Attachment 1 - General Specifications.docx
DOCX document 147 KB Posted
- Attached to
- Replace Kadena Tanks
- Solicitation number
- FA527025R0032
About this file
This document is a comprehensive General Specifications attachment for a design-build contract for replacing fuel tanks at Kadena Air Base in Okinawa, Japan. The project involves replacing fuel and waste oil storage tanks at eight different facilities (B176, B329, B613, B786, B1206, B3413, B3489, B3506) with new Convault tanks or approved equivalents to mitigate leak and corrosion risks. The contract requires integrating sustainable principles, implementing seismic protection, antiterrorism, and fire protection measures, and addressing potential asbestos and lead-based paint abatement.
The specifications provide detailed requirements for the contractor's quality control, design process, submittals, and execution, including mandatory qualifications for key personnel such as a Program Manager, Project Manager, and Quality Control System Manager. The contract emphasizes comprehensive documentation, design review processes, and adherence to various standards including Unified Facilities Criteria, Japanese Industrial Standards, and environmental regulations. Contractors must prepare detailed design submissions at 35%, 95%, and 100% stages, with specific technical requirements for architectural, structural, mechanical, and electrical components, and must obtain government approval before commencing construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 8 - QASP.docx | DOCX document | |
| Attachment 2 - 01 57 19.01 30, Temporary Env Controls (2024-12).docx | DOCX document | |
| Attachment 7 - 02 82 00.00 30, ACM SUPPLEMENT (2024-12).docx | DOCX document | |
| DOD Standard AW 078-24-27 Above Ground Vertical Fuel Tanks with Fixed Roofs.pdf_safe.pdf | ||
| Attachment 7 - 02 83 00.00 30, LEAD SUPPLEMENT (2024-12).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT – 1 GENERAL
REQUIREMENTS
PROJECT TITLE
KADENA AIR BASE, OKINAWA, JAPAN
LXEZXXXXXX
Table of Contents
GENERAL REQUIREMENTS
TABLE OF CONTENTS
| GENERAL REQUIREMENTS | 2 | |
| TABLE OF CONTENTS | 2 | |
| SECTION 01-00-00 GENERAL REQUIREMENTS PREFACE | 6 | |
| PART 1 GENERAL | 6 | |
| 1.1 | PREFACE | 6 |
| 1.2 | DEFINITIONS | 6 |
| PART 2 PRODUCTS | 7 | |
| PART 3 EXECUTION | 7 | |
| SECTION 01 01 00 SUMMARY OF WORK | 8 | |
| PART 1 GENERAL | 8 | |
| 1.1 | WORK COVERED BY CONTRACT DOCUMENTS | 8 |
| 1.2 | CONTRACT REQUIREMENTS | 8 |
| 1.3 | APPLICABILITY OF THE REQUIREMENTS | 9 |
| 1.4 | SUBCONTRACTORS | 9 |
| 1.5 | INTERPRETER | 9 |
| 1.6 | WRITTEN COMMUNICATIONS IN ENGLISH | 10 |
| 1.7 | RESPONSIBILITY OF CONTRACTOR TO NOTIFY | 10 |
| PART 2 PERTINENT INFORMATION | 11 | |
| 2.1 | BASE / CAMP REGULATIONS | 11 |
| 2.2 | ENTRY ON BASES | 11 |
| 2.3 | ENTRY ON OTHER INSTALLATIONS | 11 |
| 2.4 | KEY PERSONNEL | 11 |
| 2.5 | COMMENCEMENT OF WORK | 13 |
| 2.6 | WORKING HOURS | 13 |
| 2.7 | TROPICAL CYCLONE CONDITIONS OF READINESS (TCCOR) | 14 |
| 2.8 | DISPOSAL OF TRANSFORMERS | 16 |
| 2.9 | UTILITIES | 16 |
| 2.10 | DAMAGE TO UTILITIES | 19 |
| 2.11 | WORK ON FIRE ALARM SYSTEMS REQUIREMENTS | 19 |
| 2.12 | INSTALLATION FIRE, SAFETY, AND ENVIRONMENTAL REGULATIONS | 20 |
| 2.13 | DELIVERY AND STORAGE | 21 |
| 2.14 | DRAWINGS, SPECIFICATIONS AND CONSTRUCTION SCHEDULE ON SITE | 21 |
| 2.15 | GENERAL INDUSTRY SAFETY AND HEALTH STANDARDS | 21 |
| PART 3 DESIGN-BUILD PROCEDURE | 22 | |
| 3.1 | DESIGN‐BUILD PROJECT SCOPE | 22 |
| 3.2 | DESIGN-BUILD PROCESS | 22 |
| 3.3 | DESIGN‐BID‐BUILD PROCESS (CONSTRUCTION ONLY) | 23 |
| 3.4 | PRE-CONSTRUCTION / SAFETY MEETING | 24 |
| 3.5 | AVAILABILITY OF MATERIALS | 25 |
| 3.6 | PREPARATION OF PROGRESS SCHEDULES AND REPORTS | 25 |
| 3.7 | PREPARATION OF MATERIAL APPROVAL SUBMITTALS | 25 |
| 3.8 | AS-BUILT DRAWINGS | 26 |
| 3.9 | PHOTOGRAPHIC RECORD | 26 |
| 3.10 | DAILY REPORTS | 26 |
| PART 4 PROPOSAL DESIGN | 27 | |
| 4.1 | GENERAL DESIGN SUBMITTAL REQUIREMENTS | 27 |
| PART 5 PRODUCTS | 28 | |
| 5.1 | MINIMUM DESIGN LOADS | 28 |
| 5.2 | GOVERNMENT FURNISHED PROPERTIES ITEMS | 28 |
| 5.3 | CONTRACTOR FURNISHED ITEMS | 28 |
| 5.4 | CORROSION PREVENTION | 29 |
| PART 6 EXECUTION | 30 | |
| 6.1 | FIRE PREVENTION DURING CONSTRUCTION | 30 |
| 6.2 | WELDING | 30 |
| 6.3 | CONFINED SPACES | 30 |
| 6.4 | AIRFIELD SAFETY REQUIREMENTS | 31 |
| 6.5 | PROTECTION OF WORK AREA | 32 |
| 6.6 | GOVERNMENT WORK CLEARANCE REQUEST | 33 |
| 6.7 | INTERFERENCE WITH GOVERNMENT OPERATIONS | 33 |
| 6.8 | TRAFFIC CONTROL | 33 |
| 6.9 | VEHICLE CONTROL | 34 |
| 6.10 | CONSTRUCTION SITE MAINTENANCE | 34 |
| 6.11 | EMERGENCY MEDICAL TREATMENT | 34 |
| 6.12 | EXCAVATIONS | 35 |
| 6.13 | WORKING CONDITIONS | 35 |
| 6.14 | DELIVERY AND HANDLING OF MATERIALS AND EQUIPMENT | 35 |
| 6.15 | BARRICADES AND WARNING SIGNS | 35 |
| 6.16 | FIELD TESTS | 35 |
| 6.17 | OPERATION AND MAINTENANCE MANUAL | 36 |
| 6.18 | IMPLEMENTATION OF WARRANTY | 37 |
| 6.19 | CONTRACTOR COMPLETED DD FORM 1354 | 38 |
| SECTION 01 10 00 DESIGN AFTER AWARD | 39 | |
| PART 1 GENERAL | 39 | |
| 1.1 | OVERVIEW | 39 |
| 1.2 | CONTRACTOR’S ROLE DURING DESIGN | 39 |
| 1.3 | DESIGN ENGINEERS | 39 |
| 1.4 | DESIGN ENGINEER RESPONSIBILITIES | 39 |
| 1.5 | DESIGN CONFERENCES | 39 |
| 1.6 | GOVERNMENT REVIEW COMMENTS & TIMELINES | 40 |
| PART 2 PRODUCTS | 41 | |
| PART 3 EXECUTION | 42 | |
| 3.1 | SEQUENCE OF DESIGN-CONSTRUCTION | 42 |
| 3.2 | GENERAL DESIGN SUBMITTAL REQUIREMENTS | 42 |
| 3.3 | SPECIFICATIONS: | 43 |
| 3.4 | SCHEMATIC DESIGN SUBMITTAL (35%) | 44 |
| 3.5 | PRE-FINAL DESIGN SUBMITTAL (95%) | 47 |
| 3.6 | PRE-FINAL DESIGN CORRECTED SUBMITTAL (95%) | 48 |
| 3.7 | RECORD DOCUMENTS (100% As-Built) | 49 |
| 3.8 | DEVIATING FROM THE ACCEPTED DESIGN | 49 |
| 3.9 | INTERIOR DESIGN | 49 |
| SECTION 01 42 01 ACCEPTABLE ALTERNATIVE JAPANESE STANDARDS | 51 | |
| PART 1 GENERAL | 51 | |
| 1.1 | SECTION INCLUDES | 51 |
| 1.2 | ACCEPTABLE ALTERNATIVE JAPANESE STANDARDS | 51 |
| 1.3 | REFERENCES | 51 |
| 1.4 | SUBMITTALS | 52 |
| 1.5 | ACCEPTANCE OF ALTERNATIVE JAPANESE STANDARDS | 52 |
| PART 2 PRODUCTS | 52 | |
| PART 3 EXECUTION | 52 | |
| SECTION 01 45 00 CONTRACTOR’S QUALITY CONTROL | 54 | |
| PART 1 GENERAL | 54 | |
| 1.1 | OVERVIEW | 54 |
| 1.2 | REFERENCES | 54 |
| 1.3 | PAYMENT | 54 |
| PART 2 PRODUCTS | 54 | |
| PART 3 EXECUTION | 54 | |
| 3.1 | GENERAL REQUIREMENTS | 54 |
| 3.2 | QUALITY CONTROL PLAN | 55 |
| 3.3 | COORDINATION MEETING | 57 |
| 3.4 | QUALITY CONTROL ORGANIZATION | 57 |
| 3.5 | QUALITY CONTROL DOCUMENTATION | 58 |
| 3.6 | INTERFACE WITH GOVERNMENT INSPECTORS | 59 |
| 3.7 | TESTS | 59 |
| SECTION 01 78 00 CLOSEOUT SUBMITTALS | 61 | |
| PART 1 GENERAL | 61 | |
| 1.1 | AS-BUILT DRAWINGS | 61 |
| 1.2 | WORKING AS-BUILT AND FINAL AS-BUILT DRAWINGS | 61 |
| 1.3 | COMPUTER AIDED DESIGN AND DRAFTING (CADD) | 61 |
| 1.4 | OTHER DOCUMENTS | 62 |
| PART 2 PRODUCTS | 62 | |
| PART 3 EXECUTION | 62 |
SECTION 01-00-00
GENERAL REQUIREMENTS PREFACE
GENERAL
PREFACE
This contract will be used for performance of specified contract actions on Air Force real property located on Kadena Air Base in Okinawa, Japan. The Contractor and subcontractors shall research, identify and comply with all base standards, supplements, guidelines, procedures, rules, and specifications applicable to the work being performed. Contractor work procedures and performance for both design and construction shall comply with the applicable specifications and standards listed below, other requirements as specified herein, and requirements identified in the contract. All work performed by the Contractor and subcontractors shall be accomplished in strict accordance with the Unified Facilities Criteria (UFC). The contractor shall use the most recent and updated specifications, standards, and codes. In cases of discrepancies or conflicts, the contractor shall use the most stringent code unless otherwise approved.
DEFINITIONS
As used throughout the contract, the following terms shall have the meaning set forth below:
Contracting Officer (CO): The individual designated to administer the contract. Throughout this contract this individual will be responsible and possess the authority to act on behalf of the Government with respect to the specific contract.
Contracting Officer Representative (COR): The individual designated by the Contracting Officer as the authorized representative of the Contracting Officer. The COR is responsible for monitoring performance and technical management of the effort required and should be contacted regarding questions or problems of a technical nature.
Contractor: The term Contractor refers to both the prime Contractor and subcontractors, including the Designer of Record.
Designer of Record (DOR): Licensed architect/engineer working as subcontractor to or partner with prime Contractor who provides design for this contract.
Quality Control (QC) Program: Contractor’s program to control the quality of design, material, equipment, and construction.
Quality Assurance (QA) Program: Government’s program to evaluate the effectiveness of the Contractor’s quality control. The Government’s QA Program is not a substitute for the Contractor’s QC Program.
Federal Holidays: New Year’s Day, Martin Luther King Jr. Day, President’s Day, Memorial Day, Juneteenth, Independence Day, Labor Day, Columbus’ Day, Veteran’s Day, Thanksgiving Day, and Christmas Day.
PRODUCTS
(Not Used)
EXECUTION
(Not Used)
END OF SECTION
REPLACE KADENA TANKS; MULTI
KADENA AIR BASE, OKINAWA, JAPAN LXEZ241015
Return to TOC
SECTION 01 01 00
SUMMARY OF WORK
1. GENERAL
WORK COVERED BY CONTRACT DOCUMENTS
The Contractor shall provide all labor, materials, equipment, transportation, supervision, quality control, and other items necessary to design, manage and accomplish specified repair, and/or minor construction work on Air Force Real Property. The Contractor is responsible for adhering to the current regulations and specifications in force at the time of the contract award.
Scope of Work: The work shall consist of, but is not limited to, provide modern and efficient housing for military members and their dependents stationed in Okinawa, Japan. The housing must be upgraded to meet current life safety codes and to provide a comfortable and appealing living environment. All units will meet standards and are programmed in accordance with the 2015 Housing Community Profile. Repair of interior and exterior utilities infrastructure is required. The project may require phasing of work.
Contractor Organization: The prime construction Contractor shall form a partnership with an Architect-Engineering (A-E) design team to meet the requirements of this contract, if in-house design capabilities are not practicable. The Contractor’s organizational approach shall be integrated with the design team to provide comprehensive design capabilities including assessment, analysis, planning, management and quality control to ensure a completely functional and finished product. The Contractor shall not change teaming members unless approved by the Contracting Officer (CO).
Project Design: Construction may not begin until the final design documents are approved in writing from the CO. Once the design is approved, design changes are not allowed without Government approval.
CONTRACT REQUIREMENTS
Contract Organization: The Contractor’s organizational approach shall integrate with this staff to provide project management, licensed project design/engineering, CADD support, on-site supervision, quality control, sub-contracting purchasing and general office administration, and any other staffing requirements needed to execute performance of this contract.
Collusion: Collusion between Contractors to establish prices or allocate work is strictly prohibited. By submitting a proposal, the Contractor has certified that it has and will independently offer proposals for the basic solicitation under the contract. When architecture or engineering work is subcontracted, designs and other information developed in the course of those professional relationships may result in information that should not be shared with other Contractors; caution should be exercised to control information related to the formulation of a proposal under the solicitation or the resulting contract. Anticompetitive practices may violate United States and Japanese civil law, criminal law, or a combination thereof. Substantiated allegations also may result in the rescission of a Contractor’s contract and may lead to the suspension or debarment of the Contractor and persons involved with substantiated allegation.
Following Government review of the proposal, the Contracting Officer will arrange and conduct negotiations with the Contractor, Government Project Manager, and any other persons deemed necessary, for resolving any variations involving price, time, quantities, and any other relevant items.
Following award of the contract, the successful Contractor will begin execution of the requirements as stated within the specific project criteria.
Meetings: The Contractor shall perform a site visit and/or attend a pre-proposal conference, a post- award conference, pre-performance conference, or pre-construction conference as specified in the contract. The Contractor also shall attend and/or support meetings and teleconferences to discuss technical or regulatory issues and project progress and status. Meetings will include purposes such as contract discussion, progress reviews, planning, design reviews, construction reviews, project status, and the general exchange of information concerning current and future activities. The Contractor shall prepare briefings with all applicable material and minutes for all meetings attended.
Notification: The Contractor shall immediately notify the CO and COR of critical issues that may affect the contract performance and/or human health and the environment. The types of issues that require notification include, but are not limited to, health risks, spills, improper utility location, differing site conditions, changes in critical personnel, and identification of hazardous materials, e.g. asbestos.
APPLICABILITY OF THE REQUIREMENTS
Codes, regulations, standards, required documents, and other requirements specified in this specification shall be applied to all installations unless indicated otherwise.
This contract involves work located at Kadena AFB and Marine Corps Bases throughout Okinawa, Japan. Reference to Military Standards and Standard Forms may be replaced with standards and forms that are required by the local United States Military Command having jurisdiction.
SUBCONTRACTORS
The Contractor shall have the ability to manage and control multiple subcontractors at multiple job sites. Also, the prime Contractor shall ensure subcontractors are competent and capable of handling all assigned tasks.
INTERPRETER
The Contractor shall have an English-speaking representative at meetings and on the job site at all times during the performance of work under this contract. Failure to provide such representative could result in the Contracted work being stopped (at his/her expense) until such time as one is provided.
WRITTEN COMMUNICATIONS IN ENGLISH
Any project files or written correspondences generated by the Contractor shall be submitted in the English language. All proposal documents required under this Contract, including, but not limited to, statements of work, cost estimate, asbestos and lead based paint survey results, safety hazard analysis plans, all correspondence of any nature whatsoever, and all other written communications, documents, submittals, drawings, reports, etc., of every description, shall be written in English or translated into English before being provided to the Government by the Contractor. Delays encountered because a translated copy was not submitted shall be at the Contractor’s expense. All written documents shall be subject to approval by the Government.
RESPONSIBILITY OF CONTRACTOR TO NOTIFY
It is the Contractor’s responsibility to contact the government representative once a discrepancy, error, emission or code violation exists prior to any construction or as soon as it is detected. It is also incumbent on the Contractor to notify the government immediately upon discovery of any unforeseen conditions.
PERTINENT INFORMATION
BASE / CAMP REGULATIONS
The Contractor, Contractor’s employees, and subcontractor(s) shall become familiar with and agree to comply with the regulations of all US Military Facilities on which the Contractor is working, including fire, traffic, safety, and security regulations. All Contractors shall keep themselves within the limits of the work site (and avenues of ingress and egress), and shall not enter any restricted areas. The Contractor’s equipment shall be conspicuously marked for identification
ENTRY ON BASES
Contractor shall plan and schedule work-starting times in an appropriate manner. As Threat Conditions (THREATCON) change, the entry procedure will become slow and restrictive in some cases. Since these conditions are subject to change at any time, it is the Contractor’s responsibilities to ensure their workers arrive at the gates with adequate time to perform work under the Standard workdays and hours for the contract period. It will be the Contractor’s responsibility to ensure that sufficient personnel within their staffing office have approved escort capabilities on their base pass to sign in personnel to the base on a day-to-day basis. The Contractor’s personnel are restricted to the area of construction only. Transiting to areas not in the contract is not permitted except as required in the performance of this contract. Current Security Conditions on Bases may be obtained at the Main Gates, from the Contracting Officer (CO), and/or Contracting Officer’s Technical Representative (COR). Pass duration from date of pass issuance will be determined by Base security.
Work in Secure Areas: The Contractor shall comply with security regulations imposed by the installation commander and/or the agency responsible for the project location. The Project requires a local agency check of the Contractor’s employees, and all sub-contractors through the base security police before commencement of on-site work. The Contractor should allow approximately 60 calendar days to accomplish this check. Contractor personnel must provide two forms of identification (at least one picture ID) for access to controlled/restricted areas. The Contractor shall schedule work that may require escorts.
ENTRY ON OTHER INSTALLATIONS
The contractor will comply with the entry requirements of any facility on which the Contractor is completing work. The Contractor is responsible for contacting the facility security personnel to determine the entry regulations and requirements.
KEY PERSONNEL
Program Manager: A Program Manager (10 years of verifiable construction experience working on projects of complexity similar to the work for this contract) shall be assigned to oversee all Project Managers. The Program Manager shall be available to the Contracting Officer or COR upon request. The Program Manager shall have overall responsibility for all operations of the ECOM contract and be authorized to make decisions, negotiate contract terms and sign contract documents on behalf of the Contractor. English speaking and writing are recommended.
Project Manager: A Project Manager (5 years of verifiable construction experience working on projects of complexity similar to the work for this contract) shall be assigned for this contract. The Project Manager shall be available to the Contracting Officer or COR upon request. The Project Manager shall have applicable construction experience as a project manager on construction projects of similar scope and size. The Project Manager shall have overall responsibility for all operations at the jobsite and be authorized to make decisions, negotiate contract terms and sign contract documents on behalf of the Contractor. Fluent English speaking and writing is recommended.
CQC System Manager: The Contractor shall identify a Contractor Quality Control (CQC) System Manager (7 years of verifiable construction experience working on projects of complexity similar to the work for this contract). This individual within the onsite work organization shall be responsible for overall management of CQC and have the authority to act in all CQC matters for the Contractor. The CQC System Manager shall have applicable construction experience as a CQC system manager on construction projects of similar scope and size. The CQC manager shall oversee quality aspects on this contract. The Contractor shall appoint additional Quality Control Officials as required. The CQC Manager shall be subject to acceptance by the Contracting Officer. English speaking and writing is recommended.
Project Superintendent (Genba Kantoku): The Project Superintendent (5 years of verifiable construction experience working on projects of complexity similar to the work for this contract) supervises jobsite workers, controls all jobsite activities, oversees subcontractors, quality control and oversees the safety program for jobsite workers. The Project Superintendent shall have applicable construction experience as a project superintendent on construction projects of similar scope and size. This Project Superintendent shall be on the site at all times during construction and shall be employed by the prime Contractor. An alternate for the Project Superintendent will be identified to serve in the event of the primary Project Superintendent’s absence. The Project Superintendent shall be subject to acceptance by the Contracting Officer. English speaking and writing is recommended.
Emergency Contact Information: The Contractor shall provide the CO and the Contracting Officer Representative (COR) with the names of a primary and alternate PMs or contacts with telephone numbers, in case of emergency.
Standards of Dress: The Contractor’s employees shall present a clean, neat appearance and be easily recognized as Contractor employees. This may be accomplished by wearing distinctive clothing, bearing the name of the company, and/or by wearing appropriate badges which contain the company name and the employee’s name. Clothing or badges shall be provided by the Contractor.
Removal of Contractor’s Employees: The Contractor agrees to utilize only experienced, responsible and capable people in the performance of work. The CO may require that the Contractor remove employees who endanger persons or property, whose continued employment under this contract is inconsistent with the interest of military security, or who are determined by the CO or COR as being incapable of rendering the services IAW this contract.
The Contractor shall, using a SF 1413, identify all subcontractors (including second-tier) that are performing work that meet the qualifications identified in the Statement of Work as part of the Contractor's Bid Proposal.
COMMENCEMENT OF WORK
After Award the Contractor shall attend the pre-performance conference with the Government. Upon issuance of the Notice To Proceed (NTP), the Contractor shall begin all required design and/or construction activities.
Work Clearance Request (AF Form 103): Prior to commencing on-site construction work, the contractor must submit a work clearance request (AF Form 103) through the COR for approval. Site Permits for constructing storage area, if required, shall be submitted to the COR for approval. Approval is based on site location, proposed structure(s), fencing, electrical / plumbing utility’s needs, and any other modifications the contractor proposes to the area. On-site work shall not commence without an approved AF Form 103.
Project Site Surveys: Surveys for Unexploded Ordinances (UXO), Cultural Resources, and Protected Species shall be performed in all areas where new construction will disturb undeveloped areas when required by the contract. Surveys shall be performed by qualified professionals with a university or college degree in the required field of expertise and shall be certified to perform the type of work with a minimum of three years of work experience.
Contractor Generated Debris: The Contractor shall remove and dispose of Contractor generated debris outside the confines of Kadena Air Base unless otherwise directed by the Contracting Officer, in accordance with Japanese environmental standards and laws, at no additional cost to the Government. Contractor generated debris shall be removed from government facilities at the end of each shift, or more frequently if required, to keep the space usable.
WORKING HOURS
Normal Construction Working Hours and workdays shall be from 08:00 to 17:00, Monday through Saturday, excluding U.S. Federal holidays, listed in the table below, and other days specifically designated by the Contracting Officer. U.S. Legal Holidays: The following are the only observed federal holidays.
| · New Year’s Day | 1 January* |
| · Martin Luther King’s Birthday | Third Monday in January |
| · Presidents Day | Third Monday in February |
| · Memorial Day | Last Monday in May |
| · Juneteenth | 19 June* |
| · Independence Day | 4 July* |
| · Labor Day | First Monday in September |
| · Columbus Day | Second Monday in October |
| · Veteran’s Day | 11 November* |
| · Thanksgiving Day | Fourth Thursday in November |
| · Christmas Day | 25 December* |
*Note: If a holiday falls on a Saturday, it will be observed on the preceding Friday. If the holiday falls on a Sunday, it will be observed on the following Monday. No work shall be done on Saturdays that require Government inspection or approval.
Special Conditions: The buildings/facilities may be in use by the Government during the contract period. The Contractor shall make all necessary provisions to keep interference to a minimum as to the scheduling and phasing of work and storage of materials. Scheduling and performance of work shall be done in such a manner as to cause the least possible inconvenience to personnel using the buildings/facilities and the least possible interference with activities in and around the buildings/facilities. The Contractor shall provide adequate weather protection for the buildings/facilities at the end of each workday.
TROPICAL CYCLONE CONDITIONS OF READINESS (TCCOR)
In order to protect people and U.S. Government property, the following actions will be taken upon declaration of Tropical Cyclone conditions and/or high wind warnings.
Tropical Cyclone Condition 3: When Condition 3 is declared, the Contractor will perform general area clean-up which will exceed the requirements contained in contract FAR 52.236 12 entitled Cleaning Up. All loose debris, waste and excess Contractor owned supplies materials and equipment will be removed from U.S. Government facilities and disposed of off base in accordance with local Prefecture and Japanese laws at Contractor’s expense. Work may continue provided effective and adequate clean-up has been accomplished.
Tropical Cyclone Condition 2: When Condition 2 is declared, all exterior work will cease immediately. In Condition 2, interior work will continue until Condition 1C is given. The Contractor will take the necessary action listed below to secure the job site against damages which may result from anticipated weather conditions. The Contractor may be called at any time to complete typhoon proofing; therefore, the Contractor will provide emergency telephone numbers and/or addresses where at least three (3) officials of the company may be reached and notified that immediate typhoon proofing (Contractor activities to safeguard lives and property. These following actions are taken upon declaration of the designated tropical cyclone condition (or high winds):
General Area Clean Up: Clean up and disposal of loose debris and waste will continue as directed by Paragraph 2.7.1.
Barrels and Similar Containers: All remaining barrels will be placed within the construction building when available. When a building is not available, barrels will be tied together and securely staked to the ground or filled with sand or gravel.
Contractor Field Office: All Contractor field offices will be either (i) removed from the military installation or (ii) securely anchored by heavy cable as approved by the COR.
Concrete Forms, Form Supports, and Accessory Materials: All concrete forms, form supports, and accessory materials required for future construction will be tied together into bundles with heavy wire, cable or rope and will be placed within the construction building or structures where available and practical.
Sand and Aggregate: All piles of sand or aggregate will be completely covered by either a tarpaulin weighted with building blocks or other methods approved by the COR.
Contractor Equipment: All medium size equipment will be removed, or placed close to a building or placed inside a building. Equipment placed close to a building will be secured with blocks or anchored with cable or both. Items of small equipment will be moved inside a building and secured or moved off U.S. Government facilities.
Tropical Cyclone Condition 1: When Condition 1 is declared without the normal progression through Condition 3 and/or 2, the Contractor will take actions listed in Paragraph 2.7.2.1-2.7.2.6 above. These actions will commence immediately upon declaration of Condition 1. The Contractor will be notified either at the job site or at the emergency phone numbers and/or addresses when typhoon proofing is required in accordance with this paragraph.
High Wind Warning: When wind gusts of 30 knots per hour or greater are forecasted, the Contractor may be required to accomplish general area clean up in accordance with Paragraph 2.7.2.1; to bundle and securely tie or securely cover and weight small wooden items, to remove and secure wood barricades and to remove loose materials from roofs and other high unprotected areas.
Tropical Cyclone Condition 1Emergency (TC 1-E): All outside activities are prohibited.
TC-1 Recovery: Destructive sustained winds of 50 knots are no longer occurring. No outdoor activity is authorized other than workers from pre-designated emergency crews.
0.1.1.1 TC - Storm Watch: Normal activities may resume with caution two hours after declaration of STORM WATCH.
0.1.1.2 Salvageable Material: Salvageable material may not be taken to Defense Logistics Agency (DLA) after a tropical cyclone condition is declared. The Contractor will be responsible for typhoon proofing of such material.
0.1.1.3 Contractor’s Representative: The COR will not leave the job site after notification under paragraphs 2.7.2, 2.7.3 and 2.7.4 above until the area has been inspected and cleared by said representative. The Contractor may request an inspection by calling Chief, Construction Management, name and number to be provided during project pre-construction meeting.
0.1.1.4 The Contractor shall provide to the Contracting Officer the names, addresses, and telephone numbers of at least three individuals (who speak English) who can be contacted during typhoon emergencies. The individuals named by the Contractor shall be responsible for monitoring the various forms of communications (i.e., local radio and television stations) during the typhoon season. The Contractor is responsible for ensuring these individuals are available during and after duty hours – to include weekends.
0.1.1.5 If the Government has to perform typhoon proofing of a construction site or field office, due to the non-availability of the designated individuals, the Contractor may be held liable for all cost associated with performing said work. In addition, Contractor waives all claims to damage or loss that arise from governments actions.
DISPOSAL OF TRANSFORMERS
Removal and disposal of transformers shall be in accordance with Japan Environmental Governing Standards. The Contractor shall sample and test transformers for the presence of PCBs using a local Japanese laboratory. All costs for removal sampling, testing, and disposal shall be included in the contract.
UTILITIES
When available, water and electric utilities will be furnished by the U.S. Government at no cost to the Contractor. The Contractor, at the Contractor’s own expense and in a satisfactory workmanlike manner, shall install and maintain all necessary temporary connections and distribution lines. Before final acceptance of the contract work by the Government, the Contractor shall remove all the temporary connections, distribution lines, and associated paraphernalia.
Cross Connection: Contractor shall be responsible for preventing actual or potential cross connections between potable and non-potable water supply during the construction work. Backflow preventers shall be utilized as required. The Contractor must notify the Government Designated Inspector for use, installation or maintenance of potable water service connection to ensure the following provision:
0.1.1.6 No water service connection will be installed / maintained to / at any premises where actual or potential cross connections to the potable water system may exist, unless such actual or potential cross connections are properly abated or controlled.
0.1.1.7 No connection will be installed or maintained whereby an auxiliary water supply may enter a public water system, unless such auxiliary water supply will have been approved by COR.
0.1.1.8 No water service connection will be installed / maintained to / at any premises in which the plumbing system, facilities and fixtures have not been constructed and installed using acceptable plumbing practices.
Utilities Outage: The Contractor shall submit a schedule of all utility outage (water, sewer, electrical, communications/data) to the COR and shall notify COR in writing at least 45 days in advance of the proposed interruptions. The following requirements are to be submitted with the Contractor’s proposal package:
0.1.1.9 Outage Identification and Planning: Identify any proposed utility outages affecting facility or facilities listed in the contract. Identify any and all other facilities that will be affected by any utility shut down or interruption of services from surrounding areas or facilities with shared main utility connections with the facility or area indicated in the contract. Identification requirements would consist of facility numbers, and area locations affected by the outage. When these utility outages are required as part of the contract, a separate drawing will be submitted illustrating the facility locations, and area locations of the outage and all affected areas. Drawing submitted in AutoCAD 2015 or current Government software version.
0.1.1.9.1 Outage Plan: Provide as part of the contract a utility outage plan which will include the following information:
0.1.1.9.1.1 What systems are affected by this outage? Where is the outage going to take place, (building numbers and area locations)? Why is the utility outage required? How long will the outage last? Example: (Replace 225 amp power panel inside break room facility 867, upgrade to existing facility power panel is required due to increase electrical load requirements, no work at the transformer or facility main power distribution panel is required, panel replacement inside facility break room will require rooms 1‐12 inside facility 867 to be without power during the panel replacement, anticipated duration of switch out and hookup is 2 hours. No other facilities or areas will be affected by this outage). Provide this for all utility outages.
0.1.1.9.1.2 Provide possible concept work‐around options to minimize impact to facility occupants, and Base populace. Part of the concept work around needs to include an analysis on possible contingencies that could happen during any utility outage. Identify possible situations that might result if something goes wrong with the scheduled outage. What would the required fix be? How much time will the fix require? Any possible additional materials required for the fix. The Contractor submitted analysis on utility outage contingencies shall be listed in the proposal statement of work, and will be evaluated by the Technical Representative during the Technical Evaluation. Any additional comments, ideas, or work‐around options to minimize impact to Base populace will be suggested at that time by Technical Representative.
0.1.1.9.1.3 Provide a sample notification letter containing the dates of the proposed outages, start and completion time, brief scope of work and drawing illustrating the affected areas, company name, and emergency point of contact and telephone. This letter should also contain hazard information such as water sampling, lock out tag out procedures.
0.1.1.9.1.4 Provide a sample notification letter containing the dates of the proposed outages, start and completion time, brief scope of work and drawing illustrating the affected areas, company name, and emergency point of contact and telephone. This letter should also contain hazard information such as water sampling, lock out tag out procedures.
0.1.1.10 Utility Outages and Road Cuts: All utility (electrical, alarms, water, sewer, etc.) outage and road cut requests will be reviewed and coordinated before submission in writing to the Contracting Officer and COR. The finalized utility outage and road cut request will be submitted to the Contracting Officer through the COR for approval 45 work days before the scheduled utility outage and road cut. All utility outages and road cuts require coordination with numerous operations and facilities support staff. The COR will identify the procedures for utility outages and the affected buildings and facilities and support staff requiring coordination by the Contractor. The procedures used for approval and coordination of utility outages and road cuts on installations shall be started 45 calendar days prior to the outage and/or road cut(s). The Contractor is responsible for coordination of outages and disseminating the initial notification and completion notification of all affected facilities and housing occupants. The number of allowable utility interruptions in Military Family Housing, Industrial and Administrative facilities is limited by duration (0830 to 1630) and frequency (14 days between outages) unless other restrictions apply or as approved by the COR.
0.1.1.11 Accompanied and Unaccompanied Military Housing Utility Outages: Outages to accompanied and unaccompanied military housing will be limited between 0900 to 1500 hours daily, Monday through Friday, excluding Saturdays and Sundays and U.S. legal holidays. Utility outages will not be permitted at night. The maximum utility outage for any one interruption shall not exceed two hours per day, unless the need for a longer outage can be fully justified in writing to the Contracting Officer. In the event the Contractor disagrees with the contract documents in the phasing and scheduling of utility interruptions, the Contractor shall submit a written plan for the approval by the Contracting Officer. Such alternate plan, when approved, shall be part of the contract documents. In no event shall utility outages be granted for a period in excess of eight hours, unless suitable temporary connections are approved by the Contracting Officer. Power shall be restored to all affected areas by 1500 hours each working day. The Contractor shall notify occupants in writing 14 calendar days in advance before turning off any utility to the unit or building.
0.1.1.12 Industrial or Administration Offices Utility Outages: Industrial or administration office outages shall be limited from 0900 to 1500 hours daily, Monday through Friday, excluding Saturdays and Sundays and U.S. legal holidays. The maximum utility outage for any one interruption shall not exceed two 2 hours per day, unless the need for a longer outage can be fully justified in writing to the Contracting Officer. In specific cases per the contract, and depending on the facility user, outages may be scheduled after hours, on weekends, holidays, etc. in order to minimize impact to facility operations. In the event the Contractor disagrees with the contract documents in the phasing and scheduling of utility interruptions, the Contractor shall submit a written plan for the approval by the Contracting Officer. Such alternate plan, when approved, shall be part of the contract documents. In no event shall utility outages be granted for a period in excess of eight hours, unless suitable, temporary connections are approved by the Contracting Officer. The Contractor shall notify occupants in writing 21 calendar days in advance before turning off any utility to the building.
0.1.1.13 Emergency Declaration: In the event of an emergency, such as typhoon or military exercise, the Contracting Officer shall declare such event to the Contractor and the Contractor shall have a period of no more than two hours to return all utility services to normal operation.
0.1.1.14 Temporary Power: Contractor shall make use of temporary connections if power cannot be returned to normal by 1500 hours daily. Temporary connections are authorized to restore service interrupted by accident until permanent repairs are made during a normal workday. All temporary connections will be removed upon restoration of normal service. Temporary connection shall be made in a manner that the safety of the personnel in the area of the work or personnel traveling through the area of work is properly safeguarded. Under no circumstance shall a temporary connection be made that is hazardous to the public, Contractor or Government personnel.
Electrical/Communications: If relocation or removal of wiring and associated material is required per the contract, the Contractor shall notify the Contracting Officer within a minimum of 45 calendar days in advance of the requirement. Licensed Japanese Government communication linemen shall, at the Contractors’ own expense, repair any identified and marked communication lines that are damaged by the Contractor. The repair action shall meet Government and local telephone standards. The Government reserves the right to repair all damaged electrical and communication lines and to deduct any repair costs from the contract.
Water sampling and Testing Requirements: All potable waterline projects that require interruption of service require water sampling and testing. Contractor is required to perform the sampling and submit the sample for analysis to a government licensed/certified laboratory for analysis. Coordinate with Bioenvironmental Engineering on the location and number of samples to be collected. The testing criteria should include the following:
0.1.1.15 Total Coliform analysis – conducted by laboratory analysis.
0.1.1.16 PH and chlorine residual tests - conducted at the site shall be documented on the laboratory analysis results for “Total Coliform”.
0.1.1.17 Provide results to COR, who will submit to Bio Environmental for review and approval. Non-favorable results may require further effort and coordination from the Contractor until system is returned to normal.
0.1.1.18 Refer to paragraph 2.9.2-2.9.5 for instructions on coordination for Contractor Utility Outages.
DAMAGE TO UTILITIES
In the event that the Contractor causes utility failure/disruption, the Contractor will first make the area safe, then immediately contact COR and the Contracting Officer. COR is responsible for coordination with the managers of the affected systems.
WORK ON FIRE ALARM SYSTEMS REQUIREMENTS
The following are procedures for work on Fire Alarm Systems. The Contractor will follow these procedures and accomplish all notifications and coordination’s required. Record any site visit inspections with Technical Representative or Government alarm personnel as meeting minutes. Submit meeting minutes to Contracting Officer for Technical Representative’s evaluation, within three calendar days of any meeting with Government representatives.
0.1.1.19 Prior to start of construction; attend the safety meeting for fire alarm system status. Sign the inspection attendance and memorandum sheet. Record site visit minutes and submit to Contracting Officer for Technical Representative’s review, within three calendar days of site visit.
0.1.1.20 Ensure fire alarm system status is returned to the Government in the same or better condition as recorded during the pre-construction meeting. Record of meeting minutes submitted to the Contracting Officer will provide the basis for the fire alarm system inspection criteria during the project final inspection.
0.1.1.21 All fire alarm installations and modifications to systems must be in accordance with current National Fire Protection Act (NFPA), Uniform Facilities Criteria (UFC) and National Electric Code (NEC) requirements, current year and edition.
0.1.1.22 Contractor will correct all deficiencies (i.e., alarm, trouble conditions not annotated on the preconstruction inspection) noted during the post-acceptance inspection provided the discrepancies with the system are within contract warranty requirements.
0.1.1.23 Contact the applicable facilities fire department before beginning work on any the fire alarm systems or any fire suppression systems. The contractor will provide facility numbers where work will take place, and the duration that the fire alarm system will not be operational. Inform fire department personnel if work requires disconnection of any heat detectors, fire alarm pull stations, smoke detectors or suppression systems. Inform all building occupants, to include other co-located activities and entire work force that the Fire Alarm system or Fire Suppression System is not operational and brief all on fire watch duties. Include information for other emergencies and how to contact appropriate emergency service(s).
0.1.1.24 OUTAGES FOR FIRE SYSTEM Provide at least 45 calendar days advance notice of planned fire systems outages. Fire system disconnection and reactivation requires the coordination with the COTR.
INSTALLATION FIRE, SAFETY, AND ENVIRONMENTAL REGULATIONS
The Contractor shall comply with all pertinent requirements and regulations determined by Fire Department, to include UFC 3-600-01 and NFPA 241, and insure compliance by all subcontractors. All temporary wiring at the construction site shall be installed with ground fault protection.
The Contractor shall not commence work at the job site until an Accident Prevention Plan, Job Hazard Analysis, and Environmental Protection Plan are submitted for review and approved by the Contracting Officer.
Work Progress Schedule: In addition to the requirement of the construction schedule set forth in the contract, the Contractor shall, when required by the Government, provide and submit to COR photographs and a detailed work progress schedule in the form of a Bar Chart Work Schedule showing the step-by- step phases of work to be accomplished prior to performing actual work. The Contractor shall require coordination with COR to make a work progress schedule. The work shall, so far as practicable, be done in definite sections or divisions and confined to limited area which shall be completed before work in other sections or divisions are begun. The construction schedule shall have no period of work that is longer than 4 days, if it is longer than 5 days it should be detailed into a smaller period of time on the schedule.
Temporary Protection Plan: When requested by the Government, the Contractor shall provide appropriate temporary protection plans such as nets, barricades, safety access roads and etc., to protect Government personnel and workers at construction work site during construction, and submit the Temporary Protection Plan to the COR to the respective work site commencement. The Contractor shall be responsible for minimizing the inconvenience and avoid any danger to the Government personnel and workers.
Temporary Airfield Construction Waiver: The Contractor shall provide a temporary airfield construction checklist (provided by the government project manager) for review and waiver for any project that requires the use of a crane on or near the airfield or if required by security.
DELIVERY AND STORAGE
Materials and equipment stored at the Contractor’s pre-approved materials storage area shall be properly stored, adequately protected from adverse weather conditions, and carefully handled to prevent damage during transit to and from work sites, and during material installation on all project work sites. Damaged or defective materials and equipment shall be replaced with new materials and or equipment at no additional cost to the Government. Materials stored on work sites will be the sole responsibility of the Contractor for secure and proper handling. The Contractor will secure facilities, offices, housing units, or any other type of structure listed on the contract at the end of each workday.
DRAWINGS, SPECIFICATIONS AND CONSTRUCTION SCHEDULE ON SITE
Contractor shall maintain in good condition on all project work sites one copy of all project drawings, specifications, modifications, approved shop drawings, construction schedule and other related documents affecting the work. Contractor shall keep ‘FOR CONSTRUCTION’ record drawings at the job site of all changes and corrections from the negotiated project drawings. These documents shall be made available to the Contracting Officer and Technical Representative during construction site inspections.
GENERAL INDUSTRY SAFETY AND HEALTH STANDARDS
The Contractor shall comply with current OSHA Laws and Regulations. OSHA publications are available online at http://www.gpo.gov/ or may be purchased from the U.S. Government Publishing Office Bookstore located at:
U.S. Government Publishing Office Bookstore 710 North Capitol Street N.W.
Washington, DC toll free 866.512.1800 fax 202.512.2104 email ContactCenter@gpo.gov Additional sources of regulations are the Japanese Industrial Labor Standards (http://www.jil.go.jp/index.html), and the U.S. army Corps of Engineers EM 385-1-1, Safety and Health Requirements Manual (http://www.publications.usace.army.mil/).PART 3 PROCEDURES
DESIGN-BUILD PROCEDURE
DESIGN‐BUILD PROJECT SCOPE
Whenever the Government has work to be performed under this contract as a “Design‐Build” Contract, the Contracting Officer will provide a project scope. The project scope will include the scope of work, design requirements, construction method requirements, cost limitations, and required project duration (Concept drawing may also be included). It is the Contractor’s responsibility to procure the ‘As‐Built’ Drawings from the Government vault. The Contractor is advised to contact the ‘Geo‐base department’ to obtain As‐Built documents.
DESIGN-BUILD PROCESS
Contractors’ Proposal: The Contractors shall submit a proposal in accordance with the schedule and requirements outlined in the project procurement package.
0.1.1.25 The Contractors shall consider the project scope, design and construction requirements, code requirements, safety requirements, quality, maintainability, operability, and cost when preparing the proposal. The Contractor shall provide concept drawings for their proposed methods, proposed schedules (design and construction), proposals, and other information as required at no cost to the Government. These concept drawings will capture the intent of the Statement of Work (SOW), will be deliverables from the Contractor, and will concisely and practically but not overly elaborately reflect the requirements of SOW.
0.1.1.26 The Contractors shall submit the proposal including all necessary direct and indirect costs such as materials, equipment rentals, disposal, testing and laboratories required for the project as requested by the Government. The proposal shall directly represent the proposed design and construction requirements outlined in the SOW and Site Visit. In addition, the proposal should reflect the recommended design and construction methodology. The Contractors shall provide quotes for known materials, equipment, disposal, testing and laboratory costs that will be conducted for this contract. The Contractors shall select the quotes that meet the specifications.
0.1.1.27 Except for those items specifically stated to be Government furnished, the Contractors shall provide all materials required for this contract. Unless indicated otherwise, all replacement materials and parts shall be equal to or better than the manufacturer’s original and shall comply with the specifications and all applicable Government, Commercial, and Industrial Standards/Codes.
0.1.1.28 Where materials are to be turned over to the Contractor for disposal, every effort shall be made to obtain credit from the disposal to reduce the cost of the contract. The Contractor’s material disposal costs shall include hauling and disposal costs for work performed in accordance with all applicable local, JEGS, or U.S. laws and regulations.
0.1.1.29 Site Visit: Upon issuance of a IFB to the Contractors, and within the lead time specified, the Government will notify Contractors that the job site shall be…