Attachment 02 - Drawings 646-24-100.pdf
PDF 32 MB Posted
- Solicitation number
- 36C77626R0105
About this file
This is a set of construction drawings for the VA Pittsburgh Upgrade Bed Tower Elevators project located at 1 University Drive, Pittsburgh, PA 15240. The drawings are 100% Construction Documents dated March 26, 2026, with project number 22164.005 and building number 646-24-100. The document serves as the Designer of Record set prepared by Mott MacDonald Architects Penn, P.C. in Philadelphia and Specialized Engineering Services (SES) in Greenwood Village, Colorado.
The scope encompasses complete elevator system upgrades including demolition and new construction of two passenger elevators (Elevators 13 and 14) serving floors 1-6, with the machine room located on the seventh floor. Key work includes removal of existing elevator machinery, controls, counterweights, and buffers; replacement with new equipment; installation of new fire-rated partition walls with 2-hour and 1-hour ICRA (Infection Control Risk Assessment) barriers; new electrical systems including 150A fused disconnects with shunt trip capability, dedicated lighting circuits, fire alarm integration, and access control systems; mechanical and plumbing modifications; and fire protection updates. The project is fully sprinklered and requires strict adherence to fire safety codes, NFPA 70 (NEC) Article 620 for elevator wiring, and coordination with multiple trades. Electrical work includes new branch circuits serving the elevator cars, hoistway lighting with three-way and four-way switching controls, sump pump systems, and integration with the existing fire alarm system for elevator recall and power shutdown functions. All work must maintain two means of egress, protect existing services, coordinate with building operations, and comply with VA requirements throughout the phased construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 03- Wage Rates 6.24.26.pdf | ||
| Attachment 04 - Limitations on Subcontracting - Construction.pdf | ||
| 36C77626R0105.docx | DOCX document | |
| Attachment 05 - Site Visit Instructions.docx | DOCX document | |
| Attachment 01 - Specifications 646-24-100.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
646-100
G000 COVER SHEET
AE-001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, & CODE DATA
AE-011 EXISTING SEVENTH FLOOR PLAN - OVERALL
EP000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED100 FLOOR PLAN - ELECTRICAL DEMOLITION
ED101 FLOOR PLAN - ELECTRICAL DEMOLITION
EP500 ONE-LINE DIAGRAM
EP600 ELECTRICAL DETAILS
AE-101 ENLARGED PLANS - DEMOLITION
AE-601 FINISH ROOM SCHEDULE, DOOR SCHEDULE AND DETAILS
EP601 ELECTRICAL DETAILS
EP602 ELECTRICAL DETAILS
EP700 ELECTRICAL SCHEDULES
MD101 FLOOR PLAN - MECHANICAL DMOLITION
MH201 FLOOR PLAN - DUCTWORK/PIPING
AE-102 ENLARGED PLANS
EP200 FLOOR PLAN - ELECTRICAL
EP201 FLOOR PLAN - ELECTRICAL
FX001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
FX201 FLOOR PLAN - FIRE PROTECTION - DEMOLITION & NEW
MH000 MECHANICAL SYMBOLS AND ABBREVIATIONS
MH501 MECHANICAL DETAILS & SCHEDULES
PP201 FLOOR PLAN - PLUMBING - DEMOLITION & NEW
PP001 PLUMBING SYMBOLS AND ABBREVIATIONS
PP501 PLUMBING DETAILS & SCHEDULES
VT-001 ELEVATOR DETAILS
VT-002 HALL FIXTURE DETAILS
VT-003 ELEVATOR CAB INTERIOR DETAILS
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h
U p g ra d e
B e d T o w e r
E le v a to r/
-1
.B
.G .R
.r v t
/9
/2
:2
:1
P
M
G000
COVER SHEET VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
University Drive C Pittsburgh, PA 15240
646-24-100
02/26/2026 JS AEA
22164.005
100% CONSTRUCTION
DOCUMENTS
VA PITTSBURGH UPGRADE BED TOWER ELEVATORS
University Drive C Pittsburgh, PA 15240
Revisions: Date:
SITE MAP: VICINITY MAP:
646-24-100
GI-003 ICRA ASSESSMENT
GI-004 ICRA ASSESSMENT DETAILS
AE-001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, & CODE DATA
AE-011 EXISTING SEVENTH FLOOR PLAN -OVERALL
AE-101 ENLARGED PLANS -DEMOLITION
AE-102 ENLARGED PLANS
AE-601 FINISH ROOM SCHEDULE, DOOR SCHEDULE AND DETAILS
EP000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED100 FLOOR PLAN - ELECTRICAL DEMOLITION
ED101 FLOOR PLAN - ELECTRICAL DEMOLITION
EP200 FLOOR PLAN - ELECTRICAL
EP201 FLOOR PLAN - ELECTRICAL
EP500 ONE-LINE DIAGRAM
EP600 ELECTRICAL DETAILS
EP601 ELECTRICAL DETAILS
EP602 ELECTRICAL DETAILS
EP700 ELECTRICAL SCHEDULES
FX001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
FX201 FLOOR PLAN - FIRE PROTECTION - DEMOLITION & NEW
MH001 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD101 FLOOR PLAN - MECHANICAL DEMOLITION
MH201 FLOOR PLAN - DUCTWORK / PIPING
MH501 MECHANICAL DETAILS & SCHEDULES
PP001 PLUMBING SYMBOLS AND ABBREVIATIONS
PP201 FLOOR PLAN - PLUMBING - DEMOLITION & NEW
PP501 PLUMBING DETAILS & SCHEDULES
VT-001 ELEVATOR DETAILS
VT-002 HALL FIXTURE DETAILS
VT-003 ELEVATOR CAB INTERIOR DETAILS
ELEVATOR PIT ELEVATOR
MACHINE ROOM
VARIES VARIES VARIES CORRIDOR
• PUBLIC CORRIDOR IN FRONT OF ELEVATOR / ELEVATOR SHAFT FLOORS 1-6
• ELEVATOR MACHINE ROOM - SEVENTH FLOOR
X
X
1 University DR, Pittsburgh, PA 15240
646-24-100
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:3
:5
P
M
GI-003
ICRA ASSESSMENT VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
22164.005
100% CONSTRUCTION
DOCUMENTS
Revisions: Date: 3/26/2026
B B
A A
ELEVATOR-14
ELEVATOR 13
4' - 4 1/2" +/-
B
E .Q
E
.Q
C L
A01
6'-0" MIN.
I1 I6
I3
I5 I7
I7 I8
B B
A A
ELEVATOR-14
ELEVATOR 13
A
/4
4' - 6" +/- 6'-0" MIN.
C L
A01
I1
I2
I3
A L
IG
N
I5 I8
UNDERSIDE OF
STRUCTURE ABOVE
FIRE RESISTANT SEALANT
BOTH SIDES
UL DESIGN NO. U404 - 2 HOUR
FIRE RATING
WALL BASE
FIRE RESISTANT SEALANT
BOTH SIDES
ICRA 2-HOUR RATED PARTITION
A
W A
L L
H E
IG
H
T V
A R
IE
S
V
.I .F
M
IN
CEMENTIOUS BACKER TO
ENCLOSURE SIDE
PAINT
ELEVATOR
WALL
UNDERSIDE OF
STRUCTURE ABOVE
FIRE RESISTANT SEALANT
BOTH SIDES
UL DESIGN NO. U419 - 1 HOUR
FIRE RATING
WALL BASE
FIRE RESISTANT SEALANT
BOTH SIDES
ICRA 1-HOUR RATED PARTITION
B
M
IN
CEMENTIOUS BACKER TO
ENCLOSURE SIDE
PAINT
ELEVATOR
WALL
B B
A A
ELEVATOR
MACHINE ROOM
7W-139B
73' - 10"
139B
I4
I5
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
GI-004
ICRA ASSESSMENT DETAILS VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA LAA
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
1/4" = 1'-0"2
ENLARGED ICRA PLAN - 2ND THRU 6TH FLOORS
1/4" = 1'-0"1
ENLARGED ICRA PLAN - 1ST FLOOR
DOOR SCHEDULE
DOOR FRAME
HARDWARE COMMENTSMARK WIDTH HEIGHT THK TYPE MATERIAL TYPE MATERIAL DEPTH
A01 4' - 0" 7' - 0" 0' - 1 3/4" A HM F1 HM 7" COORDINATE
WITH VA
PROVIDE 90 MIN FIRE RATING IN 2 HOUR CONSTRUCTION -
PROVIDE 45 MIN IN 1 HOUR CONSTRUCTION
1 1/2" = 1'-0"3
ICRA BARRIER WALL TYPES
KEYNOTES
MARK DESCRIPTION
I1 WALK OFF MAT - INSIDE ENCLOSURE
I2 2-HR FIRE RATED - ICRA BARRIER
I3 MAINTAIN 6'-0" MIN CORRIDOR WIDTH AT ALL TIMES
I4 INSTALL PLASTIC ZIPPER ENCLOSURE AT ELEVATOR MACHINE ROOM
I5 EXISTING 2-HR FIRE RATED BARRIER
I6 1-HR FIRE RATED - ICRA BARRIER - ALTERNATIVE USE OF PLASTIC BARRIER IS
PERMISSABLE - COORDINATE WITH VA
I7 CONTRACTOR TO SEAL ELEVATOR DOORS ON LEVELS 2 THRU 6 WITH PAINTED DRY WALL
I8 FULL BARRIERS TO BE REVIEWED WITH STATION PRIOR TO WORK ON EACH FLOOR
1/4" = 1'-0"4
ENLARGED ICRA MACHINE ROOM PLAN
3/26/2026
DEMOLITION NOTES NOTED BELOW ARE GENERAL. REFER TO DEMOLITION PLAN FOR
SPECIFIC SCOPE NOTES.
1. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS AND
INSURANCES.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION & MAINTENANCE
OF ALL EXISTING SERVICES FOR THE DURATION OF THE WORK. I.E.
MECHANICAL, ELECTRICAL, FIRE ALARM SYSTEM, SECURITY SYSTEM, AND
PLUMBING.
3. THE CONTRACTOR SHALL FULLY ACQUAINT HIMSELF WITH THE EXISTING
CONDITIONS AND SHALL HAVE VISITED THE JOB SITE & BE FULLY INFORMED AS
TO THE NATURE OF THE EQUIPMENT AND FACILITIES NEEDED FOR THE
PROPER EXECUTION OF THE WORK.
4. CONTRACTOR IS RESPONSIBLE TO FURNISH, INSTALL & MAINTAIN CLEAN
CONSTRUCTION FILTERS ON THE FLOOR AIR HANDLERS & TO FURNISH,
INSTALL & MAINTAIN AIR FILTERS PRIOR TO PERFORMING TEST & BALANCE OF
HVAC SYSTEM.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF THE
PASSENGER & SERVICE ELEVATORS & PREMISES FOR THE DURATION OF THE
WORK.
6. CLEAR ACCESS TO BATHROOMS, ELEVATORS LOBBIES, ELECTRICAL CLOSETS,
FA EQUIPMENT AND MECHANICAL ROOMS NOT UNDER CONSTRUCTION SHALL
BE MAINTAINED AT ALL TIMES.
7. THE DEMOLITION OPERATIONS SHALL AT ALL TIMES BE CARRIED OUT IN SUCH
A MANNER SO AS TO PREVENT DAMAGE OR DUST TO ADJOINING SPACES AND
FLOORS.
8. DEMOLITION OF ANY WORK OF A NOISE MAKING NATURE SHALL BE DONE AS
REQUIRED BY BUILDING POLICIES AND ANY PREMIUM TIME, IF REQUIRED,
SHALL BE INCLUDED IN THE DESCRIPTION OF WORK.
9. CONTRACTOR IS TO COORDINATE ALL DEMOLITION AND LOADING OPERATIONS
WITH OWNER.
10. MAINTAIN PREMISES & PUBLIC PROPERTIES FREE FROM ACCUMULATION OF
WASTE, DEBRIS & RUBBISH CAUSED BY OPERATIONS. AT COMPLETION OF
WORK, LEAVE PREMISES & PUBLIC PROPERTIES CLEAN ON A DAILY BASIS.
11. CONTRACTOR TO COORDINATE BUILDING'S HOURS OF OPERATION FOR
ELEVATOR, SERVICES, ETC. W/ OWNER AND BUILDING OFFICE PRIOR TO THE
COMMENCEMENT OF ANY WORK.
12. ALL DEMOLITION SHALL BE PERFORMED BY THE TRADE HAVING JURISDICTION.
13. PROTECT ALL EXISTING FINISHES TO REMAIN THROUGHOUT THE LIFE OF THE
PROJECT.
14. CONTRACTOR TO PROTECT ALL EXISTING AND NEW FLOOR FINISHES AND
WALLS LEADING FROM PHASED AREAS TO OCCUPIED AREAS. ALL AREAS ARE
TO BE VACUUMED ON A DAILY BASIS.
15. FOR EACH PHASE, TEMPORARY MEANS OF EGRESS SHALL BE MARKED WITH
DIRECTIONAL EXIT SIGNS.
16. MAINTAIN TWO MEANS OF EGRESS FROM ALL PORTIONS OF THE FLOOR
DURING ALL PHASES OF CONSTRUCTION.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF RUBBISH FROM
AREA OF WORK AND THE LEGAL DISPOSAL OF ALL REMOVED AND
DEMOLISHED MATERIALS.
18. CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS NOT TO REMOVE &/OR
DISCONNECT ANY EXISTING FIRE ALARM WIRING. WHEN DEMOLITION IS TO
TAKE PLACE IN THE AREA OF THE BUILDING WHERE FIRE SAFETY EQUIPMENT
SUCH AS ALARMS, SPEAKERS, SMOKE DETECTORS, FLOOR WARDEN STATION,
ETC. ARE LOCATED. BUILDING MANAGER SHALL BE NOTIFIED (5) WORKING
DAYS PRIOR TO START OF DEMOLITION SO EQUIPMENT MAY BE REMOVED
AND/OR PROTECTED. A FULLY WORKING FIRE ALARM SYSTEM IS TO BE
MAINTAINED OPERATIONAL AT THE END OF EACH WORKING DAY.
19. REMOVE ANY PIPES, CONDUITS, METAL, ANCHORS AND ANY ITEMS THAT HAVE
BEEN ABANDONED OR ARE NO LONGER REQUIRED FOR BUILDING SYSTEMS
OPERATIONS THAT PROJECT FROM EXISTING FINISH LINE OF FLOORS, WALLS
OR COLUMNS THAT ARE SCHEDULED TO REMAIN. U.O.N. COORDINATE WITH
BUILDING ENGINEER.
GENERAL DEMOLITION NOTES
1. ON ALL FIRE RATED PARTITIONS - ALL PENETRATIONS AND JOINTS ARE TO BE
TAPED AND SPACKLED SLAB TO SLAB. FIRE STOP ALL PENETRATIONS.
2. DOUBLE STUDS ARE REQUIRED AT BOTH JAMBS OF DOOR FRAMES AND
HEADER.
3. STUDS AT DOOR JAMBS AND ON TOPS OF DOOR FRAMES MUST BE SCREWED
TO RUNNERS AT TOP, BOTTOMS AND BOTH SIDES.
4. PARTITIONS SHALL NOT BE FASTENED OR BRACED TO DUCTWORK, CONDUIT
OR PIPING.
5. FLOOR MUST REMAIN IN A STATE OF SAFE CONDITIONS WITH REGARD TO FIRE
SAFETY FOR PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,
SPEAKERS ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES.
6. ALL WOOD TO BE FIRE RETARDANT.
7. ALL FIRE-STOPPING UTILIZED AT PENETRATIONS THROUGH FLOOR
ASSEMBLIES SHALL PROVIDE A FIRE RESISTANCE RATING PER THE
APPLICABLE CODE. FIRE-STOPPING/FIRE-SAFING THROUGH PARTITION
ASSEMBLIES SHALL PROVIDE A FIRE RESISTIVE RATING THAT MATCHES THAT
OF THE PARTITION. COMPLY WITH UL 1479 "FIRE TESTS OF THROUGH
PENETRATION FIRE-STOP".
8. WHERE NEW AND EXISTING BUILDING PARTITIONS ARE SHOWN TO ALIGN, THE
JUNCTION SHALL BE TAPED, SPACKLED AND FINISHED SMOOTH.
9. FIRE SAFETY EQUIPMENT AND THEIR ASSOCIATED CONDUIT AND WIRING
SYSTEMS SHALL NOT BE MARRED DURING CONSTRUCTION AND SHALL BE
PROTECTED FROM ANY PHYSICAL DAMAGE BY THE GENERAL CONTRACTOR
AND SUBCONTRACTOR FOR THE DURATION OF THE PROJECT.
10. WHERE FIREPROOFING OF EXISTING COLUMNS OR BEAMS IS DISTURBED BY
NEW WORK, THE FIREPROOFING SHALL BE RESTORED TO PROVIDE A MINIMUM
RESISTANCE RATING AS REQUIRED BY THE APPLICABLE BUILDING CODE.
11. CONTRACTOR SHALL ISSUE COMPLETE, FULL SETS OF DRAWINGS AND
SPECIFICATIONS TO SUB-CONTRACTORS FOR BIDDING PURPOSES.
CONTRACTOR SHALL NOTIFY ARCHITECT OF ANY CONFLICTS BETWEEN
DRAWINGS, FOR RESPONSE AND RESOLUTION.
12. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, AND REPAIRING AS
REQUIRED TO PERFORM ALL OF THE WORK INDICATED ON THE DRAWINGS
AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE PROJECT.
13. ALL ITEMS RECESSED INTO ONE OR TWO HOUR FIRE RATED PARTITIONS
(SUCH AS OUTLET BOXES, PANEL BOXES, ETC) SHALL HAVE THE OPENINGS
PROTECTED WITH BACK-UP MATERIALS SO AS TO RETAIN THE INTEGRITY OF
THE FIRE RATING OF THE PARTITION THROUGHOUT. PROTECTION OF THE ONE
AND TWO HOUR RATED PARTITIONS SHALL BE IN STRICT CONFORMANCE WITH
THE APPLICABLE BUILDING CODE.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL
CONDITIONS AND MATERIALS WITHIN THE PROPOSED CONSTRUCTION AREAS.
THE CONTRACTOR SHALL DESIGN AND INSTALL ADEQUATE SHORING AND
BRACING FOR ANY STRUCTURAL TASKS. THE CONTRACTOR SHALL HAVE SOLE
RESPONSIBILITY FOR ANY DAMAGE OR INJURY CAUSED BY OR DURING THE
EXECUTION OF THE WORK.
15. THE CONTRACTOR SHALL HAVE SOLE RESPONSIBILITY FOR CONSTRUCTION
SITE SAFETY AND FOLLOW ALL OSHA REGULATIONS.
16. ALL WALLS AND/OR FLOORS THAT ARE SCHEDULED FOR PAINTING SHALL BE
PROPERLY PREPARED (SEALED, SPACKLED, SANDED, ETC)AS REQUIRED
BEFORE PRIMING AND PAINTING WORK COMMENCES. CONTRACTOR SHALL
FOLLOW MANUFACTURER'S SPECIFICATIONS FOR SUBSTRATE AND PAINT
TYPE.
17. ALL PAINT SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS FOR THE PARTICULAR SURFACE. PAINTS SHALL BE OF TYPE
SPECIFICALLY MANUFACTURED FOR APPLICATION TO THE SURFACE TO WHICH
IT IS TO BE APPLIED.
18. CONTRACTOR SHALL PERFORM ALL FINISH MATERIAL INSTALLATION AS TO
AVOID DAMAGE TO OTHER SURFACES. ALL DAMAGE TO ADJACENT SURFACES
SHALL BE REPAIRED IN A MANNER SATISFACTORY TO THE OWNER.
GENERAL CONSTRUCTION NOTES
ABBREVIATIONS
ACT
A.F.F
ALUM.
APPROX
ASHRAE
ASTM
BLDG
CLG
CMU
CONC
CONT.
DIA
DIM
DWGS
EA
EF
ELEV
ETC.
EQ
EXIST.
F.E.
FIN.FL.LVL.
GA
GWB
HM
HORIZ
HR
HW
I.D.
ACOUSTICAL CEILING TILE
ABOVE FINISHED FLOOR
ALUMINUM
APPROXIMATELY
AMERICAN SOCIETY OF HEATING,
REFRIGERATING, & AIR-CONDITIONING
ENGINEERS
AMERICAN SOCIETY FOR TESTING & MATERIALS
BUILDING
CEILING
CONCRETE MASONRY UNIT
CONCRETE
CONTINUOUS
DIAMETER
DIMENSION
DRAWINGS
EACH
EXHAUST FAN
ELEVATION
ETCETERA
EQUAL
EXISTING
FIRE EXTINGUISHER
FINISHED FLOOR LEVEL
GAUGE
GYPSUM WALLBOARD
HOLLOW METAL
HORIZONTAL
HOUR
HARDWARE
IDENTIFICATION
MAX
MECH.
MIN
M.O.
NFPA
N.I.C.
N.I.S.
NO.
NTS
O.C.
OCC
OSHA
PT
REQ.
RM
R.O.
SS
STL
SF
THK
T.O.
TYP.
UL
V.I.F.
WD
W/ W/O Ø
MAXIMUM
MECHANICAL
MINIMUM
MASONRY OPENING
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NOT IN SCOPE
NUMBER
NOT TO SCALE
ON CENTER
OCCUPANTS
OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
PAINT
REQUIRED
ROOM
ROUGH OPENING
STAINLESS STEEL
STEEL
SQUARE FEET
THICK
TOP OF
TYPICAL
UNDERWRITER'S LABORATORY
VERIFY IN FIELD
WOOD
WITH
WITHOUT
DIAMETER
AT
AND
CENTERLINE
NUMBER
SYMBOLS
NUMBER
IDENTIFICATION
X
X
ELEVATION
SECTION
X
X
DETAIL
DRAWING NUMBER
WHERE REFERENCE
IS LOCATED
LETTER
IDENTIFICATION
DRAWING NUMBER
WHERE REFERENCE
IS LOCATED
LETTER
IDENTIFICATION
DRAWING NUMBER
WHERE REFERENCE
IS LOCATED
AXXXX
AXXXX
NUMBER
IDENTIFICATION
DRAWING NUMBER
WHERE REFERENCE
IS LOCATED
INTERIOR ELEVATION
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
AE-001
GENERAL NOTES, SYMBOLS,
ABBREVIATIONS, & CODE DATA
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
22164.005
100% CONSTRUCTION
24 25 26
9 10 11 12 13 14 16 17 19 21
F
E
D
C
B
A
ELEVATOR
MACHINE ROOM
7W-139B
AE-101
ELECTRICAL
EQUIPMENT
7W-139C
GI-004
NORTH
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
AE-011
EXISTING SEVENTH FLOOR PLAN -
OVERALL
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/8" = 1'-0"
1680 4
1/8" = 1'-0"1
EXISTING SEVENTH FLOOR PLAN - PARTIAL
B
A
11' - 2" ±
ELEVATOR
LOWER PIT
EXISTING SHAFT WALL
F
G
G
F
H
I
J
K
B
A
12' - 6" +/-
EXISTING ELECTRIC RISER TO REMAIN
EXISTING SAFETY
GUARD RAIL
ELEVATOR
MACHINE ROOM
7W-139B
UP
139B
EXISTING
SAFETY GATE
8' - 10 1/4" +/-
/8
A
A
ELEVATOR
MACHINE
PLATFORM
78' - 8"
73' - 10"
A
B
B
B
B
C
DD
E
E
NORTH
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
DEMO LEGEND
NEW CONSTRUCTION
CEILING - TYPE 0
OPEN TO STRUCTURE
2 HR FIRE RATING
B
A
ELEVATOR
MACHINE ROOM
7W-139B
TYPE 0
TYPE 0
L
L
L
L
M M
N
O R
1. DEMOLITION PLANS ARE INTENDED TO INDICATE MINIMUM DEMOLITION WORK.
CONTRACTOR SHALL VERIFY IN FIELD THE FULL EXTENT OF THE WORK.
REFER TO MEP & VT DRAWINGS FOR ADDITIONAL INFORMATION.
2. UNLESS OTHERWISE NOTED, ALL EXISTING WORK DISTURBED BY THE
REMOVAL, RELOCATION, OR INSTALLATION OF PLUMBING, ELECTRICAL,
MECHANICAL, OR STRUCTURAL WORK SHALL BE PATCHED TO MATCH
ORIGINAL WORK.
3. UNLESS OTHERWISE NOTED ON DRAWINGS OR SPECIFICATIONS, ALL EXISTING
SURFACES DISTURBED BY ANY DEMOLITION WORK SHALL BE PATCHED TO
MATCH ORIGINAL WORK:
- NEW WORK IS ADDED TO EXISTING WORK
- EXISTING OPENINGS ARE TO BE SEALED
- EXISTING WORK IS TO BE REMOVED
DEMOLITION NOTES
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
AE-101
ENLARGED PLANS - DEMOLITION VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
22164.005
100% CONSTRUCTION
DOCUMENTS
1/2" = 1'-0"3
ENLARGED LOWER ELEV. PIT PLAN - DEMO
1/2" = 1'-0"1
ENLARGED MACHINE ROOM PLAN - DEMO
SCALE: 1/2" = 1'-0"
420 1
KEYNOTES
MARK DESCRIPTION
A REMOVE EXISTING ELEVATOR MACHINERY IN ITS ENTIRETY - REFER TO MEP & ELEVATOR DRAWINGS
B REMOVE EXISTING ELEVATOR CONTROLS - REFER TO ELEVATOR DRAWINGS
C REMOVE EXISTING DOOR, FRAME AND ASSOCIATED HARDWARE
D PREPARE EXISTING CONCRETE SLAB TO RECEIVE NEW FLOOR FINISH
E CONFIRM REPLACEMENT OF EXISTING FURNISHINGS WITH VA
F REMOVE EXISTING ELEVATOR COUNTER WEIGHT - REFER TO ELEVATOR DRAWINGS
G REMOVE EXISTING BUFFER - REFER TO ELEVATOR DRAWINGS
H REMOVE EXISTING PIT LADDER - REFER TO ELEVATOR DRAWINGS
I REMOVE EXISTING SUMP PUMP AND REPLACE IN KIND- REFER TO ELEVATOR DRAWINGS
J CONFIRM ACCESS PANEL MEETS FIRE RATING REQUIREMENTS OF EXISTING 2 HR FIRE RATING - REPLACE AS
REQUIRED
K EXISTING 24" X 36" ACCESS OPENING TO BE PATCHED W/ 2 HR RATED CONSTRUCTION
L REMOVE EXISTING LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS
M EXISTING EXPOSED STRUCTURAL DECK W/ FIREPROOFING TO REMAIN
N REMOVE EXISTING DAMPER - SEE MECHANICAL DRAWINGS
O EXISTING FP PIPING - SEE FIRE PROTECTION DRAWINGS
R EXISTING FIRE DAMPER - SEE MECH DRAWINGS
1/2" = 1'-0"2
ENLARGED MACHINE ROOM RCP - DEMO
B
A
C L
E A
R D
IM
E
N S
IO
N
V
.I .F
CLEAR DIMENSION (V.I.F.)
11' - 2" ±
ELEVATOR
LOWER PIT
E L E
V A
T O
R -1
C
A B
A B
O V
E E
L E
V A
T O
R -1
C
A B
A B
O V
E
PIT GRATE FRAMING ABOVE
EXISTING TO REMAIN
NEW CONSTRUCTION
CONSTRUCTION LEGEND
CEILING - TYPE 0 OPEN TO STRUCTURE
DOOR NUMBERXXX
FIRE EXTINGUISHERFE
PL
PENDANT LIGHT- SEE ELECTRICAL
DRAWINGS
2 HR FIRE RATING
NORTH
B
A
EXISTING ELECTRIC
RISER
EXISTING SAFETY
PIPE GUARD RAIL
ELEVATOR
MACHINE ROOM
7W-139B
UP
EXISTING
SAFETY GATE
ELEVATOR
MACHINE
PLATFORM
78' - 8"
73' - 10"
139B
CLEAR
3' - 0" 4' - 8" ±
FE
B
A
ELEVATOR
MACHINE ROOM
7W-139B
TYPE 0
TYPE 0
PL
PL
PL
PL
PL
PL
PL
PL
16 16
B
A
EXISTING UPPER ROOF
EXISTING LOWER ROOF
EXISTING
SCUPPER
EXISTING EPDM ROOF
E X
IS
T
IN
G
S L O
P E
ROOF EDGE
ROOF EDGE EXISTING EXTERIOR WALL
1/2" = 1'-0"3
ENLARGED LOWER ELEVATOR PIT PLAN
SCALE: 1/2" = 1'-0"
420 1
1/2" = 1'-0"1
ENLARGED MACHINE ROOM PLAN
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
AE-102
ENLARGED PLANS VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
22164.005
100% CONSTRUCTION
DOCUMENTS
KEYNOTES
MARK DESCRIPTION
1 ELEVATOR COUNTERWEIGHT - SEE ELEVATOR DRAWINGS
2 ELEVATOR PIT LADDER - SEE ELEVATOR DRAWINGS
3 ELEVATOR BUFFER - SEE ELEVATOR DRAWINGS
4 CONFIRM ACCESS PANEL MEETS FIRE RATING REQUIREMENTS OF EXISTING 2 HR FIRE RATING -
MINIMUM REQUIREMENT - 90 MIN RATING REPLACE AS REQUIRED
5 PATCH EXISTING OPENING TO MATCH 2 HR FIRE RATING
6 SUMP PUMP - SEE ELEVATOR DRAWINGS
7 ELEVATOR MACHINE EQUIPMENT - SEE ELEVATOR DRAWINGS
8 ELEVATOR GOVERNOR - SEE ELEVATOR DRAWINGS
9 ELEVATOR CONTROLLERS, DRIVERS AND TRANSFORMERS - SEE ELEVATOR DRAWINGS
10 ELEVATOR DISCONNECTS - SEE ELEVATOR DRAWINGS
11 EXISTING FURNISHINGS - CONFIRM REPLACEMENT WITH VA
12 NEW HOLLOW METAL DOOR AND FRAME WHITHIN EXISTING OPENING - 90 MIN FIRE RATED
13 NEW EPOXY FLOOR FINISH OVER EXISTING CONCRETE SLAB
14 PAINT WALLS AS PER FINISH SCHEDULE ON SHEET AE-601
15 PENDANT LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS
16 REPAIR ANY DAMAGED EXISTING SPRAY FIREPROOFING TO MAINTAIN FIRE RATING
17 EXISTING FP PIPING - SEE FIRE PROTECTION DRAWINGS
18 INSPECT SCUPPER FOR POSSIBLE LEAKS, REPAIR AND OR REPLACE AS NECESSARY TO CREATE A
WEATHER TIGHT CONDITION
19 ROOF REPLACEMENT TO BE PERFORMED UNDER SEPARATE CONTRACT - COORDINATE WITH THE VA
20 INSPECT WINDOW TO MASONRY FLASHING AND SEAL, REPAIR AND REPLACE AS NECESSARY TO
CREATE A WEATHER TIGHT CONDITION
21 INSPECT FLASHING AT WALL TO ROOF CONDITION FOR POSSIBLE LEAKS, REPAIR AND OR REPLACE
AS NECESSARY TO CREATE A WEATHER TIGHT CONDITION
1/2" = 1'-0"2
ENLARGED MACHINE ROOM RCP
3/8" = 1'-0"4
ENLARGED ROOF PLAN
ROOM SCHEDULE LEGEND
EX EXISTING
P PAINT
RES RESINOUS FLOORING (EPOXY)
RB RUBBER BASE
ROOM FINISH SCHEDULE
SPACE
FLOOR
FINISH
WALL
FINISH
BASE
ELEVATOR MACHINE ROOM
7W-139B
INTEGRAL
BASE
P-1RES-1
CEILING
FINISH
NOTES
EX
TYPE A TYPE F1
SEE
BELOW
SEE
BELOW
JAMB TYPE 1 (J1)HEAD TYPE 1 (H1)
1/2" 1/2"
1 15/16" VARIES VARIES
VARIES
EXISTING 2 HOUR FIRE
RATED PARTITION
JAMB ANCHORS
/2
/2
2"
/1
V A
R
IE
S V
A R
IE
S
V A
R
IE
S
HOLLOW METAL FRAME
NOTES:
• FOR DOOR WIDTH- SEE DOOR SCHEDULE
• FRAME WIDTH VARIES WITH PARTITION WIDTH - SEE PARTITION TYPE
EXISTING 2 HOUR FIRE
RATED PARTITION
TYPE 1
DOOR IN FIRE-RATED
WALL
℄ OF
DOOR
TYPE 1B: RES-1 TYPE 1: EXISTING FLOOR
FIRE-RATED
ALUMINUM SADDLE
/2
4"
FIRE RATED
ALUMINUM SADDLE
ABBREVIATIONS
AL ALUMINUM
HW HOLLOW METAL
P PAINT
7100 East Belleview Ave.
Suite 107 Greenwood Village, CO 80111 Phone: 720.200.5955
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r
E le v a to r/
-1
.B
.A
.R
.r v t
/2
/2
:2
:4
P
M
AE-601
FINISH ROOM SCHEDULE, DOOR
SCHEDULE AND DETAILS
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
UNIVERSITY DRIVE C PITTSBURGH, PA 15240
646-24-100
VA DIRECTOR 001
03/26/2026 DH/LAA CN
22164.005
100% CONSTRUCTION
DOCUMENTS
DOOR SCHEDULE
TO ROOM NAME
TO ROOM
NUMBER
DOOR FRAME THRESHOLD
HARDWARE
(SEE SPECS)
CARD
READER
(Y/N) COMMENTSMARK WIDTH HEIGHT THK TYPE MATERIAL DOOR FINISH TYPE MATERIAL HEAD JAMB FINISH MATERIAL DETAIL
ELEVATOR MACHINE ROOM 7W-139B 139B 3' - 0" 7' - 0" 0' - 1 3/4" A HW P F1 HM H1 J1 P AL 1 HW-5G Y MAINTAIN EXISTING CARD READING ACCESS - 90 MIN FIRE RATING
1/4" = 1'-0"1
DOOR / FRAME TYPES
3" = 1'-0"2
DOOR FRAME DETAILS
P-5 (DOOR/ FRAMES) SHERWIN WILLIAMS 7047 - PORPOISE
P-1 SHERWIN WILLIAMS 6183 - CONSERVATIVE GREY
PAINT BRAND NAME
RES-1 STONHARD STONSHIELD MEDIUM TEXTURE ASH PROVIDE 6" INTEGRAL BASE
RESINOUS MANUFACTURER MANUFACTURER NO. PATTERN COLOR COMMENTS
MATERIAL AND FINISHES LEGEND
3" = 1'-0"3
DOOR THRESHOLD DETAILS
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CONDUIT
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
LEGEND: (LOW VOLTAGE COORDINATION LEGEND)
CF: CONTRACTOR FURNISHED
CI: CONTRACTOR INSTALLED
OF: OWNER FURNISHED
OI: OWNER INSTALLED
REMARKS: (LOW VOLTAGE COORDINATION LEGEND)
1. PATCH PANELS SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED PER SPECIFICATION. REFER TO
TYPICAL COMMUNICATION TERMINATION DETAIL.
2. FIRE ALARM IS AN EXTENSION OF AN EXISTING SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE
EXISTING SYSTEM. REFER TO SPECIFICATIONS.
GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)
A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.
C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.
D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS
OTHERWISE INDICATED.
E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER
SPECIFICATION.
1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
03/26/2026
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r E le v a to r/
-1
.B
.M E
P .R
.r v t
/2
/2
:1
:4
P
M
EP000
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
University Drive C Pittsburgh, PA 15240
646-24-100
03/26/2026 CGH EAH
22164.005
100% CONSTRUCTION
DOCUMENTS
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DOUBLE DUPLEX
- EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV -
GFCI
RECEPTACLE - SIMPLEX
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
DUPLEX AND DATA (CONV) -
GFCI
PROVIDE DUPLEX RECEPTACLE AND COMATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL LEGEND
ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.
JUNCTION BOX - WALL ELECTRICAL VERTICAL WALL-TYPE JUNCTION BOX.
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM HEAT -
CEILING
DETECTOR - SYSTEM SMOKE -
CEILING
HORN AND STROBE
COMBINATION - WALL
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
SWITCH - 3 WAY
LIGHTING DEVICE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
PUSH BUTTON REFER TO LIGHTING CONTROL WALL DEVICE SCHEDULE FOR KEYPAD ID, DESCRIPTION, REQUIRED BUTTON FUNCTIONS, AND ADDITIONAL REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
LOW VOLTAGE COORDINATION LEGEND
SYSTEMS
ROUGH-INS &
PATHWAYS
CABLING &
TERMINATIONS
DEVICES &
EQUIPMENT REMARKS
ACCESS CONTROL CF / CI CF / CI CF / CI -
FIRE ALARM CF / CI CF / CI CF / CI 2
LIGHTING CONTROLS CF / CI CF / CI CF / CI -
SECURITY SURVEILLANCE (CCTV) CF / CI CF / CI CF / CI -
VOICE / DATA CF / CI CF / CI OF / OI 1
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
DISTRIBUTION PANEL
ENCLOSED DISCONNECT
SWITCH - FUSED
ENCLOSED DISCONNECT
SWITCH - NON-FUSED
PANELBOARD - SURFACE
TRANSFORMER - DRY TYPE
COMMUNICATION SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
WALL MOUNT COMMUNICATIONS
RACK
DATA/COMMUNICATIONS RACK.
SECURITY SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ACCESS CONTROL DEVICE GENERAL:
PROVIDE ACCESS CONTROL COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH ACCESS CONTROLLED DEVICE TYPE AT DOORS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION. PROVIDE ROUGH-INS PER ACCESS CONTROL ROUGH-IN DETAIL. DOOR ACCESS COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. COORDINATE REQUIRED CONDUITS TO DOOR FRAME AND WALL MOUNTED DEVICES WITH DOOR HARDWARE CONTRACTOR. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. PROVIDE 20A 120V EQUIPMENT BRANCH CIRCUIT TO DOOR CONTROLLERS LOCATED WITHIN ACCESS CONTROL CABINET IN ASSOCIATED COMMUNICATIONS ABOVE THE ACCESS CONTROLLED DOOR. PROVIDE FINAL CONNECTION OF 120V BRANCH CIRCUIT TO ALL POWER SUPPLIES REQUIRED FOR EACH DOOR FUNCTION.
REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. PROVIDE ACCESS CONTROL CABLING FROM DOOR CONTROLLER TO COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, DOOR POSITION SWITCH, ELECTRIC STRIKE, ELECTRIFIED HINGE, DOOR RELEASE PUSH BUTTON, MAGNETIC LOCK, AND REQUEST TO EXIT. PROVIDE DOOR POSITION SWITCH AND REQUEST TO EXIT AT EACH ACCESS CONTROLLED DOOR, UNLESS PROVIDED BY DOOR HARDWARE CONTRACTOR. CONTRACTOR SHALL TERMINATE ACCESS CONTROL CABLING TO DEVICES AT DOOR LOCATION AND PROVIDE A 7'-0" PIGTAIL WITHIN COMMUNICATIONS ROOM AT ACCESS CONTROL CABINET WITH APPROPRIATE DEVICE LABEL FOR OWNER TERMINATION. COORDINATE ALL TERMINATION REQUIREMENTS AND EXACT LOCATION OF TERMINATIONS WITH OWNER'S ACCESS CONTROL MANAGER. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE DOOR OPERATOR, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. SUBMIT SHOP DRAWINGS FOR APPROVAL. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR DOOR RELEASE UPON ALARM. INTEGRATE ACCESS CONTROL SYSTEM WITH DOOR OPERATORS, FIRE ALARM, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND
CONNECTIONS REQUIRED.
ACCESS CONTROL PANEL CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL [EQUIPMENT] [NORMAL] BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS.
COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDE NEMA 5-20
RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED.
CREDENTIAL CARD READER GENERAL:
PROVIDE PROXIMITY CARD READER AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE AT APPROXIMATE LOCATION INDICATED. REFER TO FLOOR PLANS FOR CARD READER DESIGNATION. PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT CARD READER SURFACE MOUNTED ON MULLION.
CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MANUFACTURER. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, NURSE CALL CANCEL STATIONS, INTRUSION DETECTION KEYPADS, WANDER PREVENTION KEYPADS, AND INFANT PROTECTION KEYPADS. REFER TO ACCESS CONTROL
SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.
TYPE ‘KEYPAD’, COMBINATION KEYPAD PROXIMITY CARD READER:
PROVIDE COMBINATION KEYPAD PROXIMITY CARD READER PER SPECIFICATION.
DOOR OPERATOR PROVIDE 20A 120V LIFE SAFETY BRANCH DOOR OPERATOR. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE REQUIRED ROUGH-IN TO DOOR FRAME FOR PUSH PLATE OR HAND WAVE ACTUATOR CABLING WITH DOOR HARDWARE CONTRACTOR. INCLUDE INTERLOCKS WITH OTHER DOOR HARDWARE COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, ELECTRIC STRIKE, ELECTRIFIED HINGE, MAGNETIC LOCK, REQUEST TO EXIT, MOTION SAFETY CONTROLS, KEY SWITCH, AND POWER SUPPLY. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE ACCESS CONTROL, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR OPERATOR DISABLING UPON ALARM.
INTEGRATE DOOR OPERATOR WITH FIRE ALARM, ACCESS CONTROL, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO PUSH PLATE OR HAND WAVE ACTUATOR SYMBOL LEGEND DESCRIPTION FOR ADDITIONAL REQUIREMENTS. COORDINATE INSTALLATION WITH DOOR HARDWARE
CONTRACTOR.
ROUGH-IN ACCESS CONTROL
REQUEST TO EXIT PUSH
BUTTON
PROVIDE REQUEST TO EXIT PUSH BUTTON AT APPROXIMATE LOCATION INDICATED. PROVIDE ROUGH-IN AS INDICATED WITHIN ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT PUSH BUTTON SURFACE MOUNTED ON MULLION. CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MULLION MANUFACTURER. PUSH BUTTONS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL.
COORDINATE EXACT LOCATION OF PUSH BUTTON WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, CARD READERS. REFER TO ACCESS CONTROL SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.
SECURITY SURVEILLANCE
CAMERA - CEILING
GENERAL:
PROVIDE POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CAMERA TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR CAMERA DESIGNATION. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK AT LOCATION INDICATED. INSTALL CAMERA CENTERED IN CEILING TILE. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT MOUNTING LOCATION WITH OWNER
PRIOR TO INSTALLATION.
TYPE ‘ELEV’, ELEVATOR SECURITY SURVEILLANCE CAMERA:
PROVIDE SECURITY SURVEILLANCE CAMERA WITHIN ELEVATOR CAB INDICATED ON FLOOR PLANS. COORDINATE EXACT MOUNTING LOCATION WITHIN CAB WITH OWNER. COORDINATE ROUGH-IN, CABLING, AND INSTALLATION
REQUIREMENTS WITH FINAL SELECTED ELEVATOR MANUFACTURER.
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
DISCONNECT SWITCH
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
MOTOR
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD/SWITCHGEAR
TRANSFORMER
Revisions: Date:
OFFICE 3
1W115
C
STORAGE
CC C
20'
C C
C
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST
REMAIN. REFER TO FLOORPLANS FOR INDICATION OF DEMOLITION TYPE FOR EACH AREA:
a. SELECTIVE DEMOLITIONS AREAS:
• PROVIDE DEMOLITION FOR ITEMS AS SHOWN. EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF
DEMOLITION SHALL REMAIN UNLESS OTHERWISE INDICATED.
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED
ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE
CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND
IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE BOXES ARE NOT REUSED. REMOVE CONCRETE EQUIPMENT PADS THAT REMAIN, TO BE FLUSH
WITH FLOOR/GRADE.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE
CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT BECOME INACCESSIBLE DUE
TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING
AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND
FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS. SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL TIMES.
L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH
ADJACENT SURFACE.
M. ALL UNLABELED ELECTRICAL DEVICES WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE SHALL BE CIRCUIT TRACED AS NEEDED WITH A
LABEL PROVIDED.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES: 13
D
E
B
A
EE
E E
E
E
D
B
A
E E
E E
E
E
LOBBY
C2W2A
B
A
EE
E E
E
E
CORRIDOR
3W200C
B
A
E E
EE
E
E
CORRIDOR
C4W3
B
A
EE
E E
E
E
CORRIDOR
C5W3
13 14
B
A
E E
E E
TELE
6W145
CORRIDOR
C6W3
E
E
W6LS
E
E
E
ELEC
6W144
D
D
D
D
1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
03/26/2026
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r E le v a to r/
-1
.B
.M E
P .R
.r v t
/2
/2
:1
:5
P
M
ED100
FLOOR PLAN - ELECTRICAL
DEMOLITION
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
University Drive C Pittsburgh, PA 15240
646-24-100
03/26/2026 CGH EAH
22164.005
100% CONSTRUCTION
DOCUMENTS
SHEET NOTES:
1. DEMOLISH EXISTING WALL MOUNTED LIGHT FIXTURES AND INSTALL NEW LED WALL MOUNTED FIXTURES.
REFER TO FLOOR PLAN SHEET 01-EP200 FOR NEW FIXTURE LOCATIONS.
2. DEMOLISH EXISTING QUAD RECEPTACLE (DUPLEX GFCI AND DUPLEX NON-GFCI) IN SURFACE BOX. PROVIDE
NEW TWIST-LOCK RECEPTACLE FOR SUMP PUMP AND NEW DUPLEX GFCI RECEPTACLE. UTILIZE EXISTING
CIRCUIT AND BRANCH.
3. DEMOLISH EXISTING HEAT DETECTOR ON TOP OF HOISTWAY. HOISTWAY SHALL NOT INCLUDE ANY HEAT
DETECTORS IN THE TOP OR PIT.
1/4" = 1'-0"
GROUND FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
FIRST FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
SECOND FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
THIRD FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
FOURTH FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
FIFTH FLOOR - ELECTRICAL DEMOLITION
1/4" = 1'-0"
SIXTH FLOOR - ELECTRICAL DEMOLITION
N N
N N
N N N
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
1/4" = 1'-0"
BASEMENT FLOOR - ELECTRICAL - DEMOLITION
N
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
C
F
13 14 16
B
A
D
D
ELEV. LIGHTS
EE
E
E
E
DDD
D D D
W E
D
E
E
XFMR DISC.
D
(MS) SWBD
E
EXISTING EQDS
E
DSEM
E
EXISTING LSDS
E
E
E
E
E
D
D
MCEM
E
ELECTRICAL EQUIPMENT
7W-139C
ELEVATOR MACHINE ROOM
7W-139B
1300 Baxter Street, Suite 230 Charlotte, NC 28204 Phone: 704.348.3097
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
KEY PLAN :-
MOTT MACDONALD
ARCHITECTS PENN, P.C.
325 CHESTNUT STREET,
SUITE 300
PHILADELPHIA, PA 19016 U.S.A.
03/26/2026
A u to d e s k D o c s /2
.0
V A
P it ts b u rg h U p g ra d e B e d
T o w e r E le v a to r/
-1
.B
.M E
P .R
.r v t
/2
/2
:1
:5
P
M
ED101
FLOOR PLAN - ELECTRICAL
DEMOLITION
VA PITTSBURGH UPGRADE BED
TOWER ELEVATORS
University Drive C Pittsburgh, PA 15240
646-24-100
03/26/2026 CGH EAH
22164.005
100% CONSTRUCTION
DOCUMENTS
1/2" = 1'-0"
SEVENTH FLOOR - ELECTRICAL DEMOLITION
N
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
SHEET NOTES:
1. DEMOLISH EXISTING ELEVATOR DISCONNECT SWITCH AND
INSTALL NEW FUSED 150A DISCONNECT IN THE SAME
LOCATION.
2. DEMOLISH EXISTING SHUNT TRIP DEVICE. NEW ELEVATOR
DISCONNECTS SHALL INCLUDE INTEGRAL SHUNT TRIP.
3. DEMOLISH EXISTING CONTROLLERS AND UTILIZE EXISTING
CIRCUITS TO FEED NEW CONTROLLERS.
OFFICE 3
1W115
C
STORAGE
CCC
C
J
J
J
C
20'
C C
C
A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS FOR ALL DEVICES. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL INTERIOR ELEVATIONS, SYMBOL LEGENDS, AND TYPICAL ELECTRICAL DEVICE MOUNTING HEIGHTS DETAIL. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, SYMBOL LEGENDS, OR DETAILS, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH
ARCHITECTURAL DRAWINGS TO ENSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE
ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND
CONDUITS WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, COORDINATE WORK TO INSTALL
PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.
C. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR
REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.
D. GFCI TYPE…
This is the start of the file's text. The full file is on GovTribe.