Attachment 1 -Cummings standby generator spec sheet.pdf
PDF 194 KB Posted
- Attached to
- Sanitary Lift Stations Generator Install
- Solicitation number
- RFP-03-07-2025-001
- Issued by
- Berrien County, Ann Arbor City, Michigan
About this file
This document is a specification sheet for Cummins spark-ignited generator sets, ranging from 45-100 kW Standby with EPA emissions compliance, potentially related to a Michigan state and local contract opportunity for sanitary lift station generator installation. The specification sheet details a series of generator models (C45 N6 to C100 N6) that can operate on natural gas or propane, with standby power ratings from 45 to 100 kilowatts and corresponding kilovolt-ampere (kVA) ratings from 56 to 125 kVA.
The generators feature a rugged 4-cycle Cummins QSJ5.9G spark-ignited engine, electronic air/fuel ratio control, and a PowerCommand 1.1 electronic control system that provides comprehensive generator set integration, including automatic starting/stopping, precise frequency and voltage regulation, and NFPA 110 Level 1 compliance. The specification sheet highlights additional features such as a standard cooling package capable of operating at up to 50°C, an aesthetically appealing and durable enclosure that can withstand 180 MPH wind loads, and multiple configuration options including different voltage outputs, enclosure types, and warranty periods. The generators are certified to various standards, including UL 2200, International Building Code 2012, and U.S. EPA Stationary Emission Regulations.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
power.cummins.com ©2018 Cummins Inc. | NAS-6092-EN - 06DEC2019.DOCX (12/19) A054P028
Specification sheet
Spark-ignited generator set
45–100 kW Standby
EPA emissions
Description
Cummins® generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary Standby applications.
Cooling system - Standard cooling package provides reliable running at up to 50 °C (122 °F) ambient temperature.
Enclosures - The aesthetically appealing enclosure incorporates special designs that deliver one of the quietest generators of its kind.
Aluminium material plus durable powder coat paint provides the best anti-corrosion performance. The generator set enclosure has been evaluated to withstand 180 MPH wind loads in accordance with ASCE7 -10. The design has hinged doors to provide easy access for service and maintenance.
NFPA - The generator set accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.
Features
Gas engine - Rugged 4-cycle Cummins QSJ5.9G spark-ignited engine delivers reliable power. The electronic air/fuel ratio control provides optimum engine performance and fast response to load changes.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
Control system - The PowerCommand® 1.1 electronic control is standard equipment and provides total generator set system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance. The PowerCommand 2.3 control is also optional and is UL 508 Listed and provides AmpSentryTM protection.
Natural gas Propane
Data sheets
Standby Standby
Model kW kVA kW kVA
C45 N6 45 56 45 56 NAD-6093-EN
C50 N6 50 63 50 63 NAD-6094-EN
C60 N6 60 75 60 75 NAD-6095-EN
C70 N6 70 88 70 88 NAD-6096-EN
C80 N6 80 100 80 100 NAD-6097-EN
C100 N6 100 125 100 125 NAD-6098-EN
Generator set specifications
Governor regulation class ISO8528 Part 1 Class G3
Voltage regulation, no load to full load ± 1.0%
Random voltage variation ± 1.0%
Frequency regulation Isochronous
Random frequency variation ± 0.25% @ 60 Hz
Radio frequency emissions compliance Meets requirements of most industrial and commercial applications
Engine specifications
Design Naturally aspirated or turbocharged (varies by generator set model)
Bore 102.1 mm (4.02 in.)
Stroke 119.9 mm (4.72 in.)
Displacement 5.9 liters (359 in3)
Cylinder block Cast iron, in-line 6 cylinder
Battery capacity 850 amps at ambient temperature of 0 °F to 32 °F (-18 °C to 0 °C)
Battery charging alternator 52 amps
Starting voltage 12 volt, negative ground
Lube oil filter type(s) Spin-on with relief valve
Standard cooling system 50 °C (122 °F) ambient cooling system
Rated speed 1800 rpm
Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temperature rise 120 ºC (248 °F) Standby
Exciter type Torque match (shunt) with PMG as option
Alternator cooling Direct drive centrifugal blower
AC waveform Total Harmonic Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic
Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) < 3%
Available voltages
1-phase 3-phase
• 120/240 • 120/208 • 120/240 • 277/480 • 347/600 • 127/220
Generator set options Fuel system
• Single fuel - natural gas or propane vapor, field selectable
• Dual fuel – natural gas and propane vapor auto changeover
• Low fuel gas pressure warning
Engine
• Engine air cleaner
• Shut down – low oil pressure
• Extension – oil drain
• Engine oil heater
Alternator
• 120 °C temperature rise alternator
• 105 °C temperature rise alternator
• PMG
• Alternator heater, 120 V
• Reconnectable full 1 phase output alternator
Control
• AC output analog meters
• Stop switch – emergency
• Auxiliary output relays (2)
• Auxiliary configurable signal inputs (8) and relay outputs (8)
Electrical
• One, two or three circuit breaker configurations
• 80% rated circuit breakers
• 100% rated LSI circuit breakers
• Battery charger
Enclosure
• Sound Level 1 or Level 2 enclosure, sandstone or green color
• Weather protective enclosure with muffler installed, green color
• Winter protective enclosure, green color
Cooling system
• Shutdown – low coolant level
• Warning – low coolant level
• Extension – coolant drain
• Coolant heater options:
- <4 °C (40 °F) – cold weather
- <-17 °C (0 °F) – extreme cold
Exhaust system
• Exhaust connector NPT
• Exhaust muffler mounted
Generator set application
• Base barrier – elevated genset
• Battery rack, standard battery
• Battery rack, larger battery
• Radiator outlet duct adapter
Warranty
• Base warranty – 2 year/1000 hours, Standby
• 3 year Standby warranty options
• 5 year Standby warranty options
Generator set accessories
• Coolant heaters – 1000 W/1500 W
• Battery rack, standard/larger battery
• Battery heater kit
• Engine oil heater
• Remote control displays
• Auxiliary output relays (2)
• Auxiliary configurable signal inputs (8) and relay outputs (8)
• Annunciator – RS485
• Remote monitoring device – PowerCommand 500/550
• Battery charger – stand-alone, 12 V
• Circuit breakers
• Enclosure Sound Level 1 to Sound Level 2 upgrade kit
• Base barrier – elevated generator set
• Mufflers – industrial, residential or critical
• Alternator PMG
• Alternator heater
Control system PowerCommand 1.1
• Low coolant temperature warning
• High, low and weak battery voltage warning
• Fail to start (overcrank) shutdown
• Fail to crank shutdown
• Redundant start disconnect
• Cranking lockout
• Sensor failure indication
• Low fuel level warning or shutdown
Alternator data
• Line-to-Line and Line-to-neutral AC volts
• 3-phase AC current
• Frequency
• Total kVa
Engine data
• DC voltage
• Lube oil pressure
• Coolant temperature
• Engine speed
Other data
• Generator set model data
• Start attempts, starts, running hours
• Fault history
• RS485 Modbus® interface
• Data logging and fault simulation (requires InPower service tool)
Digital governing (optional)
• Integrated digital electronic isochronous governor
• Temperature dynamic governing
Digital voltage regulation
• Integrated digital electronic voltage regulator
• 2-phase Line-to-Line sensing
• Configurable torque matching
Control functions
• Time delay start and cooldown
• Cycle cranking
• PCCNet interface
• (2) Configurable inputs
• (2) Configurable outputs
• Remote emergency stop
• Automatic Transfer Switch (ATS) control
• Generator set exercise, field adjustable
PowerCommand control is an integrated generator set control system providing voltage regulation, engine protection, operator interface and isochronous governing (optional). Major features include:
• Battery monitoring and testing features and smart starting control system.
• Standard PCCNet interface to devices such as remote annunciator for NFPA 110 applications.
• Control boards potted for environmental protection.
• Control suitable for operation in ambient temperatures from -40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000 meters (13,000 feet).
• Prototype tested; UL, CSA, and CE compliant.
• InPower™ PC-based service tool available for detailed diagnostics.
Operator/display panel
• Manual off switch
• Alpha-numeric display with pushbutton access for viewing engine and alternator data and providing setup, controls and adjustments (English or international symbols)
• LED lamps indicating generator set running, not in auto, common warning, common shutdown, manual run mode and remote start
• Suitable for operation in ambient temperatures from -40 °C to +70 °C
• Bargraph display (optional)
AC protection
• Over current warning and shutdown
• Over and under voltage shutdown
• Over and under frequency shutdown
• Over excitation (loss of sensing) fault
• Field overload
Engine protection
• Overspeed shutdown
• Low oil pressure warning and shutdown
• High coolant temperature warning and shutdown
• Low coolant level warning or shutdown
Options
• Auxiliary output relays (2)
• Remote annunciator with (3) configurable inputs and
(4) configurable outputs
• PMG alternator excitation
• PowerCommand 500/550 for remote monitoring and alarm notification (accessory)
• Auxiliary, configurable signal inputs (8) and configurable relay outputs (8)
• Digital governing
• AC output analog meters (bargraph)
- Color-coded graphical display of:
- 3-phase AC voltage
- 3-phase current
- Frequency
- kVa
• Remote operator panel
• PowerCommand 2.3 control with AmpSentry protection
Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.
This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.
Do not use for installation design
Model Dim “A” mm (in.)
Dim “B” mm (in.)
Dim “C” mm (in.)
Set weight*wet kg (lbs.)
Open set
C45 N6 2489 (98) 1016 (40) 1473 (58) 989 (2180)
C50 N6 2489 (98) 1016 (40) 1473 (58) 989 (2180)
C60 N6 2489 (98) 1016 (40) 1473 (58) 1103 (2431)
C70 N6 2489 (98) 1016 (40) 1473 (58) 1111 (2449)
C80 N6 2489 (98) 1016 (40) 1473 (58) 1173 (2587)
C100 N6 2489 (98) 1016 (40) 1473 (58) 1233 (2719)
Weather protective enclosure
C45 N6 2489 (98) 1016 (40) 1473 (58) 1070 (2359)
C50 N6 2489 (98) 1016 (40) 1473 (58) 1070 (2359)
C60 N6 2489 (98) 1016 (40) 1473 (58) 1184 (2610)
C70 N6 2489 (98) 1016 (40) 1473 (58) 1192 (2628)
C80 N6 2489 (98) 1016 (40) 1473 (58) 1255 (2766)
C100 N6 2489 (98) 1016 (40) 1473 (58) 1315 (2898)
Sound attenuated enclosure Level 1
C45 N6 3023 (119) 1016 (40) 1473 (58) 1114 (2455)
C50 N6 3023 (119) 1016 (40) 1473 (58) 1114 (2455)
C60 N6 3023 (119) 1016 (40) 1473 (58) 1227 (2706)
C70 N6 3023 (119) 1016 (40) 1473 (58) 1236 (2724)
C80 N6 3023 (119) 1016 (40) 1473 (58) 1298 (2862)
C100 N6 3023 (119) 1016 (40) 1473 (58) 1358 (2994)
Sound attenuated enclosure Level 2
C45 N6 3454 (136) 1016 (40) 1473 (58) 1127 (2485)
C50 N6 3454 (136) 1016 (40) 1473 (58) 1127 (2485)
C60 N6 3454 (136) 1016 (40) 1473 (58) 1241 (2736)
C70 N6 3454 (136) 1016 (40) 1473 (58) 1249 (2754)
C80 N6 3454 (136) 1016 (40) 1473 (58) 1312 (2892)
C100 N6 3454 (136) 1016 (40) 1473 (58) 1372 (3024)
Winter protective enclosure
C45 N6 3701 (146) 1016 (40) 1473 (58) 1152 (2535)
C50 N6 3701 (146) 1016 (40) 1473 (58) 1152 (2535)
C60 N6 3701 (146) 1016 (40) 1473 (58) 1266 (2786)
C70 N6 3701 (146) 1016 (40) 1473 (58) 1275 (2804)
C80 N6 3701 (146) 1016 (40) 1473 (58) 1337 (2942)
C100 N6 3701 (146) 1016 (40) 1473 (58) 1397 (3074)
* Weights above are average. Actual weight varies with product configuration.
For more information contact your local Cummins distributor or visit power.cummins.com
©2018 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-6092-EN - 06DEC2019.DOCX (12/19) A054P028
Codes and standards Codes or standards compliance may not be available with all model configurations – consult factory for availability.
The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins products bearing the PTS symbol meet the prototype test requirements of NFPA 110 for Level 1 systems.
The generator set is available Listed to UL 2200, Stationary Engine Generator Assemblies.
International Building Code
The generator set is certified to International Building Code
(IBC) 2012.
All low voltage models are CSA certified to product class 4215-01.
This generator set is designed in facilities certified to ISO 9001 and manufactured in facilities certified to ISO 9001 or
ISO 9002.
U.S. EPA
Engine certified to U.S. EPA SI Stationary Emission Regulation 40 CFR, Part 60.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.
File details come from the government source that posted it. Updated .