Attachment 02 - Specifications.pdf
PDF 1 MB Posted
- Attached to
- 70 and 90 Ton Trane Chiller
- Solicitation number
- FA441725Q0276
About this file
This document is a Trane CGAM Product Report for a 70-ton air-cooled chiller being prepared for Hurlburt Field in 2025. The chiller features a CGAM model with R-454B refrigerant, four compressors across two refrigerant circuits, and an ETL listing to US/Canadian safety standards. Key performance specifications include a refrigeration capacity of 69.87 tons, cooling efficiency of 10.83 EER, and an IPLV of 16.19 EER.
The unit is designed for wide ambient applications with six condenser fans and operates on 460V, 3-phase power. Notable technical features include a braze plate stainless steel evaporator, hermetic scroll compressors, a Symbio 800 unit control module with adaptive control, and dual refrigerant circuits with passive oil management. The chiller is prepared by the Trane Sales Office in Pensacola, with a unit tag of B 90639, and meets ASHRAE 90.1-2019 efficiency requirements. The operating weight is 5,194 lbs, with dimensions of 153.4" x 88.4" x 84.8".
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Updated Supplemental RFQ (Trane Chillers).pdf | ||
| Solicitation - FA441725Q0276.pdf | ||
| Attachment 01 - Specifications .pdf | ||
| RFQ_SupplementalDocument(TraneChiller).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CGAM Product Report
General Chiller Model CGAM
Unit nominal tonnage 70 tons
Elevation 0.00 ft
Unit voltage 460. volt 3 phases
REFRIG_CHARGE Refrigerant Charge R-454B
Number of Refrigerant Circuits 2
Number of Compressors (Capacity Steps) 4
Agency Listing ETL Listed to US/Canadian Safety Std
Chiller Performance Refrigeration Capacity 69.87 tons
Cooling Efficiency 10.83 EER
IPLV 16.19 EER (Btu/W-h)
NPLV 15.74 EER (Btu/W-h)
Evaporator Evaporator Application Standard Cooling
Fouling Factor 0.000100 hr-sq ft-deg F/ Btu
Flow switch set point Flow switch set point 60 cm/sec
Design Flow 167.1 gpm
VPF Min Flow 89.47 gpm
Evap Head Loss 12.6 ft H2O
Fluid Type Water
Fluid Freeze Point 32.00 F
Entering Temperature 54.00 F
Leaving Temperature 44.00 F
Evap + Strainer Head Loss 20.0 ft H2O
Condenser Unit application Wide Ambient
Total Number of Fans 6
Ambient Air Temperature 95.0 F
Electrical Information Unit Voltage 460. volt 3 phases
Unit Hertz 60. hertz
Total power input 77.43 kW
Compressor Starter Across the line
Incoming Line Connection Type Single point
MCA
Single Point Power 147 A
RLA
RLA - compressor 1A 25.00 A
RLA - compressor 1B 33.00 A
RLA - compressor 2A 33.00 A
RLA - compressor 2B 25.00 A
Short Circuit Current Rating Default
Power Line Connction Type Circuit breaker
Short Circuit Current Rating 5000 A
FLA - Condenser Fan (each) 3.30 A
MOP
Single Point Power 200 A
LRA
LRA - compressor 1A 155.00 A
LRA - compressor 1B 215.00 A
LRA - compressor 2A 215.00 A
LRA - compressor 2B 155.00 A
Job Name: Hurlburt Field 2025 Year End Chillers Quantity: 1
Prepared For: Sales Office: Pensacola
Unit Tag: B 90639
2025/07/30 19:41:15 Page 1 of 19
Acoustics
Sound attenuator package Super quiet
Sounds Power Levels (Lw, indb. ref1, pW)
Octave Band Center Frequency (Hz)
Percent Load 63(Hz) 125 250 500 1K 2K 4K 8K Overall A- Wtd
Sounds Pressure Levels (Lp, indb. ref1, 20 uPa)
10m from center of broad sides of chiller
Octave Band Center Frequency (Hz)
Percent Load 63(Hz) 125 250 500 1K 2K 4K 8K Overall A- Wtd
Acoustic Note 1 Acoustic Note 2 Acoustic Note 3
Sound power data collected per AHRI 370 methodology.
Sound power referenced to 1 pW; sound pressure referenced to 20 µPa.
Sound pressure values are at 10 meters from broadside of unit.
Physical Information
Dimensions
Length 153.400 in
Width 88.400 in
Height 84.800 in
Weights
Operating weight 5194 lb
Shipping weight 5118 lb
Circuits Refrigerant Charge Oil Charge
Circuit 1 52.0 lb 2.70 gal
Circuit 2 52.0 lb 2.70 gal
Standard Rating Performance and Information for LEED Rating Refrigerant Charge Circuit 1 52.0 lb
Refrigerant Charge Circuit 2 52.0 lb
Rated Refrigerating Capacity 69.78 tons
Rated Cooling Efficiency 10.82 EER (Btu/W-h)
Rated IPLV 16.19 EER (Btu/W-h)
Refrigerating Capacity 69.87 tons
Cooling Efficiency 10.83 EER
Fan Power 7.540 kW
Compressor Power 69.45 kW
ASHRAE 90.1 - 2019
This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 (which are based on AHRI standard rating conditions with water) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in the Energy and Atmosphere section.
The LEED Green Building Rating System™, developed by the U.S.
Green Building Council, provides independent, third-party verification that a building project meets green building and performance measures.
Regulatory Compliance
AHRI certification
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Publication Data Generation Date 7/30/2025
Trane Select Assist Version Number 297
Job Name: Hurlburt Field 2025 Year End Chillers Quantity: 1
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 2 of 19
Job Name: Hurlburt Field 2025 Year End Chillers Quantity: 1
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 3 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 4 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 5 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 6 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 7 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 8 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 9 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 10 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 11 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 12 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 13 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 14 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 15 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 16 of 19
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 17 of 19
Foundation Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the applicable operating weight (i.e. including completed piping, and full operating charges of refrigerant, oil and water). The expectation of Trane equipment is that piping is fully supported by an independent structure/system, without being connected to the waterbox. Once in place, the unit must be level within 1/2" across the length and width of the unit. The Trane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation.
Center Of Gravity
Different unit configurations and options may cause a variation in the center of gravity from what is listed in the submittal.. Refer to the Installation, Operating and Maintenance manual for specific lifting instructions.
General Units are constructed of a galvanized steel frame with galvanized steel panels and access doors.
Component surfaces are finished with a powder-coated paint.
Each unit ships with full operating charges of refrigerant and oil.
Compressor and Motor The unit is equipped with four hermetic, direct-drive, 3600 rpm 60 Hz suction gas-cooled scroll compressors. The simple design has only three major moving parts and a completely enclosed compression chamber which leads to increased efficiency. Overload protection is internal to the compressors. The compressor includes: centrifugal oil pump, oil level sight glass and oil charging valve. Each compressor will have compressor heaters installed and properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles.
Unit-Mounted Starter The control panel is designed per UL 60335. The starter is in an across-the-line configuration, factory-mounted and fully pre-wired to the compressor motor and control panel. Typically, Trane scroll compressors are up to full speed in one second when started across-the-line.
A factory-installed, factory-wired 820 VA control power transformer provides all unit control power (120 Vac secondary) and Trane Symbio (TM) 800 controller module power (24 Vac secondary).
A molded case standard interrupting capacity circuit breaker, factory pre-wired with terminal block power connections and equipped with a lockable external operator handle, is available to disconnect the chiller from main power.
Power Connection Power connections include main three-phase power and two separate 115V, 20 amp customer provided single phase power connections are required to power the heaters (if used for freeze protection) as well as the programmable relays.
Short circuit current rating of 5 kA is provided.
Evaporator Braze plate evaporator is made of stainless steel with copper as the braze material. It is designed to withstand a refrigerant side working pressure of 430 psig (29.6 bars) and a waterside working pressure of 150 psig (10.5 bars). Evaporator is tested at 1.1 times maximum allowable refrigerant side working pressure and 1.5 times maximum allowable water side working pressure. It has one water pass. A water strainer and a flow switch are factory installed.
Immersion heaters protect the evaporator to an ambient of -20°F (-29°C).
All evaporators have grooved pipe connections.
Note: An additional 115V, 20 amp field provided single phase power connection is required to power the heaters (if used for freeze protection).
Job Name: Hurlburt Field 2025 Year End Chillers Quantity: 1
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 18 of 19
Condenser Air-cooled condenser coils have aluminum fins mechanically bonded to internally-finned copper tubes.
Completely assembled coils are then dipped and baked in an electro-mechanically bonded flexible epoxy coating. Coating covers all condenser coil surfaces with uniform coating to protect against corrosion with negligible performance loss. Coil with coating successfully passed 6000+ hour salt spray test.
The condenser coil has an integral sub-cooling circuit. The maximum allowable working pressure of the condenser is 650 psig (44.8 bars). Condensers are factory proof tested at 650 psig (44.8 bars).
Direct-drive vertical discharge condenser fans are balanced and individually protected. Three-phase condenser fan motors with permanently lubricated ball bearings and external thermal overload protection are provided.
A variable speed drive on the first fan of each circuit allows the unit to start and operate with ambient temperatures between 0.0 F and 125.0 F.
Refrigerant Circuits The unit has dual refrigerant circuits. Each refrigerant circuit has Trane scroll compressors piped in parallel with a passive oil management system. A passive oil management system maintains proper oil levels within compressors and has no moving parts. Each refrigerant circuit includes filter drier, electronic expansion valve, liquid line and discharge service valves. Capacity modulation is achieved by turning compressors on and off. The unit has four capacity stages.
Unit Controls All unit controls are housed in an outdoor rated weather tight enclosure with removable plates to allow for customer connection of power wiring and remote interlocks. All controls, including sensors, are factory mounted and tested prior to shipment. Microcomputer controls provide all control functions including startup and shut down, leaving chilled/hot water temperature control, evaporator flow proving, compressor staging and speed control, electronic expansion valve modulation, condenser fan sequencing and speed control, anti-recycle logic, automatic lead/lag compressor starting and load limiting.
The Symbio (TM) 800 unit control module, utilizing Adaptive Control microprocessor, automatically takes action to avoid unit shut-down due to abnormal operating conditions associated with low refrigerant pressure, high condensing pressure, Should the abnormal operating condition continue until a protective limit is violated, the unit will be shut down. Unit protective functions of the Symbio (TM) 800, include loss of chilled water flow, evaporator freezing, loss of refrigerant, low refrigerant pressure, high refrigerant pressure, high compressor motor temperature, and loss of oil to the compressor..
Programmable Relays Predefined, factory-installed, programmable relays allow the user to select four relay outputs. Available outputs are: Alarm-Latching, Alarm-Auto Reset, General Alarm, Warning, Chiller Limit Mode, Compressor Running, and Tracer Control.
Note: An additional 115V, 20 amp field provided power connection is required to power the programmable relays.
Architectural Louvered Panels Louvered panels cover the complete condensing coil and service area beneath the condenser.
Isolators Molded elastomeric isolators, sized to reduce vibration transmission to the supporting structure when the unit is installed, ship with the chiller.
Job Name: Hurlburt Field 2025 Year End Chillers Quantity: 1
Prepared For: Sales Office: Pensacola
2025/07/30 19:41:15 Page 19 of 19