Attachment_#1_23-0148-ITB-Goods.pdf

PDF 6 MB Posted

Attached to
Uninterruptible Power Source (UPS) Batteries, Traffic & Solar Flashers
Solicitation number
23-0148-ITB - Goods
Issued by
Pinellas County, Florida

About this file

This document is a manufacturer specification sheet for battery products from multiple manufacturers including NorthStar, Odyssey Battery, Bright Way Group, and Alpha Technologies, related to a Pinellas County, Florida solicitation for Uninterruptible Power Source (UPS) Batteries, Traffic & Solar Flashers. The specifications cover detailed technical characteristics for various battery models, including voltage ratings, capacity measurements, discharge rates, temperature performance, dimensions, weight, and operational specifications for different battery types such as AGM (Absorbed Glass Mat) and lead-acid batteries designed for extreme temperature environments and specialized applications like telecommunications, traffic systems, and outdoor infrastructure.

The specification sheets provide comprehensive technical details including terminal configurations, cranking amps, reserve capacity, internal resistance, charging characteristics, cycle life, self-discharge rates, and warranty information. The batteries are designed for diverse applications including broadband, traffic, security systems, and outdoor installations, with models ranging from 12V configurations with capacities between 55-112 Ah. The specifications highlight performance features such as vibration resistance, high cranking capabilities, extended service life, and operation across wide temperature ranges from -40°F to 176°F. Manufacturers emphasize qualities like made-in-USA production, OEM compatibility, durability, and advanced technologies like Computerized Charge/Discharge Systems.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment #1 - Manufacturer Specifications

EnerSys World Headquarters 2366 Bernville Road Reading, PA 19605, USA Tel: +1-800-964-2837

EnerSys EMEA EH Europe GmbH Baarerstrasse 18 6300 Zug, Switzerland

EnerSys Asia 152 Beach Road #11-08 Gateway East Building Singapore 189721 Tel: +65 6416 4800

Want more info?

Scan code to access the ODYSSEY® Battery Literature Library

© 2022 EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted. Subject to revisions without prior notice. E.&O.E.

Date Downloaded: February 16, 2022 www.odysseybattery.com www.enersys.com

PDF Generated at https://www.odysseybattery.com 02/16/2022 18:28:39 Information correct at time of exporting PDF. Please check website for updates.

Drawings & Terminal Position

Handling and Storage Can be mounted or stored in any orientation except inverted 2-years storage life at 68°F (20°C) without needing to charge. Recharge when the OCV is <12.6V (50% SOC).

Classified as non-spillable and approved as non-hazardous cargo for ground, sea and air transportation in accordance with the requirements of IMDG (International Maritime code for Dangerous Goods) and ICAO (International Civil Aviation Organisation)

Charging and Self-Discharge Type of charging curve IUU

Charger voltage at 68°F (20°C) 14.4V to 14.8V

Self-discharge per month at 68°F (20°C) 1.25%

Self-discharge per month at 104°F (40°C) 5%

80% depth of discharge cycles 400

Technical Data Sheet

ODX-AGM31

(31-PC2150S)

Battery Type Group 31 with SS 3/8 inch threaded stud terminals and single external vent Absorbed Glass Mat (AGM) with Thin Plate Pure Lead (TPPL) Advanced dual purpose battery for engine start and deep cycle use

Power and Performance Voltage 12V

Pulse (5 second) Hot Cranking Amps

(PHCA)

2150A

Cold Cranking Amps (CCA) 1150A

HCA 1545A

MCA 1370A

20Hr Nominal Capacity (Ah) 100Ah

10Hr Nominal Capacity (Ah) 92Ah

Reserve Capacity Minutes 205 mins

Terminal 3/8-16" Stud

Torque Spec in-lbs (Nm max) 200 (22.6) studs only

Internal Resistance (mΩ) 2.2 mΩ

Short Circuit (A) 5000A

Dimensions and Weight Length 13 in / 330 mm

Width 6.8 in / 173 mm

Height (terminals included) 9.5 in / 241 mm

Height (container) 8.5 in / 216 mm

Weight 77.8 lbs / 35.3 kg

Temperature Operating temperature range -40°F / -40°C to 176°F / +80°C

Optimum storage temperature 68°F / +20°C

Accreditations The management systems governing the manufacture of this product are ISO 9001 and ISO 14001 certified.

*Cold Start Performance S.A.E J537 Apr 2016

469.248.0380 | batterysales@bwgllc.com

POWERING PERFORMANCE

BW 12550 DC (12V55Ah)

SPECIFICATIONS

DIMENSIONS

TERMINAL

CONSTRUCTION

Component Positive plate Negative plate Container Cover Separator Electrolyte Safety valve Terminal

Raw material Lead dioxide Lead ABS ABS AGM Sulfuric acid Rubber Copper

CONSTANT CURRENT DISCHARGE CHARACTERISTICS (A, 25℃)

F.V/TIME 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h 9.60V 109 84.0 50.3 30.9 18.3 13.0 10.5 8.98 6.17 5.09 2.70 9.90V 106 82.0 49.2 30.4 18.2 12.9 10.4 8.92 6.13 5.08 2.69 10.2V 101 79.0 47.7 29.7 18.0 12.8 10.4 8.86 6.09 5.07 2.68 10.5V 97.0 76.3 46.6 29.0 17.7 12.8 10.3 8.80 6.05 5.04 2.67 10.8V 91.6 72.2 44.9 28.1 17.3 12.4 9.99 8.54 5.87 5.00 2.65

Nominal Voltage 12 V

Capacity (25℃)

20HR 55 Ah 5HR 44 Ah 1HR 30.5 Ah

Dimension

Length 229±2mm (9.02inch)

Width 138±2mm (5.43inch)

Height 211±2mm (8.31inch)

Total Height 214±2mm (8.43inch)

Approx. Weight 15.5kg (34.2lbs)±4% Terminal type Z (Pic) or M6

Internal resistance (Fully charged, 25℃) Approx. 7.5mΩ

Capacity affected by temperature

(10HR)

40℃ 102% 25℃ 100% 0℃ 85%

-15℃ 65%

Self-discharge (25℃)

3 month Remaining Capacity: 91% 6 month Remaining Capacity: 82%

12 month Remaining Capacity: 65% Nominal operating temperature 25℃±3℃(77℉±5℉)

Operating temperature range

Discharge -15℃~50℃(5℉~122℉) Charge -10℃~50℃(14℉~122℉) Storage -20℃~50℃(-4℉~122℉)

Float charging voltage(25℃)

13.50 to 13.80V Temperature compensation:

-18mV/℃

Cyclic charging voltage(25℃)

14.50 to 15.00V Temperature compensation:

-30mV/℃

Maximum charging current 15A Maximum discharge current 500 A(5 sec.)

Designed floating life(20℃) 10 years

469.248.0380 | batterysales@bwgllc.com

POWERING PERFORMANCE

CONSTANT POWER DISCHARGE CHARACTERISTICS (WATT, 25℃)

F.V/TIME 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h 9.60V 1177 922 564 352 212 153 124 106 73.3 60.8 32.4 9.90V 1142 900 553 347 210 152 123 105 72.9 60.7 32.3 10.2V 1095 867 536 338 208 151 122 105 72.4 60.5 32.2 10.5V 1048 837 523 331 205 150 121 104 71.9 60.1 32.0 10.8V 989 793 503 321 200 145 117 101 69.7 59.7 31.8

Note: The above characteristics data can be obtained within three charge/discharge cycles.

Discharge Characteristics (25℃)

The Relationship for Open Circuit Voltage and Residual Capacity (25℃)

Floating Life on Temperature

Effect of Temperature on Capacity

Charging Characteristics (25℃)

The Relationship for Charging Voltage and Temperature

Cycle Life on D.O.D (25℃)

Self-discharge Characteristics

Charged Volume

Charge Voltage

Charging Current discharge% Depth of 30

• Extreme temperature Absorbed Glass Mat (AGM) technology

• Significant cold temperature performance improvement over gel

• Longer runtimes help increase network reliability

• Multiple models provide options for all network architectures

• Power density gains allow more runtime from smaller sized battery

• Extended service life for non-temperature controlled outdoor enclosures

• Full 5 year replacement warranty

The AlphaCell XTV Battery line is specifically designed for extreme outdoor temperature applications. Its virgin lead-alloy grids minimize corrosion and maximize life expectancy.

Patented Computerized Charge/Discharge System (CCDS) provides 100% out-of-box runtime capacity. Strategic global manufacturing and distribution locations available with non-spillable transportation ratings. Optimized for remote advanced status monitoring.

AlphaCell® XTV Extreme Temperature Batteries for Broadband, Traffic and Security Applications

100XTV

150XTV

195XTV

240XTV

Alpha Technologies Services, Inc. reserves the right to make changes to the products and information contained in this document without notice.

Copyright © 2019 Alpha Technologies Services, Inc. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies Services, Inc.

AlphaCell XTV Specifications 09/2019 www.alpha.com

General 100XTV 150XTV 195XTV 240XTV Operating Temperature Range (w/ Temperature Compensation):

-40 to 60°C / -40 to 140°F (Charger temperature compensation @ ±3.3mVpc per °C)

Storage Temperature: -10 to 40°C / 14 to 104°F -10 to 40°C / 14 to 104°F -10 to 40°C / 14 to 104°F -10 to 40°C / 14 to 104°F

Self Discharge: Battery can be stored up to 12 months at 25°C / 77°F. Higher temperatures during storage will require more frequent recharge.

Voltage Per Unit: 12V 12V 12V 12V

Float Charge Voltage: 13.5 to 13.8VDC average per 12V unit at 25°C / 77°F

Refresh/Boost Charging Voltage: 14.4 to 15.0VDC average 12V unit at 25°C / 77°F

Maximum AC Ripple (Charger): 0.5% RMS or 1.5% of float recommended for best results. Maximum voltage allowed = 4% P/P

Terminal Type: Threaded alloy insert terminal to accept M6 x 12mm bolt

Threaded alloy insert terminal to accept M6 x 20mm bolt

Terminal Hardware Torque: 13.6NM / 120in-lbs 13.6NM / 120in-lbs 13.6NM / 120in-lbs 13.6NM / 120in-lbs

Case Sizes: 22NF 24 27 31

Dimensions H x L x W (in/mm): 8.17 x 9.01 x 5.46 / 207 x 228 x 138 8.44 x 10.85 x 6.65 / 214 x 275 x 168 8.43 x 12.71 x 6.67 / 214 x 322 x 169 8.57 x 13.50 x 6.71 / 217 x 343 x 170

Weight Approximate (lbs/kg): 39 / 17.7 56 / 25.4 67 / 30.5 75 / 32

Battery 100XTV 150XTV 195XTV 240XTV Runtime Rating 25A (@ 25°C / 77°F to 1.75Vpc): 100 minutes 150 minutes 195 minutes 240 minutes

Amp Hour Capacity 20Hr Rate (@ 25°C / 77°F to 1.75Vpc): 56Ah 80Ah 100Ah 112Ah

Maximum Discharge Current: 300A 800A 800A 850A

Short Circuit Current: 1450A 1900A 2250A 2650A

Impedance 60Hz (Approximate): 0.005Ω 0.0045Ω 0.0039Ω 0.0034Ω

Conductance Range Fully Charged New Battery (@ 25°C / 77°F): 700 to 800 900 to 1100 1050 to 1250 1250 to 1550 Note: Terminal hardware included with every battery.

Constant Current Nominal Ratings in Amps (@ 25°C / 77°F to 1.75V per Cell) Discharge Time (Hours) 1 2 3 4 5 6 8 10 12 20

100XTV: 39.4 22.1 15.8 12.4 10.3 8.7 6.7 5.4 4.6 2.8

150XTV: 53.0 30.6 21.6 16.8 13.9 11.9 9.3 7.7 6.5 4.0

195XTV: 65.5 37.6 26.9 21.0 17.3 14.7 11.3 9.4 7.9 5.0

240XTV: 81.7 45.5 32.1 25.0 19.8 16.6 13.0 10.5 9.0 5.6

Estimated Runtime Minutes Using XM3-918HP (Deduct 4 to 6% for Legacy XM Power Supplies)

90VAC @ 4A 6A 8A 10A

Models: 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV

3 Batteries: 280 401 506 581 183 262 335 389 133 190 245 289 101 146 190 228

6 Batteries: 597 869 1083 1240 402 579 726 830 298 427 538 617 232 332 421 485

9 Batteries: 914 1349 1673 1927 621 905 1128 1292 465 672 841 961 366 527 662 757

90VAC @ 12A 14A 16A 18A

Models: 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV

3 Batteries: 81 117 153 188 66 96 127 158 55 81 108 136 47 69 92 118

6 Batteries: 188 269 344 399 157 224 288 336 133 191 246 290 113 163 211 251

9 Batteries: 300 430 542 621 252 360 456 524 215 307 391 451 185 264 337 391

Estimated Runtime Minutes Using XM3-624HP (Deduct 4 to 6% for Legacy XM, VMX, and GMX Power Supplies)

60VAC @ 4A 6A 8A 10A

Models: 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV

3 Batteries: 416 599 751 858 276 396 500 574 203 290 369 427 157 224 288 336

6 Batteries: 869 1280 1588 1828 590 858 1070 1225 441 637 797 912 347 499 627 717

9 Batteries: 1321 1941 2441 2832 904 1333 1653 1904 681 995 1237 1419 539 783 977 1118

60VAC @ 12A 14A 16A 18A

Models: 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV 100XTV 150XTV 195XTV 240XTV

3 Batteries: 126 181 234 276 104 150 195 233 87 127 166 201 74 108 142 175

6 Batteries: 284 407 513 589 238 340 431 497 203 291 370 428 174 249 319 371

9 Batteries: 444 461 803 918 375 539 677 774 322 432 582 667 278 398 503 577 Based on .92 cable plant factor @ 25°C / 77°F

Attachment #1-Manufacturer Specifications
BWG_Spec_Sheet_BW-12550-final
NorthStar NSB-AGM31_Page_1
NorthStar NSB-AGM31_Page_2
Odyssey_Battery_ODX-AGM31

alphacellXTV_datasheet

File details come from the government source that posted it. Updated .