cabinets will be provided where fire extinguishers are not mounted in cabinets. Infection Control Risk Assessment and Life Safety Plans will also be provided.
4.2 Applicable Codes and Standards
The following codes and standards will be used for this project:
• National Fire Protection Association (NFPA); NFPA 101, Code for Life Safety
• International Building Code 2015 (IBC, as Adopted by New York State)
• New York City (NYC) Building Code
• VA Design Standards
4.3 Code Review
The code review will be based on the above-mentioned codes and standards, and will address the following code requirements:
• Existing Occupancy Classification: IBC Chapter 3
• Group U: Utility and Miscellaneous
• Existing Construction Classification: IBC Chapter 6
• Existing construction type assumed to be IIB
• Height and Area Requirements
• Existing not applicable to the project. No height or area modifications.
• Fire Resistance Rating for Building Elements
• Building is not occupied and fire barriers are not required
• Means of Egress
• The existing egress path will be maintained throughout construction.
4.4 Masonry Work
• Patch and repair work as required
D2X ASSOCIATES 09/28/23
5. STRUCTURAL BASIS OF DESIGN
5.1 Scope of Work
The structural scope of work includes the design of required structural modifications to the existing building to accommodate:
• Modifications to the existing mezzanine to accommodate new vertical pump motors if and where required.
• Concrete maintenance pads for mechanical equipment where required
5.2 Applicable Codes and Standards
The following codes and standards will be used for this project:
• General
• American Society of Civil Engineers (ASCE); ASCE 7-10, Minimum Design Loads for Buildings and Other Structures (ASCE 7)
• International Building Code 2015 (IBC, as Adopted by New York State)
• Structural Steel
• American Institute of Steel Construction (AISC); AISC 360-10, Specification for Structural Steel Buildings
• Research Council on Structural Connections (RCSC) Structural Bolting Specification
• American Welding Society (AWS); AWS D.1.1-10, Structural Welding Code – Steel
• Concrete
• American Concrete Institute (ACI); ACI 318-11, Building Code Requirements for Structural
Concrete
• Concrete Reinforcing Steel Institute (CRSI); CRSI MSP-2-09, Manual of Standard Practice
D2X ASSOCIATES 09/28/23
6. CIVIL BASIS OF DESIGN
6.1 Scope of Work
The civil scope of work includes the design to accommodate an underground controls conduit run between Buildings 92 and 176 on the St Albans VA Medical Center campus. A general summary of the construction items required to provide the conduit run is provided below.
• Trenching for controls conduit from Building 176 to Building 92
• Underground conduit line encased in concrete
• Backfill and compaction
• Electrical manholes
• Erosion and sediment control
• Building exterior wall penetrations
• Restoration of surfaces (pavement, sidewalk, curbs, and turf)
• Construction phasing
A topographic survey of the proposed underground controls conduit route was completed by Dewberry Engineers Inc in November of 2020. The topographic survey includes the approximate location of existing underground utilities. The completed survey was utilized to develop the site plan drawings for the conduit run.
On March 9, 2021 Patriot Design & Consulting was on-site at St. Albans VA Medical Center and reviewed the existing site conditions. The topographic survey, site review, and direction from VA were utilized to select the route of the new underground conduit run.
6.2 VA Design Manuals and Guides
The following VA Design Manual and Guides will be used for this project:
• Site Development Design Manual – February 2013
• Electrical Design Manual – December 2019
• 26 05 41 Underground Electrical Construction
Based on the VA standards, the controls conduit run shall be concrete encased and provided with a minimum of 30-inches of cover above the encasement.
6.3 Site Phasing
A site phasing plan is being developed and is shown on drawing CU-002. The goal of the site phasing plan will be to:
• Ensure that construction causes minimal interference with the normal function of VA facility and surrounding community.
• Coordinate the phasing/shutdown requirements with facility personnel.
• Minimize or avoid disruptions to existing systems. Delineate phasing of construction to ensure that installations of new systems are expedited, and where possible, maintain existing systems in service.
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
7. PLUMBING BASIS OF DESIGN
7.1 Background
7.1.1 Building 176 – Existing Water Booster Pump Station
The existing domestic water and sprinkler supply system consists of a ground water storage tank, altitude valve, reduced pressure zone system and six dry pit multistage vertical turbine pumps, including two jockey pumps. The largest pumps (P1 and P2) are fixed speed pumps and used for peak domestic flow. All remaining pumps are on variable frequency drives (VFDs); two are jockey pumps and two are domestic pumps for lower flow demands. The VA wants to replace all six water booster pumps and associated controls, as well as any severely corroded piping and fittings per visual inspection at time of site visit. The current sizing of the existing water booster pumps and piping are shown in Table 1 below.
Table 1. Existing Water Booster Pumps Description
Nominal Pipe Size
(inch) Pump Stage(a) Design
Capacity(a)
Design Head(a)
(ft)
HP
VFD or Fixed Speed
Use/Type
10 P1 5 1000 289 150 Fixed Booster/
Peak Flow
10 P2 5 1000 289 150 Fixed Booster/
Peak Flow
8 P3 3 750 200 50 VFD Booster
4 P4 7 100 312 10 VFD Jockey
8 P5 3 750 200 50 VFD Booster
4 P6 7 100 312 10 VFD Jockey
Notes:
aA request for information was sent to the VA to obtain the design operating points for all six pumps on 01/30/2020 and was not yet received at the time of this report. It is assumed that existing pump stage is the same as proposed pumps for replacement.
VFD – Variable Frequency Drives
Source: Ramboll (Table by Ramboll)
The current operations were described on the existing drawings as follows:
• P1 and P2 are alternating lead and lag pumps for peak flow based on demand
• P3 and P5 are alternating pumps for flows less than peak flow
• P4 and P6 are alternating jockey pumps designed primarily to maintain pressure in the line for the sprinkler system
At the time of the site visit on January 22, 2020, Pump P1 was not connected to the horizontal discharge in the Shallow Pipe Trench Area and Pump P2 was not installed. The system appears to have been operating on the remaining pumps (P3 to P6). See Figures 1 and 2.
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
Figure 1. Missing Dry Pit Vertical Turbine Pump (P1)
Figure 2. Missing Reducer Connection to Surge Valve (P2)
Missing VT Pump (P1)
Connected VT Pump (P2)
Missing Reducer Connection from VT Pump Discharge to
Surge Valve
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
Table 2 below summarizes the design operational pressure set points for the existing pumps.
Table 2. Existing Pump Operation Pressure Set Points
Pump ON OFF
P1 (Lead Peak Flow)
60 psi
Lead ON at 60 psi from pressure controller. Lag ON at extreme low pressure of 55 psi from pressure switch or pressure controller.
70 psi
Lead OFF at 70 psi from pressure controller. Lag OFF at 72 psi from pressure controller or pressure switch.
P2 (Lag Peak Flow) 55 psi 72 psi
P3 or P5 (Alternating) 75 psi
80 psi
OR
If flow <100 gpm for X Time
P4 or P6 (Alternating) 77 psi 80 psi
OR
Disabled if P3 or P5 are ON
Source: Ramboll (Table by Ramboll)
The existing pumps and controls are past their useful life, and the VA wants them to be replaced.
The existing pumps do not operate as outlined in the VA Plumbing Design Manual for Patient Care Buildings which requires a three pump system (N+1) where two pumps can service the facility if one pump is taken out of service. The existing system operates such that one pump can service peak demand, and this pump has a designated backup (P1 and P2) and one pump can service lower demands. This second pump also has a designated backup (P3 and P5). The existing system also has one jockey pump and designated backup (P4 and P6). The jockey pump is meant to maintain a minimum pressure in the water sprinkler system. Flows above peak demand can be met by operating the largest pumps (P1 and P2) simultaneously.
7.2 Scope of Work
This project includes the replacement of all six water booster and jockey pumps. The new pumps shall be dry pit vertical turbine pumps and installed similar to the existing pumps. Pumps P3 thru P6 will have VFDs (matching existing). The new pumps were estimated to provide the same capacity and head as the existing. The pump operation pressure set points for the new pumps shall also be as described in Table 2. Additionally, the existing ground water storage tank shall be cleaned, level sensors checked and replaced if necessary. Confined space requirements are necessary for tank cleaning procedures. These should be in accordance with OSHA CFR 1910.146 and Veterans Affairs design standards.
The new plumbing equipment manufacturers’ data sheets are included in Appendix 1. The following scope of work will be included for this project as directed by VA personnel:
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
7.2.1 Building 176 – Pump Station Booster Pump Area
• Design to replace six vertical pump motors. Four pumps shall be on VFDs. Electrical replacement is described in Section 8. New controls to connect to the existing building management system (Automated Logic).
• Pump motor sizing shall be coordinated with the pump manufacturer
7.2.2 Building 176 – Pump Station Shallow Pipe Trench Area
• Design for replacing horizontal pipe spools to discharge header for each pump
• Design for replacing two 8-inch surge valves for Pumps P1 and P2
• Design for replacing two 8-inch swing check valves and two 4-inch spring check valves for pump pairs P3/P6 and P4/P5, respectively
• Design for replacing two 10-inch isolation butterfly valves, two 8-inch isolation butterfly valves and two 4-inch isolation butterfly valves, including associated valve stem assemblies. Valve handwheels shall be made accessible from the Booster Pump Area.
• Design for connecting to new vertical shaft of the new multistage vertical turbine pumps (six total). Considerations shall be given for pump/valve removal in the future.
• Design for the installation of pressure gauges on the horizontal before the check and surge valves (six total)
7.2.3 Building 176 – Pump Station Deep Pipe Trench Area
• Design for replacement of dry pit vertical turbine pumps to connect to new discharge piping and valves in Shallow Pipe Trench Area and to motor in the Booster Pump Area
7.2.4 Ground Water Storage Tank
• Clean interior of existing 150,000 gallon ground water storage tank
• Check operability of existing tank level sensors and replace, as necessary
• Water quality testing after cleaning
7.3 Applicable Codes and Standards
The following codes and standards will be used for this project:
• International Building Code 2015 (IBC, as Adopted by New York State)
• International Plumbing Code (IPC)
• American Society of Mechanical Engineers (ASME)/American National Standards Institute
(ANSI); ASME/ANSI B31.9, Building Services Piping
• National Fire Protection Association (NFPA) 90A, Air Conditioning and Ventilating Systems
• New York City (NYC) Building Code
• OSHA CFR 1910.146
• VA Design Standards
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
8. ELECTRICAL BASIS OF DESIGN
The following shall be involved for this project:
• Site investigation to establish existing electrical conditions and verify as-builts
• Design for demolition and installation of the existing four domestic water pumps’ and two fire pumps’ electrical services
• Design for the replacement of the pump station interior and electrical lighting fixtures
• Design for the demolition, rerouting, addition, and reconfiguration of supporting 120/280-V branch power circuitry due to the existing electrical distribution system changes
• Design for the replacement of the pump station electrical service and the existing motor control center (MCC). Existing utility transformer and service entrance cable to the building will remain in place for reuse.
• New DDC system for the meter bypass valve, surge valves, flow meters, tank level sensors, pump VFDs and pressure switches pump to connect to existing BMS systems in Building 89.
The new DDC system shall be compatible to the BMS. The BMS is in process by other of being upgraded to Johnson Controls system.
8.1 General Demolition
The electrical contractor shall de-energize and disconnect all live circuits such that no electrical hazards exist. The electrical contractor shall provide temporary lighting and general use power for use by all trades during the construction period.
8.2 Electric Service
The existing Consolidated Edison, Inc. (Con Edison) pad-mount transformer located at the rear of the pump station will remain. In general, the mechanical equipment replacement will be of similar size and capacity as the existing being replaced. No reports of building service overload conditions were reported or observed. No increase to the building electrical service loading is expected once the project is completed.
8.3 Power Distribution System and Devices
The existing electrical distribution system and equipment in the pump station consist of an underground 480Y/277-V electrical service from the exterior Con Edison transformer, routed through a current transformer enclosure within the pump station to a Square D Model 5 MCC.
The MCC contains various sections with MCC buckets; VFDs for the pumps; a step-down, dry-type transformer to a 208Y/120-V power panel and a programmable logic controller for the pump system controls.
The existing mcc will be removed completely, the service entrance conductors and the conductors from the generator will remain for reuse.
In order to completely replace the existing electrical secondary service and MCC, the pump station will have to take an electrical outage. The VA has indicated that the pumps have been inactive for 2 years and that temporary distribution equipment to source pumps during replacement is not required. During the electrical outage the MCC will be removed completely.
Upon installation of the service entrance rated enclosed circuit breaker and the automatic transfer switch the utility power can be turned back on.
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
The pump station 208Y/120-V power panel is also located within the MCC. This power panel will be removed and replaced. The branch circuits will be transferred to the new power panel. This will be essential in maintaining pump station lighting, emergency lighting, fire alarm and pump controls during the changeover.
A main distribution switchboard will be installed after the automatic transfer switch. This main distribution switchboard will source the booster pump VFDs and step-down transformer for the 208Y/120-V power panel.
8.4 Branch Circuits
The branch circuit voltage drop values will be in accordance with Institute of Electrical and Electronic Engineers (IEEE) Std. 141-1993. It should also be noted, however, that a branch circuit voltage drop for general power and lighting circuits cannot exceed 3%.
8.5 Grounding Systems
The existing building grounding system will remain. Equipment grounding conductors will be provided in each proposed feeder and branch circuit raceways in accordance with the NEC.
8.6 Lighting System
The existing interior lighting fixtures in the pump station will be replaced with new light emitting diode (LED) type light fixtures rated for the spaces served. Please refer to the lighting simulations in Appendix 2 for the proposed lighting upgrades.
The existing exterior light fixtures on the building consist of large high-intensity discharge (HID) type fixtures on the building exterior. These HID fixtures have been previously retrofitted with LED drivers and LED packs. The VA should advise if these retrofitted HID fixtures are functional as these could not be tested while in the field, and if the retrofitted HID fixtures should be replaced assuming they are functional.
Additionally, the jelly jar exterior fixtures located over the entrance doors will be replaced with new LED-type fixtures.
The existing interior and exterior light fixture rigid steel conduit/raceway system will be reused to the furthest extent possible. The lighting system circuitry conductors and light switches will be replaced with new.
8.7 Fire Alarm System
The existing fire alarm system will remain. No functional or operational issues have been discussed or are known at this time.
8.8 BMS System
The existing pump station doesn’t have any connection to the BMS system in the main building.
New underground conduit with fiber optic will be installed between the pump station and building 89 where the BMS system is located.
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
8.9 Applicable Codes and Standards
The following codes and standards will be used for this project:
• National Electrical Code (NEC)
• Underwriters Laboratories, Inc. (UL)
• National Electrical Manufacturers Association (NEMA)
• Institute of Electrical and Electronic Engineers (IEEE)
• American Society for Testing and Materials (ASTM)
• Insulated Cable Engineers Association (ICEA)
• Association of Edison Illuminating Companies (AEIC)
• Illuminating Engineering Society of North America (IESNA)
• American National Standards Institute (ANSI)
• International Conference of Building Officials (ICBO)
• New York City (NYC) Building Code
• VA Design Standards
• National Fire Protection Association (NFPA) 72, National Fire Alarm Code
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
APPENDIX 1
PLUMBING MANUFACTURERS’ DATA/CUT SHEETS
Peerless Pump P1 thru P6
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
Peerless Express 21.1.3
G A FLEET & ASSOCIATES, INC · 6 International Drive, Suite 210 · Rye Brook, NY 10573 phone: 914-835-4000 · fax: 914-835-1331
Pump Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp Power
H ea d
- f t 9.14 / 8.75 in
9.66 / 8.91 in
7.26 / 7.26 in
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600N
PS
H r -ft
Flow - USgpm
NPSHr
Customer :
Customer ref. / PO :
Tag Number : 001
Service :
Quantity : 1
Quote Number / ID : 1402407
Date last saved : 20 May 2021 2:29 PM
Flow, rated : 1,000 USgpm
Differential head / pressure, rated
: 290.0 ft
Fluid density, rated / max : 1.000 / 1.000 SG
Peerless Model : GL12ME/LC
Stages : 5
Speed, rated : 1785 rpm
Based on curve number : GL12MELC4606114 Rev Jul2020
Efficiency (bowl / pump) : 84.08 / 83.40 %
Power (bowl / pump) : 89.9 / 90.3 hp
Max power (non-overloading) : 92.9 hp
NPSH required : 16.1 ft
Viscosity : 1.00 cP
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00
Flow Head Efficiency Power NPSHr Thrust, total (USgpm) (ft) (%) (hp) (ft) (lbf)
0 409.9 0.00 43.2 - 3,811
144 405.4 30.00 49.1 - 3,476
288 388.4 51.56 54.8 - 3,140
432 374.3 65.90 61.9 - 2,885
576 363.3 74.71 70.7 7.9 2,666
720 353.0 80.09 80.1 9.4 2,431
864 331.6 83.59 86.5 11.8 2,081
1,008 297.3 83.98 90.1 16.4 1,619
1,152 251.0 79.22 92.1 24.5 1,093
1,296 194.0 69.00 92.0 - 575
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Multi-Speed Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp 1785 rpm
1607 rpm
1428 rpm 1250 rpm
1071 rpm 893 rpm
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
H ea d
- f t
Flow - USgpm
1785 rpm
1607 rpm
1428 rpm
1250 rpm 1071 rpm
893 rpm
Project name : St. Albans VA Hospital Commissioned Representative
Customer :
Customer ref. / PO :
Quote Number / ID : 1402407 Date last saved : 20 May 2021 2:29 PM
Tag Number : 001 Service :
Peerless Model : GL12ME/LC Quantity : 1 Quoted By (Sales Office) : G.A. FLEET Quoted By (Sales Engineer) : Serdar Umur Stages : 5
Speed, rated : 1785 rpm Flow, rated : 1,000 USgpm Differential head / pressure, rated : 290.0 ft Fluid density, rated / max : 1.000 / 1.000 SG Viscosity : 1.00 cP Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Based on curve number : GL12MELC4606114 Rev
Jul2020
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
"Construction Datasheet"
Customer :
Customer Reference :
Item Number : 001
Pump Size - Stages : GL12ME/LC - 5
Construction
Bowl construction : Discharge Case
Impeller type : Static (single plane) Balance
Impeller fastening : Carbon Steel (lock collets)
Strainer : N/A
Column construction : Direct Connect (No Column Required)
Column dia (nominal) : -
Column pipe length : 0.00 in
Max column length : 0.00 in
Lineshaft diameter : 1.19 in
Lineshaft construction : OLS
Lineshaft lubrication : Product Lubrication
Discharge : Above Base (floor)
Materials
Bowl : Cast iron
Impeller : 316LSS
Bowl bearing : Standard (Bronze/Rubber)
Bowl shaft : 416 Stainless Steel
Bowl wear ring : None
Impeller wear ring : None
Strainer : -
Column : Steel
Lineshaft : 416 SS
Bearing retainer / ELS Tube : -
Lineshaft bearing : Standard (Rubber)
Discharge head : Cast Iron
Sole plate : None
Paint : Standard Peerless Blue
Approximate Weights
Complete pump : 3,033 lb
Driver : 1,903 lb
Quote Number : 1402407
Service :
Date Last Saved : 20 May 2021 2:29 PM
Quantity of Pumps : 1
Motor Information
Manufacturer : Aurora
Vertical shaft type : VHS
Full load speed : 1789 rpm
Power : 100.0 hp
Service Factor : 1.15
Volts / Phase / Hz : 460 V / 3 / 60 Hz
Frame size / Base diameter : 20.00 in
Enclosure : WP1
Duty Type : Continuous duty
Inverter Duty Rated : 0
Efficiency Class, 100%/75%/50% : Premium, 0.00 % / 0.00 % / 95.40
Power factor : 0 / 0 / 0
Driver amp full load : 0.000 A
NEMA design : B
Motor starting : Full Volt
Insulation : F
Ambient temperature : 104.0 deg F
Max altitude : 3300
Thrust rating : Standard High Thrust
Additional information
Pit / sump depth : 0.00 in
Pump length : 77.75 in
Max pump dia below mounting surface
: 13.50 in
Max sphere size : 0.50 in
Total / best lateral setting : 150 in
Max suction pressure** : 0.00 psi.g
Testing
Hydraulic performance test : None
Hydrostatic test : None
Curve approval : No
NPSH test : None
String test : None
Test w/ motor : None
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
Peerless Express 21.1.3ISSUED FOR CONSTRUCTION REV 0 phone: 914-835-4000 · fax: 914-835-1331
General Arrangement Drawing
Notes
1. Unless otherwise specified, dimensions are in
2. Baseplate requires support on all sides.
3. Read instructions before beginning pump assembly or installation.
4. Drawing is preliminary until certified by factory.
APPROXIMATE DRY WEIGHT
Driver 1,903 lb
Discharge Head 375 lb
Column / Shaft 0 lb / 0 lb
Bowl Assembly 755 lb
Total 3,033 lb
GENERAL DATA
Capacity 1,000 USgpm Liquid Cold Water
Head 290.0 ft Specific Gravity 1.000 SG
Pump Speed 1785 rpm
DRIVER DATA
MFGR - Shaft Type OLS
Hp 100.0 hp Enclosure / Type WP1
Volt / Ph / Hz 460 / 3 / 60 Hz Frame / Model 404TP
Service Factor 1.15
Customer Name
Quote No 0
Item No. 001
Project St. Albans VA Hospital
Date 20 May 2021 2:14 PM
0-001
60.62
N/A
42.50
18.12
77.75
6.00
13.30
13.16
1.12
N/A
16.50
1.19
32.09
77.75
N/A
12.12
8.25
N/A
-1.00
GL12ME
11.65
N/A
3.50
No Sump Data
8x8x12/16.5 G
21.25
14.25 1.12
23.50
N/A
NOT
8 inch ANSI FLANGE, 125# RATING
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Customer Price Sheet Total Only Customer Quote Number / ID 1402407
Tag Number 001 Model / Stages GL12ME/LC / 5
Customer ref. / PO Flow, rated 1,000 USgpm
Differential head / pressure, rated
290.0 ft
Speed, rated 1785 rpm
Total Grand Total Lead Time Total
Pump Qty Description
1 GL12ME/LC
Bowl Assembly
Pump Type: New Pump
Bowl Size: GL12ME
Number of Stages: 5 stage
Materials of Construction: Materials (Cast Iron, 316LSS)
Bowl Configuration (Connection)
Top Bowl (Discharge Connection): Discharge Case
Suction: Bell Suction
Shaft, Pump: 1 1/2 inch
Pump shaft material (Bowl Shaft): 416 Stainless Steel
Efficiency: Standard Efficiency
Impeller Wear Rings: None
Bowl Wear Rings: None
Suction Accessory: None
Lateral Travel in Bowl Assembly: Standard
Bowl Bearing Materials: Standard (Bronze/Rubber)
Impeller Balance: Static (single plane) Balance
Dry Pit Application: Yes
Impeller Fastening: Carbon Steel (lock collets)
Bowl Bolting: 18-8 Stainless Steel
Column / Line Shaft / Coupling
Column Pipe Design: Direct Connect (No Column Required)
Line Shaft Lubrication: Product Lubrication
Line Shaft Sleeves: None
Line Shaft Material: 416 SS
Coupling Design: Threaded Coupling
Coupling Material: Carbon Steel
Line Shaft Bearing Material: Standard (Rubber)
Discharge Head
Discharge Head Assembly: 8x8x12/16.5G
Discharge Head Flange Rating: 125#
Discharge Head Material: Cast Iron
Discharge Location: Above Base (floor)
Line Shaft Construction: Open Line Shaft (OLS)
Sealing Type: Packed Stuffing Box (No Stuffing Box Sleeve - Packing Contacts the Shaft)
Motor Spacer Required: No
Column to Discharge Head Fastener Material: 18-8 Stainless Steel
Sole Plate: None
Stuffing Box Bearing Material: Standard (Bronze)
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Qty Description
Driver
Driver Supplied By: Factory
Efficency: Premium
Motor (Design Types): NEMA
Adapter
Adapter Required: No
Coating / Painting Systems
System: Standard factory paint - enamel
Outside Bowl Assembly: Standard factory paint - enamel
Inside Bowl Assembly: Standard Glass/Scotchkote 134
Outside Discharge Head: Standard factory paint - enamel
Inside Discharge Head: None
Testing
Tolerance Type: Hyd Ins 14.6 Unilateral (1U)
Hydrostatic Pressure Tests
Factory Hydrostatic Pressure Test (bowl) with Suction Flange - Non-Witness
Assembly / Match Marking / Shipping
Factory Assembly for Shipment: Factory Assembled
Drawings, Curves, and Instructions
Outline Drawing: Standard Dimension Print "A" size - Grundfos Express Generated
Cross Sectional Drawing: Standard Prints on three "A" size drawing - Grundfos Express Generated
Motor Qty Description
Driver
Motor: Motor-electric, 100hp, 1789rpm, 460/0/0/0V, 3Ph, 60Hz, 404TP, VHS, WP1, PremEff., Stock, Aurora, 46WP1HS100PE**D**X
Commercial Qty Description
1 Incoterms 2020: EXW
Named Place
Named Place: Seller's Facility
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Performance Datasheet Customer :
Customer ref. / PO :
Tag Number : 002 Service :
Quantity : 1
Quote Number / ID : 1402407 Peerless Model : M12LD/LC Stages : 3 Based on curve number : M12LDLC-4605509 Date last saved : 20 May 2021 3:12 PM
Operating Conditions Flow, rated : 750 USgpm Differential head / pressure, rated (requested) : 200.0 ft Differential head / pressure, rated (actual) : 206.4 ft Suction pressure, rated / max : 0.00 / 0.00 psi.g NPSH available, rated : Ample Site Supply Frequency : 60 Hz
Performance Speed, rated : 1775 rpm Impeller diameter, rated : 9.60 / 8.79 in Impeller diameter, maximum : 9.72 / 8.94 in Impeller diameter, minimum : 8.91 / 7.88 in Efficiency (bowl / pump) : 81.99 / 81.09 % NPSH required / margin required : 7.2 / 0.0 ft Ns (imp. eye flow) / Nss (imp. eye flow) : 1,925 / 11,206 US Units MCSF : 150 USgpm Head, maximum, rated diameter : 310.0 ft Head rise to shutoff (bowl / pump) : 50.17 / 50.87 % Flow, best eff. point (bowl / pump) : 721 / 717 USgpm Flow ratio, rated / BEP (bowl / pump) : 104.04 / 104.62 % Diameter ratio (rated / max) : 98.41 % Head ratio (rated dia / max dia) : 94.25 % Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Selection status : Acceptable
Liquid Liquid type : Cold Water Additional liquid description :
Solids diameter, max : 0.00 in Solids concentration, by volume : 0.00 % Temperature, max : 68.00 deg F Fluid density, rated / max : 1.000 / 1.000 SG Viscosity, rated : 1.00 cP Vapor pressure, rated : 0.34 psi.a
Material Material selected : Material Group, Standard
Pressure Data Maximum working pressure : See the Additional Data page Maximum allowable working pressure : See the Additional Data page Maximum allowable suction pressure : N/A Hydrostatic test pressure : See the Additional Data page
Driver & Power Data (@Max density) Motor sizing specification : Rated power (based on duty point) Margin over specification : 0.00 % Service factor : 1.15 (used) Power, hydraulic : 39.1 hp Power (bowl / pump) : 47.7 / 48.0 hp Max power (non-overloading) : 53.3 hp Nameplate motor rating : 50.0 hp / 37.3 kW
Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U) Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp Power
H ea d
- f t
9.60 / 8.79 in
36 52
82 82
9.72 / 8.94 in
8.91 / 7.88 in
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400N
PS
H r -ft
Flow - USgpm
NPSHr
SA PUMP STATION
630A-17-520
D2X ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp Power
H ea d
- f t
9.60 / 8.79 in
36 52
82 82
9.72 / 8.94 in
8.91 / 7.88 in
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400N
PS
H r -ft
Flow - USgpm
NPSHr
Customer :
Customer ref. / PO :
Tag Number : 002
Service :
Quantity : 1
Quote Number / ID : 1402407
Date last saved : 20 May 2021 3:12 PM
Flow, rated : 750 USgpm
Differential head / pressure, rated
: 200.0 ft
Fluid density, rated / max : 1.000 / 1.000 SG
Peerless Model : M12LD/LC
Stages : 3
Speed, rated : 1775 rpm
Based on curve number : M12LDLC-4605509
Efficiency (bowl / pump) : 81.99 / 81.09 %
Power (bowl / pump) : 47.7 / 48.0 hp
Max power (non-overloading) : 53.3 hp
NPSH required : 7.2 ft
Viscosity : 1.00 cP
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00
Flow Head Efficiency Power NPSHr Thrust, total (USgpm) (ft) (%) (hp) (ft) (lbf)
0 310.0 0.00 35.0 - 3,226
137 294.1 28.10 36.2 - 2,878
274 278.2 50.61 38.1 4.2 2,519
412 261.1 67.15 40.4 5.1 2,212
549 241.6 77.56 43.2 5.3 1,956
686 218.6 81.93 46.2 6.2 1,721
823 191.2 80.58 49.3 9.0 1,468
961 158.7 74.05 52.0 15.0 1,179
1,098 120.4 63.10 52.9 25.3 862
1,235 75.76 48.73 48.5 40.6 537
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Multi-Speed Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp
1775 rpm
1598 rpm
1420 rpm 1243 rpm
1065 rpm 888 rpm
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400
H ea d
- f t
Flow - USgpm
1775 rpm 1598 rpm
1420 rpm 1243 rpm1065 rpm888 rpm
Project name : St. Albans VA Hospital Commissioned Representative
Customer :
Customer ref. / PO :
Quote Number / ID : 1402407 Date last saved : 20 May 2021 3:12 PM
Tag Number : 002 Service :
Peerless Model : M12LD/LC Quantity : 1 Quoted By (Sales Office) : G.A. FLEET Quoted By (Sales Engineer) : Serdar Umur Stages : 3
Speed, rated : 1775 rpm Flow, rated : 750 USgpm Differential head / pressure, rated : 200.0 ft Fluid density, rated / max : 1.000 / 1.000 SG Viscosity : 1.00 cP Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Based on curve number : M12LDLC-4605509
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
"Construction Datasheet"
Customer :
Customer Reference :
Item Number : 002
Pump Size - Stages : M12LD/LC - 3
Construction
Bowl construction : Discharge Case
Impeller type : Static (single plane) Balance
Impeller fastening : Carbon Steel (lock collets)
Strainer : N/A
Column construction : Direct Connect (No Column Required)
Column dia (nominal) : -
Column pipe length : 0.00 in
Max column length : 0.00 in
Lineshaft diameter : 1.00 in
Lineshaft construction : OLS
Lineshaft lubrication : Product Lubrication
Discharge : Above Base (floor)
Materials
Bowl : Cast iron
Impeller : Al Brz C952
Bowl bearing : Standard (Bronze/Rubber)
Bowl shaft : 416 Stainless Steel
Bowl wear ring : None
Impeller wear ring : None
Strainer : -
Column : Steel
Lineshaft : 416 SS
Bearing retainer / ELS Tube : -
Lineshaft bearing : Standard (Rubber)
Discharge head : Cast Iron
Sole plate : None
Paint : Standard Peerless Blue
Approximate Weights
Complete pump : 1,693 lb
Driver : 924 lb
Quote Number : 1402407
Service :
Date Last Saved : 20 May 2021 3:12 PM
Quantity of Pumps : 1
Motor Information
Manufacturer : Aurora
Vertical shaft type : VHS
Full load speed : 1775 rpm
Power : 50.0 hp
Service Factor : 1.15
Volts / Phase / Hz : 460 V / 3 / 60 Hz
Frame size / Base diameter : 16.50 in
Enclosure : WP1
Duty Type : Continuous duty
Inverter Duty Rated : 0
Efficiency Class, 100%/75%/50% : Premium, 0.00 % / 0.00 % / 94.50
Power factor : 0 / 0 / 0
Driver amp full load : 0.000 A
NEMA design : B
Motor starting : Full Volt
Insulation : F
Ambient temperature : 104.0 deg F
Max altitude : 3300
Thrust rating : Standard High Thrust
Additional information
Pit / sump depth : 0.00 in
Pump length : 51.00 in
Max pump dia below mounting surface
: 18.00 in
Max sphere size : 0.88 in
Total / best lateral setting : 150 in
Max suction pressure** : 0.00 psi.g
Testing
Hydraulic performance test : None
Hydrostatic test : None
Curve approval : No
NPSH test : None
String test : None
Test w/ motor : None
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
General Arrangement Drawing
Notes
1. Unless otherwise specified, dimensions are in
2. Baseplate requires support on all sides.
3. Read instructions before beginning pump assembly or installation.
4. Drawing is preliminary until certified by factory.
APPROXIMATE DRY WEIGHT
Driver 924 lb
Discharge Head 225 lb
Column / Shaft 0 lb / 0 lb
Bowl Assembly 544 lb
Total 1,693 lb
GENERAL DATA
Capacity 750 USgpm Liquid Cold Water
Head 200.0 ft Specific Gravity 1.000 SG
Pump Speed 1775 rpm
DRIVER DATA
MFGR - Shaft Type OLS
Hp 50.0 hp Enclosure / Type WP1
Volt / Ph / Hz 460 / 3 / 60 Hz Frame / Model 326TP
Service Factor 1.15
Customer Name
Quote No 1402407
Item No. 002
Project St. Albans VA Hospital
Date 20 May 2021 2:48 PM
1402407-002
49.52
N/A
32.52
17.00
51.00
6.00
9.78
11.08
1.00
N/A
14.00
1.00
28.46
51.00
N/A
9.62
7.50
N/A
-1.00
M12LD
11.70
N/A
3.50
No Sump Data
6x6x12 G
17.00
11.44 1.00
19.00
N/A
NOT
6 inch ANSI FLANGE, 125# RATING
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Customer Price Sheet Total Only Customer Quote Number / ID 1402407
Tag Number 002 Model / Stages M12LD/LC / 3
Customer ref. / PO Flow, rated 750 USgpm
Differential head / pressure, rated
200.0 ft
Speed, rated 1775 rpm
Total Lead Time Total 8 wks
Pump Qty Description
1 M12LD/LC
Bowl Assembly
Pump Type: New Pump
Bowl Size: M12LD
Number of Stages: 3 stage
Materials of Construction: Materials (Cast Iron, Alum Bronze)
Bowl Configuration (Connection)
Top Bowl (Discharge Connection): Discharge Case
Suction: Bell Suction
Shaft, Pump: 1 1/2 inch
Pump shaft material (Bowl Shaft): 416 Stainless Steel
Efficiency: Standard Efficiency
Impeller Wear Rings: None
Bowl Wear Rings: None
Suction Accessory: None
Lateral Travel in Bowl Assembly: Standard
Bowl Bearing Materials: Standard (Bronze/Rubber)
Impeller Balance: Static (single plane) Balance
Dry Pit Application: No
Impeller Fastening: Carbon Steel (lock collets)
Bowl Bolting: 18-8 Stainless Steel
Column / Line Shaft / Coupling
Column Pipe Design: Direct Connect (No Column Required)
Line Shaft Lubrication: Product Lubrication
Line Shaft Sleeves: None
Line Shaft Material: 416 SS
Coupling Design: Threaded Coupling
Coupling Material: Carbon Steel
Line Shaft Bearing Material: Standard (Rubber)
Discharge Head
Discharge Head Assembly: 6x6x12G
Discharge Head Flange Rating: 125#
Discharge Head Material: Cast Iron
Discharge Location: Above Base (floor)
Line Shaft Construction: Open Line Shaft (OLS)
Sealing Type: Packed Stuffing Box (No Stuffing Box Sleeve - Packing Contacts the Shaft)
Motor Spacer Required: No
Column to Discharge Head Fastener Material: 18-8 Stainless Steel
Sole Plate: None
Stuffing Box Bearing Material: Standard (Bronze)
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Qty Description
Driver
Driver Supplied By: Factory
Efficency: Premium
Motor (Design Types): NEMA
Adapter
Adapter Required: No
Coating / Painting Systems
System: Standard factory paint - enamel
Outside Bowl Assembly: Standard factory paint - enamel
Inside Bowl Assembly: Standard Glass/Scotchkote 134
Outside Discharge Head: Standard factory paint - enamel
Inside Discharge Head: None
Testing
Tolerance Type: Hyd Ins 14.6 Unilateral (1U)
Assembly / Match Marking / Shipping
Factory Assembly for Shipment: Factory Assembled
Drawings, Curves, and Instructions
Outline Drawing: Standard Dimension Print "A" size - Grundfos Express Generated
Cross Sectional Drawing: Standard Prints on three "A" size drawing - Grundfos Express Generated
Motor Qty Description
Driver
Motor: Motor-electric, 50hp, 1775rpm, 460/0/0/0V, 3Ph, 60Hz, 326TP, VHS, WP1, PremEff., Stock, Aurora, 46WP1HS50PE**D**X
Commercial Qty Description
1 Incoterms 2020: EXW
Named Place
Named Place: Seller's Facility
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Performance Datasheet Customer :
Customer ref. / PO :
Tag Number : 003 Service :
Quantity : 1
Quote Number / ID : 1402407 Peerless Model : 6LB/LC Stages : 7 Based on curve number : 6LBLC-2616324 Date last saved : 20 May 2021 3:19 PM
Operating Conditions Flow, rated : 100 USgpm Differential head / pressure, rated (requested) : 312.0 ft Differential head / pressure, rated (actual) : 329.7 ft Suction pressure, rated / max : 0.00 / 0.00 psi.g NPSH available, rated : Ample Site Supply Frequency : 60 Hz
Performance Speed, rated : 3540 rpm Impeller diameter, rated : 4.47 / 3.96 in Impeller diameter, maximum : 4.47 / 4.47 in Impeller diameter, minimum : 4.47 / 3.88 in Efficiency (bowl / pump) : 71.31 / 69.90 % NPSH required / margin required : 8.3 / 0.0 ft Ns (imp. eye flow) / Nss (imp. eye flow) : 1,920 / 7,140 US Units MCSF : 30 USgpm Head, maximum, rated diameter : 489.3 ft Head rise to shutoff (bowl / pump) : 52.21 / 52.28 % Flow, best eff. point (bowl / pump) : 108 / 107 USgpm Flow ratio, rated / BEP (bowl / pump) : 92.95 / 93.13 % Diameter ratio (rated / max) : 94.02 % Head ratio (rated dia / max dia) : 76.45 % Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Selection status : Acceptable
Liquid Liquid type : Cold Water Additional liquid description :
Solids diameter, max : 0.00 in Solids concentration, by volume : 0.00 % Temperature, max : 68.00 deg F Fluid density, rated / max : 1.000 / 1.000 SG Viscosity, rated : 1.00 cP Vapor pressure, rated : 0.34 psi.a
Material Material selected : Material Group, Standard
Pressure Data Maximum working pressure : See the Additional Data page Maximum allowable working pressure : See the Additional Data page Maximum allowable suction pressure : N/A Hydrostatic test pressure : See the Additional Data page
Driver & Power Data (@Max density) Motor sizing specification : Rated power (based on duty point) Margin over specification : 0.00 % Service factor : 1.15 (used) Power, hydraulic : 8.1 hp Power (bowl / pump) : 11.4 / 11.6 hp Max power (non-overloading) : 11.6 hp Nameplate motor rating : 15.0 hp / 11.2 kW
Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U) Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp
Power
H ea d
- f t
4.47 / 3.96 in 54
4.47 / 4.47 in
4.47 / 3.88 in
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200N
PS
H r -ft
Flow - USgpm
NPSHr
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Pump Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp
Power
H ea d
- f t
4.47 / 3.96 in 54
4.47 / 4.47 in
4.47 / 3.88 in
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200N
PS
H r -ft
Flow - USgpm
NPSHr
Customer :
Customer ref. / PO :
Tag Number : 003
Service :
Quantity : 1
Quote Number / ID : 1402407
Date last saved : 20 May 2021 3:19 PM
Flow, rated : 100 USgpm
Differential head / pressure, rated
: 312.0 ft
Fluid density, rated / max : 1.000 / 1.000 SG
Peerless Model : 6LB/LC
Stages : 7
Speed, rated : 3540 rpm
Based on curve number : 6LBLC-2616324
Efficiency (bowl / pump) : 71.31 / 69.90 %
Power (bowl / pump) : 11.4 / 11.6 hp
Max power (non-overloading) : 11.6 hp
NPSH required : 8.3 ft
Viscosity : 1.00 cP
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00
Flow Head Efficiency Power NPSHr Thrust, total (USgpm) (ft) (%) (hp) (ft) (lbf)
0 489.3 0.00 7.4 - 1,140
18 447.0 25.25 8.0 - 1,010
36 423.6 43.18 8.9 - 935
54 405.4 55.80 9.8 8.0 873
71 382.6 64.43 10.7 8.0 798
89 348.5 69.72 11.3 8.0 698
107 300.1 71.66 11.3 8.6 573
125 238.1 69.53 10.8 10.3 429
143 166.6 61.95 9.7 13.5 278
161 93.12 46.84 8.1 18.6 140
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
Multi-Speed Performance Curve Bowl performance. Adjusted for construction and viscosity.
The duty point represents the head at the bowl.
Performance based on test acceptance - Hyd Ins 14.6 Unilateral (1U)
Performance curve represents typical performance. When tested, only the design flow and head are guaranteed. Contact factory for additional requirements.
Po w er hp
3540 rpm 3186 rpm
2832 rpm 2478 rpm
2124 rpm1770 rpm
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
H ea d
- f t
Flow - USgpm
3540 rpm 3186 rpm
2832 rpm2478 rpm2124 rpm1770 rpm
Project name : St. Albans VA Hospital Commissioned Representative
Customer :
Customer ref. / PO :
Quote Number / ID : 1402407 Date last saved : 20 May 2021 3:19 PM
Tag Number : 003 Service :
Peerless Model : 6LB/LC Quantity : 1 Quoted By (Sales Office) : G.A. FLEET Quoted By (Sales Engineer) : Serdar Umur Stages : 7
Speed, rated : 3540 rpm Flow, rated : 100 USgpm Differential head / pressure, rated : 312.0 ft Fluid density, rated / max : 1.000 / 1.000 SG Viscosity : 1.00 cP Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Based on curve number : 6LBLC-2616324
SA PUMP STATION
630A-17-520
DX ASSOCIATES 09/28/23
phone: 914-835-4000 · fax: 914-835-1331
"Construction Datasheet"
Customer :
Customer Reference :
Item Number : 003
Pump Size - Stages : 6LB/LC - 7
Construction
Bowl construction : Threaded Discharge
Impeller type : Static (single plane) Balance
Impeller fastening : Carbon Steel (lock collets)
Strainer : N/A
Column construction : Direct Connect (No Column Required)
Column dia (nominal) : -
Column pipe length : 0.00 in
Max column length : 0.00 in
Lineshaft diameter : -1.00 in
Lineshaft construction : OLS
Lineshaft lubrication : Product Lubrication
Discharge : Above Base (floor)
Materials
Bowl : Cast iron
Impeller : Al Brz C952
Bowl bearing : Standard (Bronze/Rubber)
Bowl shaft : 416 Stainless Steel
Bowl wear ring : None
Impeller wear ring : None
Strainer : -
Column : Steel
Lineshaft : 416 SS
Bearing retainer / ELS Tube : -
Lineshaft bearing : Standard (Rubber)
Discharge head : Cast Iron
Sole plate : None
Paint : Standard Peerless Blue
Approximate Weights
Complete pump : 528 lb
Driver : 178 lb
Quote Number : 1402407
Service :
Date Last Saved : 20 May 2021 3:19 PM
Quantity of Pumps : 1
Motor Information
Manufacturer : GE
Vertical shaft type : VHS
Full load speed : 3525 rpm
Power : 15.0 hp
Service Factor : 1.15
Volts / Phase / Hz : 460 V / 3 / 60 Hz
Frame size / Base diameter : 10.00 in
Enclosure : WP1
Duty Type : Continuous duty
Inverter Duty Rated : 0
Efficiency Class, 100%/75%/50% : Premium, 91.00 % / 92.80 % / 92.70 %
Power factor : 88 / 85.8 / 79.4
Driver amp full load : 14.08 A
NEMA design : B
Motor starting :…