This document contains quality assurance plans (QAPs) and fuel specifications for various petroleum products required by the Defense Logistics Agency Energy across multiple countries in Europe and the Middle East. The QAPs specify the applicable commercial standards and grades for fuel oil No. 2, diesel fuel, and unleaded gasoline to be delivered under DLA Energy contracts. The diesel fuel QAP also includes additional testing and property requirements for deliveries to specific locations like Kosovo and Afghanistan. The related federal contract opportunity is a solicitation from DLA Energy for direct delivery fuels in Spain, with responses due under solicitation number SPE60524R0201.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF30_SPE60524R02010006.pdf | ||
| SF30_SPE60524R02010004.pdf | ||
| SF30_SPE60524R02010003.pdf | ||
| SF30_SPE60524R02010002.PDF | ||
| SF30_SPE60524R02010001.PDF | ||
| Attachment C - Requesting the OET Vendor Role in AMPS.pdf | ||
| Attachment 7 - ENERGY QAP E37.pdf | ||
| Attachment F - Price Data Sheet.pdf | ||
| Attachment D Offeror Submission Package.pdf | ||
| Attachment B - PCS OET VendorGuide.pdf | ||
| Attachment A - Amps Registration.pdf | ||
| Attachment 6 - ENERGY QAP E35.pdf | ||
| Attachment 5 - ENERGY QAP E22.pdf | ||
| Solicitation No. SPE60524R0201.pdf | ||
| Attachment E - Fuel Source Data Sheet.pdf | ||
| Attachment 4 - ENERGY QAP E21.01.pdf | ||
| Attachment 3 - ENERGY QAP E18 01.pdf | ||
| Attachment 2 - ENERGY QAP E12.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
DEFENSE LOGISTICS AGENCY ENERGY Page 1 of 1
8725 JOHN J. KINGMAN ROAD
FORT BELVOIR, VIRGINIA 22060-6222
Signature
Prepared by:
Quality/Technical Support Office Approval
Contracting Approval:
DISTRIBUTION STATEMENT – A: APPROVED FOR PUBLIC RELEASE. DISTRIBUTION IS UNLIMITED
C16.67-1 GASOLINE FUEL SPECIFICATIONS (PC&S) (EUROPE) (DLA ENERGY JUN 2017)
NATIONAL STOCK NUMBER PRODUCT NOMENCLATURE PRODUCT CODE
9130-01-527-5763 Gasoline, Premium, Unleaded ULG
Supplies delivered under this contract shall conform to all National and local environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. The list of such requirements contained in this contract is not intended to be a complete list and the Contractor shall be responsible for determining the existence of all such requirements. In the event that a National and/or local environmental requirement is more stringent than a specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent requirement will be considered to be a nonconforming supply. Product(s) to be supplied shall fully meet the requirements of the applicable specification(s) as cited.
Product shall conform to the latest revision of commercial specification EN 228, Gasoline, Automotive, Unleaded, Premium Grade. Product classification is shown above.
2017-06-07T13:34:43-0400
MEREDITH.MICHAEL.E.1290973453
2017-06-07T14:17:06-0400
BANISZEWSKI.DANIEL.J.1287388698
2017-08-24T07:15:23-0400
PETERSON.DAVID.W.1074069483
C16.38-2 Fuel Oil, Burner No. 2 S5000 (DLA ENERGY JUN 2021)
NATIONAL STOCK NUMBER PRODUCT NOMENCLATURE DLA ENERGY PRODUCT CODE
9140-00-247-4365 Fuel Oil, Burner No. 2 S5000 FS2
Supplies delivered under this contract shall conform to all Federal, State, and local environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. This includes delivery of fuel and documentation in a manner consistent with existing or future Title V (Clean Air Act) Permits. In the event that a Federal, State, or local environmental requirement is more stringent than a similar requirement in a fuel specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent environmental requirement will be considered to be a nonconforming supply. All supplies furnished under this contract shall fully meet the requirements of the applicable specification(s) as cited below. In the event that compliance with the more stringent requirement causes the contractor to incur additional costs, the contractor may request an equitable adjustment.
COUNTRY SPECIFICATION/GRADE
UNITED STATES, TERRITORIES and OTHER
LOCATIONS
ASTM D396 – GRADE 2
ITALY STD UNI CTI 6579 – GRADE B
GERMANY DIN 51603-1 – REGULAR HEATING OIL
UNITED KINGDOM BS 2869 – CLASS D
(a) SULFUR REQUIREMENT. The maximum allowable sulfur content for Burner Oil, Grade No. 2 S5000, shall be 0.50 weight percent or per State/local environmental requirements, whichever is more stringent.
(b) BLENDING REQUIREMENT. Blending of various compatible grades of burner oil to produce an intermediate grade is permitted, however, such blending shall be accomplished by mechanical mixing or agitation in a tank, or by in-line blending, prior to loading the product into transport equipment, and the resultant product must meet all the requirements of the grade produced.
(c) DYE REQUIREMENT. Under United States regulations, fuel oil burner Grade No. 2 is required by 40 CFR Part 80 to contain a sufficient amount of the dye Solvent Red 164 so its presence is visually apparent. At or beyond terminal storage tanks, they are required by CFR Part 48 to contain the dye Solvent Red 164 at a concentration spectrally equivalent to 3.9 pounds per thousand barrels of the solid dye standard Solvent Red 26.
Quality / Technical Support Office Approval:
Legal Approval:
(Only required for E QAPs)
2021-06-30T11:39:01-0400
ATKINS.RENRICK.L.1024389320
2021-06-30T11:49:45-0400
BANISZEWSKI.DANIEL.J.1287388698
2021-07-01T09:28:03-0400
SHILLINGFORD.JAMES.V.1046542440
DEFENSE LOGISTICS AGENCY ENERGY Page 1 of 1
8725 JOHN J. KINGMAN ROAD
FORT BELVOIR, VIRGINIA 22060-6222
Quality/Technical Support Office Approval
DISTRIBUTION STATEMENT – A: APPROVED FOR PUBLIC RELEASE. DISTRIBUTION IS UNLIMITED
C16.67-2 DIESEL FUEL SPECIFICATION (SFD) (PC&S) (EUROPE) (MIDDLE EAST) (DLA ENERGY NOV 2018)
NATIONAL STOCK NUMBER PRODUCT NOMENCLATURE DLA ENERGY PRODUCT CODE
9140-01-556-9156 Diesel Fuel SFD
Supplies delivered under this contract shall conform to all National environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. The list of such requirements contained in this contract is not intended to be a complete list and the Contractor shall be responsible for determining the existence of all such requirements. In the event that a National environmental requirement is more stringent than a specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent requirement will be considered a nonconforming supply. Product(s) supplied shall fully meet the requirements of the applicable specification(s) as cited below.
Product shall conform to the latest revision of commercial specification EN 590. Product shall be visually free of undissolved water, sediment, and suspended matter. Product classification is shown above. Maximum sulfur content, as stated in EN 590, is 10 mg/kg (0.0010 wt%).
a) FOR LOCATIONS IN KOSOVO:
(1) TESTING REQUIREMENTS: The following additional tests shall be performed and results reported:
i. Color: ISO 2049/ASTM D1500
ii. Acid Number: ISO 6618/ASTM D974
(2) In addition to the EN 590 specification requirement for water content of 200 mg/kg or ppm (0.0200 wt%) maximum, and particulate content of 24 mg/kg or ppm (0.0024 wt%) maximum, the diesel fuel shall have a maximum haze rating of 2 when tested in accordance with ASTM D4176, Procedure 2. In case of dispute, the haze rating shall be determined at 25 °C (77 °F) with a maximum haze rating of 2 and shall contain no more than 24 mg/kg (0.0024 wt%) sediment and no more than 200 mg/kg (0.0200 wt%) water.
(3) Diesel during the summer months, May 1st to September 30th, shall comply with Grade A of Table 2 in EN 590.
(4) Diesel during winter months, October 1 to April 30th, shall comply with the Class 1 limits set in Table 3 of EN 590.
b) FOR LOCATIONS IN AFGHANISTAN: Diesel fuel delivered to all locations in Afghanistan shall meet the Grade E, -
15°C maximum cold filter plugging point, as detailed in EN 590 Section 5.6.1, Table 2 – Climate Related Requirements and Test Methods – Temperate Climates.
c) FOR ALL LOCATIONS: Written exception(s) or deviation(s) must be submitted to DLA Energy contracting officer if the Contractor is unable to meet any of the characteristic requirements of the above listed specification(s). Exception(s) and/or deviation(s) must state the reason why the contractor is unable to meet requirements, if this will be for the entirety of the performance period, if it is source specific, the Contractor’s course of action on how they plan on resolving this issue, and any proposed changes to specification requirement limit(s) for that product.
2018-11-16T10:10:12-0500
ATKINS.RENRICK.L.1024389320
2018-11-16T10:25:11-0500
BANISZEWSKI.DANIEL.J.1287388698
2018-11-16T21:11:17-0500
PETERSON.DAVID.W.1074069483