Attachment 1 - Chiller Specifications.pdf

PDF 764 KB Posted

Attached to
DFAC Chiller
Solicitation number
FA460825QC155
Issued by

About this file

This document is a detailed Model Number Description for a Trane Air-Cooled Scroll Packaged Chiller (CGAM) with a comprehensive breakdown of configuration options across 50 different digits. The model number system allows for extensive customization of the chiller, covering specifications such as tonnage (ranging from 20 to 130 tons), voltage options (200V to 575V), manufacturing location, unit efficiency, agency listings, ambient temperature applications, refrigerant charge, evaporator types, water connections, electrical configurations, communication interfaces, and numerous additional features like pump types, wireless connectivity, sound attenuation, and installation accessories. Key configuration options include multiple voltage configurations, high and extra efficiency unit types, various ambient temperature ranges (from 32°F to -20°F), refrigerant charge types, evaporator applications, and optional features like heat recovery, programmable relays, buffer tanks, and wireless connectivity options including Wi-Fi, LTE modem, and Air-Fi.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CG-SVX063D-EN 9

Model Number Description Unit Model Number Digit 1, 2, 3, 4 – Unit Model

CGAM = Air-Cooled Scroll Packaged Chiller

Digit 5, 6, 7 – Nominal Tonnage

020 = 20 Tons 026 = 26 Tons 030 = 30 Tons 035 = 35 Tons 040 = 40 Tons 052 = 52 Tons 060 = 60 Tons 070 = 70 Tons 080 = 80 Tons 090 = 90 Tons 100 = 100 Tons 110 = 110 Tons 120 = 120 Tons 130 = 130 Tons

Digit 8 – Unit Voltage

A = 200V/60Hz/3 phase B = 230V/60Hz/3 phase D = 380V/60Hz/3 phase F = 460V/60Hz/3 phase G = 575V/60Hz/3 phase

Digit 9 – Manufacturing Location

2 = Trane Commercial Systems, Pueblo, CO USA

Digits 10, 11 – Design Sequence

** = Factory assigned

Digit 12 – Unit Type

2 = High Efficiency 3 = Extra Efficiency

Digit 13 – Agency Listing

X = No Agency Listing E = ETL Listed/Certified to CSA/Conforms to UL

Digit 14 – Pressure Vessel Code

X = Not Applicable 1 = CRN or Canada Equivalent

Digit 15 – Unit Application

B = High Ambient (32-125°F/0-52°C) D = Wide Ambient (0-125°F/-18-52°C) J = Extreme Low Ambient — down to -20°F (-28.9°C)

Digit 16 – Refrigerant Isolation Valves

2 = Refrigerant Isolation Valves (Discharge)

Digit 17 – Structural Options

A = Standard Unit Structure B = Seismic to International Building Code (IBC) C = California Office of Statewide Health Planning and Development (OSHPD) D = Wind Load for Florida Hurricane

Digit 18 – Freeze Protection (Factor-Installed Only) 1 = With Freeze Protection (External T-Stat control)

Digit 19 – Insulation

A = Factory Insulation - All Cold Parts B = Insulation for High Humidity/Low Evap Temp

Digit 20 – Factory Charge

3 = Full Factory Refrigerant Charge R-454B 4 = Nitrogen Charge — R-454B Field Supplied

Digit 21 – Evaporator Application

A = Standard Cooling (40 to 65°F/4.4 to 18°C) B = Low Temperature Process (10 to 40°F/-12.2 to 4.4°C) C = Ice-Making - Hardwired Interface (20 to 65°F/-7 to 18°C) D = Low Leaving Water (Below 10°F/-12.2°C)

Digit 22 – Water Connections

1 = Grooved Pipe Connection

Digit 23 – Condenser Fin Material

A = Lanced Aluminum Fins D = Lanced Aluminum Fins with CompleteCoat™

Digit 24 – Condenser Heat Recovery

X = No Heat Recovery 1 = Partial Heat Recovery with Fan Control

Digit 25 – Not Used

Digit 26 – Starter Type

A = Across the Line Starter/Direct On Line

Digit 27 – Incoming Power Line Connection

1 = Single Point Power Connect

Digit 28 – Power Line Connection Type

A = Terminal Block C = Circuit Breaker Standard Fault D = Circuit Breaker with High Fault Rated Control Panel E = Circuit Breaker with High Fault Rated Control Panel with Energy Meter

Digit 29 – Enclosure Type

2 = Enclosure type UL 60335 Rated for Outdoor Applications

Digit 30 – Unit Operator Interface

B = Tracer® AdaptiView™ TD-7

Digit 31 – Remote Interface (Digital Comm)

X = No Remote Digital Communication 2 = LonTalk®/Tracer® Summit Interface 4 = BACNet® Interface

Digit 32 – External Chilled/Hot Water and Current Demand Limit Setpoint X = No External Chilled Water Setpoint A = External Chilled Water and Demand Limit Setpoint 4-20 mA B = External Chilled Water and Demand Limit Setpoint 2-10 Vdc

Digit 33 – Percent Capacity

X = Without Percent Capacity 1 = With Percent Capacity

Digit 34 – Programmable Relays

X = No Programmable Relays A = With Programmable Relays

Digit 35 – Pump Type

X = No Pumps and No Contactors 8 = Dual High Head Pump

FA460825QC155

Attachment 1

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

10 CG-SVX063D-EN

Digit 36 – Pump Flow Control

X = No Pump Control B = Pump Flow Controlled by the Variable Speed Drive

Digit 37 – Buffer Tank

X = No Buffer Tank 1 = Buffer Tank

Digit 38 – Short Circuit Rating

X = No Short Circuit Rating A = Default A Short Circuit Rating B = High A Short Circuit Rating

Digit 39 – Installation Accessories

X = No Installation Accessories 1 = Elastomeric Isolators 3 = Seismic Neoprene Pads 5 = Elastomeric Pads

Digit 40 – Water Strainer

A = With Water Strainer Factory Installed

Digit 41 – Sound Attenuator Package

3 = Super Quiet 5 = Comprehensive Acoustic Package

Digit 42 – Appearance Options

X = No Appearance Options A = Architectural Louvered Panels B = Half Louvers

Digit 43 – Exterior Finish

1 = Standard Paint

Digit 44 – Label, Literature Language

B = Spanish and English D = English E = French and English

Digit 45 – Phase Reversal Protection

1 = Phase Reversal Protection 2 = Convenience Outlet and Phase Reversal Protection

Digit 46 – Shipping Package

X = No Skid (Standard) A = Unit Containerization Package B = Shipped with tarp Covering Full Unit C = Unit Containerization Package and Tarp

Digit 47 – Performance Test Options

X = No Performance Test 1 = Customer Inspection 2 = One-Point Test with Report 3 = Witness One-Point Test with Report 4 = Operational Test with Water

Digit 48 – Flow Switch Setpoint

C = Flow Switch Setpoint 15 F = Flow Switch Setpoint 35 H = Flow Switch Setpoint 45 L = Flow Switch Setpoint 60

Digit 49 – Wireless Connectivity Options

X = None A = Wi-Fi® B = LTE Modem C = Air-Fi™ D = Wi-Fi and LTE Modem E = Wi-Fi and Air-Fi F = LTE Modem and Air-Fi G = Wi-Fi, LTE Modem and Air-Fi

Digit 50 – Specials

X = None S = Special

Note: If a digit is not defined, it may be held for future use.

Model Number Description

FA460825QC155

Attachment 1

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

1096040470C Highlight

File details come from the government source that posted it. Updated .