Attachment 02 - Drawings 646-24-100.pdf

PDF 32 MB Posted

Attached to
Y1DA--646-24-100 | Elevator Upgrade Bed Tower | Pittsburgh - UD
Solicitation number
36C77626R0105
Issued by

About this file

This is a set of construction drawings for the VA Pittsburgh Upgrade Bed Tower Elevators project located at 1 University Drive, Pittsburgh, PA 15240. The drawings are 100% Construction Documents dated March 26, 2026, with project number 22164.005 and building number 646-24-100. The document serves as the Designer of Record set prepared by Mott MacDonald Architects Penn, P.C. in Philadelphia and Specialized Engineering Services (SES) in Greenwood Village, Colorado.

The scope encompasses complete elevator system upgrades including demolition and new construction of two passenger elevators (Elevators 13 and 14) serving floors 1-6, with the machine room located on the seventh floor. Key work includes removal of existing elevator machinery, controls, counterweights, and buffers; replacement with new equipment; installation of new fire-rated partition walls with 2-hour and 1-hour ICRA (Infection Control Risk Assessment) barriers; new electrical systems including 150A fused disconnects with shunt trip capability, dedicated lighting circuits, fire alarm integration, and access control systems; mechanical and plumbing modifications; and fire protection updates. The project is fully sprinklered and requires strict adherence to fire safety codes, NFPA 70 (NEC) Article 620 for elevator wiring, and coordination with multiple trades. Electrical work includes new branch circuits serving the elevator cars, hoistway lighting with three-way and four-way switching controls, sump pump systems, and integration with the existing fire alarm system for elevator recall and power shutdown functions. All work must maintain two means of egress, protect existing services, coordinate with building operations, and comply with VA requirements throughout the phased construction.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

646-100

G000 COVER SHEET

AE-001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, & CODE DATA

AE-011 EXISTING SEVENTH FLOOR PLAN - OVERALL

EP000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

ED100 FLOOR PLAN - ELECTRICAL DEMOLITION

ED101 FLOOR PLAN - ELECTRICAL DEMOLITION

EP500 ONE-LINE DIAGRAM

EP600 ELECTRICAL DETAILS

AE-101 ENLARGED PLANS - DEMOLITION

AE-601 FINISH ROOM SCHEDULE, DOOR SCHEDULE AND DETAILS

EP601 ELECTRICAL DETAILS

EP602 ELECTRICAL DETAILS

EP700 ELECTRICAL SCHEDULES

MD101 FLOOR PLAN - MECHANICAL DMOLITION

MH201 FLOOR PLAN - DUCTWORK/PIPING

AE-102 ENLARGED PLANS

EP200 FLOOR PLAN - ELECTRICAL

EP201 FLOOR PLAN - ELECTRICAL

FX001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

FX201 FLOOR PLAN - FIRE PROTECTION - DEMOLITION & NEW

MH000 MECHANICAL SYMBOLS AND ABBREVIATIONS

MH501 MECHANICAL DETAILS & SCHEDULES

PP201 FLOOR PLAN - PLUMBING - DEMOLITION & NEW

PP001 PLUMBING SYMBOLS AND ABBREVIATIONS

PP501 PLUMBING DETAILS & SCHEDULES

VT-001 ELEVATOR DETAILS

VT-002 HALL FIXTURE DETAILS

VT-003 ELEVATOR CAB INTERIOR DETAILS

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h

U p g ra d e

B e d T o w e r

E le v a to r/

-1

.B

.G .R

.r v t

/9

/2

:2

:1

P

M

G000

COVER SHEET VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

University Drive C Pittsburgh, PA 15240

646-24-100

02/26/2026 JS AEA

22164.005

100% CONSTRUCTION

DOCUMENTS

VA PITTSBURGH UPGRADE BED TOWER ELEVATORS

University Drive C Pittsburgh, PA 15240

Revisions: Date:

SITE MAP: VICINITY MAP:

646-24-100

GI-003 ICRA ASSESSMENT

GI-004 ICRA ASSESSMENT DETAILS

AE-001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, & CODE DATA

AE-011 EXISTING SEVENTH FLOOR PLAN -OVERALL

AE-101 ENLARGED PLANS -DEMOLITION

AE-102 ENLARGED PLANS

AE-601 FINISH ROOM SCHEDULE, DOOR SCHEDULE AND DETAILS

EP000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

ED100 FLOOR PLAN - ELECTRICAL DEMOLITION

ED101 FLOOR PLAN - ELECTRICAL DEMOLITION

EP200 FLOOR PLAN - ELECTRICAL

EP201 FLOOR PLAN - ELECTRICAL

EP500 ONE-LINE DIAGRAM

EP600 ELECTRICAL DETAILS

EP601 ELECTRICAL DETAILS

EP602 ELECTRICAL DETAILS

EP700 ELECTRICAL SCHEDULES

FX001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

FX201 FLOOR PLAN - FIRE PROTECTION - DEMOLITION & NEW

MH001 MECHANICAL SYMBOLS AND ABBREVIATIONS

MD101 FLOOR PLAN - MECHANICAL DEMOLITION

MH201 FLOOR PLAN - DUCTWORK / PIPING

MH501 MECHANICAL DETAILS & SCHEDULES

PP001 PLUMBING SYMBOLS AND ABBREVIATIONS

PP201 FLOOR PLAN - PLUMBING - DEMOLITION & NEW

PP501 PLUMBING DETAILS & SCHEDULES

VT-001 ELEVATOR DETAILS

VT-002 HALL FIXTURE DETAILS

VT-003 ELEVATOR CAB INTERIOR DETAILS

ELEVATOR PIT ELEVATOR

MACHINE ROOM

VARIES VARIES VARIES CORRIDOR

• PUBLIC CORRIDOR IN FRONT OF ELEVATOR / ELEVATOR SHAFT FLOORS 1-6

• ELEVATOR MACHINE ROOM - SEVENTH FLOOR

X

X

1 University DR, Pittsburgh, PA 15240

646-24-100

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:3

:5

P

M

GI-003

ICRA ASSESSMENT VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

22164.005

100% CONSTRUCTION

DOCUMENTS

Revisions: Date: 3/26/2026

B B

A A

ELEVATOR-14

ELEVATOR 13

4' - 4 1/2" +/-

B

E .Q

E

.Q

C L

A01

6'-0" MIN.

I1 I6

I3

I5 I7

I7 I8

B B

A A

ELEVATOR-14

ELEVATOR 13

A

/4

4' - 6" +/- 6'-0" MIN.

C L

A01

I1

I2

I3

A L

IG

N

I5 I8

UNDERSIDE OF

STRUCTURE ABOVE

FIRE RESISTANT SEALANT

BOTH SIDES

UL DESIGN NO. U404 - 2 HOUR

FIRE RATING

WALL BASE

FIRE RESISTANT SEALANT

BOTH SIDES

ICRA 2-HOUR RATED PARTITION

A

W A

L L

H E

IG

H

T V

A R

IE

S

V

.I .F

M

IN

CEMENTIOUS BACKER TO

ENCLOSURE SIDE

PAINT

ELEVATOR

WALL

UNDERSIDE OF

STRUCTURE ABOVE

FIRE RESISTANT SEALANT

BOTH SIDES

UL DESIGN NO. U419 - 1 HOUR

FIRE RATING

WALL BASE

FIRE RESISTANT SEALANT

BOTH SIDES

ICRA 1-HOUR RATED PARTITION

B

M

IN

CEMENTIOUS BACKER TO

ENCLOSURE SIDE

PAINT

ELEVATOR

WALL

B B

A A

ELEVATOR

MACHINE ROOM

7W-139B

73' - 10"

139B

I4

I5

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

GI-004

ICRA ASSESSMENT DETAILS VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA LAA

100% CONSTRUCTION

DOCUMENTS

Revisions: Date:

1/4" = 1'-0"2

ENLARGED ICRA PLAN - 2ND THRU 6TH FLOORS

1/4" = 1'-0"1

ENLARGED ICRA PLAN - 1ST FLOOR

DOOR SCHEDULE

DOOR FRAME

HARDWARE COMMENTSMARK WIDTH HEIGHT THK TYPE MATERIAL TYPE MATERIAL DEPTH

A01 4' - 0" 7' - 0" 0' - 1 3/4" A HM F1 HM 7" COORDINATE

WITH VA

PROVIDE 90 MIN FIRE RATING IN 2 HOUR CONSTRUCTION -

PROVIDE 45 MIN IN 1 HOUR CONSTRUCTION

1 1/2" = 1'-0"3

ICRA BARRIER WALL TYPES

KEYNOTES

MARK DESCRIPTION

I1 WALK OFF MAT - INSIDE ENCLOSURE

I2 2-HR FIRE RATED - ICRA BARRIER

I3 MAINTAIN 6'-0" MIN CORRIDOR WIDTH AT ALL TIMES

I4 INSTALL PLASTIC ZIPPER ENCLOSURE AT ELEVATOR MACHINE ROOM

I5 EXISTING 2-HR FIRE RATED BARRIER

I6 1-HR FIRE RATED - ICRA BARRIER - ALTERNATIVE USE OF PLASTIC BARRIER IS

PERMISSABLE - COORDINATE WITH VA

I7 CONTRACTOR TO SEAL ELEVATOR DOORS ON LEVELS 2 THRU 6 WITH PAINTED DRY WALL

I8 FULL BARRIERS TO BE REVIEWED WITH STATION PRIOR TO WORK ON EACH FLOOR

1/4" = 1'-0"4

ENLARGED ICRA MACHINE ROOM PLAN

3/26/2026

DEMOLITION NOTES NOTED BELOW ARE GENERAL. REFER TO DEMOLITION PLAN FOR

SPECIFIC SCOPE NOTES.

1. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS AND

INSURANCES.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION & MAINTENANCE

OF ALL EXISTING SERVICES FOR THE DURATION OF THE WORK. I.E.

MECHANICAL, ELECTRICAL, FIRE ALARM SYSTEM, SECURITY SYSTEM, AND

PLUMBING.

3. THE CONTRACTOR SHALL FULLY ACQUAINT HIMSELF WITH THE EXISTING

CONDITIONS AND SHALL HAVE VISITED THE JOB SITE & BE FULLY INFORMED AS

TO THE NATURE OF THE EQUIPMENT AND FACILITIES NEEDED FOR THE

PROPER EXECUTION OF THE WORK.

4. CONTRACTOR IS RESPONSIBLE TO FURNISH, INSTALL & MAINTAIN CLEAN

CONSTRUCTION FILTERS ON THE FLOOR AIR HANDLERS & TO FURNISH,

INSTALL & MAINTAIN AIR FILTERS PRIOR TO PERFORMING TEST & BALANCE OF

HVAC SYSTEM.

5. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF THE

PASSENGER & SERVICE ELEVATORS & PREMISES FOR THE DURATION OF THE

WORK.

6. CLEAR ACCESS TO BATHROOMS, ELEVATORS LOBBIES, ELECTRICAL CLOSETS,

FA EQUIPMENT AND MECHANICAL ROOMS NOT UNDER CONSTRUCTION SHALL

BE MAINTAINED AT ALL TIMES.

7. THE DEMOLITION OPERATIONS SHALL AT ALL TIMES BE CARRIED OUT IN SUCH

A MANNER SO AS TO PREVENT DAMAGE OR DUST TO ADJOINING SPACES AND

FLOORS.

8. DEMOLITION OF ANY WORK OF A NOISE MAKING NATURE SHALL BE DONE AS

REQUIRED BY BUILDING POLICIES AND ANY PREMIUM TIME, IF REQUIRED,

SHALL BE INCLUDED IN THE DESCRIPTION OF WORK.

9. CONTRACTOR IS TO COORDINATE ALL DEMOLITION AND LOADING OPERATIONS

WITH OWNER.

10. MAINTAIN PREMISES & PUBLIC PROPERTIES FREE FROM ACCUMULATION OF

WASTE, DEBRIS & RUBBISH CAUSED BY OPERATIONS. AT COMPLETION OF

WORK, LEAVE PREMISES & PUBLIC PROPERTIES CLEAN ON A DAILY BASIS.

11. CONTRACTOR TO COORDINATE BUILDING'S HOURS OF OPERATION FOR

ELEVATOR, SERVICES, ETC. W/ OWNER AND BUILDING OFFICE PRIOR TO THE

COMMENCEMENT OF ANY WORK.

12. ALL DEMOLITION SHALL BE PERFORMED BY THE TRADE HAVING JURISDICTION.

13. PROTECT ALL EXISTING FINISHES TO REMAIN THROUGHOUT THE LIFE OF THE

PROJECT.

14. CONTRACTOR TO PROTECT ALL EXISTING AND NEW FLOOR FINISHES AND

WALLS LEADING FROM PHASED AREAS TO OCCUPIED AREAS. ALL AREAS ARE

TO BE VACUUMED ON A DAILY BASIS.

15. FOR EACH PHASE, TEMPORARY MEANS OF EGRESS SHALL BE MARKED WITH

DIRECTIONAL EXIT SIGNS.

16. MAINTAIN TWO MEANS OF EGRESS FROM ALL PORTIONS OF THE FLOOR

DURING ALL PHASES OF CONSTRUCTION.

17. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF RUBBISH FROM

AREA OF WORK AND THE LEGAL DISPOSAL OF ALL REMOVED AND

DEMOLISHED MATERIALS.

18. CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS NOT TO REMOVE &/OR

DISCONNECT ANY EXISTING FIRE ALARM WIRING. WHEN DEMOLITION IS TO

TAKE PLACE IN THE AREA OF THE BUILDING WHERE FIRE SAFETY EQUIPMENT

SUCH AS ALARMS, SPEAKERS, SMOKE DETECTORS, FLOOR WARDEN STATION,

ETC. ARE LOCATED. BUILDING MANAGER SHALL BE NOTIFIED (5) WORKING

DAYS PRIOR TO START OF DEMOLITION SO EQUIPMENT MAY BE REMOVED

AND/OR PROTECTED. A FULLY WORKING FIRE ALARM SYSTEM IS TO BE

MAINTAINED OPERATIONAL AT THE END OF EACH WORKING DAY.

19. REMOVE ANY PIPES, CONDUITS, METAL, ANCHORS AND ANY ITEMS THAT HAVE

BEEN ABANDONED OR ARE NO LONGER REQUIRED FOR BUILDING SYSTEMS

OPERATIONS THAT PROJECT FROM EXISTING FINISH LINE OF FLOORS, WALLS

OR COLUMNS THAT ARE SCHEDULED TO REMAIN. U.O.N. COORDINATE WITH

BUILDING ENGINEER.

GENERAL DEMOLITION NOTES

1. ON ALL FIRE RATED PARTITIONS - ALL PENETRATIONS AND JOINTS ARE TO BE

TAPED AND SPACKLED SLAB TO SLAB. FIRE STOP ALL PENETRATIONS.

2. DOUBLE STUDS ARE REQUIRED AT BOTH JAMBS OF DOOR FRAMES AND

HEADER.

3. STUDS AT DOOR JAMBS AND ON TOPS OF DOOR FRAMES MUST BE SCREWED

TO RUNNERS AT TOP, BOTTOMS AND BOTH SIDES.

4. PARTITIONS SHALL NOT BE FASTENED OR BRACED TO DUCTWORK, CONDUIT

OR PIPING.

5. FLOOR MUST REMAIN IN A STATE OF SAFE CONDITIONS WITH REGARD TO FIRE

SAFETY FOR PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,

SPEAKERS ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES.

6. ALL WOOD TO BE FIRE RETARDANT.

7. ALL FIRE-STOPPING UTILIZED AT PENETRATIONS THROUGH FLOOR

ASSEMBLIES SHALL PROVIDE A FIRE RESISTANCE RATING PER THE

APPLICABLE CODE. FIRE-STOPPING/FIRE-SAFING THROUGH PARTITION

ASSEMBLIES SHALL PROVIDE A FIRE RESISTIVE RATING THAT MATCHES THAT

OF THE PARTITION. COMPLY WITH UL 1479 "FIRE TESTS OF THROUGH

PENETRATION FIRE-STOP".

8. WHERE NEW AND EXISTING BUILDING PARTITIONS ARE SHOWN TO ALIGN, THE

JUNCTION SHALL BE TAPED, SPACKLED AND FINISHED SMOOTH.

9. FIRE SAFETY EQUIPMENT AND THEIR ASSOCIATED CONDUIT AND WIRING

SYSTEMS SHALL NOT BE MARRED DURING CONSTRUCTION AND SHALL BE

PROTECTED FROM ANY PHYSICAL DAMAGE BY THE GENERAL CONTRACTOR

AND SUBCONTRACTOR FOR THE DURATION OF THE PROJECT.

10. WHERE FIREPROOFING OF EXISTING COLUMNS OR BEAMS IS DISTURBED BY

NEW WORK, THE FIREPROOFING SHALL BE RESTORED TO PROVIDE A MINIMUM

RESISTANCE RATING AS REQUIRED BY THE APPLICABLE BUILDING CODE.

11. CONTRACTOR SHALL ISSUE COMPLETE, FULL SETS OF DRAWINGS AND

SPECIFICATIONS TO SUB-CONTRACTORS FOR BIDDING PURPOSES.

CONTRACTOR SHALL NOTIFY ARCHITECT OF ANY CONFLICTS BETWEEN

DRAWINGS, FOR RESPONSE AND RESOLUTION.

12. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, AND REPAIRING AS

REQUIRED TO PERFORM ALL OF THE WORK INDICATED ON THE DRAWINGS

AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE PROJECT.

13. ALL ITEMS RECESSED INTO ONE OR TWO HOUR FIRE RATED PARTITIONS

(SUCH AS OUTLET BOXES, PANEL BOXES, ETC) SHALL HAVE THE OPENINGS

PROTECTED WITH BACK-UP MATERIALS SO AS TO RETAIN THE INTEGRITY OF

THE FIRE RATING OF THE PARTITION THROUGHOUT. PROTECTION OF THE ONE

AND TWO HOUR RATED PARTITIONS SHALL BE IN STRICT CONFORMANCE WITH

THE APPLICABLE BUILDING CODE.

14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL

CONDITIONS AND MATERIALS WITHIN THE PROPOSED CONSTRUCTION AREAS.

THE CONTRACTOR SHALL DESIGN AND INSTALL ADEQUATE SHORING AND

BRACING FOR ANY STRUCTURAL TASKS. THE CONTRACTOR SHALL HAVE SOLE

RESPONSIBILITY FOR ANY DAMAGE OR INJURY CAUSED BY OR DURING THE

EXECUTION OF THE WORK.

15. THE CONTRACTOR SHALL HAVE SOLE RESPONSIBILITY FOR CONSTRUCTION

SITE SAFETY AND FOLLOW ALL OSHA REGULATIONS.

16. ALL WALLS AND/OR FLOORS THAT ARE SCHEDULED FOR PAINTING SHALL BE

PROPERLY PREPARED (SEALED, SPACKLED, SANDED, ETC)AS REQUIRED

BEFORE PRIMING AND PAINTING WORK COMMENCES. CONTRACTOR SHALL

FOLLOW MANUFACTURER'S SPECIFICATIONS FOR SUBSTRATE AND PAINT

TYPE.

17. ALL PAINT SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S

SPECIFICATIONS FOR THE PARTICULAR SURFACE. PAINTS SHALL BE OF TYPE

SPECIFICALLY MANUFACTURED FOR APPLICATION TO THE SURFACE TO WHICH

IT IS TO BE APPLIED.

18. CONTRACTOR SHALL PERFORM ALL FINISH MATERIAL INSTALLATION AS TO

AVOID DAMAGE TO OTHER SURFACES. ALL DAMAGE TO ADJACENT SURFACES

SHALL BE REPAIRED IN A MANNER SATISFACTORY TO THE OWNER.

GENERAL CONSTRUCTION NOTES

ABBREVIATIONS

ACT

A.F.F

ALUM.

APPROX

ASHRAE

ASTM

BLDG

CLG

CMU

CONC

CONT.

DIA

DIM

DWGS

EA

EF

ELEV

ETC.

EQ

EXIST.

F.E.

FIN.FL.LVL.

GA

GWB

HM

HORIZ

HR

HW

I.D.

ACOUSTICAL CEILING TILE

ABOVE FINISHED FLOOR

ALUMINUM

APPROXIMATELY

AMERICAN SOCIETY OF HEATING,

REFRIGERATING, & AIR-CONDITIONING

ENGINEERS

AMERICAN SOCIETY FOR TESTING & MATERIALS

BUILDING

CEILING

CONCRETE MASONRY UNIT

CONCRETE

CONTINUOUS

DIAMETER

DIMENSION

DRAWINGS

EACH

EXHAUST FAN

ELEVATION

ETCETERA

EQUAL

EXISTING

FIRE EXTINGUISHER

FINISHED FLOOR LEVEL

GAUGE

GYPSUM WALLBOARD

HOLLOW METAL

HORIZONTAL

HOUR

HARDWARE

IDENTIFICATION

MAX

MECH.

MIN

M.O.

NFPA

N.I.C.

N.I.S.

NO.

NTS

O.C.

OCC

OSHA

PT

REQ.

RM

R.O.

SS

STL

SF

THK

T.O.

TYP.

UL

V.I.F.

WD

W/ W/O Ø

MAXIMUM

MECHANICAL

MINIMUM

MASONRY OPENING

NATIONAL FIRE PROTECTION

ASSOCIATION

NOT IN CONTRACT

NOT IN SCOPE

NUMBER

NOT TO SCALE

ON CENTER

OCCUPANTS

OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

PAINT

REQUIRED

ROOM

ROUGH OPENING

STAINLESS STEEL

STEEL

SQUARE FEET

THICK

TOP OF

TYPICAL

UNDERWRITER'S LABORATORY

VERIFY IN FIELD

WOOD

WITH

WITHOUT

DIAMETER

AT

AND

CENTERLINE

NUMBER

SYMBOLS

NUMBER

IDENTIFICATION

X

X

ELEVATION

SECTION

X

X

DETAIL

DRAWING NUMBER

WHERE REFERENCE

IS LOCATED

LETTER

IDENTIFICATION

DRAWING NUMBER

WHERE REFERENCE

IS LOCATED

LETTER

IDENTIFICATION

DRAWING NUMBER

WHERE REFERENCE

IS LOCATED

AXXXX

AXXXX

NUMBER

IDENTIFICATION

DRAWING NUMBER

WHERE REFERENCE

IS LOCATED

INTERIOR ELEVATION

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

AE-001

GENERAL NOTES, SYMBOLS,

ABBREVIATIONS, & CODE DATA

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

22164.005

100% CONSTRUCTION

24 25 26

9 10 11 12 13 14 16 17 19 21

F

E

D

C

B

A

ELEVATOR

MACHINE ROOM

7W-139B

AE-101

ELECTRICAL

EQUIPMENT

7W-139C

GI-004

NORTH

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

AE-011

EXISTING SEVENTH FLOOR PLAN -

OVERALL

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

100% CONSTRUCTION

DOCUMENTS

SCALE: 1/8" = 1'-0"

1680 4

1/8" = 1'-0"1

EXISTING SEVENTH FLOOR PLAN - PARTIAL

B

A

11' - 2" ±

ELEVATOR

LOWER PIT

EXISTING SHAFT WALL

F

G

G

F

H

I

J

K

B

A

12' - 6" +/-

EXISTING ELECTRIC RISER TO REMAIN

EXISTING SAFETY

GUARD RAIL

ELEVATOR

MACHINE ROOM

7W-139B

UP

139B

EXISTING

SAFETY GATE

8' - 10 1/4" +/-

/8

A

A

ELEVATOR

MACHINE

PLATFORM

78' - 8"

73' - 10"

A

B

B

B

B

C

DD

E

E

NORTH

EXISTING TO REMAIN

EXISTING TO BE DEMOLISHED

DEMO LEGEND

NEW CONSTRUCTION

CEILING - TYPE 0

OPEN TO STRUCTURE

2 HR FIRE RATING

B

A

ELEVATOR

MACHINE ROOM

7W-139B

TYPE 0

TYPE 0

L

L

L

L

M M

N

O R

1. DEMOLITION PLANS ARE INTENDED TO INDICATE MINIMUM DEMOLITION WORK.

CONTRACTOR SHALL VERIFY IN FIELD THE FULL EXTENT OF THE WORK.

REFER TO MEP & VT DRAWINGS FOR ADDITIONAL INFORMATION.

2. UNLESS OTHERWISE NOTED, ALL EXISTING WORK DISTURBED BY THE

REMOVAL, RELOCATION, OR INSTALLATION OF PLUMBING, ELECTRICAL,

MECHANICAL, OR STRUCTURAL WORK SHALL BE PATCHED TO MATCH

ORIGINAL WORK.

3. UNLESS OTHERWISE NOTED ON DRAWINGS OR SPECIFICATIONS, ALL EXISTING

SURFACES DISTURBED BY ANY DEMOLITION WORK SHALL BE PATCHED TO

MATCH ORIGINAL WORK:

- NEW WORK IS ADDED TO EXISTING WORK

- EXISTING OPENINGS ARE TO BE SEALED

- EXISTING WORK IS TO BE REMOVED

DEMOLITION NOTES

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

AE-101

ENLARGED PLANS - DEMOLITION VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

22164.005

100% CONSTRUCTION

DOCUMENTS

1/2" = 1'-0"3

ENLARGED LOWER ELEV. PIT PLAN - DEMO

1/2" = 1'-0"1

ENLARGED MACHINE ROOM PLAN - DEMO

SCALE: 1/2" = 1'-0"

420 1

KEYNOTES

MARK DESCRIPTION

A REMOVE EXISTING ELEVATOR MACHINERY IN ITS ENTIRETY - REFER TO MEP & ELEVATOR DRAWINGS

B REMOVE EXISTING ELEVATOR CONTROLS - REFER TO ELEVATOR DRAWINGS

C REMOVE EXISTING DOOR, FRAME AND ASSOCIATED HARDWARE

D PREPARE EXISTING CONCRETE SLAB TO RECEIVE NEW FLOOR FINISH

E CONFIRM REPLACEMENT OF EXISTING FURNISHINGS WITH VA

F REMOVE EXISTING ELEVATOR COUNTER WEIGHT - REFER TO ELEVATOR DRAWINGS

G REMOVE EXISTING BUFFER - REFER TO ELEVATOR DRAWINGS

H REMOVE EXISTING PIT LADDER - REFER TO ELEVATOR DRAWINGS

I REMOVE EXISTING SUMP PUMP AND REPLACE IN KIND- REFER TO ELEVATOR DRAWINGS

J CONFIRM ACCESS PANEL MEETS FIRE RATING REQUIREMENTS OF EXISTING 2 HR FIRE RATING - REPLACE AS

REQUIRED

K EXISTING 24" X 36" ACCESS OPENING TO BE PATCHED W/ 2 HR RATED CONSTRUCTION

L REMOVE EXISTING LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

M EXISTING EXPOSED STRUCTURAL DECK W/ FIREPROOFING TO REMAIN

N REMOVE EXISTING DAMPER - SEE MECHANICAL DRAWINGS

O EXISTING FP PIPING - SEE FIRE PROTECTION DRAWINGS

R EXISTING FIRE DAMPER - SEE MECH DRAWINGS

1/2" = 1'-0"2

ENLARGED MACHINE ROOM RCP - DEMO

B

A

C L

E A

R D

IM

E

N S

IO

N

V

.I .F

CLEAR DIMENSION (V.I.F.)

11' - 2" ±

ELEVATOR

LOWER PIT

E L E

V A

T O

R -1

C

A B

A B

O V

E E

L E

V A

T O

R -1

C

A B

A B

O V

E

PIT GRATE FRAMING ABOVE

EXISTING TO REMAIN

NEW CONSTRUCTION

CONSTRUCTION LEGEND

CEILING - TYPE 0 OPEN TO STRUCTURE

DOOR NUMBERXXX

FIRE EXTINGUISHERFE

PL

PENDANT LIGHT- SEE ELECTRICAL

DRAWINGS

2 HR FIRE RATING

NORTH

B

A

EXISTING ELECTRIC

RISER

EXISTING SAFETY

PIPE GUARD RAIL

ELEVATOR

MACHINE ROOM

7W-139B

UP

EXISTING

SAFETY GATE

ELEVATOR

MACHINE

PLATFORM

78' - 8"

73' - 10"

139B

CLEAR

3' - 0" 4' - 8" ±

FE

B

A

ELEVATOR

MACHINE ROOM

7W-139B

TYPE 0

TYPE 0

PL

PL

PL

PL

PL

PL

PL

PL

16 16

B

A

EXISTING UPPER ROOF

EXISTING LOWER ROOF

EXISTING

SCUPPER

EXISTING EPDM ROOF

E X

IS

T

IN

G

S L O

P E

ROOF EDGE

ROOF EDGE EXISTING EXTERIOR WALL

1/2" = 1'-0"3

ENLARGED LOWER ELEVATOR PIT PLAN

SCALE: 1/2" = 1'-0"

420 1

1/2" = 1'-0"1

ENLARGED MACHINE ROOM PLAN

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

AE-102

ENLARGED PLANS VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

22164.005

100% CONSTRUCTION

DOCUMENTS

KEYNOTES

MARK DESCRIPTION

1 ELEVATOR COUNTERWEIGHT - SEE ELEVATOR DRAWINGS

2 ELEVATOR PIT LADDER - SEE ELEVATOR DRAWINGS

3 ELEVATOR BUFFER - SEE ELEVATOR DRAWINGS

4 CONFIRM ACCESS PANEL MEETS FIRE RATING REQUIREMENTS OF EXISTING 2 HR FIRE RATING -

MINIMUM REQUIREMENT - 90 MIN RATING REPLACE AS REQUIRED

5 PATCH EXISTING OPENING TO MATCH 2 HR FIRE RATING

6 SUMP PUMP - SEE ELEVATOR DRAWINGS

7 ELEVATOR MACHINE EQUIPMENT - SEE ELEVATOR DRAWINGS

8 ELEVATOR GOVERNOR - SEE ELEVATOR DRAWINGS

9 ELEVATOR CONTROLLERS, DRIVERS AND TRANSFORMERS - SEE ELEVATOR DRAWINGS

10 ELEVATOR DISCONNECTS - SEE ELEVATOR DRAWINGS

11 EXISTING FURNISHINGS - CONFIRM REPLACEMENT WITH VA

12 NEW HOLLOW METAL DOOR AND FRAME WHITHIN EXISTING OPENING - 90 MIN FIRE RATED

13 NEW EPOXY FLOOR FINISH OVER EXISTING CONCRETE SLAB

14 PAINT WALLS AS PER FINISH SCHEDULE ON SHEET AE-601

15 PENDANT LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

16 REPAIR ANY DAMAGED EXISTING SPRAY FIREPROOFING TO MAINTAIN FIRE RATING

17 EXISTING FP PIPING - SEE FIRE PROTECTION DRAWINGS

18 INSPECT SCUPPER FOR POSSIBLE LEAKS, REPAIR AND OR REPLACE AS NECESSARY TO CREATE A

WEATHER TIGHT CONDITION

19 ROOF REPLACEMENT TO BE PERFORMED UNDER SEPARATE CONTRACT - COORDINATE WITH THE VA

20 INSPECT WINDOW TO MASONRY FLASHING AND SEAL, REPAIR AND REPLACE AS NECESSARY TO

CREATE A WEATHER TIGHT CONDITION

21 INSPECT FLASHING AT WALL TO ROOF CONDITION FOR POSSIBLE LEAKS, REPAIR AND OR REPLACE

AS NECESSARY TO CREATE A WEATHER TIGHT CONDITION

1/2" = 1'-0"2

ENLARGED MACHINE ROOM RCP

3/8" = 1'-0"4

ENLARGED ROOF PLAN

ROOM SCHEDULE LEGEND

EX EXISTING

P PAINT

RES RESINOUS FLOORING (EPOXY)

RB RUBBER BASE

ROOM FINISH SCHEDULE

SPACE

FLOOR

FINISH

WALL

FINISH

BASE

ELEVATOR MACHINE ROOM

7W-139B

INTEGRAL

BASE

P-1RES-1

CEILING

FINISH

NOTES

EX

TYPE A TYPE F1

SEE

BELOW

SEE

BELOW

JAMB TYPE 1 (J1)HEAD TYPE 1 (H1)

1/2" 1/2"

1 15/16" VARIES VARIES

VARIES

EXISTING 2 HOUR FIRE

RATED PARTITION

JAMB ANCHORS

/2

/2

2"

/1

V A

R

IE

S V

A R

IE

S

V A

R

IE

S

HOLLOW METAL FRAME

NOTES:

• FOR DOOR WIDTH- SEE DOOR SCHEDULE

• FRAME WIDTH VARIES WITH PARTITION WIDTH - SEE PARTITION TYPE

EXISTING 2 HOUR FIRE

RATED PARTITION

TYPE 1

DOOR IN FIRE-RATED

WALL

℄ OF

DOOR

TYPE 1B: RES-1 TYPE 1: EXISTING FLOOR

FIRE-RATED

ALUMINUM SADDLE

/2

4"

FIRE RATED

ALUMINUM SADDLE

ABBREVIATIONS

AL ALUMINUM

HW HOLLOW METAL

P PAINT

7100 East Belleview Ave.

Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r

E le v a to r/

-1

.B

.A

.R

.r v t

/2

/2

:2

:4

P

M

AE-601

FINISH ROOM SCHEDULE, DOOR

SCHEDULE AND DETAILS

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

UNIVERSITY DRIVE C PITTSBURGH, PA 15240

646-24-100

VA DIRECTOR 001

03/26/2026 DH/LAA CN

22164.005

100% CONSTRUCTION

DOCUMENTS

DOOR SCHEDULE

TO ROOM NAME

TO ROOM

NUMBER

DOOR FRAME THRESHOLD

HARDWARE

(SEE SPECS)

CARD

READER

(Y/N) COMMENTSMARK WIDTH HEIGHT THK TYPE MATERIAL DOOR FINISH TYPE MATERIAL HEAD JAMB FINISH MATERIAL DETAIL

ELEVATOR MACHINE ROOM 7W-139B 139B 3' - 0" 7' - 0" 0' - 1 3/4" A HW P F1 HM H1 J1 P AL 1 HW-5G Y MAINTAIN EXISTING CARD READING ACCESS - 90 MIN FIRE RATING

1/4" = 1'-0"1

DOOR / FRAME TYPES

3" = 1'-0"2

DOOR FRAME DETAILS

P-5 (DOOR/ FRAMES) SHERWIN WILLIAMS 7047 - PORPOISE

P-1 SHERWIN WILLIAMS 6183 - CONSERVATIVE GREY

PAINT BRAND NAME

RES-1 STONHARD STONSHIELD MEDIUM TEXTURE ASH PROVIDE 6" INTEGRAL BASE

RESINOUS MANUFACTURER MANUFACTURER NO. PATTERN COLOR COMMENTS

MATERIAL AND FINISHES LEGEND

3" = 1'-0"3

DOOR THRESHOLD DETAILS

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CONDUIT

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM

CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

LEGEND: (LOW VOLTAGE COORDINATION LEGEND)

CF: CONTRACTOR FURNISHED

CI: CONTRACTOR INSTALLED

OF: OWNER FURNISHED

OI: OWNER INSTALLED

REMARKS: (LOW VOLTAGE COORDINATION LEGEND)

1. PATCH PANELS SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED PER SPECIFICATION. REFER TO

TYPICAL COMMUNICATION TERMINATION DETAIL.

2. FIRE ALARM IS AN EXTENSION OF AN EXISTING SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE

EXISTING SYSTEM. REFER TO SPECIFICATIONS.

GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)

A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.

B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.

C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.

D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS

OTHERWISE INDICATED.

E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER

SPECIFICATION.

1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

03/26/2026

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r E le v a to r/

-1

.B

.M E

P .R

.r v t

/2

/2

:1

:4

P

M

EP000

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

University Drive C Pittsburgh, PA 15240

646-24-100

03/26/2026 CGH EAH

22164.005

100% CONSTRUCTION

DOCUMENTS

ELECTRICAL FIXTURE

SYMBOLS

PLAN SYMBOL NAME

RECEPTACLE - DOUBLE DUPLEX

- EMERGENCY (RED) - CONV

RECEPTACLE - DUPLEX - CONV

RECEPTACLE - DUPLEX - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV -

GFCI

RECEPTACLE - SIMPLEX

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

DUPLEX AND DATA (CONV) -

GFCI

PROVIDE DUPLEX RECEPTACLE AND COMATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL LEGEND

ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

JUNCTION BOX - WALL ELECTRICAL VERTICAL WALL-TYPE JUNCTION BOX.

FIRE ALARM SYMBOLS

PLAN SYMBOL NAME

DETECTOR - SYSTEM HEAT -

CEILING

DETECTOR - SYSTEM SMOKE -

CEILING

HORN AND STROBE

COMBINATION - WALL

LIGHTING DEVICE SYMBOLS

PLAN SYMBOL NAME

LIGHT SWITCH

SWITCH - 3 WAY

LIGHTING DEVICE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

PUSH BUTTON REFER TO LIGHTING CONTROL WALL DEVICE SCHEDULE FOR KEYPAD ID, DESCRIPTION, REQUIRED BUTTON FUNCTIONS, AND ADDITIONAL REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

LOW VOLTAGE COORDINATION LEGEND

SYSTEMS

ROUGH-INS &

PATHWAYS

CABLING &

TERMINATIONS

DEVICES &

EQUIPMENT REMARKS

ACCESS CONTROL CF / CI CF / CI CF / CI -

FIRE ALARM CF / CI CF / CI CF / CI 2

LIGHTING CONTROLS CF / CI CF / CI CF / CI -

SECURITY SURVEILLANCE (CCTV) CF / CI CF / CI CF / CI -

VOICE / DATA CF / CI CF / CI OF / OI 1

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

DISTRIBUTION PANEL

ENCLOSED DISCONNECT

SWITCH - FUSED

ENCLOSED DISCONNECT

SWITCH - NON-FUSED

PANELBOARD - SURFACE

TRANSFORMER - DRY TYPE

COMMUNICATION SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

WALL MOUNT COMMUNICATIONS

RACK

DATA/COMMUNICATIONS RACK.

SECURITY SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ACCESS CONTROL DEVICE GENERAL:

PROVIDE ACCESS CONTROL COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH ACCESS CONTROLLED DEVICE TYPE AT DOORS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION. PROVIDE ROUGH-INS PER ACCESS CONTROL ROUGH-IN DETAIL. DOOR ACCESS COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. COORDINATE REQUIRED CONDUITS TO DOOR FRAME AND WALL MOUNTED DEVICES WITH DOOR HARDWARE CONTRACTOR. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. PROVIDE 20A 120V EQUIPMENT BRANCH CIRCUIT TO DOOR CONTROLLERS LOCATED WITHIN ACCESS CONTROL CABINET IN ASSOCIATED COMMUNICATIONS ABOVE THE ACCESS CONTROLLED DOOR. PROVIDE FINAL CONNECTION OF 120V BRANCH CIRCUIT TO ALL POWER SUPPLIES REQUIRED FOR EACH DOOR FUNCTION.

REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. PROVIDE ACCESS CONTROL CABLING FROM DOOR CONTROLLER TO COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, DOOR POSITION SWITCH, ELECTRIC STRIKE, ELECTRIFIED HINGE, DOOR RELEASE PUSH BUTTON, MAGNETIC LOCK, AND REQUEST TO EXIT. PROVIDE DOOR POSITION SWITCH AND REQUEST TO EXIT AT EACH ACCESS CONTROLLED DOOR, UNLESS PROVIDED BY DOOR HARDWARE CONTRACTOR. CONTRACTOR SHALL TERMINATE ACCESS CONTROL CABLING TO DEVICES AT DOOR LOCATION AND PROVIDE A 7'-0" PIGTAIL WITHIN COMMUNICATIONS ROOM AT ACCESS CONTROL CABINET WITH APPROPRIATE DEVICE LABEL FOR OWNER TERMINATION. COORDINATE ALL TERMINATION REQUIREMENTS AND EXACT LOCATION OF TERMINATIONS WITH OWNER'S ACCESS CONTROL MANAGER. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE DOOR OPERATOR, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. SUBMIT SHOP DRAWINGS FOR APPROVAL. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR DOOR RELEASE UPON ALARM. INTEGRATE ACCESS CONTROL SYSTEM WITH DOOR OPERATORS, FIRE ALARM, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND

CONNECTIONS REQUIRED.

ACCESS CONTROL PANEL CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL [EQUIPMENT] [NORMAL] BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS.

COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDE NEMA 5-20

RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED.

CREDENTIAL CARD READER GENERAL:

PROVIDE PROXIMITY CARD READER AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE AT APPROXIMATE LOCATION INDICATED. REFER TO FLOOR PLANS FOR CARD READER DESIGNATION. PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT CARD READER SURFACE MOUNTED ON MULLION.

CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MANUFACTURER. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, NURSE CALL CANCEL STATIONS, INTRUSION DETECTION KEYPADS, WANDER PREVENTION KEYPADS, AND INFANT PROTECTION KEYPADS. REFER TO ACCESS CONTROL

SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.

TYPE ‘KEYPAD’, COMBINATION KEYPAD PROXIMITY CARD READER:

PROVIDE COMBINATION KEYPAD PROXIMITY CARD READER PER SPECIFICATION.

DOOR OPERATOR PROVIDE 20A 120V LIFE SAFETY BRANCH DOOR OPERATOR. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE REQUIRED ROUGH-IN TO DOOR FRAME FOR PUSH PLATE OR HAND WAVE ACTUATOR CABLING WITH DOOR HARDWARE CONTRACTOR. INCLUDE INTERLOCKS WITH OTHER DOOR HARDWARE COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, ELECTRIC STRIKE, ELECTRIFIED HINGE, MAGNETIC LOCK, REQUEST TO EXIT, MOTION SAFETY CONTROLS, KEY SWITCH, AND POWER SUPPLY. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE ACCESS CONTROL, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR OPERATOR DISABLING UPON ALARM.

INTEGRATE DOOR OPERATOR WITH FIRE ALARM, ACCESS CONTROL, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO PUSH PLATE OR HAND WAVE ACTUATOR SYMBOL LEGEND DESCRIPTION FOR ADDITIONAL REQUIREMENTS. COORDINATE INSTALLATION WITH DOOR HARDWARE

CONTRACTOR.

ROUGH-IN ACCESS CONTROL

REQUEST TO EXIT PUSH

BUTTON

PROVIDE REQUEST TO EXIT PUSH BUTTON AT APPROXIMATE LOCATION INDICATED. PROVIDE ROUGH-IN AS INDICATED WITHIN ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT PUSH BUTTON SURFACE MOUNTED ON MULLION. CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MULLION MANUFACTURER. PUSH BUTTONS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL.

COORDINATE EXACT LOCATION OF PUSH BUTTON WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, CARD READERS. REFER TO ACCESS CONTROL SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.

SECURITY SURVEILLANCE

CAMERA - CEILING

GENERAL:

PROVIDE POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CAMERA TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR CAMERA DESIGNATION. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK AT LOCATION INDICATED. INSTALL CAMERA CENTERED IN CEILING TILE. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT MOUNTING LOCATION WITH OWNER

PRIOR TO INSTALLATION.

TYPE ‘ELEV’, ELEVATOR SECURITY SURVEILLANCE CAMERA:

PROVIDE SECURITY SURVEILLANCE CAMERA WITHIN ELEVATOR CAB INDICATED ON FLOOR PLANS. COORDINATE EXACT MOUNTING LOCATION WITHIN CAB WITH OWNER. COORDINATE ROUGH-IN, CABLING, AND INSTALLATION

REQUIREMENTS WITH FINAL SELECTED ELEVATOR MANUFACTURER.

ONE LINE SYMBOL

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CONTINUATION

DIGITAL METER

DISCONNECT SWITCH

GROUND BAR

GROUNDING ELECTRODE

KEY INTERLOCK

MOTOR

PANEL BOARD

SURGE PROTECTIVE DEVICE

SWITCHBOARD/SWITCHGEAR

TRANSFORMER

Revisions: Date:

OFFICE 3

1W115

C

STORAGE

CC C

20'

C C

C

A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST

REMAIN. REFER TO FLOORPLANS FOR INDICATION OF DEMOLITION TYPE FOR EACH AREA:

a. SELECTIVE DEMOLITIONS AREAS:

• PROVIDE DEMOLITION FOR ITEMS AS SHOWN. EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF

DEMOLITION SHALL REMAIN UNLESS OTHERWISE INDICATED.

B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).

C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED

ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE

CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND

IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.

D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.

E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE BOXES ARE NOT REUSED. REMOVE CONCRETE EQUIPMENT PADS THAT REMAIN, TO BE FLUSH

WITH FLOOR/GRADE.

F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE

CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.

G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT BECOME INACCESSIBLE DUE

TO NEW WORK.

H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING

AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND

FUNCTIONALITY.

J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE

ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.

K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS. SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL TIMES.

L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH

ADJACENT SURFACE.

M. ALL UNLABELED ELECTRICAL DEVICES WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE SHALL BE CIRCUIT TRACED AS NEEDED WITH A

LABEL PROVIDED.

(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND

ALL ELECTRICAL DEMOLITION WORK)

ELECTRICAL DEMOLITION GENERAL NOTES: 13

D

E

B

A

EE

E E

E

E

D

B

A

E E

E E

E

E

LOBBY

C2W2A

B

A

EE

E E

E

E

CORRIDOR

3W200C

B

A

E E

EE

E

E

CORRIDOR

C4W3

B

A

EE

E E

E

E

CORRIDOR

C5W3

13 14

B

A

E E

E E

TELE

6W145

CORRIDOR

C6W3

E

E

W6LS

E

E

E

ELEC

6W144

D

D

D

D

1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

03/26/2026

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r E le v a to r/

-1

.B

.M E

P .R

.r v t

/2

/2

:1

:5

P

M

ED100

FLOOR PLAN - ELECTRICAL

DEMOLITION

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

University Drive C Pittsburgh, PA 15240

646-24-100

03/26/2026 CGH EAH

22164.005

100% CONSTRUCTION

DOCUMENTS

SHEET NOTES:

1. DEMOLISH EXISTING WALL MOUNTED LIGHT FIXTURES AND INSTALL NEW LED WALL MOUNTED FIXTURES.

REFER TO FLOOR PLAN SHEET 01-EP200 FOR NEW FIXTURE LOCATIONS.

2. DEMOLISH EXISTING QUAD RECEPTACLE (DUPLEX GFCI AND DUPLEX NON-GFCI) IN SURFACE BOX. PROVIDE

NEW TWIST-LOCK RECEPTACLE FOR SUMP PUMP AND NEW DUPLEX GFCI RECEPTACLE. UTILIZE EXISTING

CIRCUIT AND BRANCH.

3. DEMOLISH EXISTING HEAT DETECTOR ON TOP OF HOISTWAY. HOISTWAY SHALL NOT INCLUDE ANY HEAT

DETECTORS IN THE TOP OR PIT.

1/4" = 1'-0"

GROUND FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

SECOND FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

THIRD FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

FOURTH FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

FIFTH FLOOR - ELECTRICAL DEMOLITION

1/4" = 1'-0"

SIXTH FLOOR - ELECTRICAL DEMOLITION

N N

N N

N N N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

BASEMENT FLOOR - ELECTRICAL - DEMOLITION

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

C

F

13 14 16

B

A

D

D

ELEV. LIGHTS

EE

E

E

E

DDD

D D D

W E

D

E

E

XFMR DISC.

D

(MS) SWBD

E

EXISTING EQDS

E

DSEM

E

EXISTING LSDS

E

E

E

E

E

D

D

MCEM

E

ELECTRICAL EQUIPMENT

7W-139C

ELEVATOR MACHINE ROOM

7W-139B

1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

KEY PLAN :-

MOTT MACDONALD

ARCHITECTS PENN, P.C.

325 CHESTNUT STREET,

SUITE 300

PHILADELPHIA, PA 19016 U.S.A.

03/26/2026

A u to d e s k D o c s /2

.0

V A

P it ts b u rg h U p g ra d e B e d

T o w e r E le v a to r/

-1

.B

.M E

P .R

.r v t

/2

/2

:1

:5

P

M

ED101

FLOOR PLAN - ELECTRICAL

DEMOLITION

VA PITTSBURGH UPGRADE BED

TOWER ELEVATORS

University Drive C Pittsburgh, PA 15240

646-24-100

03/26/2026 CGH EAH

22164.005

100% CONSTRUCTION

DOCUMENTS

1/2" = 1'-0"

SEVENTH FLOOR - ELECTRICAL DEMOLITION

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

SHEET NOTES:

1. DEMOLISH EXISTING ELEVATOR DISCONNECT SWITCH AND

INSTALL NEW FUSED 150A DISCONNECT IN THE SAME

LOCATION.

2. DEMOLISH EXISTING SHUNT TRIP DEVICE. NEW ELEVATOR

DISCONNECTS SHALL INCLUDE INTEGRAL SHUNT TRIP.

3. DEMOLISH EXISTING CONTROLLERS AND UTILIZE EXISTING

CIRCUITS TO FEED NEW CONTROLLERS.

OFFICE 3

1W115

C

STORAGE

CCC

C

J

J

J

C

20'

C C

C

A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS FOR ALL DEVICES. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL INTERIOR ELEVATIONS, SYMBOL LEGENDS, AND TYPICAL ELECTRICAL DEVICE MOUNTING HEIGHTS DETAIL. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, SYMBOL LEGENDS, OR DETAILS, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH

ARCHITECTURAL DRAWINGS TO ENSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE

ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND

CONDUITS WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, COORDINATE WORK TO INSTALL

PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.

C. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR

REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.

D. GFCI TYPE…

This is the start of the file's text. The full file is on GovTribe.