Attach G 437-23-105 100 CD Drawings Vol 2 - Fargo-Replace Fire Alarm System.pdf

PDF 16 MB Posted

Attached to
Y1DA--437-23-105 Replace Fire Alarm System 437-26-1-6690-0001
Solicitation number
36C26326B0004
Issued by

About this file

These construction documents detail a comprehensive fire alarm system replacement project for Buildings 1-9, 46, 10-13, 40, 51-52, 56-57 at the VA Medical Center in Fargo, North Dakota. The project involves completely removing existing fire alarm panels, controllers, devices, conduits, and wiring across multiple buildings and floor levels, including basements, first through fourth floors, penthouses, and additions. The demolition plans specify precise removal procedures, including:

Key requirements include maintaining full fire alarm system functionality during construction, ensuring no interruption of existing safety systems, and completing comprehensive testing before final demolition. The project is fully sprinklered, involves multiple building sections with detailed floor plans, and is scheduled for completion by June 12, 2025. The consulting firm Fourrent Design Inc. prepared the construction documents for the VA Office of Construction and Facilities Management, with Todd Dalzell as the primary point of contact.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTTTTTTTT

TT TT

TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT

5 5

N

5 4

4 4

AHU-82

AHU-40

MDAC-15

DACU 6

DACU-5

MDAC-4

AHU-83 AHU-84

AHU-61

AHU-81

AHU-65AHU-66

EXISTING NAC PANEL TO BE

REMOVED IN IT'S ENTIRETY

EXISTING FIRE

SUPPRESSION

CONTROL PANEL

TO REMAIN

EXISTING FIRE ALARM PRE-ACTION

PANEL TO BE REMOVED IN IT'S

ENTIRETY

SECTION

0A

SECTION

0C

SECTION

0D

SECTION

0E

SECTION

0B

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-100

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 21 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

BASEMENT FIRE ALARM DEMOLITION PLAN - SECTION 0A

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

BASEMENT FIRE ALARM

DEMO PLAN - SECTION 0A

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

MATCH LINE - SHEET FAD-102

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

MATCH LINE - SHEET FAD-102

TT

TT TT

TT

TT

TT

TTTT

TT

TT

TTTT

TT

TT

TT TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TTTTTT

TTTTTTTT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT

1 1

5 4

MDAC-16

AHU-15

AHU-16

AHU-82

MDAC-4

MDAC-3

EXISTING FIRE

SUPPRESSION

CONTROL PANEL

TO REMAIN

EXISTING FIRE

SUPPRESSION

CONTROL PANEL TO

REMAIN.

SECTION

0A

SECTION

0C

SECTION

0D

SECTION

0E

SECTION

0B

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

BASEMENT FIRE ALARM DEMOTION PLAN - SECTION 0B

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

BASEMENT FIRE ALARM

DEMO PLAN - SECTION 0B

MATCH LINE - SHEET FAD-103

MATCH LINE - SHEET FAD-103

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

TT TT TT TT

TTTT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTTTTTTTT

TT

TT

TT TT

TT

TT

TTTT

TT TT TT TT TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT

TT

TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTTTT

TTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TT

TT

TT

N

5 54 4

T

T

AHU-1

EXISTING BASEMENT FIRE

ALARM TRANSPONDER

FATC-(E)0B

EXISTING BASEMENT FIRE

ALARM TRANSPONDER

FATC-(E)0A

HALLWAY CONNECTING TO UND BUILDING.

REFER TO OVERALL SITE MAP ON SHEET

E-001 FOR LOCATION OF EXISTING FACP IN

UND BUILDING.

SECTION

0A

SECTION

0C

SECTION

0D

SECTION

0E

SECTION

0B

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-102

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

BASEMENT FIRE ALARM DEMOLITION PLAN - SECTION 0C SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

BASEMENT FIRE ALARM

DEMO PLAN - SECTION 0C

MATCH LINE - SHEET FAD-100

MATCH LINE - SHEET FAD-100

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

TT

TT

TT TT TT

TTTTTTTTTTTTTTTT

TT

TT

TTTTTTTT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

TTTTTTTT

TT

TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TT

TT

TT

TTTTTT

TTTTTTTTTTTT

TT

TT TT TT TT TT

A

FAD-103

AHU-1 AHU-2

MDAC-16

AHU-48

EXISTING PANEL ANN-(E)B1 TO BE

REMOVED IN ITS ENTIRETY.

M

SECTION

0A

SECTION

0C

SECTION

0D

SECTION

0E

SECTION

0B

5 4

AHU-17

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-103

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

BASEMENT FIRE ALARM DEMOTION PLAN - SECTION 0D

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

BASEMENT FIRE ALARM

DEMO PLAN - SECTION 0D

2 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

SUB-BASEMENT FIRE ALARM DEMOTION PLAN

MATCH LINE - SHEET FAD-104 MATCH LINE - SHEET FAD-104

MATCH LINE - SHEET FAD-101

MATCH LINE - SHEET FAD-101

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

TT TT TT

TT

TT

TT

TTTTTT

TT

TT

TT

TT

TTTTTTTTTTTT

TT

TTTTTTTT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TT

5 5

4 4

AHU-78

AHU-76

AHU-77

SECTION

0A

SECTION

0C

SECTION

0D

SECTION

0E

SECTION

0B

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

BASEMENT FIRE ALARM DEMOLITION PLAN - SECTION 0E

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

BASEMENT FIRE ALARM

DEMO PLAN - SECTION 0E

MATCH LINE - SHEET FAD-103 MATCH LINE - SHEET FAD-103

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T TTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

T T

T

TTTTTT

T T

T

T T

T

TTTTTTT

T T

T T

T T

TTTTTT

T T

T T T T T T

T T

T

T T

T T

TTTT

T T T T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT

TT

TT TT

TT

TT

TT

TT

TTTTTTTT

TT

TT

TT

TTTTTTTTTTTTTTTT

TTTTT

T

T T

T T T T T T T

T T

TTTTTTTT

TT

TT TT TT TT

TT

TTTTTT

TT

TT

TT TT TT

TT

TT

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T

T

T

T T T T T

T T T T T T T

T T

T T

T

TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT

TT

TTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TT

TT TT TT

TT

TT TT TT TT TT TT

TT

TT

TT

TT

TT

TT

TTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTT

TTTTTTTTTTTT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTTTT

TT

TTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

TTTTTTTT

TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

1 1

A

A

EXISTING FIRE ALARM

ANNUNCIATOR PANEL

ANN-(E)1C WITH

MICROPHONE TO BE

REMOVED IN IT'S

ENTIRETY

EXISTING FIRE ALARM QSC

MICROPHONE PUBLIC

ADDRESS PANEL TO BE

REMOVED IN IT'S ENTIRETY.

EXISTING FIRE ALARM

ANNUNCIATOR ANN-(E)1D PANEL

TO BE REMOVED IN IT'S ENTIRETY.

SECTION

1A

SECTION

1C

SECTION

1B

SECTION

1D

SECTION

1E

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-105

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 21 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

FIRST FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 1A

1,9,46

SCALE: NTS

BUILDING SECTION KEY PLAN

FIRST FLOOR FIRE ALARM

DEMO PLAN - SECTION 1A

MATCH LINE - SHEET FAD-107

MATCH LINE - SHEET FAD-107

MATCH LINE - SHEET FAD-107

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

SECTION

1A

SECTION

1C

SECTION

1B

SECTION

1D

SECTION

1E

TT

TT

TT

TT

TT

TT

TT

TT

TTTTT

T

T T

T T T T T T T

T T

TTTTTTTT

TT

TT TT TT TT

TT

TTTTTT

TT

TT

TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

T T

T T T

T T

TTT

TT

TT

TT

TTTTTT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTTTTTTTT

TT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TTTTTT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTT

TTTTTTT

T T

T T

T T

T T

T T

T T

T T T T T T T T T T T

T T

T T

T T

T T

T T

T T

T T

T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TT

TT

TTTTTT

TT

TT

TT

TT

TT

TT

TT

TT TT TT

TT

TT TT

TT

TT

TT

TT

TT

TT

A

A

C

C

C

AHU-46

EXISTING FIRE ALARM

CONTROL PANELS FACP-(E)1A,

FACP-(E)1B, FACP-(E)1C TO BE

REMOVED IN THEIR ENTIRETY.

EXISTING BATTERY

CABINET TO BE REMOVED

IN ITS ENTIRETY.

LOCATION OF EXISTING MAIN FIRE ALARM CONTROL

PANELS AND COMMAND CENTER WORKSTATION FOR

ENTIRE CAMPUS. ALL FIRE ALARM PANELS, CABINETS

AND DEVICES TO BE REMOVED IN THEIR ENTIRETY. NOTE

THAT THE EXISTING COMMAND CENTER MUST REMAIN IN

PLACE AND BE FULLY FUNCTIONAL UNTIL THE NEW FIRE

ALARM SYSTEM IS COMPLETE AND FULLY FUNCTIONAL.

EXISTING FIRE ALARM

ANNUNCIATOR PANEL

ANN-(E)1C WITH

MICROPHONE TO BE

REMOVED IN IT'S

ENTIRETY

LOCATION OF EXISTING

FIRE ALARM COMMAND

CENTER WORK STATION.

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-106

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 21 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

FIRST FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 1B SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,461,9,46

FIRST FLOOR FIRE ALARM

PLAN - SECTION 1B

MATCH LINE - SHEET FAD-108

MATCH LINE - SHEET FAD-108

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

SECTION

1C

SECTION

1B

SECTION

1D

SECTION

1E

T T

T T

T T

T T

T T

T T

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TTTTT

T

T T

T T T T T T T

T T

TTTTTTTT

TT

TT TT TT TT

TT

TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TTTTTTTTTTTT

TT TT TT TT

TT

TTTTTT

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

T

T T T T T

T T T T T T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

TTTTTTTTTTTTTTTTTTTTTTTTTTTT

T

TTT

TT

TT

TT

TT

TT

TTTTTT

TTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT

TTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT TT

TT

TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT

TT TT TT

TT

TT

TTTT

TT

TT

44 5

A

AHU-62

AHU-9

CONTROL PANELS FACP-(E)1A,

FACP-(E)1B, FACP-(E)1C TO BE

REMOVED IN THEIR ENTIRETY.

EXISTING FIRE ALARM

ANNUNCIATOR PANEL ANN-(E)1B

TO BE REMOVED IN IT'S ENTIRETY

EXISTING FIRE ALARM

ANNUNCATOR PANEL ANN-(E)1A

TO BE REMOVED IN IT'S ENTIRETY

LOCATION OF EXISTING

FIRE ALARM COMMAND

CENTER WORK STATION.

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-107

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

FIRST FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 1C SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

FIRST FLOOR FIRE ALARM

DEMO PLAN - SECTION 1C

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

MATCH LINE - SHEET FAD-105

MATCH LINE - SHEET FAD-105

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

SECTION

1C

SECTION

1B

SECTION

1D

SECTION

1E

TTTTTT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TTTTTT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTT

TT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

TTTTTTTT

TTTTTT

TT

TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTTTT

T T

T

T T T

T T

T

TTTTTT

T T

T T

T T

T

T T T T T T

T T

T

TT

TT

TT

TT

TT TT TT

TTTTTTTTTTTTTTTT

TT

TT

T T T T

T T

T T

T

TTTT

T T

T T

T

TTTTTTTT

TT

TT TT TT TT TT TT

T T

T T T T T T T T T T T

T T

T

T T T T T

T T

T T

T T

TTTTTTTT

T

T T

T T

T T

T T T T T 1

3 2

A

C

C

C

AHU-9

EXISTING FIRE ALARM

CONTROL PANELS FACP-(E)1A,

FACP-(E)1B, FACP-(E)1C TO BE

REMOVED IN THEIR ENTIRETY.

EXISTING BATTERY

CABINET TO BE REMOVED

IN ITS ENTIRETY.

PANELS AND COMMAND CENTER WORKSTATION FOR

ENTIRE CAMPUS. ALL FIRE ALARM PANELS, CABINETS

AND DEVICES TO BE REMOVED IN THEIR ENTIRETY. NOTE

THAT THE EXISTING COMMAND CENTER MUST REMAIN IN

PLACE AND BE FULLY FUNCTIONAL UNTIL THE NEW FIRE

ALARM SYSTEM IS COMPLETE AND FULLY FUNCTIONAL.

EXISTING FIRE ALARM

ANNUNCATOR PANEL ANN-(E)1A

TO BE REMOVED IN IT'S ENTIRETY

LOCATION OF EXISTING

FIRE ALARM COMMAND

CENTER WORK STATION.

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-108

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

FIRST FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 1D

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

FIRST FLOOR FIRE ALARM

DEMO PLAN - SECTION 1D

MATCH LINE - SHEET FAD-106

MATCH LINE - SHEET FAD-106

MATCH LINE - SHEET FAD-109 MATCH LINE - SHEET FAD-109

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

SECTION

1C

SECTION

1B

SECTION

1D

SECTION

1E

T T T T

T T

T

TT

TT

TT

TT

TT

TTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TTTTTT

TT

TT

TT

TT TT TT

TT TT TT TT TT TT TT

TT

TT

TT

TT TT TT TT

TT

TT

TT

TTTTTTTT

TT

TT

TT

TT

TT

TT

TT

TTTTTTTT

T T

T

TTT

T T

T

T T T

T T T T

T T

TTTT

T

T T

TT

T T

T

T T

TTTTTTT

T

T

T T T T T T

T T T T T T T T

T T

T T

T T

TTTTTT

TTTTTT

T

T T

T

T T T T T T

T T

TTTTT

T T

T T T T T

1 1

1 1

3 2

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-109

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

FIRST FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 1E

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

FIRST FLOOR FIRE ALARM

DEMO PLAN - SECTION 1E

MATCH LINE - SHEET FAD-108

2B

SECTION

2E

SECTION

2D

SECTION

2A

SECTION

2C

T T

T T

T T

T

TTTT

T T

T T T T

TT

TT

TTTTT

T

T T

T T

T T

T T

T T T T T

T T

TTT

TTTTTT

T T

T T

T

T T T T T T T T

T T

T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TTTT

T

T

T T TTTT

TTTTTTTTTTTT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT

TT

TTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TTTTTTTT

T T

T

T T T T T T T

T T

T

T

TTTTTT

T T

T

T T T T T T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

T T

T T

T T

T

TTTT

T T

T T

T T

T T

N

EXISTING NAC PANEL

TO BE REMOVED IN

ITS ENTIRETY.

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-110

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

SECOND FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 2A

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

SECOND FLOOR FIRE ALARM

DEMO PLAN - SECTION 2A

MATCH LINE - SHEET FAD-112

MATCH LINE - SHEET FAD-112

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

SECTION

2E

SECTION

2D

SECTION

2A

SECTION

2C

TT

TT

TTTTT

T

T T

T T

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT

TTTTTT

TT

TT

TT

TT

TT

TT

TT

TT

TTTTTTTT

T T

T

T T T T T T T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

T T

T T

T T

T

T T T T

T T

T T

T T

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT

TT TT TT

TT

TT

TT

TTTT

N

T T

EXISTING 2ND FLOOR

TRANSPONDERS TO BE

REMOVED IN THEIR

ENTIRETY.

EXISTING NAC PANEL

TO BE REMOVED IN

ITS ENTIRETY.

AHU-25 IS LOCATED ON

ROOF. RELAYS AND

SMOKE DETECTORS

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO REMAIN.

EXISTING MONITORING MODULE FOR FLOW SWITCH TO

BE REMOVED. DEMOLITION OF EXISTING MODULE NOT

TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FLOW SWITCH TO REMAIN.

EXISTING FAN RELAY MONITORING MODULE TO BE

REMOVED. DEMOLITION OF EXISTING MODULE NOT TO

BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING FAN RELAY TO REMAIN.

EXISTING DUCT SMOKE DETECTOR AND MONITORING

MODULE TO BE REMOVED AND REPLACED. DEMOLITION

OF EXISTING EQUIPMENT SHALL NOT BE PERFORMED

UNTIL NEW EQUIPMENT IS OPERATIONAL.

KEYED FIRE ALARM DEMOLITION NOTES

ALL EXISTING FIRE ALARM PANELS, CONTROLLERS, AND

DEVICES, ALONG WITH ALL ASSOCIATED CONDUIT AND

WIRING ARE TO BE REMOVED IN THEIR ENTIRETY.

AFTER REMOVAL, WALLS ARE TO BE PATCHED AND

PAINTED TO MATCH EXISTING CONDITIONS.

EXISTING FIRE ALARM SYSTEM MUST REMAIN IN PLACE

AND BE FULLY FUNCTIONAL AT ALL TIMES DURING

CONSTRUCTION OF NEW FIRE ALARM SYSTEM.

NO DEMOLITION OF EXISTING FIRE ALARM SYSTEMS IS TO

OCCUR UNTIL NEW FIRE ALARM SYSTEM IS COMPLETE,

COMPREHENSIVELY TESTED AND COMMISSIONED.

GENERAL FIRE ALARM DEMOLITION NOTE

SYMBOL DESCRIPTION

FIRE ALARM LEGEND - EXISTING

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM AUDIO DEVICE W/ STROBE - WALL

MAGNETIC DOOR HOLDER

FIRE SPRINKLER FLOW SWITCH

DUCT MOUNTED SMOKE DETECTOR

ALARM, SIGNAL LIGHT, STROBE - WALL MOUNT

SMOKE DETECTOR FOR ELEVATOR RECALL

FIRE ALARM CONTROL PANEL

FIRE ALARM AUDIO DEVICE

FIRE ALARM ANNUNCIATOR PANEL

TAMPER SWITCH

FAN SHUT-DOWN RELAY

FIRE ALARM BELL

CONTROL MODULE

RELAY

INDICATOR ADDRESSABLE MODULE

INTEGRAL MAGNETIC DOOR HOLDER

HEAT SENSOR

EXTERIOR WEATHER-PROOF FIRE ALARM

AUDIO DEVICE W/ STROBE

PHOTOELECTRIC SMOKE DETECTOR AND BASE

FIRE ALARM AUDIO DEVICE W/ STROBE - CEILING

CLG

FIRE ALARM TRANSPONDER CABINET

C

T

A

NOTIFICATION APPLIANCE CIRCUIT EXTENDERN

SMOKE BARRIER

1 HOUR FIRE RATED PARTITION

2 HOUR FIRE RATED PARTITION

RATED WALL LINE TYPE LEGEND

TT TT TT TT TT TT TT TT TT TT

T T T T T T

FAD-111

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FARGO REPLACE FIRE

ALARM SYSTEM

437-23-105

Project Director

06/12/2025 WEW JMSRevisions: Date:

2101 ELM STREET, FARGO, ND 58102

VERITAS FIRE ENGINEERING, INC.

12364 WEST ALAMEDA PARKWAY, SUITE 135

LAKEWOOD, COLORADO 80228

PH: (303) 985-3300FIRE ENGINEERING, INC.

www.veritasfire.com

TODD DALZELL517 7TH STREET

RAPID CITY, SD 57701

PH: (605) 342-9470

POC: JARED LOTT

FFD PROJECT NO:

23.2730.M01 Dwg. of 91

VOLUME OF 2

1 SCALE: 1/8" = 1'

BUILDINGS 1,9 & 46

SECOND FLOOR FIRE ALARM DEMOLITION PLAN - SECTION 2B

SCALE: NTS

BUILDING SECTION KEY PLAN

1,9,46

SECOND FLOOR FIRE ALARM

DEMO PLAN - SECTION 2B

MATCH LINE - SHEET FAD-113

MATCH LINE - SHEET FAD-113

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

M

AT

C H

L

IN

E

- S

H

EE

T

FA

D -1

MATCH LINE - SHEET FAD-112

SECTION

2E

SECTION

2D

SECTION

2A

SECTION

2C

T T

T T

T T

T T

TTTTTTT

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T

T T T T

T T

T T T

T T

T T

T T

T

TTT

TT TT

TT

TT

TTTT

TT

TT

T T

T T

T T

T T

T T T T T T T T T T T T T

T T

T T

T T

TTTTTTTTTTT

TT TT TT

TT

TTTT

TT

TT

TT

TT

TT

TT

TTTT

TT

TTTTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

T T

T T

T T

T

T T T T T T

T T

T

T T

T T

T

TTTTTTTTTTT

T

T T

T

TT

TT

TT

TT

TTTTTTTTTTTTTTTT

TT

TT

TT

TT

TT

TTTTTT

TTTTTTTTTT

TT

TT

TT

TT

TT TT TT TT TT

TT

TT

TT

TT

TT TT TT TT TT TT TT TT TT TT TT

TT

TT

TT

TT

TTTTTTTTTTTTTTTTTTTTTT

TTTTTT

T T

T T

T T

T T

TTT

T T

T

T T T

T T

T

T

TTTTTT

T T

T

T T T T T T

AHU-67

EXISTING CONTROL RELAY MODULE FOR MAGNETIC

DOOR HOLD TO BE REMOVED. DEMOLITION OF

EXISTING MODULE NOT TO BE PERFORMED UNTIL

SWITCHOVER TO NEW CONTROL MODULE AND NEW

FIRE ALARM SYSTEM IS COMPLETE. EXISTING

ELECTRONIC DOOR HOLD DEVICE TO REMAIN.

EXISTING MONITORING MODULE FOR TAMPER SWITCH

TO BE REMOVED. DEMOLITION OF EXISTING MODULE

NOT TO BE PERFORMED UNTIL SWITCHOVER TO NEW

MONITORING MODULE AND NEW FIRE ALARM SYSTEM

IS COMPLETE. EXISTING TAMPER SWITCH TO…