Attach 4 - Appendix A NIST- Site Wide Counts 8-2025.xls

XLS spreadsheet 1 MB Posted

Attached to
Fire Protection Systems Inspection, Testing, Maintenance, Repair & Impairment Coordinator (FPS-ITMR & IC) Services
Solicitation number
1333ND26QNB190185
Issued by

About this file

This is a Fire Alarm System Inspection Report appendix containing comprehensive device count documentation for the NIST Boulder/Fort Collins Sites as of August 2025. The report details fire alarm system infrastructure across multiple buildings at the NIST facility, providing an itemized inventory of all fire protection equipment and components organized by building and node designation.

The site-wide summary indicates a total of 6,482 devices across the Boulder/Fort Collins location, including 49 fire panels/workstations/DVCs, 14 releasing panels (Sapphire/FM200), 127 power supplies, 23 CO2 releasing panels, 40 Signaling Line Circuits (SLCs), and 8 Intelligent Device Circuits (IDCs). Alarm initiating devices total 3,073 units, consisting primarily of 1,365 photo smoke detectors, 300 manual pull stations, 77 flow switches, 63 heat detectors, 46 gas detection interfaces, and additional specialized detectors. Alarm notification appliances include 359 speakers, 188 strobes, 143 horn/strobes, and 60 horns. The inventory also encompasses 1,352 speaker/strobes, 422 relays/control modules, 291 trouble monitors, 147 duct detectors, 139 Vesda alert/action devices, and 121 tamper switches/valves. Battery backup systems total 403 units across various amp-hour ratings (7 AH through 110 AH). Individual building reports provide granular breakdowns for Buildings 1, 2, 3, 4/5/3A/111, 8/11/12, 21-27, 42/CUP/9/Tunnel, 81 (Main and Cleanroom sections), 92, WWV, and WWVB, with each building section specifying panel types, circuit configurations, device distribution by circuit, and battery allocations to support inspection, testing, maintenance, and repair coordination services.

View the file

Other files

File Type Posted
1333ND26QNB190185.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Boulder - Ft. Collins Site

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Boulder / Fort Collins Sites, Total Device Count 8-2025
Total # of Fire Panels/WS/DVC49Total # of Releasing- Sapphire / FM20014
Total # of Power Supplies127Total # of Releasing Panels- CO223
Total Number of SLC's40
Total Number of IDC's8
Total Number Of Notification Circuits on Entire System436
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station3007 AH114
I-Quad Smoke Acclimate Det.3412 AH87
Photo Smoke Detector136518 AH14
Heat Detector6326 AH14
Laser Detector535 AH10
Flow Switch7755 AH16
Flame Detector3675 AH2
Beam Smoke Detector5
Gas Detection Interface46Alarm Notification Appliances
Kitchen Hood/Ansul1Device typeQuantity
AirSense4Horns3
Vesda Fire 1 / 2143Horn/Strobe60
Releasing / Solenoid48Strobe188
Speakers359
Supervisory Initiating Devices/PointsSpeaker/Strobes1352
Device TypeQuantityChime0
Tamper Switch/Valves121Panic/Strobe34
Duct Detectors147Bells0
Low Air Switch7Outside Horn/ Strobes32
AirSense4
Vesda Alert/Action139
Releasing29
Fume Hood Panic32
AED31Panel Types
Security Door18Device typeQuantity
Fire Pump1Workstation3
NCA2
NFS2-303011
NFS2-64011
Miscellaneous Initiating Devices/PointsNFS-3203
Device TypeQuantityDVC21
Relays/Control Modules422LCD-1602
Trouble Monitors291LCD-804
Non-Fire Modules67
Liquid Level2Batteries Continued
Air Flow2APC- RBC3
Totals From Above=6482

B-1 Totals

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Total Device Count 8-2025
Nodes: 1, 2, 3, 4, 13, 15, 16, 17, 20, 101, 102, 103, 104, 105, 113, 115, 116
Total # of Fire Panels/WS/DVC18Total # of Releasing Panels- Sapphire2
Total # of Power Supplies27Total # of Releasing Panels- CO20
Total Number of SLC's14
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System136
Alarm Initiating Devices/Points **Batteries **
Device typeQuantitySizeQuantity
Manual Pull Station867 AH38
Fire/CO Multi-Criteria Detector1612 AH2
Photo Smoke Detector68018 AH2
Heat Detector1126 AH2
Laser Detector535 AH0
Flow Switch2255 AH14
Flame Detector075 AH2
Beam Smoke Detector3
Gas Detection Interface0Alarm Notification Appliances **
Kitchen Hood/Ansul0Device typeQuantity
AirSense4Horns0
Vesda1Horn/Strobe0
Releasing / Solenoid5Strobe50
Speakers272
Supervisory Initiating Devices/Points **Speaker/Strobes750
Device TypeQuantityChime0
Tamper Switch/Valves36Panic/Strobe13
Duct Detectors57Bells0
Low Air Switch3Outside Horn/ Strobes7
AirSense4
Vesda Alert/Action1Panel Types
Releasing2Device typeQuantity
Fume Hood Panic9Workstation1
AED11NCA1
Security Door7NFS2-30307
NFS2-6400
Miscellaneous Initiating Devices/Points **NFS-3200
Device TypeQuantityDVC8
Relays/Control Modules142LCD-1601
Trouble Monitors52LCD-800
Non-Fire Modules16
Liquid Level0
Air Flow0Totals From Above=1343
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 1, 101, 17, 105
Total # of Fire Panels/WS/DVC4Total # of Releasing Panels- Sapphire1
Total # of Power Supplies4Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's
Total Number Of Notification Circuits on Entire System11
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station147 AH4
Fire/CO MultiCriteria212 AH0
Fire/CO Multi-Criteria Detector8218 AH0
Heat Detector726 AH0
Laser Detector035 AH0
Flow Switch255 AH4
Flame Detector0110 AH0
Beam Smoke Detector3
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing / Solenoid1Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeQuantityChime
Tamper Switch/Valves2Panic/Strobe
Duct Detectors9Bells
Low Air Switch0Outside Horn/ Strobes
AirSense0
Vesda Alert/Action0Panel Types
Releasing1Device typeQuantity
Fume Hood Panic0Workstation1
AED2NCA1
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC2
Relays/Control Modules12LCD-1600
Trouble Monitors9LCD-800
Non-Fire Modules4
Liquid Level0
Air Flow0Totals From Above=185
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 2, 102
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire1
Total # of Power Supplies6Total # of Releasing Panels- CO20
Total Number of SLC's4
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System28
Alarm Initiating Devices/PointsBatteries
Device typeTotalsSizeQuantity
Manual Pull Station267 AH10
Fire/CO Multi-Criteria Detector712 AH0
Photo Smoke Detector24418 AH0
Heat Detector426 AH0
Laser Detector535 AH
Flow Switch855 AH2
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense1HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing / Solenoid3Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeTotalsChime
Tamper Switch/Valves9Panic/Strobe
Duct Detectors3Bells
Low Air Switch1Outside Horn/ Strobes
AirSense1
Vesda Alert/Action0Panel Types
Fire Pump1Device typeQuantity
Fume Hood Panic4Workstation0
AED1NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeTotalsDVC1
Relays/Control Modules38LCD-1601
Trouble Monitors13LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=428
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 12-2020
Nodes: Node 2, 102
Alarm Initiating Devices/Points
Device typeSLC 1SLC 2SLC 3SLC 4
Manual Pull Station510120
Fire/CO Multi-Criteria110
Photo Smoke Detector6683810
Heat Detector8010
Laser Detector5000
Flow Switch0180
Flame Detector0000
Beam Smoke Detector0000
Gas Detection Interface0000
Kitchen Hood/Ansul0000
AirSense0100
Vesda0000
Releasing& Soleniod1100
Supervisory Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3SLC 4
Tamper Switch/Valves0180
Duct Detectors1020
Low Air Switch0010
AirSense0100
Vesda Alert/Action0000
Releasing1000
Fume Hood Panic0140
AED1000
Security Door1000
Miscellaneous Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3SLC 4
Relays/Control Modules21890
Trouble Monitors12100
Non-Fire Modules1100
Liquid Level0000
Air Flow0000
NIST/Boulder - Building 1 - Page 4 of 11
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 3, 103
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies3Total # of Releasing Panels- CO20
Total Number of SLC's4
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System30
Alarm Initiating Devices/PointsBatteries
Device typeTotalsSizeQuantity
Manual Pull Station137 AH6
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector20218 AH0
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch055 AH2
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense2HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing / Solenoid0Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeTotalsChime
Tamper Switch/Valves0Panic/Strobe
Duct Detectors0Bells
Low Air Switch0Outside Horn/ Strobes
AirSense2
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic1Workstation0
AED1NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeTotalsDVC1
Relays/Control Modules5LCD-1600
Trouble Monitors10LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=286
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 12-2020
Nodes: Node 3, 103
Alarm Initiating Devices/Points
Device typeSLC 1SLC 2SLC 3SLC 4
Manual Pull Station4080
Fire/CO MultiCriteria000
Photo Smoke Detector8801130
Heat Detector0000
Laser Detector0000
Flow Switch0000
Flame Detector0000
Beam Smoke Detector0000
Gas Detection Interface0000
Kitchen Hood/Ansul0000
AirSense1010
Vesda0000
Releasing0000
Supervisory Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3SLC 4
Tamper Switch/Valves0000
Duct Detectors0000
Low Air Switch0000
AirSense1010
Vesda Alert/Action0000
Releasing0000
Fume Hood Panic0010
AED1000
Security Door1000
Miscellaneous Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3SLC 4
Relays/Control Modules3020
Trouble Monitors9010
Non-Fire Modules0000
Liquid Level0000
Air Flow0000
NIST/Boulder - Building 1 - Page 6 of 11
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 4, 104
Total # of Fire Panels/WS/DVC3Total # of Releasing Panels- Sapphire0
Total # of Power Supplies1Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System4
Alarm Initiating Devices/PointsBatteries
Device typeTotalsSizeQuantity
Manual Pull Station77 AH2
Fire/CO Multi-Criteria Detector712 AH0
Photo Smoke Detector11518 AH0
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch255 AH2
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense1HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing / Solenoid0Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeTotalsChime
Tamper Switch/Valves4Panic/Strobe
Duct Detectors1Bells
Low Air Switch0Outside Horn/ Strobes
AirSense1
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED2NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeTotalsDVC1
Relays/Control Modules9LCD-1600
Trouble Monitors7LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=174
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 12-2020
Nodes: Node 4, 104
Alarm Initiating Devices/Points
Device typeSLC 1
Manual Pull Station7
I-Quad Smoke Acclimate Det.7
Photo Smoke Detector115
Heat Detector0
Laser Detector0
Flow Switch2
Flame Detector0
Beam Smoke Detector0
Gas Detection Interface0
Kitchen Hood/Ansul0
AirSense1
Vesda0
Releasing0
Supervisory Initiating Devices/Points
Device TypeSLC 1
Tamper Switch/Valves4
Duct Detectors1
Low Air Switch0
AirSense1
Vesda Alert/Action0
Fire Pump0
Fume Hood Panic0
AED2
Security Door1
Miscellaneous Initiating Devices/Points
Device TypeSLC 1
Relays/Control Modules9
Trouble Monitors7
Non-Fire Modules2
Liquid Level0
Air Flow0
NIST/Boulder - Building 1 - Page 8 of 11
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 13, 113
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies2Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System15
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station47 AH2
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector318 AH0
Heat Detector026 AH2
Laser Detector035 AH0
Flow Switch455 AH0
Flame Detector075 AH2
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing / Solenoid0Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeQuantityChime
Tamper Switch/Valves9Panic/Strobe
Duct Detectors16Bells
Low Air Switch1Outside Horn/ Strobes
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic4Workstation0
AED0NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules17LCD-1600
Trouble Monitors5LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=94
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 15, 115
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies **8Total # of Releasing Panels- CO20
Total Number of SLC's **2
Total Number of IDC's **0
Total Number Of Notification Circuits on Entire System **36
Alarm Initiating Devices/Points **Batteries
Device typeQuantitySizeQuantity
Manual Pull Station **127 AH12
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector **3018 AH2
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch **355 AH2
Flame Detector075 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda0Horn/Strobe
Releasing0Strobe
Speakers
Supervisory Initiating Devices/Points **Speaker/Strobes
Device TypeQuantityChime
Tamper Switch/Valves **4Panic/Strobe
Duct Detectors **10Bells
Low Air Switch **0Outside Horn/ Strobes
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED5NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/Points **NFS-3200
Device TypeQuantityDVC1
Relays/Control Modules **36LCD-1600
Trouble Monitors **5LCD-800
Non-Fire Modules **4
Liquid Level0
Air Flow0Totals From Above=176
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 1, Device Count 8-2025
Nodes: Node 16, 116
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies3Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System12
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station107 AH2
Fire/CO Multi-Criteria Detector012 AH2
Photo Smoke Detector418 AH0
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch355 AH0
Flame Detector075 AH2
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0HornsSee Total Device Count Building 1 - Page 1 of 10
Vesda1Horn/Strobe
Releasing / Solenoid1Strobe
Speakers
Supervisory Initiating Devices/PointsSpeaker/Strobes
Device TypeQuantityChime
Tamper Switch/Valves8Panic/Strobe
Duct Detectors18Bells
Low Air Switch1Outside Horn/ Strobes
AirSense0
Vesda Alert/Action1Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED0NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules25LCD-1600
Trouble Monitors3LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=104

&C&F

B-2 Node 5

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 2, Device Count 8-2025
Nodes: 5, 55
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies4Total # of Releasing Panels- CO20
Total Number of SLC's2
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System32
Alarm Initiating Devices/PointsBatteries
Device typeSLC 1SLC 2TotalSizeQuantity
Manual Pull Station1515307 AH8
Fire/CO Multi-Criteria Detector01112 AH0
Photo Smoke Detector12114726818 AH0
Heat Detector1001026 AH2
Laser Detector00035 AH0
Flow Switch36955 AH0
Flame Detector000110 AH0
Beam Smoke Detector022
Gas Detection Interface000Alarm Notification Appliances
Kitchen Hood/Ansul000Device typeQuantity
AirSense000Horns0
Vesda000Horn/Strobe0
Releasing / Solenoid000Strobe8
Speakers9
Supervisory Initiating Devices/PointsSpeaker/Strobes49
Device TypeSLC 1SLC 2TotalChime0
Tamper Switch/Valves268Panic/Strobe18
Duct Detectors101Bells0
Low Air Switch011Outside Horn/ Strobes2
AirSense000
Vesda Alert/Action000Panel Types
Fire Pump000Device typeQuantity
Fume Hood Panic61218Workstation0
AED213NCA0
Security Door101NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeSLC 1SLC 2TotalDVC1
Relays/Control Modules31619LCD-1600
Trouble Monitors145LCD-803
Non-Fire Modules369
Liquid Level000
Air Flow000Totals From Above=526

&C&F

B-3 Node 33

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 3 Main FACP Device Count 8-2025
Nodes:33, 34
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies3Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System14
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station117 AH6
Fire/CO Multi-Criteria Detector012 AH8
Photo Smoke Detector1118 AH0
Heat Detector326 AH2
Laser Detector035 AH0
Flow Switch555 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns1
Vesda4Horn/Strobe0
Releasing / Solenoid1Strobe3
Speakers34
Supervisory Initiating Devices/PointsSpeaker/Strobes116
Device TypeQuantityChime0
Tamper Switch/Valves9Panic/Strobe0
Duct Detectors6Bells0
Low Air Switch1Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action4Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door1NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules9LCD-1600
Trouble Monitors9LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=270

&C&F

B-3 Node 35

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 3 Anechoic Chambers, Device Count 8-2025
Nodes: 35
Total # of Fire Panels/WS/DVC1Total # of Releasing Systems- Sapphire3
Total # of Power Supplies3Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System9
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station37 AH2
Fire/CO Multi-Criteria Detector012 AH6
Photo Smoke Detector218 AH2
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch055 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda Fire 1 / 26Horn/Strobe3
Releasing / Solenoid3Strobe3
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes0
Device TypeQuantityChime0
Tamper Switch/Valves3Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action6Panel Types
Releasing0Device typeQuantity
Fume Hood Panic0Workstation0
AED0NCA0
Security Door0NFS2-30300
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3201
Device TypeQuantityDVC0
Relays/Control Modules15LCD-1600
Trouble Monitors3LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=75

&C&F

B-4,5,3A,111 Node 30

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 4, 5, 3A, and 111 Device Count 8-2025
Nodes: 30, 31, 50
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies1Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System12
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station137 AH2
Fire/CO Multi-Criteria Detector512 AH0
Photo Smoke Detector8118 AH0
Heat Detector226 AH0
Laser Detector035 AH2
Flow Switch155 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe10
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes25
Device TypeQuantityChime0
Tamper Switch/Valves1Panic/Strobe2
Duct Detectors0Bells0
Low Air Switch1Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic2Workstation1
AED2NCA1
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules13LCD-1600
Trouble Monitors1LCD-800
Non-Fire Modules1
Liquid Level0
Air Flow0Totals From Above=186

&C&F

B- 8,11,12 Node 8

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 8, 11, and 12 Device Count 8-2025
Nodes: 8, 9
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System7
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station77 AH0
Fire/CO Multi-Criteria Detector112 AH0
Photo Smoke Detector918 AH0
Heat Detector126 AH0
Laser Detector035 AH0
Flow Switch055 AH2
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns1
Vesda0Horn/Strobe1
Releasing / Solenoid0Strobe2
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes3
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes3
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED0NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules0LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=43

&C&F

B- 21 Node 21

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 21, Device Count 8-2025
Nodes: 21, 121
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System10
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station37 AH0
Fire/CO Multi-Criteria Detector112 AH0
Photo Smoke Detector718 AH0
Heat Detector326 AH0
Laser Detector035 AH2
Flow Switch055 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe3
Speakers1
Supervisory Initiating Devices/PointsSpeaker/Strobes6
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED0NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules2LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules1
Liquid Level0
Air Flow0Totals From Above=45

&C&F

B-22 Node 22

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 22, Device Count 8-2025
Nodes: 22, 122
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System10
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station87 AH0
Fire/CO Multi-Criteria Detector112 AH0
Photo Smoke Detector3418 AH0
Heat Detector326 AH0
Laser Detector035 AH2
Flow Switch155 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe4
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes14
Device TypeQuantityChime0
Tamper Switch/Valves1Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules2LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules1
Liquid Level0
Air Flow0Totals From Above=89

&C&F

B-23 Node 23

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 23, Device Count 8-2025
Nodes:23
Total # of Fire Panels/WS/DVC1Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System5
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station47 AH0
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector118 AH2
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch155 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface2Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns1
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe0
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes0
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe1
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes2
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic1Workstation0
AED0NCA0
Security Door0NFS2-30300
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3201
Device TypeQuantityDVC0
Relays/Control Modules1LCD-1600
Trouble MonitorsLCD-800
Non-Fire Modules
Liquid Level2
Air Flow2Totals From Above=28

&C&F

B-24 Node 24

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 24, Device Count 8-2025
Nodes: 24, 124
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- FM-2002
Total # of Power Supplies5Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System25
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station207 AH10
Fire/CO Multi-Criteria Detector212 AH0
Photo Smoke Detector10518 AH2
Heat Detector626 AH2
Laser Detector035 AH0
Flow Switch555 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda8Horn/Strobe4
Releasing / Solenoid4Strobe15
Speakers5
Supervisory Initiating Devices/PointsSpeaker/Strobes37
Device TypeQuantityChime0
Tamper Switch/Valves4Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes2
AirSense0
Vesda Alert/Action8Panel Types
Releasing4Device typeQuantity
Fume Hood Panic3Workstation0
AED1NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules27LCD-1600
Trouble Monitors12LCD-800
Non-Fire Modules2
Liquid Level0
Air Flow0Totals From Above=326

&C&F

B-25 Node 25

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 25, Device Count 8-2025
Nodes: 25, 125
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System10
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station67 AH0
Fire/CO Multi-Criteria Detector212 AH0
Photo Smoke Detector1818 AH0
Heat Detector1026 AH0
Laser Detector035 AH2
Flow Switch055 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe2
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes7
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules3LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=67

&C&F

B-26 Node 26

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 26, Device Count 8-2025
Nodes: 26, 126
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System10
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station17 AH0
Fire/CO Multi-Criteria Detector212 AH0
Photo Smoke Detector3118 AH0
Heat Detector226 AH0
Laser Detector035 AH2
Flow Switch155 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul1Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe12
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes13
Device TypeQuantityChime0
Tamper Switch/Valves1Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules12LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules1
Liquid Level0
Air Flow0Totals From Above=97

&C&F

B-27 Node 27

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 27, Device Count 8-2025
Node: 27
Total # of Fire Panels/WS/DVC1Total # of Releasing Panels- Sapphire0
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System4
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station17 AH0
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector118 AH2
Heat Detector226 AH0
Laser Detector035 AH0
Flow Switch055 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe1
Releasing / Solenoid0Strobe0
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes0
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation0
AED0NCA0
Security Door1NFS2-30300
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3201
Device TypeQuantityDVC0
Relays/Control Modules0LCD-1600
Trouble Monitors0LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=16

&C&F

B-42 Node 45

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 42/CUP, 9, and Tunnel Device Count 8-2025
Nodes: 45, 46
Total # of Fire Panels/WS/DVC3Total # of Releasing Panels- Sapphire0
Total # of Power Supplies2Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System10
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station157 AH6
Fire/CO Multi-Criteria Detector212 AH0
Photo Smoke Detector2518 AH2
Heat Detector326 AH0
Laser Detector035 AH0
Flow Switch855 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe0
Releasing / Solenoid0Strobe14
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes21
Device TypeQuantityChime0
Tamper Switch/Valves10Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes2
AirSense0
Vesda Alert/Action0Panel Types
Fire Pump0Device typeQuantity
Fume Hood Panic0Workstation1
AED1NCA0
Security Door1NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules7LCD-1600
Trouble Monitors1LCD-801
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=138

&C&F

B-81 Total

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Device Count 8-2025
Nodes: 60, 61, 62, 63
Total # of Fire Panels/WS/DVC4Total # of Releasing Panels- Sapphire0
Total # of Power Supplies76Total # of Releasing Panels- CO223
Total Number of SLC's9
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System116
Alarm Initiating Devices/PointsBatteries
Device typeTOTALSSizeQuantity
Manual Pull Station637 AH34
Fire/CO Multi-Criteria Detector112 AH63
Photo Smoke Detector4218 AH0
Heat Detector726 AH4
Laser Detector035 AH0
Flow Switch2455 AH0
Flame Detector34110 AH0
Beam Smoke Detector0
Gas Detection Interface44Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda Fire 1 / 2112Horn/Strobe23
Releasing / Solenoid23Strobe27
Speakers38
Supervisory Initiating Devices/PointsSpeaker/Strobes287
Device TypeTOTALSChime0
Tamper Switch/Valves40Panic/Strobe0
Duct Detectors83Bells0
Low Air Switch0Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action112Panel Types
Gas Detection Interface42Device typeQuantity
Security Door0Workstation0
AED6NCA0
Fire Pump1NFS2-30302
Releasing23NFS2-6400
NFS-3200
Miscellaneous Initiating Devices/PointsDVC2
Device TypeTOTALSLCD-1601
Relays/Control Modules149LCD-800
Trouble Monitors181
Non-Fire Modules26
Liquid Level0Totals From Above=1725
Air Flow0
Pendant2
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Main, Device Count 8-2025
Nodes: 60, 61
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies18Total # of Releasing Panels- CO20
Total Number of SLC's2
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System98
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station267 AH28
I-Quad Smoke Acclimate Det.112 AH8
Photo Smoke Detector4018 AH0
Heat Detector726 AH2
Laser Detector035 AH0
Flow Switch1355 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface- O23Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda2Horn/Strobe0
Releasing0Strobe27
Speakers38
Supervisory Initiating Devices/PointsSpeaker/Strobes237
Device TypeQuantityChime0
Tamper Switch/Valves29Panic/Strobe0
Duct Detectors/Smokes79Bells0
Low Air Switch0Outside Horn/ Strobes1
AirSense0
Vesda Alert/Action2Panel Types
Fire Pump Points4Device typeQuantity
Fume Hood Panic0Workstation0
AED5NCA0
Security Door0NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules86LCD-1601
Trouble Monitors14LCD-800
Non-Fire Modules15
Liquid Level0
Air Flow0Totals From Above=790
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Cleanroom, Device Count 8-2025
Nodes: 62, 63
Total # of Fire Panels/WS/DVC2Total # of Releasing Panels- Sapphire0
Total # of Power Supplies58Total # of Releasing Panels- CO223
Total Number of SLC's7
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System18
Alarm Initiating Devices/PointsBatteries
Device typeTOTALSSizeQuantity
Manual Pull Station377 AH6
I-Quad Smoke Acclimate Det.012 AH55
Photo Smoke Detector218 AH0
Heat Detector026 AH2
Laser Detector035 AH0
Flow Switch1155 AH0
Flame Detector34110 AH0
Beam Smoke Detector0
Gas Detection Interface41Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda Fire 1 / 2110Horn/Strobe23
Releasing23Strobe0
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes50
Device TypeTOTALSChime0
Tamper Switch/Valves11Panic/Strobe0
Duct Detectors4Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action110Panel Types
Gas Detection Interface42Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door0NFS2-30301
Releasing23NFS2-6400
NFS-3200
Miscellaneous Initiating Devices/PointsDVC1
Device TypeTOTALSLCD-1600
Relays/Control Modules63LCD-800
Trouble Monitors167
Non-Fire Modules11
Liquid Level0Totals From Above=939
Air Flow0
Pendant3
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Cleanroom, Device Count 2-2019
Nodes: 62, 63
Alarm Initiating Devices/Points
Device typeSLC 1SLC 2SLC 3
Manual Pull Station121011
I-Quad Smoke Acclimate Det.000
Photo Smoke Detector100
Heat Detector000
Laser Detector000
Flow Switch344
Flame Detector111310
Beam Smoke Detector000
Gas Detection Interface000
Kitchen Hood/Ansul000
AirSense000
Vesda Fire 1 / 2181216
Releasing968
Supervisory Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3
Tamper Switch/Valves344
Duct Detectors000
Low Air Switch000
AirSense000
Vesda Alert/Action181216
Gas Detection Interface000
Fume Hood Panic000
AED001
Security Door000
Releasing968
Miscellaneous Initiating Devices/Points
Device TypeSLC 1SLC 2SLC 3
Relays/Control Modules121
Trouble Monitors231824
Non-Fire Modules344
Liquid Level000
Air Flow000
Pendant003
NIST/Boulder - Building 81 Cleanroom - Page 4 of 6
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Cleanroom, Device Count 2-2019
Nodes: 62, 63
Alarm Initiating Devices/Points
Device typeSLC 4SLC 5SLC 6
Manual Pull Station000
I-Quad Smoke Acclimate Det.000
Photo Smoke Detector000
Heat Detector000
Laser Detector000
Flow Switch000
Flame Detector000
Beam Smoke Detector000
Gas Detection Interface3380
Kitchen Hood/Ansul000
AirSense000
Vesda Fire 1 / 202440
Releasing000
Supervisory Initiating Devices/Points
Device TypeSLC 4SLC 5SLC 6
Tamper Switch/Valves000
Duct Detectors000
Low Air Switch000
AirSense000
Vesda Alert/Action02440
Gas Detection Interface3480
Fume Hood Panic000
AED000
Security Door000
Releasing000
Miscellaneous Initiating Devices/Points
Device TypeSLC 4SLC 5SLC 6
Relays/Control Modules010
Trouble Monitors341620
Non-Fire Modules000
Liquid Level000
Air Flow000
Pendant000
NIST/Boulder - Building 81 Cleanroom - Page 5 of 6
FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 81 Cleanroom, Full Device Count 2-2019
Nodes: 62, 63
Alarm Initiating Devices/Points
Device typeSLC 7
Manual Pull Station4
I-Quad Smoke Acclimate Det.0
Photo Smoke Detector1
Heat Detector0
Laser Detector0
Flow Switch0
Flame Detector0
Beam Smoke Detector0
Gas Detection Interface0
Kitchen Hood/Ansul0
AirSense0
Vesda Fire 1 / 20
Releasing0
Supervisory Initiating Devices/Points
Device TypeSLC 7
Tamper Switch/Valves0
Duct Detectors4
Low Air Switch0
AirSense0
Vesda Alert/Action0
Gas Detection Interface0
Fume Hood Panic0
AED0
Security Door0
Releasing0
Miscellaneous Initiating Devices/Points
Device TypeSLC 7
Relays/Control Modules58
Trouble Monitors32
Non-Fire Modules0
Liquid Level0
Air Flow0
Pendant0

&C&F

B-92 Node 92

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. 92, Device Count 8-2025
Nodes: 92, 93
Total # of Fire Panels/WS/DVC2Total # of Releasing Systems- Sapphire3
Total # of Power Supplies6Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's0
Total Number Of Notification Circuits on Entire System18
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station157 AH2
Fire/CO Multi-Criteria Detector012 AH14
Photo Smoke Detector218 AH0
Heat Detector026 AH2
Laser Detector035 AH0
Flow Switch055 AH0
Flame Detector0110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda Fire 1 / 212Horn/Strobe6
Releasing / Solenoid8Strobe6
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes24
Device TypeQuantityChime0
Tamper Switch/Valves8Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes8
AirSense0
Vesda Alert/Action8Panel Types
Releasing0Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door0NFS2-30301
NFS2-6400
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC1
Relays/Control Modules21LCD-1600
Trouble Monitors15LCD-800
Non-Fire Modules8
Liquid Level0
Air Flow0Totals From Above=192

&C&F

Bldg. WWV

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. WWV, Full Device Count 8-2025
Nodes: N/A
Total # of Fire Panels/WS/DVC1Total # of Releasing Panels- Sapphire2
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's4
Total Number Of Notification Circuits on Entire System4
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station77 AH4
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector2718 AH4
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch055 AH0
Flame Detector1110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe13
Releasing / Solenoid2Strobe16
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes0
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action0Panel Types
Releasing2Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door0NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC0
Relays/Control Modules0LCD-1600
Trouble Monitors6LCD-800
Non-Fire Modules0
Liquid Level0
Air Flow0Totals From Above=96

&C&F

Bldg. WWVB

FIRE ALARM SYSTEM INSPECTION REPORT
NIST Bldg. WWVB, Full Device Count 8-2025
Nodes: N/A
Total # of Fire Panels/WS/DVC1Total # of Releasing Panels- Sapphire2
Total # of Power Supplies0Total # of Releasing Panels- CO20
Total Number of SLC's1
Total Number of IDC's4
Total Number Of Notification Circuits on Entire System4
Alarm Initiating Devices/PointsBatteries
Device typeQuantitySizeQuantity
Manual Pull Station77 AH4
Fire/CO Multi-Criteria Detector012 AH0
Photo Smoke Detector2118 AH2
Heat Detector026 AH0
Laser Detector035 AH0
Flow Switch055 AH0
Flame Detector1110 AH0
Beam Smoke Detector0
Gas Detection Interface0Alarm Notification Appliances
Kitchen Hood/Ansul0Device typeQuantity
AirSense0Horns0
Vesda0Horn/Strobe9
Releasing / Solenoid2Strobe13
Speakers0
Supervisory Initiating Devices/PointsSpeaker/Strobes0
Device TypeQuantityChime0
Tamper Switch/Valves0Panic/Strobe0
Duct Detectors0Bells0
Low Air Switch0Outside Horn/ Strobes0
AirSense0
Vesda Alert/Action0Panel Types
Releasing Panel2Device typeQuantity
Fume Hood Panic0Workstation0
AED1NCA0
Security Door0NFS2-30300
NFS2-6401
Miscellaneous Initiating Devices/PointsNFS-3200
Device TypeQuantityDVC0