Attach 4 - Appendix A NIST- Site Wide Counts 8-2025.xls
XLS spreadsheet 1 MB Posted
- Solicitation number
- 1333ND26QNB190185
About this file
This is a Fire Alarm System Inspection Report appendix containing comprehensive device count documentation for the NIST Boulder/Fort Collins Sites as of August 2025. The report details fire alarm system infrastructure across multiple buildings at the NIST facility, providing an itemized inventory of all fire protection equipment and components organized by building and node designation.
The site-wide summary indicates a total of 6,482 devices across the Boulder/Fort Collins location, including 49 fire panels/workstations/DVCs, 14 releasing panels (Sapphire/FM200), 127 power supplies, 23 CO2 releasing panels, 40 Signaling Line Circuits (SLCs), and 8 Intelligent Device Circuits (IDCs). Alarm initiating devices total 3,073 units, consisting primarily of 1,365 photo smoke detectors, 300 manual pull stations, 77 flow switches, 63 heat detectors, 46 gas detection interfaces, and additional specialized detectors. Alarm notification appliances include 359 speakers, 188 strobes, 143 horn/strobes, and 60 horns. The inventory also encompasses 1,352 speaker/strobes, 422 relays/control modules, 291 trouble monitors, 147 duct detectors, 139 Vesda alert/action devices, and 121 tamper switches/valves. Battery backup systems total 403 units across various amp-hour ratings (7 AH through 110 AH). Individual building reports provide granular breakdowns for Buildings 1, 2, 3, 4/5/3A/111, 8/11/12, 21-27, 42/CUP/9/Tunnel, 81 (Main and Cleanroom sections), 92, WWV, and WWVB, with each building section specifying panel types, circuit configurations, device distribution by circuit, and battery allocations to support inspection, testing, maintenance, and repair coordination services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1333ND26QNB190185.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Boulder - Ft. Collins Site
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Boulder / Fort Collins Sites, Total Device Count 8-2025 | ||||||
| Total # of Fire Panels/WS/DVC | 49 | Total # of Releasing- Sapphire / FM200 | 14 | |||
| Total # of Power Supplies | 127 | Total # of Releasing Panels- CO2 | 23 | |||
| Total Number of SLC's | 40 | |||||
| Total Number of IDC's | 8 | |||||
| Total Number Of Notification Circuits on Entire System | 436 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 300 | 7 AH | 114 | |||
| I-Quad Smoke Acclimate Det. | 34 | 12 AH | 87 | |||
| Photo Smoke Detector | 1365 | 18 AH | 14 | |||
| Heat Detector | 63 | 26 AH | 14 | |||
| Laser Detector | 5 | 35 AH | 10 | |||
| Flow Switch | 77 | 55 AH | 16 | |||
| Flame Detector | 36 | 75 AH | 2 | |||
| Beam Smoke Detector | 5 | |||||
| Gas Detection Interface | 46 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 1 | Device type | Quantity | |||
| AirSense | 4 | Horns | 3 | |||
| Vesda Fire 1 / 2 | 143 | Horn/Strobe | 60 | |||
| Releasing / Solenoid | 48 | Strobe | 188 | |||
| Speakers | 359 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 1352 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 121 | Panic/Strobe | 34 | |||
| Duct Detectors | 147 | Bells | 0 | |||
| Low Air Switch | 7 | Outside Horn/ Strobes | 32 | |||
| AirSense | 4 | |||||
| Vesda Alert/Action | 139 | |||||
| Releasing | 29 | |||||
| Fume Hood Panic | 32 | |||||
| AED | 31 | Panel Types | ||||
| Security Door | 18 | Device type | Quantity | |||
| Fire Pump | 1 | Workstation | 3 | |||
| NCA | 2 | |||||
| NFS2-3030 | 11 | |||||
| NFS2-640 | 11 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 3 | ||||
| Device Type | Quantity | DVC | 21 | |||
| Relays/Control Modules | 422 | LCD-160 | 2 | |||
| Trouble Monitors | 291 | LCD-80 | 4 | |||
| Non-Fire Modules | 67 | |||||
| Liquid Level | 2 | Batteries Continued | ||||
| Air Flow | 2 | APC- RBC | 3 | |||
| Totals From Above= | 6482 |
B-1 Totals
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Total Device Count 8-2025 | ||||||||
| Nodes: 1, 2, 3, 4, 13, 15, 16, 17, 20, 101, 102, 103, 104, 105, 113, 115, 116 | ||||||||
| Total # of Fire Panels/WS/DVC | 18 | Total # of Releasing Panels- Sapphire | 2 | |||||
| Total # of Power Supplies | 27 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 14 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 136 | |||||||
| Alarm Initiating Devices/Points ** | Batteries ** | |||||||
| Device type | Quantity | Size | Quantity | |||||
| Manual Pull Station | 86 | 7 AH | 38 | |||||
| Fire/CO Multi-Criteria Detector | 16 | 12 AH | 2 | |||||
| Photo Smoke Detector | 680 | 18 AH | 2 | |||||
| Heat Detector | 11 | 26 AH | 2 | |||||
| Laser Detector | 5 | 35 AH | 0 | |||||
| Flow Switch | 22 | 55 AH | 14 | |||||
| Flame Detector | 0 | 75 AH | 2 | |||||
| Beam Smoke Detector | 3 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances ** | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 4 | Horns | 0 | |||||
| Vesda | 1 | Horn/Strobe | 0 | |||||
| Releasing / Solenoid | 5 | Strobe | 50 | |||||
| Speakers | 272 | |||||||
| Supervisory Initiating Devices/Points ** | Speaker/Strobes | 750 | ||||||
| Device Type | Quantity | Chime | 0 | |||||
| Tamper Switch/Valves | 36 | Panic/Strobe | 13 | |||||
| Duct Detectors | 57 | Bells | 0 | |||||
| Low Air Switch | 3 | Outside Horn/ Strobes | 7 | |||||
| AirSense | 4 | |||||||
| Vesda Alert/Action | 1 | Panel Types | ||||||
| Releasing | 2 | Device type | Quantity | |||||
| Fume Hood Panic | 9 | Workstation | 1 | |||||
| AED | 11 | NCA | 1 | |||||
| Security Door | 7 | NFS2-3030 | 7 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points ** | NFS-320 | 0 | ||||||
| Device Type | Quantity | DVC | 8 | |||||
| Relays/Control Modules | 142 | LCD-160 | 1 | |||||
| Trouble Monitors | 52 | LCD-80 | 0 | |||||
| Non-Fire Modules | 16 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 1343 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 1, 101, 17, 105 | ||||||||
| Total # of Fire Panels/WS/DVC | 4 | Total # of Releasing Panels- Sapphire | 1 | |||||
| Total # of Power Supplies | 4 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 1 | |||||||
| Total Number of IDC's | ||||||||
| Total Number Of Notification Circuits on Entire System | 11 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Quantity | Size | Quantity | |||||
| Manual Pull Station | 14 | 7 AH | 4 | |||||
| Fire/CO MultiCriteria | 2 | 12 AH | 0 | |||||
| Fire/CO Multi-Criteria Detector | 82 | 18 AH | 0 | |||||
| Heat Detector | 7 | 26 AH | 0 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch | 2 | 55 AH | 4 | |||||
| Flame Detector | 0 | 110 AH | 0 | |||||
| Beam Smoke Detector | 3 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 0 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing / Solenoid | 1 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Quantity | Chime | ||||||
| Tamper Switch/Valves | 2 | Panic/Strobe | ||||||
| Duct Detectors | 9 | Bells | ||||||
| Low Air Switch | 0 | Outside Horn/ Strobes | ||||||
| AirSense | 0 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Releasing | 1 | Device type | Quantity | |||||
| Fume Hood Panic | 0 | Workstation | 1 | |||||
| AED | 2 | NCA | 1 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Quantity | DVC | 2 | |||||
| Relays/Control Modules | 12 | LCD-160 | 0 | |||||
| Trouble Monitors | 9 | LCD-80 | 0 | |||||
| Non-Fire Modules | 4 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 185 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 2, 102 | ||||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 1 | |||||
| Total # of Power Supplies | 6 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 4 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 28 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Totals | Size | Quantity | |||||
| Manual Pull Station | 26 | 7 AH | 10 | |||||
| Fire/CO Multi-Criteria Detector | 7 | 12 AH | 0 | |||||
| Photo Smoke Detector | 244 | 18 AH | 0 | |||||
| Heat Detector | 4 | 26 AH | 0 | |||||
| Laser Detector | 5 | 35 AH | ||||||
| Flow Switch | 8 | 55 AH | 2 | |||||
| Flame Detector | 0 | 110 AH | 0 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 1 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing / Solenoid | 3 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Totals | Chime | ||||||
| Tamper Switch/Valves | 9 | Panic/Strobe | ||||||
| Duct Detectors | 3 | Bells | ||||||
| Low Air Switch | 1 | Outside Horn/ Strobes | ||||||
| AirSense | 1 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Fire Pump | 1 | Device type | Quantity | |||||
| Fume Hood Panic | 4 | Workstation | 0 | |||||
| AED | 1 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Totals | DVC | 1 | |||||
| Relays/Control Modules | 38 | LCD-160 | 1 | |||||
| Trouble Monitors | 13 | LCD-80 | 0 | |||||
| Non-Fire Modules | 2 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 428 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 12-2020 | ||||||||
| Nodes: Node 2, 102 | ||||||||
| Alarm Initiating Devices/Points | ||||||||
| Device type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Manual Pull Station | 5 | 10 | 12 | 0 | ||||
| Fire/CO Multi-Criteria | 1 | 1 | 0 | |||||
| Photo Smoke Detector | 66 | 83 | 81 | 0 | ||||
| Heat Detector | 8 | 0 | 1 | 0 | ||||
| Laser Detector | 5 | 0 | 0 | 0 | ||||
| Flow Switch | 0 | 1 | 8 | 0 | ||||
| Flame Detector | 0 | 0 | 0 | 0 | ||||
| Beam Smoke Detector | 0 | 0 | 0 | 0 | ||||
| Gas Detection Interface | 0 | 0 | 0 | 0 | ||||
| Kitchen Hood/Ansul | 0 | 0 | 0 | 0 | ||||
| AirSense | 0 | 1 | 0 | 0 | ||||
| Vesda | 0 | 0 | 0 | 0 | ||||
| Releasing | & Soleniod | 1 | 1 | 0 | 0 | |||
| Supervisory Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Tamper Switch/Valves | 0 | 1 | 8 | 0 | ||||
| Duct Detectors | 1 | 0 | 2 | 0 | ||||
| Low Air Switch | 0 | 0 | 1 | 0 | ||||
| AirSense | 0 | 1 | 0 | 0 | ||||
| Vesda Alert/Action | 0 | 0 | 0 | 0 | ||||
| Releasing | 1 | 0 | 0 | 0 | ||||
| Fume Hood Panic | 0 | 1 | 4 | 0 | ||||
| AED | 1 | 0 | 0 | 0 | ||||
| Security Door | 1 | 0 | 0 | 0 | ||||
| Miscellaneous Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Relays/Control Modules | 21 | 8 | 9 | 0 | ||||
| Trouble Monitors | 1 | 2 | 10 | 0 | ||||
| Non-Fire Modules | 1 | 1 | 0 | 0 | ||||
| Liquid Level | 0 | 0 | 0 | 0 | ||||
| Air Flow | 0 | 0 | 0 | 0 | ||||
| NIST/Boulder - Building 1 - Page 4 of 11 | ||||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 3, 103 | ||||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||||
| Total # of Power Supplies | 3 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 4 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 30 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Totals | Size | Quantity | |||||
| Manual Pull Station | 13 | 7 AH | 6 | |||||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||||
| Photo Smoke Detector | 202 | 18 AH | 0 | |||||
| Heat Detector | 0 | 26 AH | 0 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch | 0 | 55 AH | 2 | |||||
| Flame Detector | 0 | 110 AH | 0 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 2 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing / Solenoid | 0 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Totals | Chime | ||||||
| Tamper Switch/Valves | 0 | Panic/Strobe | ||||||
| Duct Detectors | 0 | Bells | ||||||
| Low Air Switch | 0 | Outside Horn/ Strobes | ||||||
| AirSense | 2 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Fire Pump | 0 | Device type | Quantity | |||||
| Fume Hood Panic | 1 | Workstation | 0 | |||||
| AED | 1 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Totals | DVC | 1 | |||||
| Relays/Control Modules | 5 | LCD-160 | 0 | |||||
| Trouble Monitors | 10 | LCD-80 | 0 | |||||
| Non-Fire Modules | 0 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 286 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 12-2020 | ||||||||
| Nodes: Node 3, 103 | ||||||||
| Alarm Initiating Devices/Points | ||||||||
| Device type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Manual Pull Station | 4 | 0 | 8 | 0 | ||||
| Fire/CO MultiCriteria | 0 | 0 | 0 | |||||
| Photo Smoke Detector | 88 | 0 | 113 | 0 | ||||
| Heat Detector | 0 | 0 | 0 | 0 | ||||
| Laser Detector | 0 | 0 | 0 | 0 | ||||
| Flow Switch | 0 | 0 | 0 | 0 | ||||
| Flame Detector | 0 | 0 | 0 | 0 | ||||
| Beam Smoke Detector | 0 | 0 | 0 | 0 | ||||
| Gas Detection Interface | 0 | 0 | 0 | 0 | ||||
| Kitchen Hood/Ansul | 0 | 0 | 0 | 0 | ||||
| AirSense | 1 | 0 | 1 | 0 | ||||
| Vesda | 0 | 0 | 0 | 0 | ||||
| Releasing | 0 | 0 | 0 | 0 | ||||
| Supervisory Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Tamper Switch/Valves | 0 | 0 | 0 | 0 | ||||
| Duct Detectors | 0 | 0 | 0 | 0 | ||||
| Low Air Switch | 0 | 0 | 0 | 0 | ||||
| AirSense | 1 | 0 | 1 | 0 | ||||
| Vesda Alert/Action | 0 | 0 | 0 | 0 | ||||
| Releasing | 0 | 0 | 0 | 0 | ||||
| Fume Hood Panic | 0 | 0 | 1 | 0 | ||||
| AED | 1 | 0 | 0 | 0 | ||||
| Security Door | 1 | 0 | 0 | 0 | ||||
| Miscellaneous Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | SLC 4 | ||||
| Relays/Control Modules | 3 | 0 | 2 | 0 | ||||
| Trouble Monitors | 9 | 0 | 1 | 0 | ||||
| Non-Fire Modules | 0 | 0 | 0 | 0 | ||||
| Liquid Level | 0 | 0 | 0 | 0 | ||||
| Air Flow | 0 | 0 | 0 | 0 | ||||
| NIST/Boulder - Building 1 - Page 6 of 11 | ||||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 4, 104 | ||||||||
| Total # of Fire Panels/WS/DVC | 3 | Total # of Releasing Panels- Sapphire | 0 | |||||
| Total # of Power Supplies | 1 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 1 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 4 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Totals | Size | Quantity | |||||
| Manual Pull Station | 7 | 7 AH | 2 | |||||
| Fire/CO Multi-Criteria Detector | 7 | 12 AH | 0 | |||||
| Photo Smoke Detector | 115 | 18 AH | 0 | |||||
| Heat Detector | 0 | 26 AH | 0 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch | 2 | 55 AH | 2 | |||||
| Flame Detector | 0 | 110 AH | 0 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 1 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing / Solenoid | 0 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Totals | Chime | ||||||
| Tamper Switch/Valves | 4 | Panic/Strobe | ||||||
| Duct Detectors | 1 | Bells | ||||||
| Low Air Switch | 0 | Outside Horn/ Strobes | ||||||
| AirSense | 1 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Fire Pump | 0 | Device type | Quantity | |||||
| Fume Hood Panic | 0 | Workstation | 0 | |||||
| AED | 2 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Totals | DVC | 1 | |||||
| Relays/Control Modules | 9 | LCD-160 | 0 | |||||
| Trouble Monitors | 7 | LCD-80 | 0 | |||||
| Non-Fire Modules | 2 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 174 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 12-2020 | ||||||||
| Nodes: Node 4, 104 | ||||||||
| Alarm Initiating Devices/Points | ||||||||
| Device type | SLC 1 | |||||||
| Manual Pull Station | 7 | |||||||
| I-Quad Smoke Acclimate Det. | 7 | |||||||
| Photo Smoke Detector | 115 | |||||||
| Heat Detector | 0 | |||||||
| Laser Detector | 0 | |||||||
| Flow Switch | 2 | |||||||
| Flame Detector | 0 | |||||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | |||||||
| Kitchen Hood/Ansul | 0 | |||||||
| AirSense | 1 | |||||||
| Vesda | 0 | |||||||
| Releasing | 0 | |||||||
| Supervisory Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | |||||||
| Tamper Switch/Valves | 4 | |||||||
| Duct Detectors | 1 | |||||||
| Low Air Switch | 0 | |||||||
| AirSense | 1 | |||||||
| Vesda Alert/Action | 0 | |||||||
| Fire Pump | 0 | |||||||
| Fume Hood Panic | 0 | |||||||
| AED | 2 | |||||||
| Security Door | 1 | |||||||
| Miscellaneous Initiating Devices/Points | ||||||||
| Device Type | SLC 1 | |||||||
| Relays/Control Modules | 9 | |||||||
| Trouble Monitors | 7 | |||||||
| Non-Fire Modules | 2 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | |||||||
| NIST/Boulder - Building 1 - Page 8 of 11 | ||||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 13, 113 | ||||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||||
| Total # of Power Supplies | 2 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 1 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 15 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Quantity | Size | Quantity | |||||
| Manual Pull Station | 4 | 7 AH | 2 | |||||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||||
| Photo Smoke Detector | 3 | 18 AH | 0 | |||||
| Heat Detector | 0 | 26 AH | 2 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch | 4 | 55 AH | 0 | |||||
| Flame Detector | 0 | 75 AH | 2 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 0 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing / Solenoid | 0 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Quantity | Chime | ||||||
| Tamper Switch/Valves | 9 | Panic/Strobe | ||||||
| Duct Detectors | 16 | Bells | ||||||
| Low Air Switch | 1 | Outside Horn/ Strobes | ||||||
| AirSense | 0 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Fire Pump | 0 | Device type | Quantity | |||||
| Fume Hood Panic | 4 | Workstation | 0 | |||||
| AED | 0 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Quantity | DVC | 1 | |||||
| Relays/Control Modules | 17 | LCD-160 | 0 | |||||
| Trouble Monitors | 5 | LCD-80 | 0 | |||||
| Non-Fire Modules | 2 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 94 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 15, 115 | ||||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||||
| Total # of Power Supplies ** | 8 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's ** | 2 | |||||||
| Total Number of IDC's ** | 0 | |||||||
| Total Number Of Notification Circuits on Entire System ** | 36 | |||||||
| Alarm Initiating Devices/Points ** | Batteries | |||||||
| Device type | Quantity | Size | Quantity | |||||
| Manual Pull Station ** | 12 | 7 AH | 12 | |||||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||||
| Photo Smoke Detector ** | 30 | 18 AH | 2 | |||||
| Heat Detector | 0 | 26 AH | 0 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch ** | 3 | 55 AH | 2 | |||||
| Flame Detector | 0 | 75 AH | 0 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 0 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 0 | Horn/Strobe | ||||||
| Releasing | 0 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points ** | Speaker/Strobes | |||||||
| Device Type | Quantity | Chime | ||||||
| Tamper Switch/Valves ** | 4 | Panic/Strobe | ||||||
| Duct Detectors ** | 10 | Bells | ||||||
| Low Air Switch ** | 0 | Outside Horn/ Strobes | ||||||
| AirSense | 0 | |||||||
| Vesda Alert/Action | 0 | Panel Types | ||||||
| Fire Pump | 0 | Device type | Quantity | |||||
| Fume Hood Panic | 0 | Workstation | 0 | |||||
| AED | 5 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points ** | NFS-320 | 0 | ||||||
| Device Type | Quantity | DVC | 1 | |||||
| Relays/Control Modules ** | 36 | LCD-160 | 0 | |||||
| Trouble Monitors ** | 5 | LCD-80 | 0 | |||||
| Non-Fire Modules ** | 4 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 176 | |||||
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||||
| NIST Bldg. 1, Device Count 8-2025 | ||||||||
| Nodes: Node 16, 116 | ||||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||||
| Total # of Power Supplies | 3 | Total # of Releasing Panels- CO2 | 0 | |||||
| Total Number of SLC's | 1 | |||||||
| Total Number of IDC's | 0 | |||||||
| Total Number Of Notification Circuits on Entire System | 12 | |||||||
| Alarm Initiating Devices/Points | Batteries | |||||||
| Device type | Quantity | Size | Quantity | |||||
| Manual Pull Station | 10 | 7 AH | 2 | |||||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 2 | |||||
| Photo Smoke Detector | 4 | 18 AH | 0 | |||||
| Heat Detector | 0 | 26 AH | 0 | |||||
| Laser Detector | 0 | 35 AH | 0 | |||||
| Flow Switch | 3 | 55 AH | 0 | |||||
| Flame Detector | 0 | 75 AH | 2 | |||||
| Beam Smoke Detector | 0 | |||||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||||
| AirSense | 0 | Horns | See Total Device Count Building 1 - Page 1 of 10 | |||||
| Vesda | 1 | Horn/Strobe | ||||||
| Releasing / Solenoid | 1 | Strobe | ||||||
| Speakers | ||||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | |||||||
| Device Type | Quantity | Chime | ||||||
| Tamper Switch/Valves | 8 | Panic/Strobe | ||||||
| Duct Detectors | 18 | Bells | ||||||
| Low Air Switch | 1 | Outside Horn/ Strobes | ||||||
| AirSense | 0 | |||||||
| Vesda Alert/Action | 1 | Panel Types | ||||||
| Fire Pump | 0 | Device type | Quantity | |||||
| Fume Hood Panic | 0 | Workstation | 0 | |||||
| AED | 0 | NCA | 0 | |||||
| Security Door | 1 | NFS2-3030 | 1 | |||||
| NFS2-640 | 0 | |||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||||
| Device Type | Quantity | DVC | 1 | |||||
| Relays/Control Modules | 25 | LCD-160 | 0 | |||||
| Trouble Monitors | 3 | LCD-80 | 0 | |||||
| Non-Fire Modules | 2 | |||||||
| Liquid Level | 0 | |||||||
| Air Flow | 0 | Totals From Above= | 104 |
&C&F
B-2 Node 5
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 2, Device Count 8-2025 | |||||||
| Nodes: 5, 55 | |||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | ||||
| Total # of Power Supplies | 4 | Total # of Releasing Panels- CO2 | 0 | ||||
| Total Number of SLC's | 2 | ||||||
| Total Number of IDC's | 0 | ||||||
| Total Number Of Notification Circuits on Entire System | 32 | ||||||
| Alarm Initiating Devices/Points | Batteries | ||||||
| Device type | SLC 1 | SLC 2 | Total | Size | Quantity | ||
| Manual Pull Station | 15 | 15 | 30 | 7 AH | 8 | ||
| Fire/CO Multi-Criteria Detector | 0 | 1 | 1 | 12 AH | 0 | ||
| Photo Smoke Detector | 121 | 147 | 268 | 18 AH | 0 | ||
| Heat Detector | 10 | 0 | 10 | 26 AH | 2 | ||
| Laser Detector | 0 | 0 | 0 | 35 AH | 0 | ||
| Flow Switch | 3 | 6 | 9 | 55 AH | 0 | ||
| Flame Detector | 0 | 0 | 0 | 110 AH | 0 | ||
| Beam Smoke Detector | 0 | 2 | 2 | ||||
| Gas Detection Interface | 0 | 0 | 0 | Alarm Notification Appliances | |||
| Kitchen Hood/Ansul | 0 | 0 | 0 | Device type | Quantity | ||
| AirSense | 0 | 0 | 0 | Horns | 0 | ||
| Vesda | 0 | 0 | 0 | Horn/Strobe | 0 | ||
| Releasing / Solenoid | 0 | 0 | 0 | Strobe | 8 | ||
| Speakers | 9 | ||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 49 | |||||
| Device Type | SLC 1 | SLC 2 | Total | Chime | 0 | ||
| Tamper Switch/Valves | 2 | 6 | 8 | Panic/Strobe | 18 | ||
| Duct Detectors | 1 | 0 | 1 | Bells | 0 | ||
| Low Air Switch | 0 | 1 | 1 | Outside Horn/ Strobes | 2 | ||
| AirSense | 0 | 0 | 0 | ||||
| Vesda Alert/Action | 0 | 0 | 0 | Panel Types | |||
| Fire Pump | 0 | 0 | 0 | Device type | Quantity | ||
| Fume Hood Panic | 6 | 12 | 18 | Workstation | 0 | ||
| AED | 2 | 1 | 3 | NCA | 0 | ||
| Security Door | 1 | 0 | 1 | NFS2-3030 | 0 | ||
| NFS2-640 | 1 | ||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | |||||
| Device Type | SLC 1 | SLC 2 | Total | DVC | 1 | ||
| Relays/Control Modules | 3 | 16 | 19 | LCD-160 | 0 | ||
| Trouble Monitors | 1 | 4 | 5 | LCD-80 | 3 | ||
| Non-Fire Modules | 3 | 6 | 9 | ||||
| Liquid Level | 0 | 0 | 0 | ||||
| Air Flow | 0 | 0 | 0 | Totals From Above= | 526 |
&C&F
B-3 Node 33
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 3 Main FACP Device Count 8-2025 | ||||||
| Nodes:33, 34 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 3 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 14 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 11 | 7 AH | 6 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 8 | |||
| Photo Smoke Detector | 11 | 18 AH | 0 | |||
| Heat Detector | 3 | 26 AH | 2 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 5 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 1 | |||
| Vesda | 4 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 1 | Strobe | 3 | |||
| Speakers | 34 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 116 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 9 | Panic/Strobe | 0 | |||
| Duct Detectors | 6 | Bells | 0 | |||
| Low Air Switch | 1 | Outside Horn/ Strobes | 1 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 4 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 1 | |||
| NFS2-640 | 0 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 9 | LCD-160 | 0 | |||
| Trouble Monitors | 9 | LCD-80 | 0 | |||
| Non-Fire Modules | 2 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 270 |
&C&F
B-3 Node 35
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 3 Anechoic Chambers, Device Count 8-2025 | ||||||
| Nodes: 35 | ||||||
| Total # of Fire Panels/WS/DVC | 1 | Total # of Releasing Systems- Sapphire | 3 | |||
| Total # of Power Supplies | 3 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 9 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 3 | 7 AH | 2 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 6 | |||
| Photo Smoke Detector | 2 | 18 AH | 2 | |||
| Heat Detector | 0 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda Fire 1 / 2 | 6 | Horn/Strobe | 3 | |||
| Releasing / Solenoid | 3 | Strobe | 3 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 0 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 3 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 6 | Panel Types | ||||
| Releasing | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 0 | NCA | 0 | |||
| Security Door | 0 | NFS2-3030 | 0 | |||
| NFS2-640 | 0 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 1 | ||||
| Device Type | Quantity | DVC | 0 | |||
| Relays/Control Modules | 15 | LCD-160 | 0 | |||
| Trouble Monitors | 3 | LCD-80 | 0 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 75 |
&C&F
B-4,5,3A,111 Node 30
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 4, 5, 3A, and 111 Device Count 8-2025 | ||||||
| Nodes: 30, 31, 50 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 1 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 12 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 13 | 7 AH | 2 | |||
| Fire/CO Multi-Criteria Detector | 5 | 12 AH | 0 | |||
| Photo Smoke Detector | 81 | 18 AH | 0 | |||
| Heat Detector | 2 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 2 | |||
| Flow Switch | 1 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 10 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 25 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 1 | Panic/Strobe | 2 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 1 | Outside Horn/ Strobes | 1 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 2 | Workstation | 1 | |||
| AED | 2 | NCA | 1 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 13 | LCD-160 | 0 | |||
| Trouble Monitors | 1 | LCD-80 | 0 | |||
| Non-Fire Modules | 1 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 186 |
&C&F
B- 8,11,12 Node 8
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 8, 11, and 12 Device Count 8-2025 | ||||||
| Nodes: 8, 9 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 7 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 7 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 1 | 12 AH | 0 | |||
| Photo Smoke Detector | 9 | 18 AH | 0 | |||
| Heat Detector | 1 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 2 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 1 | |||
| Vesda | 0 | Horn/Strobe | 1 | |||
| Releasing / Solenoid | 0 | Strobe | 2 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 3 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 3 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 0 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 0 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 43 |
&C&F
B- 21 Node 21
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 21, Device Count 8-2025 | ||||||
| Nodes: 21, 121 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 10 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 3 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 1 | 12 AH | 0 | |||
| Photo Smoke Detector | 7 | 18 AH | 0 | |||
| Heat Detector | 3 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 2 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 3 | |||
| Speakers | 1 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 6 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 0 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 2 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 1 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 45 |
&C&F
B-22 Node 22
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 22, Device Count 8-2025 | ||||||
| Nodes: 22, 122 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 10 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 8 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 1 | 12 AH | 0 | |||
| Photo Smoke Detector | 34 | 18 AH | 0 | |||
| Heat Detector | 3 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 2 | |||
| Flow Switch | 1 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 4 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 14 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 1 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 1 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 2 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 1 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 89 |
&C&F
B-23 Node 23
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 23, Device Count 8-2025 | ||||||
| Nodes:23 | ||||||
| Total # of Fire Panels/WS/DVC | 1 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 5 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 4 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||
| Photo Smoke Detector | 1 | 18 AH | 2 | |||
| Heat Detector | 0 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 1 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 2 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 1 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 0 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 0 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 1 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 2 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 1 | Workstation | 0 | |||
| AED | 0 | NCA | 0 | |||
| Security Door | 0 | NFS2-3030 | 0 | |||
| NFS2-640 | 0 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 1 | ||||
| Device Type | Quantity | DVC | 0 | |||
| Relays/Control Modules | 1 | LCD-160 | 0 | |||
| Trouble Monitors | LCD-80 | 0 | ||||
| Non-Fire Modules | ||||||
| Liquid Level | 2 | |||||
| Air Flow | 2 | Totals From Above= | 28 |
&C&F
B-24 Node 24
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 24, Device Count 8-2025 | ||||||
| Nodes: 24, 124 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- FM-200 | 2 | |||
| Total # of Power Supplies | 5 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 25 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 20 | 7 AH | 10 | |||
| Fire/CO Multi-Criteria Detector | 2 | 12 AH | 0 | |||
| Photo Smoke Detector | 105 | 18 AH | 2 | |||
| Heat Detector | 6 | 26 AH | 2 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 5 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 8 | Horn/Strobe | 4 | |||
| Releasing / Solenoid | 4 | Strobe | 15 | |||
| Speakers | 5 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 37 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 4 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 2 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 8 | Panel Types | ||||
| Releasing | 4 | Device type | Quantity | |||
| Fume Hood Panic | 3 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 27 | LCD-160 | 0 | |||
| Trouble Monitors | 12 | LCD-80 | 0 | |||
| Non-Fire Modules | 2 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 326 |
&C&F
B-25 Node 25
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 25, Device Count 8-2025 | ||||||
| Nodes: 25, 125 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 10 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 6 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 2 | 12 AH | 0 | |||
| Photo Smoke Detector | 18 | 18 AH | 0 | |||
| Heat Detector | 10 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 2 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 2 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 7 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 3 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 67 |
&C&F
B-26 Node 26
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 26, Device Count 8-2025 | ||||||
| Nodes: 26, 126 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 10 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 1 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 2 | 12 AH | 0 | |||
| Photo Smoke Detector | 31 | 18 AH | 0 | |||
| Heat Detector | 2 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 2 | |||
| Flow Switch | 1 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 1 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 12 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 13 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 1 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 1 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 12 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 1 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 97 |
&C&F
B-27 Node 27
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 27, Device Count 8-2025 | ||||||
| Node: 27 | ||||||
| Total # of Fire Panels/WS/DVC | 1 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 4 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 1 | 7 AH | 0 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||
| Photo Smoke Detector | 1 | 18 AH | 2 | |||
| Heat Detector | 2 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 1 | |||
| Releasing / Solenoid | 0 | Strobe | 0 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 0 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 1 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 0 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 0 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 1 | ||||
| Device Type | Quantity | DVC | 0 | |||
| Relays/Control Modules | 0 | LCD-160 | 0 | |||
| Trouble Monitors | 0 | LCD-80 | 0 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 16 |
&C&F
B-42 Node 45
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 42/CUP, 9, and Tunnel Device Count 8-2025 | ||||||
| Nodes: 45, 46 | ||||||
| Total # of Fire Panels/WS/DVC | 3 | Total # of Releasing Panels- Sapphire | 0 | |||
| Total # of Power Supplies | 2 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 10 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 15 | 7 AH | 6 | |||
| Fire/CO Multi-Criteria Detector | 2 | 12 AH | 0 | |||
| Photo Smoke Detector | 25 | 18 AH | 2 | |||
| Heat Detector | 3 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 8 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 0 | |||
| Releasing / Solenoid | 0 | Strobe | 14 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 21 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 10 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 2 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Fire Pump | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 1 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 1 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 7 | LCD-160 | 0 | |||
| Trouble Monitors | 1 | LCD-80 | 1 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 138 |
&C&F
B-81 Total
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Device Count 8-2025 | |||||||
| Nodes: 60, 61, 62, 63 | |||||||
| Total # of Fire Panels/WS/DVC | 4 | Total # of Releasing Panels- Sapphire | 0 | ||||
| Total # of Power Supplies | 76 | Total # of Releasing Panels- CO2 | 23 | ||||
| Total Number of SLC's | 9 | ||||||
| Total Number of IDC's | 0 | ||||||
| Total Number Of Notification Circuits on Entire System | 116 | ||||||
| Alarm Initiating Devices/Points | Batteries | ||||||
| Device type | TOTALS | Size | Quantity | ||||
| Manual Pull Station | 63 | 7 AH | 34 | ||||
| Fire/CO Multi-Criteria Detector | 1 | 12 AH | 63 | ||||
| Photo Smoke Detector | 42 | 18 AH | 0 | ||||
| Heat Detector | 7 | 26 AH | 4 | ||||
| Laser Detector | 0 | 35 AH | 0 | ||||
| Flow Switch | 24 | 55 AH | 0 | ||||
| Flame Detector | 34 | 110 AH | 0 | ||||
| Beam Smoke Detector | 0 | ||||||
| Gas Detection Interface | 44 | Alarm Notification Appliances | |||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | ||||
| AirSense | 0 | Horns | 0 | ||||
| Vesda Fire 1 / 2 | 112 | Horn/Strobe | 23 | ||||
| Releasing / Solenoid | 23 | Strobe | 27 | ||||
| Speakers | 38 | ||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 287 | |||||
| Device Type | TOTALS | Chime | 0 | ||||
| Tamper Switch/Valves | 40 | Panic/Strobe | 0 | ||||
| Duct Detectors | 83 | Bells | 0 | ||||
| Low Air Switch | 0 | Outside Horn/ Strobes | 1 | ||||
| AirSense | 0 | ||||||
| Vesda Alert/Action | 112 | Panel Types | |||||
| Gas Detection Interface | 42 | Device type | Quantity | ||||
| Security Door | 0 | Workstation | 0 | ||||
| AED | 6 | NCA | 0 | ||||
| Fire Pump | 1 | NFS2-3030 | 2 | ||||
| Releasing | 23 | NFS2-640 | 0 | ||||
| NFS-320 | 0 | ||||||
| Miscellaneous Initiating Devices/Points | DVC | 2 | |||||
| Device Type | TOTALS | LCD-160 | 1 | ||||
| Relays/Control Modules | 149 | LCD-80 | 0 | ||||
| Trouble Monitors | 181 | ||||||
| Non-Fire Modules | 26 | ||||||
| Liquid Level | 0 | Totals From Above= | 1725 | ||||
| Air Flow | 0 | ||||||
| Pendant | 2 | ||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Main, Device Count 8-2025 | |||||||
| Nodes: 60, 61 | |||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | ||||
| Total # of Power Supplies | 18 | Total # of Releasing Panels- CO2 | 0 | ||||
| Total Number of SLC's | 2 | ||||||
| Total Number of IDC's | 0 | ||||||
| Total Number Of Notification Circuits on Entire System | 98 | ||||||
| Alarm Initiating Devices/Points | Batteries | ||||||
| Device type | Quantity | Size | Quantity | ||||
| Manual Pull Station | 26 | 7 AH | 28 | ||||
| I-Quad Smoke Acclimate Det. | 1 | 12 AH | 8 | ||||
| Photo Smoke Detector | 40 | 18 AH | 0 | ||||
| Heat Detector | 7 | 26 AH | 2 | ||||
| Laser Detector | 0 | 35 AH | 0 | ||||
| Flow Switch | 13 | 55 AH | 0 | ||||
| Flame Detector | 0 | 110 AH | 0 | ||||
| Beam Smoke Detector | 0 | ||||||
| Gas Detection Interface- O2 | 3 | Alarm Notification Appliances | |||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | ||||
| AirSense | 0 | Horns | 0 | ||||
| Vesda | 2 | Horn/Strobe | 0 | ||||
| Releasing | 0 | Strobe | 27 | ||||
| Speakers | 38 | ||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 237 | |||||
| Device Type | Quantity | Chime | 0 | ||||
| Tamper Switch/Valves | 29 | Panic/Strobe | 0 | ||||
| Duct Detectors/Smokes | 79 | Bells | 0 | ||||
| Low Air Switch | 0 | Outside Horn/ Strobes | 1 | ||||
| AirSense | 0 | ||||||
| Vesda Alert/Action | 2 | Panel Types | |||||
| Fire Pump Points | 4 | Device type | Quantity | ||||
| Fume Hood Panic | 0 | Workstation | 0 | ||||
| AED | 5 | NCA | 0 | ||||
| Security Door | 0 | NFS2-3030 | 1 | ||||
| NFS2-640 | 0 | ||||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | |||||
| Device Type | Quantity | DVC | 1 | ||||
| Relays/Control Modules | 86 | LCD-160 | 1 | ||||
| Trouble Monitors | 14 | LCD-80 | 0 | ||||
| Non-Fire Modules | 15 | ||||||
| Liquid Level | 0 | ||||||
| Air Flow | 0 | Totals From Above= | 790 | ||||
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Cleanroom, Device Count 8-2025 | |||||||
| Nodes: 62, 63 | |||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Panels- Sapphire | 0 | ||||
| Total # of Power Supplies | 58 | Total # of Releasing Panels- CO2 | 23 | ||||
| Total Number of SLC's | 7 | ||||||
| Total Number of IDC's | 0 | ||||||
| Total Number Of Notification Circuits on Entire System | 18 | ||||||
| Alarm Initiating Devices/Points | Batteries | ||||||
| Device type | TOTALS | Size | Quantity | ||||
| Manual Pull Station | 37 | 7 AH | 6 | ||||
| I-Quad Smoke Acclimate Det. | 0 | 12 AH | 55 | ||||
| Photo Smoke Detector | 2 | 18 AH | 0 | ||||
| Heat Detector | 0 | 26 AH | 2 | ||||
| Laser Detector | 0 | 35 AH | 0 | ||||
| Flow Switch | 11 | 55 AH | 0 | ||||
| Flame Detector | 34 | 110 AH | 0 | ||||
| Beam Smoke Detector | 0 | ||||||
| Gas Detection Interface | 41 | Alarm Notification Appliances | |||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | ||||
| AirSense | 0 | Horns | 0 | ||||
| Vesda Fire 1 / 2 | 110 | Horn/Strobe | 23 | ||||
| Releasing | 23 | Strobe | 0 | ||||
| Speakers | 0 | ||||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 50 | |||||
| Device Type | TOTALS | Chime | 0 | ||||
| Tamper Switch/Valves | 11 | Panic/Strobe | 0 | ||||
| Duct Detectors | 4 | Bells | 0 | ||||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | ||||
| AirSense | 0 | ||||||
| Vesda Alert/Action | 110 | Panel Types | |||||
| Gas Detection Interface | 42 | Device type | Quantity | ||||
| Fume Hood Panic | 0 | Workstation | 0 | ||||
| AED | 1 | NCA | 0 | ||||
| Security Door | 0 | NFS2-3030 | 1 | ||||
| Releasing | 23 | NFS2-640 | 0 | ||||
| NFS-320 | 0 | ||||||
| Miscellaneous Initiating Devices/Points | DVC | 1 | |||||
| Device Type | TOTALS | LCD-160 | 0 | ||||
| Relays/Control Modules | 63 | LCD-80 | 0 | ||||
| Trouble Monitors | 167 | ||||||
| Non-Fire Modules | 11 | ||||||
| Liquid Level | 0 | Totals From Above= | 939 | ||||
| Air Flow | 0 | ||||||
| Pendant | 3 | ||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Cleanroom, Device Count 2-2019 | |||||||
| Nodes: 62, 63 | |||||||
| Alarm Initiating Devices/Points | |||||||
| Device type | SLC 1 | SLC 2 | SLC 3 | ||||
| Manual Pull Station | 12 | 10 | 11 | ||||
| I-Quad Smoke Acclimate Det. | 0 | 0 | 0 | ||||
| Photo Smoke Detector | 1 | 0 | 0 | ||||
| Heat Detector | 0 | 0 | 0 | ||||
| Laser Detector | 0 | 0 | 0 | ||||
| Flow Switch | 3 | 4 | 4 | ||||
| Flame Detector | 11 | 13 | 10 | ||||
| Beam Smoke Detector | 0 | 0 | 0 | ||||
| Gas Detection Interface | 0 | 0 | 0 | ||||
| Kitchen Hood/Ansul | 0 | 0 | 0 | ||||
| AirSense | 0 | 0 | 0 | ||||
| Vesda Fire 1 / 2 | 18 | 12 | 16 | ||||
| Releasing | 9 | 6 | 8 | ||||
| Supervisory Initiating Devices/Points | |||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | ||||
| Tamper Switch/Valves | 3 | 4 | 4 | ||||
| Duct Detectors | 0 | 0 | 0 | ||||
| Low Air Switch | 0 | 0 | 0 | ||||
| AirSense | 0 | 0 | 0 | ||||
| Vesda Alert/Action | 18 | 12 | 16 | ||||
| Gas Detection Interface | 0 | 0 | 0 | ||||
| Fume Hood Panic | 0 | 0 | 0 | ||||
| AED | 0 | 0 | 1 | ||||
| Security Door | 0 | 0 | 0 | ||||
| Releasing | 9 | 6 | 8 | ||||
| Miscellaneous Initiating Devices/Points | |||||||
| Device Type | SLC 1 | SLC 2 | SLC 3 | ||||
| Relays/Control Modules | 1 | 2 | 1 | ||||
| Trouble Monitors | 23 | 18 | 24 | ||||
| Non-Fire Modules | 3 | 4 | 4 | ||||
| Liquid Level | 0 | 0 | 0 | ||||
| Air Flow | 0 | 0 | 0 | ||||
| Pendant | 0 | 0 | 3 | ||||
| NIST/Boulder - Building 81 Cleanroom - Page 4 of 6 | |||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Cleanroom, Device Count 2-2019 | |||||||
| Nodes: 62, 63 | |||||||
| Alarm Initiating Devices/Points | |||||||
| Device type | SLC 4 | SLC 5 | SLC 6 | ||||
| Manual Pull Station | 0 | 0 | 0 | ||||
| I-Quad Smoke Acclimate Det. | 0 | 0 | 0 | ||||
| Photo Smoke Detector | 0 | 0 | 0 | ||||
| Heat Detector | 0 | 0 | 0 | ||||
| Laser Detector | 0 | 0 | 0 | ||||
| Flow Switch | 0 | 0 | 0 | ||||
| Flame Detector | 0 | 0 | 0 | ||||
| Beam Smoke Detector | 0 | 0 | 0 | ||||
| Gas Detection Interface | 33 | 8 | 0 | ||||
| Kitchen Hood/Ansul | 0 | 0 | 0 | ||||
| AirSense | 0 | 0 | 0 | ||||
| Vesda Fire 1 / 2 | 0 | 24 | 40 | ||||
| Releasing | 0 | 0 | 0 | ||||
| Supervisory Initiating Devices/Points | |||||||
| Device Type | SLC 4 | SLC 5 | SLC 6 | ||||
| Tamper Switch/Valves | 0 | 0 | 0 | ||||
| Duct Detectors | 0 | 0 | 0 | ||||
| Low Air Switch | 0 | 0 | 0 | ||||
| AirSense | 0 | 0 | 0 | ||||
| Vesda Alert/Action | 0 | 24 | 40 | ||||
| Gas Detection Interface | 34 | 8 | 0 | ||||
| Fume Hood Panic | 0 | 0 | 0 | ||||
| AED | 0 | 0 | 0 | ||||
| Security Door | 0 | 0 | 0 | ||||
| Releasing | 0 | 0 | 0 | ||||
| Miscellaneous Initiating Devices/Points | |||||||
| Device Type | SLC 4 | SLC 5 | SLC 6 | ||||
| Relays/Control Modules | 0 | 1 | 0 | ||||
| Trouble Monitors | 34 | 16 | 20 | ||||
| Non-Fire Modules | 0 | 0 | 0 | ||||
| Liquid Level | 0 | 0 | 0 | ||||
| Air Flow | 0 | 0 | 0 | ||||
| Pendant | 0 | 0 | 0 | ||||
| NIST/Boulder - Building 81 Cleanroom - Page 5 of 6 | |||||||
| FIRE ALARM SYSTEM INSPECTION REPORT | |||||||
| NIST Bldg. 81 Cleanroom, Full Device Count 2-2019 | |||||||
| Nodes: 62, 63 | |||||||
| Alarm Initiating Devices/Points | |||||||
| Device type | SLC 7 | ||||||
| Manual Pull Station | 4 | ||||||
| I-Quad Smoke Acclimate Det. | 0 | ||||||
| Photo Smoke Detector | 1 | ||||||
| Heat Detector | 0 | ||||||
| Laser Detector | 0 | ||||||
| Flow Switch | 0 | ||||||
| Flame Detector | 0 | ||||||
| Beam Smoke Detector | 0 | ||||||
| Gas Detection Interface | 0 | ||||||
| Kitchen Hood/Ansul | 0 | ||||||
| AirSense | 0 | ||||||
| Vesda Fire 1 / 2 | 0 | ||||||
| Releasing | 0 | ||||||
| Supervisory Initiating Devices/Points | |||||||
| Device Type | SLC 7 | ||||||
| Tamper Switch/Valves | 0 | ||||||
| Duct Detectors | 4 | ||||||
| Low Air Switch | 0 | ||||||
| AirSense | 0 | ||||||
| Vesda Alert/Action | 0 | ||||||
| Gas Detection Interface | 0 | ||||||
| Fume Hood Panic | 0 | ||||||
| AED | 0 | ||||||
| Security Door | 0 | ||||||
| Releasing | 0 | ||||||
| Miscellaneous Initiating Devices/Points | |||||||
| Device Type | SLC 7 | ||||||
| Relays/Control Modules | 58 | ||||||
| Trouble Monitors | 32 | ||||||
| Non-Fire Modules | 0 | ||||||
| Liquid Level | 0 | ||||||
| Air Flow | 0 | ||||||
| Pendant | 0 |
&C&F
B-92 Node 92
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. 92, Device Count 8-2025 | ||||||
| Nodes: 92, 93 | ||||||
| Total # of Fire Panels/WS/DVC | 2 | Total # of Releasing Systems- Sapphire | 3 | |||
| Total # of Power Supplies | 6 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 0 | |||||
| Total Number Of Notification Circuits on Entire System | 18 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 15 | 7 AH | 2 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 14 | |||
| Photo Smoke Detector | 2 | 18 AH | 0 | |||
| Heat Detector | 0 | 26 AH | 2 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 0 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda Fire 1 / 2 | 12 | Horn/Strobe | 6 | |||
| Releasing / Solenoid | 8 | Strobe | 6 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 24 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 8 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 8 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 8 | Panel Types | ||||
| Releasing | 0 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 0 | NFS2-3030 | 1 | |||
| NFS2-640 | 0 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 1 | |||
| Relays/Control Modules | 21 | LCD-160 | 0 | |||
| Trouble Monitors | 15 | LCD-80 | 0 | |||
| Non-Fire Modules | 8 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 192 |
&C&F
Bldg. WWV
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. WWV, Full Device Count 8-2025 | ||||||
| Nodes: N/A | ||||||
| Total # of Fire Panels/WS/DVC | 1 | Total # of Releasing Panels- Sapphire | 2 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 4 | |||||
| Total Number Of Notification Circuits on Entire System | 4 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 7 | 7 AH | 4 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||
| Photo Smoke Detector | 27 | 18 AH | 4 | |||
| Heat Detector | 0 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 1 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 13 | |||
| Releasing / Solenoid | 2 | Strobe | 16 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 0 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Releasing | 2 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 0 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 0 | |||
| Relays/Control Modules | 0 | LCD-160 | 0 | |||
| Trouble Monitors | 6 | LCD-80 | 0 | |||
| Non-Fire Modules | 0 | |||||
| Liquid Level | 0 | |||||
| Air Flow | 0 | Totals From Above= | 96 |
&C&F
Bldg. WWVB
| FIRE ALARM SYSTEM INSPECTION REPORT | ||||||
| NIST Bldg. WWVB, Full Device Count 8-2025 | ||||||
| Nodes: N/A | ||||||
| Total # of Fire Panels/WS/DVC | 1 | Total # of Releasing Panels- Sapphire | 2 | |||
| Total # of Power Supplies | 0 | Total # of Releasing Panels- CO2 | 0 | |||
| Total Number of SLC's | 1 | |||||
| Total Number of IDC's | 4 | |||||
| Total Number Of Notification Circuits on Entire System | 4 | |||||
| Alarm Initiating Devices/Points | Batteries | |||||
| Device type | Quantity | Size | Quantity | |||
| Manual Pull Station | 7 | 7 AH | 4 | |||
| Fire/CO Multi-Criteria Detector | 0 | 12 AH | 0 | |||
| Photo Smoke Detector | 21 | 18 AH | 2 | |||
| Heat Detector | 0 | 26 AH | 0 | |||
| Laser Detector | 0 | 35 AH | 0 | |||
| Flow Switch | 0 | 55 AH | 0 | |||
| Flame Detector | 1 | 110 AH | 0 | |||
| Beam Smoke Detector | 0 | |||||
| Gas Detection Interface | 0 | Alarm Notification Appliances | ||||
| Kitchen Hood/Ansul | 0 | Device type | Quantity | |||
| AirSense | 0 | Horns | 0 | |||
| Vesda | 0 | Horn/Strobe | 9 | |||
| Releasing / Solenoid | 2 | Strobe | 13 | |||
| Speakers | 0 | |||||
| Supervisory Initiating Devices/Points | Speaker/Strobes | 0 | ||||
| Device Type | Quantity | Chime | 0 | |||
| Tamper Switch/Valves | 0 | Panic/Strobe | 0 | |||
| Duct Detectors | 0 | Bells | 0 | |||
| Low Air Switch | 0 | Outside Horn/ Strobes | 0 | |||
| AirSense | 0 | |||||
| Vesda Alert/Action | 0 | Panel Types | ||||
| Releasing Panel | 2 | Device type | Quantity | |||
| Fume Hood Panic | 0 | Workstation | 0 | |||
| AED | 1 | NCA | 0 | |||
| Security Door | 0 | NFS2-3030 | 0 | |||
| NFS2-640 | 1 | |||||
| Miscellaneous Initiating Devices/Points | NFS-320 | 0 | ||||
| Device Type | Quantity | DVC | 0 |