This is a bidding set of architectural and engineering design documents for a mechanical exhaust system project at the FDA's Southwest Pacific Laboratory facility in Irvine, California. The project, issued by GSA's Office of Design & Construction/Special Programs Division with Contracting Officer Kalish Poole and Project Manager Demian Go, P.E., involves designing and installing mechanical equipment, ductwork, and controls to reduce vaporized hydrogen peroxide (VHP) concentrations generated by laboratory isolator equipment in Room 2309. The system will convey VHP and room air from isolator exhaust ports to rooftop stacks via dedicated exhaust ductwork and includes limited architectural and electrical modifications to support the mechanical system, as well as integration and modifications to the existing Building Automation System (BAS) and HVAC systems.
The bid set includes comprehensive design documentation dated June 20, 2025 (updated August 15, 2025) covering architectural floor plans and reflected ceiling plans, structural details for roof penetrations and ductwork bracing, mechanical equipment schedules and control diagrams, electrical power distribution and conduit routing, and full construction details. Key technical specifications include one 14-15 inch diameter roof penetration through a 7-inch concrete slab with minimal reinforcement required, stainless steel 316L ductwork for hydrogen peroxide corrosion resistance, two Greenheck USF-4-B6 centrifugal exhaust fans (600 CFM each at 1.5 inches H₂O static pressure), vibration isolation mounting, and integration with existing VAV and control systems. The project requires coordination with existing isolator equipment, careful management of ceiling penetrations and roof slab cutting with encapsulation provisions to protect the occupied laboratory space and mission-critical equipment, and compliance with applicable codes including the California Building Code, AISC 360, ACI 318, ASCE 7, and AWS welding standards. Construction details address duct bracing to structural elements, weather-resistant flashing, proper support for roof-mounted equipment, and detailed electrical connections for the exhaust fans with separate 208V three-phase power connections and VFD controls.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The Miller Hull Partnership, LLP
POINT LOMA MARINA 4980 NORTH HARBOR DRIVE, SUITE 100 SAN DIEGO, CA 92106
PROJECT IDENTIFICATION
REGION: CO
DIVISION: GSA OFFICE OF DESIGN & CONSTRUCTION / SPECIAL PROGRAMS DIVISION
BUILDING NAME: SOUTHWEST PACIFIC LABORATORY
ADDRESS: 19701 FAIRCHILD RD IRVINE, CA 92612
CONTRACTING OFFICER: KALISH POOLE
PROJECT MANAGER: DEMIAN GO P.E.
VICINITY MAP LOCATION MAP
FDA IRVINE
BID SET
JUNE 20, 2025
RM 2309 EXHAUST DESIGN
SHEET INDEX
NO. SHEET NAME
G.000 COVER SHEET
A.000 LEGENDS, NOTES & ABBREVIATIONS
A.100 FLOOR PLANS
A.102 SLAB PLAN
A.300 BUILDING SECTIONS
A.310 WALL SECTIONS
AD.100 DEMOLITION PLANS
S.001 ABBREVIATIONS AND LEGENDS
S.002 GENERAL NOTES
S.101 ROOF LEVEL DRAWINGS AND DETAILS
S.102 SHED ROOF LEVEL DRAWINGS AND DETAILS
S.601 SECTIONS AND DETAILS
M.001 SYMBOL & GENERAL NOTES - MECHANICAL
M.101 FLOOR PLANS - MECHANICAL
M.201 PARTIAL FLOOR PLANS - MECHANICAL
M.301 SECTIONS - MECHANICAL
M.401 SCHEDULE & DIAGRAM - MECHANICAL
M.402 DIAGRAM & DETAILS - MECHANICAL
E.001 SYMBOL & GENERAL NOTES - ELECTRICAL
E.101 FLOOR PLANS - ELECTRICAL
E.501 SINGLE LINE DIAGRAMS - ELECTRICAL
E.601 SCHEDULES - ELECTRICAL
PROJECT SUMMARY: THIS PROJECT IS FOR MECHANICAL EQUIPMENT, DUCTWORK AND CONTROLS TO REDUCE CONCENTRATION OF VAPORIZED HYDROGEN PEROXIDE (VHP) GENERATED BY LABORATORY ISOLATOR EQUIPMENT IN ROOM 2309. VHP AND ROOM AIR WILL BE CONVEYED FROM THE EQUIPMENT EXHAUST PORTS TO ROOF TOP STACKS VIA DEDICATED EXHAUST SYSTEM. PROJECT INCLUDES LIMITED ARCHITECTURAL AND ELECTRICAL MODIFICATIONS TO EXISTING SYSTEMS TO SUPPORT MECHANICAL EXHAUST SYSTEM PROPOSED. PROPOSED EXHAUST SYSTEM WILL ALSO REQUIRE INTEGRATION AND MODIFICATIONS TO THE EXISTING BUILDING AUTOMATION SYSTEM (BAS) AND HVAC SYSTEM FOR THE ROOM, AS WELL AS THE
INTEGRATION OF THE EXISTING ROOM 2309 LABORATORY CONTROLS WITH THE EXISTING BAS.
AUGUST 15, 2025
S D
S D
S D
S D
S D
S D
ROOM IDENTIFICATION
BUILDING SECTION
WALL SECTION
EXTERIOR ELEVATION
DRAWING NUMBER, REFERENCE
SHEET & TITLE
GRID LINE
A101
SIM.
DETAIL NUMBER OVER
SHEET NUMBER
ABOVE, BELOW OR HIDDEN
INTERIOR ELEVATION
A
A211
A301
NORTH ARROW
TRUE
NORTH
PLAN
NORTH
A201
A211
A20
OFFICE
DRAWING NUMBER & TITLE1 View Title 1/8" = 1'-0"A201
1 View Title 1/8" = 1'-0"A101 A201
0' 4' 8' 16'
GRAPHIC DRAWING SCALE
SYMBOLS LEGEND
1D
1E 1F
20 A1
21 22 23 24 25 26 27 28
3A
3B
3C1A
1B
1C
2C
2B
2A
3LL
3D
2D
AREA OF WORK
1D
1E 1F
20 A1
21 22 23 24 25 26 27 28
3A
3B
3C1A
1B
1C
2C
2B
2A
3LL
3D
2D
AREA OF WORK
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
SG
03/14/25
LEGENDS,
NOTES &
ABBREVIATIONS
FDA IRVINE
A.000
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
ABBREVIATIONS
NOTE: ABBREVIATIONS NOTED IN THE DRAWINGS THAT ARE FOLLOWED BY A MODIFIER
SUCH AS "-1", "-A" ARE FURTHER DEFINED IN THE SPECIFICATIONS SECTION ASSOCIATED
WITH THE MATERIAL OR SYSTEM ASSEMBLY AS NOTED. REFERENCE FINISH LEGEND A070
RCP REFLECTED CEILING PLAN
ABV ABOVE
ACIP ARCHITECTURAL CAST-IN-PLACE
CONCRETE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ARCHITECTURAL (TECT)
AV AUDIO VISUAL
AVG AVERAGE
BLDG BUILDING
BO BOTTOM OF
C COLUMN
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
CTR CENTER
CW CURTAIN WALL, COLD WATER
D DEPTH
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG DRAWING
DWR DRAWER
(E) EXISTING
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EQ EQUAL
EW EXTERIOR WALL
EXT EXTERIOR
F FLOOR
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAPB FIRE ALARM PULL BOX
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FEC FIRE EXTINGUISHER CABINET
FEXT FIRE EXTINGUISHER
FF FINISHED FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FO FACE OF
FOF FACE OF FINISH
FOIC FURNISHED BY OWNER INSTALLED BY
CONTRACTOR
FOIO FURNISHED BY OWNER INSTALLED BY
OWNER
FRT FIRE RETARDENT TREATED (INTERIOR)
FS FIRE SPRINKLER
FT FOOT, FEET
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFRC GLASS FIBER REINFORCED CONCRETE
GWB GYPSUM WALL BOARD
GYP GYPSUM
HDW HARDWARE
HM HOLLOW METAL
HO HOLD OPEN
HORIZ HORIZONTAL
HR HOUR
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
HW HOT WATER
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IN INCH(ES)
INCL INCLUDE(D), INCLUDING, INCLUSIVE
INSUL INSULATION
INT INTERIOR
IW INTERIOR WALL
JAN JANITOR
K 100 POUNDS (KIP)
KSI KIPS PER SQUARE INCH
KW KILOWATTS
L ANGLE STEEL MEMBER
LAB LABORATORY
LAV LAVATORY
LB POUND(S)
LF LINEAR FEET
LH LEFT HAND
LIN LINEAL
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEZZ MEZZANINE
MIN MINIMUM, MINUTE(S)
MISC MISCELLANEOUS
N NORTH
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
OTS OPEN TO STRUCTURE
PCF POUNDS PER CUBIC FOOT
PERF PERFORATE(D)
PL PLATE
PNT PAINT
PREFAB PREABRICATED
PREFIN PREFINISHED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT, POST TENSIONED, PRESSURE
TREATED
QTY QUANTITY
REBAR REINFORCING BAR
REF REFERENCE
REQD REQUIRED
REV REVISED, REVISION
RM ROOM
RO ROUGH OPENING
ROW RIGHT-OF-WAY
RR RESTROOM
S SOUTH
SAM SELF ADHERED MEMBRANE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SIM SIMILAR
SOG SLAB-ON-GRADE
SPEC SPECIFICATION
SS STAINLESS STEEL
ST STAIR, STREET
STC SOUND TRANSMISSION CLASS
STOR STORAGE
STRUCT STRUCTURE (AL)
TEL TELEPHONE
TEMP TEMPORARY, TEMPERATURE
TO TOP OF
TOC TOP OF CONCRETE
TOP TOP OF PARAPET
TOPO TOPOGRAPHIC MAP
TOS TOP OF STEEL, TOP OF SLAB
TPO THERMOPLASTIC POLYOLEFIN
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
UNO UNLESS NOTED OTHERWISE
UV ULTRAVIOLET
V VOLT
VERT VERTICAL
VG VERTICAL GRAIN
VIF VERIFY IN FIELD
VOL VOLUME
VTR VENT THROUGH ROOF
W WEST, WIDE
WC WATER CLOSET
WRB WEATHER RESISTIVE BARRIER
• NFPA 70 National Electric Code
• NFPA 101 Life Safety Code
• ADA/ABA Accessibility Guidelines (www.access-board.gov)
• ANSI/BOMA Z65.1 Measuring Guide (www.BOMA.org)
• International Building Code (www.intlcode.org)
• National CAD Standard (www.nationalcadstandards.org)
• International Fire Code (www.intlcode.org)
• International Plumbing Code (www.intlcode.org)
• International Mechanical Code (www.intlcode.org)
• International Energy Conservation Code (www.intlcode.org)
• Construction Industry Standards (OSHA 2207)
• OSHA Safety and Health Standards (29 CFR 1926/1910)
• Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks, ASME A17.1
• Construction Management Association of America (CMAA) Construction Management Standards of
Practice plus related manuals (Quality Control Procedures, Cost Management Procedures, Contract Administration Procedures, Time Management Procedures)
• Occupational Safety and Health Administration (OSHA) Standards.
• Elevator Code - ANSI/ASME A17.1 Safety Code for Elevators and Escalators, & supplements.
• National Fire Protection Association (NFPA) handbooks including the National Electric Code.
• Uniform Building Code, Chapter 23
• Standard Building Code, Appendix D
• BOCA Building Code
APPLICABLE CODES
REFERENCE DESIGN STANDARDS
• National Insititues of Health Design Requirements Manual 1 (Rev 2.1 08/02/24)
• National Insititues of Health Design Requirements Manual 2 (Rev 1.5 12/12/16)
ROOF KEY PLAN
LEVEL 2 KEY PLAN
4. DEMOLITION CONSIDERATIONS
SPECIFICATIONS AND DEMOLITION PLANS MUST INCLUDE PROVISIONS FOR SAFE ENCAPSULATION
DURING ROOF SLAB CUTTING TO PROTECT THE OCCUPIED LABORATORY SPACE AND MISSION-
CRITICAL EQUIPMENT.
5. INTERIOR FINISHES & LIGHTING
• MECHANICAL DUCTS AND FITTINGS TO BE ROUTED THROUGH THE
EXISTING CEILING USING EXISTING PANELS OR SHEET METAL
PENETRATION PLATES.
• EXISTING INTERIOR LIGHTING TO BE MAINTAINED.
Photos of space above ceiling showing hangers, underside of roof slab, and ductwork.
Photos of existing ceiling, lighting, and equipment in Room 2309.
BASIS OF DESIGN
1. INTRODUCTION
THIS BASIS OF DESIGN DOCUMENT ESTABLISHES THE KEY STRUCTURAL AND MECHANICAL
CONSIDERATIONS FOR THE PROPOSED MODIFICATIONS TO THE EXISTING BUILDING. THE
INFORMATION HEREIN IS BASED ON FINDINGS FROM THE SITE VISIT CONDUCTED BY MILLER HULL AND
INTERFACE ENGINEERS ON DECEMBER 11, 2024.
2. STRUCTURAL CONSIDERATIONS
2.1 MAIN ROOF STRUCTURE
• THE EXISTING MAIN ROOF CONSISTS OF A 7-INCH CONCRETE SLAB SUPPORTED BY CONCRETE
BEAMS. NO BEAMS ARE PRESENT IN THE IMMEDIATE VICINITY OF THE PROPOSED SLAB
PENETRATIONS.
• REINFORCING IN THE SLAB IS SPACED AT APPROXIMATELY 10 INCHES (NORTH-SOUTH) AND 16
INCHES (EAST-WEST).
• A SINGLE 12-INCH BY 12-INCH PENETRATION IS FEASIBLE WITHOUT SLAB STRENGTHENING, PROVIDED SCANNING IS PERFORMED TO ADJUST CORE LOCATIONS TO AVOID EXISTING
REINFORCEMENT.
• A SINGLE 12-INCH BY 12-INCH PENETRATION IS POSSIBLE WITH MINIMAL LOCALIZED
REINFORCEMENT ADDED TO THE UNDERSIDE OF THE SLAB.
• A NEW PREFABRICATED CURB WILL BE ANCHORED TO THE EXISTING SLAB TO. THIS CURB WILL
SERVE WATERPROOFING AND STRUCTURAL SUPPORT PURPOSES FOR THE NEW UNITS AND
DUCTWORK, IF REQUIRED.
• THE ADDED CURB AND NEW UNITS (EACH ESTIMATED AT 300 POUNDS MAX) ARE EXPECTED TO BE
ACCOMMODATED BY THE EXISTING SLAB WITHOUT REINFORCEMENT, PENDING STRUCTURAL
ANALYSIS UPON FINAL LAYOUT CONFIRMATION.
2.2 PENTHOUSE ROOF STRUCTURE
• THE EXISTING PENTHOUSE ROOF CONSISTS OF BARE STEEL DECKING SUPPORTED BY STEEL
FRAMING.
• ROOF DECK PENETRATIONS ARE ALLOWED WITH MINOR LOCALIZED REINFORCEMENT TO STIFFEN
THE DECKING.
• NO STEEL BEAMS ARE DIRECTLY IN LINE WITH THE PROPOSED PENETRATIONS, BUT EXISTING
STEEL BRIDGING (RUNNING NORTH-SOUTH AT THIRD POINTS BETWEEN THE MAIN PENTHOUSE
ROOF GIRDERS) MUST BE AVOIDED.
• THE ROOF DECKING IS EXPECTED TO SUPPORT CABLING FOR BRACING THE UPPER PORTION OF
THE EXHAUST STACK, ASSUMING THE STACK EXTENDS LESS THAN 6 FEET ABOVE THE ROOF
DECK.
• BRACING TO THE EXTERIOR CLADDING SYSTEM SHOULD BE AVOIDED.
2.3 PENTHOUSE EXTERIOR WALL
• THE PENTHOUSE EXTERIOR WALL IS EXPECTED TO BE PLASTER ON METAL STUDS (TO BE
VERIFIED IN THE FIELD).
• THIS WALL CAN LIKELY BE USED FOR LATERAL BRACING OF THE EXHAUST DUCTS AND FOR
SUPPORTING SMALL EQUIPMENT (UP TO 50 POUNDS).
• HEAVIER EQUIPMENT MAY REQUIRE ADDITIONAL STRUCTURAL SUPPORT, LIKELY CONSISTING OF A
UNISTRUT SYSTEM.
3. MECHANICAL CONSIDERATIONS
3.1 ROOF PENETRATIONS
• QUANTITY: ONE (1) ROOF PENETRATION.
• SIZE: 14–15 INCHES IN DIAMETER.
3.2 DUCTING
• MATERIAL: UV-STABLE PLASTIC, NON-INSULATED, WITH A POTENTIAL STAINLESS STEEL SHROUD.
• CORROSION RESISTANCE: 316 STAINLESS STEEL IS THE TYPICAL MECHANICAL MATERIAL USED TO
RESIST HYDROGEN PEROXIDE EXPOSURE.
3.3 EQUIPMENT SUPPORT
• CURBS WILL BE PROVIDED AROUND PENETRATIONS TO SUPPORT SMALL ROOF FANS (MAXIMUM
300 LBS EACH).
• THE EXHAUST DUCT WILL EXTEND AT LEAST 6 INCHES ABOVE THE EXISTING MECHANICAL
SCREEN. THE VERTICAL DUCT WILL REQUIRE SUPPORT OFF THE BACK WALL USING UNISTRUT.
3.4 BUILDING AUTOMATION SYSTEM (BAS) INTEGRATION
• SCOPE TBD: WORK RELATED TO BAS INTEGRATION MAY BE REQUIRED IN OTHER BUILDING AREAS, SUBJECT TO FURTHER REVIEW.
No. Description Date
JUNE 20, 2025AUGUST 15, 2025
STAMP
S D
OUTLINE OF ROOM
2309 BELOW
A.300
A.300
A.300
A.300
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
(E) CONCRETE BEAMS
383736
3B
3C(E) ROOFTOP EQUIPMENT
AND CONDUIT
3B.8
1' - 2"4' - 5"2' - 10"3' - 5" 2' - 10" 2' - 6 1/2"
1'
1'
1'
1'
1/ 2"
(E) ROOF DRAIN AND
CRICKETING
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
A.600
1'
1'
1/ 2"
(E) CONDUIT
RESEARCH LAB
A.300
A.300
383736
3B
3C
(E) ISOLATOR EQUIPMENT
BELOW SHOWN DASHED
(E) HYDROPHOBIC,
SMOOTH SURFACED,
GWB CEILING TILES
3B.8
NEW EXHAUST DUCTS
PER MECHANICAL
A.600
(E) CEILING FIXTURES AND
EQUIPMENT, VIF
NEW EXHAUST GRILL PER
MECHANICAL
A.300
A.300
A.300
A.300 383736
3B
3C
3B.8
(E) CROSS BRACING
BELOW
DUCT PENETRATION
AND FLASHING
GUY WIRES AND
ANCHORS
VIF
5' - 6" CLR
(E) MECHANICAL
SCREEN
(E) BEAMS BELOW
(E) PREFINISHED
METAL ROOFING
4' - 9" 11" 11" 3' - 11"
GENERAL NOTES
1. PROTECT IN PLACE ALL EXISTING TO REMAIN EQUIPMENT, LIGHT FIXTURES,
AND DEVICES.
2. CONTRACTOR TO VIF LOCATIONS OF ISOLATORS AND COORDINATE IN FIELD
ALL CEILING PENETRATIONS TO MAINTAIN REQUIRED CLEARANCES BETWEEN
ISOLATOR EXHAUST CONNECTIONS AND PENETRATIONS.
(E) RECESSED LIGHT FIXTURE
(E) SUSPENDED T-GRID & CEILING
(E) MECHANICAL GRILL
REFLECTED CEILING PLAN
LEGEND
NEW MECHANICAL GRILL
(E) CEILING FIXTURES AND EQUIPMENT
1/8" = 1'-0"A.100
2 ROOF - ABV RM 2309 - PLAN
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
12/19/24
FLOOR PLANS
FDA IRVINE
A.100
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1/8" = 1'-0"A.100
1 LEVEL 2 - RM 2309 - REFLECTED CEILING PLAN
1/8" = 1'-0"A.100
3 HIGH ROOF - ABV RM 2309 - PLAN
0' 4' 8' 16'
No. Description Date
A.300
A.300
A.300
A.300
3C
3B.8
10' - 8" 1' - 2"
OUTLINE OF ROOM
2309 BELOW
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
(E) ROOFTOP EQUIPMENT
(E) ROOF DRAIN AND
CRICKETING
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
1' - 2"10' - 8"
1'
1'
OUTLINE OF NEW
CURBS
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
12/19/24
SLAB PLAN
FDA IRVINE
A.102
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1/4" = 1'-0"A.102
1 ROOF SLAB PLAN
0' 2' 4' 8'
No. Description Date
LEVEL 2
17' - 0 1/2"
ROOF
34' - 1 1/2"
RESEARCH LAB
A.300
A.300
CONCRETE SLAB PENETRATION
38 37
HIGH ROOF
47' - 2 11/16"
T.O. SCREEN
47' - 6 5/8"
(E) ISOLATORS
DUCTS PER MECHANICALCLR
1' - 2"
(E) CONCRETE SLAB
A.600
DUCT SUPPORTS PER MECHANICAL
PREFABRICATED CURB AND
PENETRATION FLASHING
ROOF DECK PENETRATION
FOR EXHAUST DUCT
EXHAUST DUCT SUPPORTS
ATTACHED TO METAL DECK
MECHANICAL CURB
LEVEL 2
17' - 0 1/2"
ROOF
34' - 1 1/2"
A.300
A.300
ROOF DECK PENETRATION
FOR EXHAUST DUCT
PENETRATION THROUGH (E)
CONCRETE SLAB
RESEARCH LAB
(E) STEEL FRAMED METAL ROOF
DECK. COORDINATE BETWEEN
ROOF RIB LOCATIONS
(E) EXTERIOR PARTITION
EXHAUST DUCT SUPPORTS
ATTACHED TO METAL DECK AND
(E) BEAMS
DUCT BRACING WITH UNISTRUT
PER MECHANICAL AND
STRUCTURAL
A.310 3B3C
HIGH ROOF
47' - 2 11/16"
3B.8
(E) CEILING
NEW MECHANICAL DUCT
(E) ISOLATOR EQUIPMENT
(E) CONCRETE BEAM BEYOND
A.600
SIM
A.600
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
02/21/2025
BUILDING
SECTIONS
FDA IRVINE
A.300
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1/4" = 1'-0"A.300
1 SECTION 1
1/4" = 1'-0"A.300
2 SECTION 2
0' 2' 4' 8'
No. Description Date
JUNE 20, 2025AUGUST 15, 2025
RESEARCH LAB
A.300
CO
38 37
(E)
DUCLR
1' - 2"
(E)
A.600
DU
PR
PE
RO
FO
EX
AT
ME
LEVEL 2
17' - 0 1/2"
ROOF
34' - 1 1/2"
A.300
ROOF DECK PENETRATION
FOR EXHAUST DUCT
PENETRATION THROUGH (E)
CONCRETE SLAB
RESEARCH LAB
(E) STEEL FRAMED METAL ROOF
DECK. COORDINATE BETWEEN
ROOF RIB LOCATIONS
(E) EXTERIOR PARTITION
EXHAUST DUCT SUPPORTS
ATTACHED TO METAL DECK AND
(E) BEAMS
DUCT BRACING WITH UNISTRUT
PER MECHANICAL AND
STRUCTURAL
A.310 3B3C
HIGH ROOF
47' - 2 11/16"
3B.8
(E) CEILING
NEW MECHANICAL DUCT
(E) ISOLATOR EQUIPMENT
(E) CONCRETE BEAM BEYOND
A.600
SIM
A.600
ROOF
34' - 1 1/2"
(E) CONCRETE CURB IS 8" WIDE X 18" TALL
(E) PARTITION: 92 MM METAL STUD WALL
WITH PLASTER COVERING
(E) 7" MILD CONCRETE SLAB TYPICAL AT
MAIN ROOF
NEW MECHANICAL DUCT
(E) CONCRETE BEAMS
24" WIDE X 19" DEEP (INCLUDES 7" SLAB)
DUCT BRACING WITH UNISTRUT
ATTACHED TO BACK WALL
HIGH ROOF
47' - 2 11/16"
T.O. SCREEN
47' - 6 5/8"
3B.8
A.600
A.600
A.600
A.600
C CHANNEL PER STRUCTURAL
EXHAUST DUCT SUPPORTS ATTACHED
TO METAL DECK
EXHAUST FAN AND DUCTWORK PER
MECHANICAL
WALL MOUNTED ELECTRICAL SWITCH
(E) TRAFFIC COATING
(E) BITUMINOUS BUILT-UP ROOFING
6" 1' 2'0"
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
01/06/25
WALL
SECTIONS
FDA IRVINE
A.310
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1" = 1'-0"A.310
1 SECTION DTL - EXHAUST DUCT AT ROOF
No. Description Date
JUNE 20, 2025AUGUST 15, 2025
.600
A
A.600
A.600
1/4" CABLE PER STRUCTURAL
(E) STRUCTURAL BEAM
(E) PREFORMED METAL
ROOFING
(E) PLASTER WALL BEYOND
WELDED CONNECTION PER
STRUCTURAL
1' -6
M
A X
GALVANIZED HSS AND
WELDED HINGE PER
STRUCTURAL
SS METAL FLASHING AND
COUNTER FLASHING
SS DRAWBAND
SEALANT
FLASHING SET IN MASTIC
(E) PLASTER WALL
DUCT PER MECHANICAL
UNISTRUT
ROUND CEILING TRIM COLLAR
(E) HYDROPHOBIC, SMOOTH
SURFACED, GWB CEILING
TILES
(E) ISOLATOR
RIDGED DUCT PER MECHANICAL
FLEX DUCT PER MECHANICAL
DUCT PER MECHANICAL
SS METAL FLASHING AND
COUNTER FLASHING
(E) PREFINISHED METAL
ROOFING
SEALANT
SS DRAWBAND
FLASHING SET IN MASTIC
(E) CONCRETE FLOOR SLAB
PREFABRICATED INSULATED
ROOF CURB
P E
R N
R C
A R
O O
F
IN
G M
A N
U A
L
8" M
IN
BUILT UP ROOF AND
INSULATION
METAL FLASHING
DUCT PER MECHANICAL
(E) CONCRETE FLOOR SLAB
DUCT SUPPORT PER MECHANICAL
4" M
IN
WOOD CANT STRIP
2" 4" 8"0"
(E) PLASTER WALL
DUCT PER MECHANICAL
UNISTRUT PER STRUCTURAL
ATTACH UNISTRUT TO (E) STUDS
DUCT STRAP
4" MIN
(E) CONCRETE FLOOR SLAB
(E) BUILT UP ROOF AND
INSULATION
METAL FLASHING
WOOD CANT STRIP
WOOD 6X6 BLOCKING
COUNTERSUNK POST
INSTALLED ANCHOR
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
01/06/25
DETAILS
FDA IRVINE
A.600
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
3" = 1'-0"A.600
8 GUY WIRE CONNECTION
3" = 1'-0"A.600
5 DUCT BRACING - SECTION
3" = 1'-0"A.600
3 DUCT @ CEILING
3" = 1'-0"A.600
11 DUCT @ PREFORMED METAL
3" = 1'-0"A.600
1 CONCRETE SLAB PENETRATION
3" = 1'-0"A.600
10 DUCT BRACING - PLAN
3" = 1'-0"A.600
13 FAN CURB
No. Description Date
S D
A.300
A.300
A.300
A.300 383736
3B
3C
3B.8
D.03
(E) CROSS BRACING
BELOW
(E) MECHANICAL
SCREEN
4' - 9" 11" 11" 3' - 11"
D.03
A.300
A.300
A.300
A.300 383736
3B
3C
3B.8
1'
1'
1' - 2"10' - 8"
D.02
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
(E) ROOFTOP EQUIPMENT
(E) ROOF DRAIN AND
CRICKETING
(E) W10X45 STEEL
COLUMN ON 18"
CONCRETE ENCASEMENT
383736
3B
3C
3B.8
RESEARCH LAB
(E) HYDROPHOBIC,
SMOOTH SURFACED,
GWB CEILING TILES
D.04
D.01 D.01 D.01
DEMOLITION KEYNOTES
D.01
D.02
D.03
MODIFY CEILING TILE FOR NEW DUCTWORK
PENETRATION
CREATE NEW OPENING IN EXISTING CONCRETE SLAB
CREATE NEW OPENING IN EXISTING METAL ROOF
D.04 REMOVE AND REPLACE CEILING TILES AND GRID AS
REQUIRED TO PERFORM WORK SHOWN ON
MECHANICAL DRAWINGS. REPLACE ANY DAMAGED
TILES WITH NEW TO MATCH EXISTING IN SIZE, TYPE,
AND COLOR.
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
NOT FOR
CONSTRUCTIO
N
STAMP
KEY PLAN
C
R e v it P ro je c ts
\F D
A I
R V
M
H P
R
-s g e ib e l-
.r v t
/1
/2
:4 :3
P
M
A21.0030.01
KC
CT
12/19/24
DEMOLITION
PLANS
FDA IRVINE
AD.100
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1/8" = 1'-0"AD.100
1 HIGH ROOF - ABV RM 2309 - DEMO PLAN
1/8" = 1'-0"AD.100
2 ROOF - ABV RM 2309 - DEMO PLAN
1/8" = 1'-0"AD.100
3 LEVEL 2 - RM 2309 - DEMO REFLECTED CEILING PLAN
0' 4' 8' 16'
No. Description Date
SECT
S.3
& AND
@ AT
°, DEG DEGREE
ø, DIA DIAMETER
# NUMBER, POUND
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURAL EXPOSED
STRUCTURAL STEEL
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPD APPROVED
APPROX APPROXIMATE
AR ANCHOR RODS
ARCH ARCHITECTURAL; ARCHITECT
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
BAL BALANCE
BD BOARD
BF BRACED FRAME
BLDG BUILDING
BLK BLOCK; BLOCKING
BM BEAM
BMU BRICK MASONRY UNIT
BOS BOTTOM OF STEEL; BOSOM (WELD)
BOT BOTTOM
BRB BUCKLING RESTRAINED BRACE
BRCG BRACING
BRG BEARING
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BU BUILT-UP
c CAMBER
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION WELD
CL CENTERLINE
CLR CLEARANCE; CLEAR
CLT CROSS LAMINATED TIMBER
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPRESSION
CONC CONCRETE
CONFIG CONFIGURATION
CONN CONNECTION; CONNECT
CONST CONSTRUCTION
CONT CONTINUE; CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE; COORDINATION
CORR CORRUGATED
CTR CENTER
CTSK COUNTERSINK; COUNTERSUNK
CU CUBIC
d PENNY (NAIL) db NOMINAL BAR DIAMETER (INCHES)
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DC DEMAND CRITICAL WELD
DEG, ° DEGREE
DEMO DEMOLISH; DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA, ø DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DICA DRILLED-IN CONCRETE ANCHOR
DIM DIMENSION
DISC DISCONTINUED; DISCONTINUOUS
DL DEAD LOAD
DLT DOWEL LAMINATED TIMBER
DN DOWN
DO DO OVER; DITTO
DWG DRAWING
DWL DOWEL
(E) EXISTING
E EAST
E-W EAST-WEST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDDED
ENGR ENGINEER
EQ EQUAL; EARTHQUAKE
EQUIP EQUIPMENT
ES EACH SIDE
ETC ET CETERA
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
EXTD EXTEND; EXTENDED
F DEGREES FAHRENHEIT
FD FLOOR DRAIN
FDN FOUNDATION
FF FAR FACE
FG FRICTION GRIP BOLT
FIN FINISH
FL FLOOR; FLOOR LINE
FLG FLANGE
FOS FACE OF STUD
FP FIREPROOF; FULL PENETRATION
FRMG FRAMING
FS FULL SIZE; FAR SIDE
FT FOOT; FEET; FINGER TIGHT
FTG FOOTING
FV FIELD VERIFY
GA GAGE, GAUGE
GALV GALVANIZED
GB GRADE BEAM
GFRC GLASS FIBER REINFORCED CONCRETE
GL GLUED LAMINATED (BEAM)
GR GRADE
GRND GROUND
H HORIZONTAL
HEF HORIZONTAL EACH FACE
HGR HANGER
HIF HORIZONTAL INSIDE FACE
HOF HORIZONTAL OUTSIDE FACE
HORIZ HORIZONTAL
HP HP SHAPES; HIGH POINT
HS HIGH STRENGTH
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JST JOIST
JT JOINT
K KIP (1,000 POUNDS)
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE
LAB LABORATORY
LB, # POUND
LF LINEAL FOOT
LIN LINEAL; LINEAR
LL LIVE LOAD
LLBB LONG LEGS BACK-TO-BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION; LOCATE
LONGIT LONGITUDINAL
LP LOW POINT
LSL LONG SLOTTED (HOLES)
LSW LIGHT GAGE SHEAR WALL
LTWT LIGHTWEIGHT
LVL LEVEL
LWC LIGHTWEIGHT CONCRETE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL /
PLUMBING
MEZZ MEZZANINE
MF MOMENT FRAME
MFB MOMENT FRAME BEAM
MFC MOMENT FRAME COLUMN
MFR MANUFACTURE; MANUFACTURER
MFRG MANUFACTURING
MIN MINIMUM; MINUTE
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING
MS MECHANICAL SPLICE
N NORTH
N-S NORTH-SOUTH
NF NEAR FACE
NIC NOT IN CONTRACT
NLT NAIL LAMINATED TIMBER
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMALWEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE (HAND)
OPT OPTION; OPTIONAL
OVS OVERSIZED (HOLES)
OWJ OPEN WEB JOIST
P PIPE
PC PRECAST
PCF POUNDS PER CUBIC FOOT
PCP PRECAST CONCRETE PANEL
PEN PENETRATION
PERP PERPENDICULAR
PH PENTHOUSE
PJP PARTIAL JOINT PENETRATION WELD
PL PLATE
PLC PLACE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POST-TENSIONED
PV PHOTOVOLTAICS
PVC POLYVINYL CHLORIDE
R RADIUS
RB RISER BAR
RC REINFORCED CONCRETE
RCMD RECOMMEND
REF REFERENCE
REINF REINFORCE; REINFORCING;
REINFORCEMENT
REQD REQUIRED
REQT REQUIREMENT
S1S SURFACED ONE SIDE
S2S SURFACED TWO SIDES
S4S SURFACED FOUR SIDES
S AMERICAN STANDARD SHAPE; SOUTH
SB SPACER BAR; SUPPORT BAR
SC SLIP CRITICAL
SCC STRUCTURAL CONSULTANT TO
THE CONTRACTOR
SCHED SCHEDULE, SCHEDULED
SDQ SPECIAL DUCTILE QUALITY
SECT SECTION
SEOR STRUCTURAL ENGINEER OF RECORD
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SLBB SHORT LEGS BACK-TO- BACK
SOG SLAB ON GRADE
SOSD SLAB ON STEEL DECK
SP SPIRAL
SPC SPACE
SPCG SPACING
SPEC SPECIFICATION
SQ SQUARE
SSL SHORT SLOTTED (HOLES)
STD STANDARD
STIFF STIFFENER
STIRR STIRRUP
STL STEEL
STR STRAIGHT
STRUC STRUCTURAL
SUPT SUPPORT
SW SHEAR WALL
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T&R TREAD AND RISER
TBD TO BE DETERMINED
TEMP TEMPERATURE; TEMPORARY
THK THICK; THICKNESS
THRU THROUGH
TOC TOP OF CURB; TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TYP TYPICAL
UB UNIVERSAL BEAM
UBC UNIFORM BUILDING CODE
UC UNIVERSAL COLUMN
UL UNDERWRITERS' LABORATORY, INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRASONIC TEST
V, VERT VERTICAL
VEF VERTICAL EACH FACE
VG VERTICAL GRAIN
VIF VERTICAL INSIDE FACE
VOF VERTICAL OUTSIDE FACE
W WIDE FLANGE; WIDE; WEST
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WH WEEP HOLE
WL WORK LINE
WP WORK POINT, WEB PERPENDICULAR
WPJ WEAKENED PLANE JOINT
WT WEIGHT; STRUCTURAL TEE CUT FROM W SHAPE
WV WEB VERTICAL
WWR WELDED WIRE REINFORCING
YD YARD
SECTION
PLAN
VIEW
FRONT
ELEVATION
WIDE
FLANGE
CHANNEL
ANGLE
DOUBLE
ANGLE
SQUARE OR
RECTANGULAR
HOLLOW
SECTION
CIRCULAR
HOLLOW
SECTION,
PIPE
LLBBSLBB
BACK
ELEVATION
DIAGONAL BRACING ABOVE
(DASHED LINE)
SHEAR CONNECTION
MOMENT CONNECTION
CONCRETE ENCASED
STEEL COLUMN SECTION
COLUMN IN SECTION
SPLICE
HANGER
COLUMN STARTS HERE
COLUMN ENDS HERE
HANGER BELOW FLOOR
MOMENT FRAME CONNECTION
KICKER BRACING
(x INDICATES HIGH POINT WHERE SPECIFIED)
ELEVATOR RAIL SUPPORT POST
SEE "TYPICAL ELEVATOR RAIL
SUPPORT POST" SCHEDULE & DETAILS
RX
RX
FLOOR OR WALL
OPENING
STEEL ROOF DECK
CONCRETE WALL
CONCRETE COLUMN
LIMIT OF SPAN OR
SPAN MARK
DIRECTION OF SPAN
NOTE:
THIS IS A GENERIC
SYMBOL. ACTUAL
SYMBOL USED WILL
VARY DEPENDING
UPON SLAB
CONFIGURATION.
TOP OF SLAB
VERTICAL OFFSET,
IF NOT SHOWN, REFER
TO PLAN
9" GRID LINES
SECTION NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
SECTION
ELEVATION
STRUCTURAL
ELEVATION RELATIVE
TO PROJECT ELEVATION EARTH
S.3
ELEVATION NUMBER
SHEET NUMBER
EL
EXISTING
ELEMENTS
DETAIL
MATCHLINE
1/S.2A
1/S.2B
ARCHITECTURAL
PROFILE
FUTURE
CONSTRUCTION
GRAVEL
EL [-9"] STRUCTURAL ELEVATION
RELATIVE TO REFERENCE
FLOOR ELEVATION
S.3
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
C
R e v it
P ro je c t
F ile s \F
D A
-I rv in e S
T R
U C
R
C
K M
K A
.r v t
/1
/2
:4 :1
A
M
B2291.01
GJR
CK
06/20/25
ABBREVIATIONS
AND LEGENDS
FDA IRVINE
S.001
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
ABBREVIATIONS
STEEL MEMBERS
STEEL SYMBOLS
CONCRETE SYMBOLS
MISCELLANEOUS SYMBOLS
DRAWING LIST
DRAWING LIST
SHEET NUMBER SHEET NAME
S.001 ABBREVIATIONS AND LEGENDS
S.002 GENERAL NOTES
S.101 ROOF LEVEL DRAWINGS
S.102 SHED ROOF LEVEL DRAWINGS AND DETAILS
S.601 SECTIONS AND DETAILS
No. Description Date
Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
C
R e v it
P ro je c t
F ile s \F
D A
-I rv in e S
T R
U C
R
C
K M
K A
.r v t
/1
/2
:4 :1
A
M
B2291.01
GJR
CK
06/20/25
GENERAL NOTES
FDA IRVINE
S.002
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
GENERAL
ALL TYPICAL DETAILS AND NOTES SHOWN ON DRAWINGS SHALL APPLY UNLESS NOTED
OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS BUT
SHALL STILL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS. WHERE TYPICAL DETAILS ARE
NOTED ON THE DRAWINGS, THE SPECIFIED TYPICAL DETAIL SHALL BE USED. WHERE NO
DETAIL IS NOTED, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CHOOSE THE
APPROPRIATE TYPICAL DETAIL FROM THOSE PROVIDED. THE CONTRACTOR SHALL SUBMIT
ALL PROPOSED ALTERNATE TYPICAL DETAILS TO THOSE PROVIDED WITH RELATED
CALCULATIONS TO THE ENGINEER FOR APPROVAL PRIOR TO SHOP DRAWING PRODUCTION
AND FIELD USE.
BUILDING CODE
ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE BUILDING CODE. THE
PUBLICATIONS LISTED BELOW ARE THE GOVERNING CODES AND STANDARDS AND ARE
REFERENCED BY THEIR BASIC DESIGNATION. IN THE CASE OF CONFLICTING REQUIREMENTS,
THE BUILDING CODE SHALL GOVERN.
APPLICABLE CODES AND STANDARDS
BUILDING CODE CALIFORNIA BUILDING CODE (CBC), 2022 EDITION
ACI 318 AMERICAN CONCRETE INSTITUTE, "BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE,"
2019 EDITION
RCSC RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS,
"SPECIFICATION FOR STRUCTURAL JOINTS USING
HIGH-STRENGTH BOLTS," 2014 EDITION
AISC 360 AMERICAN INSTITUTE OF STEEL CONSTRUCTION,
"SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS," 2016 EDITION
ASCE 7 AMERICAN SOCIETY OF CIVIL ENGINEERS,
"MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA
FOR BUILDINGS AND OTHER STRUCTURES," 2016 EDITION,
INCLUDING SUPPLEMENTS NO. 1, 2, AND 3
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
(ASTM INTERNATIONAL)
AWS A2.4 AMERICAN WELDING SOCIETY, "STANDARD SYMBOLS FOR
WELDING, BRAZING, AND NONDESTRUCTIVE EVALUATION,"
2020 EDITION
AWS D1.1 AMERICAN WELDING SOCIETY, "STRUCTURAL
WELDING CODE - STEEL," 2015 EDITION
AWS D1.3 AMERICAN WELDING SOCIETY, "STRUCTURAL
WELDING CODE - SHEET STEEL," 2008 EDITION
AWS D1.4 AMERICAN WELDING SOCIETY, "STRUCTURAL
WELDING CODE - REINFORCING STEEL INCLUDING
METAL INSERTS AND CONNECTIONS IN REINFORCED
CONCRETE CONSTRUCTION," 2018 EDITION
ICC INTERNATIONAL CODE COUNCIL, INTERNATIONAL
CODE COUNCIL - EVALUATION SERVICES (ICC-ES)
IAPMO INTERNATIONAL ASSOCIATION OF PLUMBING AND
MECHANICAL OFFICIALS – UNIFORM EVALUATION
SERVICE (IAPMO-UES)
ANCHORAGE TO HARDENED CONCRETE
ANCHORAGE TO HARDENED CONCRETE SHALL INCLUDE MECHANICAL AND ADHESIVE
ANCHORS OF SIZE, NUMBER, AND SPACING AS SHOWN ON THE DRAWINGS. HOLES SHALL BE
DRILLED AND CLEANED AND ANCHORS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH
THE MANUFACTURER'S PUBLISHED INSTRUCTIONS AND AN APPROVED ICC―ES (OR IAPMO-
UES EQUIVALENT) REPORT. INSPECTION AND TESTING SHALL BE PROVIDED IN ACCORDANCE
WITH THE GENERAL NOTES AND THE APPROVED ICC―ES (OR IAPMO-UES EQUIVALENT)
REPORT.
WHERE THE ANCHOR TYPE IS SPECIFIED ON THE DRAWINGS, SUBSTITUTION FOR A
DIFFERENT TYPE OF ANCHORAGE (INCLUDING SUBSTITUTING FOR CAST-IN-PLACE
ANCHORAGE) SHALL NOT BE PERMITTED WITHOUT PRIOR CONSENT OF THE ENGINEER.
ACCEPTABLE ANCHORS SHALL HAVE A CURRENT ICC―ES (OR IAPMO-UES EQUIVALENT)
REPORT INDICATING THAT THE ANCHOR IS PERMITTED FOR RESISTING SEISMIC LOADS IN
CRACKED CONCRETE. UNLESS NOTED OTHERWISE, ANCHORS SHALL BE ASTM A36
THREADED ROD OR ASTM A615, GRADE 60 REINFORCING STEEL DOWELS.
WHEN EMBEDMENT IS NOTED ON THE DRAWINGS, THE ANCHOR EFFECTIVE EMBEDMENT
DEPTH SHALL EQUAL OR EXCEED THE NOTED EMBEDMENT DEPTH. WHERE NO EMBEDMENT
IS NOTED ON THE DRAWINGS, THE MINIMUM EFFECTIVE ANCHOR EMBEDMENT DEPTH SHALL
BE 6.5 ANCHOR DIAMETERS, MINIMUM DISTANCE TO THE NEAREST CONCRETE EDGE SHALL
BE 12 ANCHOR DIAMETERS, AND MINIMUM ANCHOR SPACING SHALL BE 8 ANCHOR
DIAMETERS.
HOLES SHALL BE DRILLED WITH ROTARY IMPACT HAMMER OR EQUIVALENT METHOD TO
PRODUCE A HOLE WITH A ROUGH INSIDE SURFACE. CORE DRILLING HOLES IS NOT
PERMITTED. NO STEEL REINFORCEMENT SHALL BE CUT TO INSTALL ANCHORS. THE
ADHESIVE SHALL BE MIXED, APPLIED, AND CURED IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS IN THE ICC―ES (OR IAPMO-UES
EQUIVALENT) REPORT. ALL PLACEMENT AND CURING SHALL BE CONDUCTED WITH
CONCRETE AND AIR TEMPERATURES ABOVE 50 DEGREES FAHRENHEIT. ADHESIVE SHALL BE
APPLIED ONLY TO CLEAN, DRY CONCRETE. POSITIVE PROTECTION SHALL BE PROVIDED SO
THAT ANCHORS ARE NOT DISTURBED DURING THE CURING PERIOD. STAINLESS STEEL
ANCHORS SHALL BE USED AT ALL EXTERIOR LOCATIONS AND WHERE SPECIFICALLY
INDICATED ON THE DRAWINGS. DEFECTIVE OR ABANDONED HOLES SHALL BE FILLED WITH
NON-SHRINK GROUT OR AN INJECTABLE ADHESIVE MATCHING THE ADJACENT CONCRETE
COMPRESSIVE STRENGTH. NOTIFY THE STRUCTURAL ENGINEER OF DEFECTIVE OR
ABANDONED HOLES IN WALLS AND COLUMNS. THESE ELEMENTS MAY REQUIRE NON-SHRINK
GROUT WITH A COMPRESSIVE MODULUS OF ELASTICITY MATCHING THAT OF THE ADJACENT
CONCRETE.
STRUCTURAL STEEL
ALL STEEL SHALL CONFORM TO THE FOLLOWING:
W-SHAPES ASTM A992, Fy=50 KSI ASTM A913, Fy=50 KSI
W-SHAPES CALLED OUT ON ASTM A913, Fy=65 KSI PLANS AS (Fy=65 KSI)
ALL ANGLES AND CHANNELS ASTM A36, Fy=36 KSI
UNLESS NOTED OTHERWISE
SQUARE OR RECTANGULAR ASTM A500, GRADE C,
STRUCTURAL TUBE (HSS) Fy=50 KSI
ROUND STRUCTURAL TUBE (HSS) ASTM A500, GRADE C,
Fy=46 KSI
STEEL PIPE DIAMETER LESS ASTM A53, TYPE E OR S,
THAN OR EQUAL TO 12 INCHES GRADE B, Fy=35 KSI
MATERIAL CALLED OUT ON ASTM A36, Fy=36 KSI PLANS AS (Fy=36 KSI)
MATERIAL CALLED OUT ON ASTM A572, Fy=65 KSI PLANS AS (Fy=65 KSI)
ALL OTHER STEEL UNLESS ASTM A572, Fy=50 KSI NOTED OTHERWISE ASTM A588, Fy=50 KSI
GENERAL NOTES FOR STEEL CONNECTIONS SHALL APPLY TO ALL STEEL CONNECTIONS
UNLESS NOTED OTHERWISE.
ALL WORK SHALL BE IN ACCORDANCE WITH THE AISC SPECIFICATION. SHOP DRAWINGS
SHALL BE SUBMITTED AND REVIEWED BY THE ARCHITECT/ENGINEER BEFORE COMMENCING
FABRICATION. ALL STEEL ANCHORS AND TIES AND OTHER MEMBERS EMBEDDED IN
CONCRETE OR MASONRY SHALL BE LEFT UNPAINTED. DIMENSIONAL TOLERANCE FOR BUILT-
UP MEMBERS SHALL BE PER AWS D1.1.
STEEL BEAMS ARE EQUALLY SPACED BETWEEN DIMENSION POINTS AT THE MAXIMUM DECK
SPAN LOCATION, UNLESS NOTED OTHERWISE. STEEL BEAMS ARE ORIENTED WITH THE BEAM
WEB VERTICAL, UNLESS NOTED OTHERWISE. HSS ARE ORIENTED WITH THE WIDE FACE
VERTICAL, UNLESS NOTED OTHERWISE. MINIMUM CONNECTIONS SHALL BE A TWO-BOLT
CONNECTION USING HIGH-STRENGTH BOLTS IN SINGLE SHEAR.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE SELECTION OF
OPTIONAL DETAILS SHOWN ON THE DRAWINGS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ERECTION AIDS THAT INCLUDE, BUT ARE
NOT LIMITED TO, ERECTION ANGLES, LIFT HOLES, AND OTHER AIDS.
STRUCTURAL STEEL BOLTING
ALL BOLTS 7/8-INCH DIAMETER AND SMALLER SHALL BE GROUP A HIGH-STRENGTH BOLTS AS
DEFINED BY AISC, UNLESS NOTED OTHERWISE.
ALL BOLTS 1-INCH DIAMETER AND LARGER SHALL BE GROUP B HIGH-STRENGTH BOLTS AS
DEFINED BY AISC, UNLESS NOTED OTHERWISE.
EITHER HEAVY HEX OR TENSION-CONTROL BOLTS MAY BE USED AT THE CONTRACTOR’S
OPTION. ALL HIGH-STRENGTH BOLTS SHALL BE INSTALLED, TIGHTENED, AND INSPECTED IN
ACCORDANCE WITH THE RCSC.
BOLTS DESIGNATED “A307” IN THE DRAWINGS REFER TO ASTM A307 BOLTS. INSTALL A307
BOLTS TO SNUG-TIGHT CONDITION UNLESS NOTED OTHERWISE AND PROVIDE LOCK
WASHERS UNDER NUTS OR SELF-LOCKING NUTS. WHERE A307 BOLTS OCCUR IN SLOTTED
HOLES, PROVIDE WASHERS TO COMPLETELY COVER THE HOLES.
BOLTS DESIGNATED “THRU” IN THE DRAWINGS REFER TO ASTM A307 BOLTS, UNLESS NOTED
OTHERWISE. ALL “THRU” BOLTS ARE INSTALLED TO FINGER-TIGHT REQUIREMENTS UNLESS
NOTED OTHERWISE.
HIGH-STRENGTH BOLT THREADS ARE ALLOWED IN THE SHEAR PLANE EXCEPT WHERE
DESIGNATED “X” IN THE DRAWINGS.
ALL HIGH-STRENGTH BOLTED CONNECTIONS SHALL BE PRETENSIONED, UNLESS NOTED
OTHERWISE. PRETENSIONED AND SLIP-CRITICAL CONNECTIONS MAY USE TURN-OF-NUT
PRETENSIONING, TWIST-OFF-TYPE TENSION-CONTROL BOLT PRETENSIONING, OR DIRECT-
TENSION-INDICATOR PRETENSIONING.
BOLTS IN CONNECTIONS OF BEAM-TO-BEAM/GIRDER MAY BE SNUG-TIGHT, UNLESS
SPECIFICALLY CALLED OUT PRETENSIONED, SLIP-CRITICAL, OR FINGER-TIGHT. SNUG-TIGHT
CONNECTIONS SHALL BE INSTALLED PER THE CRITERIA FOR SNUG-TIGHT BOLTS PER THE
RCSC.
CONNECTIONS (OR JOINTS) DESIGNATED “SC” IN THE DRAWINGS SHALL HAVE BOLTS
INSTALLED TO SLIP-CRITICAL REQUIREMENTS WITH CLASS A FAYING SURFACES.
CONNECTIONS DESIGNATED “SCB” IN THE DRAWINGS SHALL HAVE BOLTS INSTALLED TO SLIP-
CRITICAL REQUIREMENTS WITH CLASS B FAYING SURFACES. WHERE SHIMS OR FILLERS ARE
REQUIRED TO MAKE A SLIP-CRITICAL CONNECTION, A SINGLE PLY FILLER SHALL BE USED
BETWEEN CONNECTING PARTS, UNLESS NOTED OTHERWISE. ALL SURFACES OF FILLERS IN
SLIP-CRITICAL JOINTS SHALL HAVE FAYING SURFACES MATCHING THE DESIGNATED FAYING
SURFACE CLASS.
CONNECTIONS DESIGNATED “FT” IN THE DRAWINGS SHALL HAVE BOLTS INSTALLED TO
FINGER-TIGHT REQUIREMENTS. WHERE FINGER-TIGHT CONNECTIONS ARE NOTED, NUTS
SHALL BE HAND-TIGHTENED AND THEN BACKED OFF ONE-QUARTER TURN. DEFORM THE
BOLT THREADS, PROVIDE A LOCKING NUT, OR PROVIDE A JAMB NUT TO ENSURE THE NUT IS
UNABLE TO BACK OFF FURTHER.
ALL HIGH-STRENGTH BOLTS SHALL HAVE WASHERS INSTALLED PER THE RCSC, UNLESS
NOTED OTHERWISE.
ALL BOLT HOLES SHALL BE STANDARD SIZE, UNLESS NOTED OTHERWISE. CENTER FINGER-
TIGHT BOLTS IN SLOTS AT LONG SLOTS, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL WELDING
STRUCTURAL STEEL SHOP DRAWINGS SHALL SHOW ALL WELDING WITH AWS A2.4 SYMBOLS.
ALL WELDING SHALL BE DONE BY AWS CERTIFIED WELDERS AND IN ACCORDANCE WITH
AWS D1.1. WELDS SHOWN ON THE DRAWINGS ARE THE MINIMUM SIZES. INCREASE WELD
SIZE TO AWS MINIMUM SIZES, BASED ON PLATE THICKNESS. THE MINIMUM WELD SIZE SHALL
BE 3/16 INCH. FIELD WELDING SYMBOLS HAVE NOT NECESSARILY BEEN INDICATED ON THE
DRAWINGS. WHERE SHOWN, PROPER FIELD WELDING PER AWS D1.1 SHALL BE USED.
WHERE NO FIELD WELDING SYMBOLS ARE SHOWN, IT IS THE CONTRACTOR'S RESPONSIBILITY
TO COORDINATE THE USE OF SHOP AND FIELD WELDS. ALL PARTIAL JOINT PENETRATION
GROOVE WELD SIZES SHOWN ON THE DRAWINGS REFER TO EFFECTIVE THROAT THICKNESS.
FLARE-GROOVE WELDS SHALL BE FILLED FULL TO MAXIMUM EFFECTIVE THROAT USING ANY
OF THE PREQUALIFIED WELDING PROCESSES PER AISC 360-16 TABLE J2.2, UNLESS NOTED
OTHERWISE. FOR BASE METALS WITH MAXIMUM YIELD STRENGTH EQUAL TO 50 KSI, ALL
WELDS SHALL BE MADE USING LOW HYDROGEN ELECTRODES WITH MINIMUM TENSILE
STRENGTH PER AWS D1.1 (MINIMUM 70 KSI). LOW HYDROGEN SMAW ELECTRODES SHALL BE
STORED IN AN OVEN OR USED WITHIN THE ATMOSPHERIC TIME PERIODS SPECIFIED IN AWS
D1.1 TABLE 5.1, OR SHALL BE REBAKED PER AWS D1.1 CLAUSE 5.3. ELECTRODES SHALL BE
REBAKED NO MORE THAN ONE TIME, AND ELECTRODES THAT HAVE BEEN WET SHALL NOT BE
USED.
FILLER METALS FOR ALL COMPLETE JOINT PENETRATION GROOVE WELDED T- AND CORNER
JOINTS WITH BACKING LEFT IN PLACE AND COMPLETE JOINT PENETRATION GROOVE WELDED
SPLICES IN HEAVY SECTIONS AS DEFINED IN AISC 360 A3.1c SHALL HAVE A MINIMUM CHARPY
V-NOTCH TOUGHNESS OF 20 FOOT-POUNDS AT 40 DEGREES FAHRENHEIT.
ALL WELDING SHALL BE PERFORMED IN STRICT ADHERENCE TO A WRITTEN WELDING
PROCEDURE SPECIFICATION (WPS) PER AWS D1.1. ALL WELDING PARAMETERS SHALL BE
WITHIN THE ELECTRODE MANUFACTURER'S RECOMMENDATIONS. WELDING PROCEDURES
SHALL BE SUBMITTED TO THE OWNER'S TESTING AGENCY FOR REVIEW PRIOR TO STARTING
FABRICATION OR ERECTION. COPIES OF THE WPS SHALL BE ON SITE AND AVAILABLE TO ALL
WELDERS AND THE SPECIAL INSPECTOR.
ALL COMPLETE JOINT PENETRATION WELDS SHALL BE ULTRASONICALLY TESTED UPON
COMPLETION OF THE CONNECTION, EXCEPT PLATE LESS THAN OR EQUAL TO 1/4 INCH THICK,
WHICH SHALL BE MAGNETIC PARTICLE TESTED. REDUCTION IN TESTING MAY BE MADE IN
ACCORDANCE WITH THE BUILDING CODE WITH APPROVAL OF THE ENGINEER.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE JOINT PREPARATIONS AND WELDING
PROCEDURES THAT INCLUDE, BUT ARE NOT LIMITED TO: REQUIRED ROOT OPENINGS, ROOT
FACE DIMENSIONS, GROOVE ANGLES, BACKING BARS, COPES, SURFACE ROUGHNESS
VALUES, AND TAPERS AND TRANSITIONS OF UNEQUAL PARTS.
SHOP DRAWINGS
SHOP DRAWINGS FOR REINFORCING STEEL, AND STRUCTURAL STEEL SHALL BE SUBMITTED
FOR REVIEW PRIOR TO FABRICATION OF THESE ITEMS.
REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL CONCRETE DIMENSIONS NOT SHOWN
ON THE STRUCTURAL DRAWINGS. IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO
DEVELOP DETAILED SLAB EDGE AND CONCRETE OUTLINE DRAWINGS THAT ARE BASED ON
THE ARCHITECTURAL, STRUCTURAL, AND MEP DRAWINGS. THE DETAILED EDGE AND
OUTLINE DRAWINGS SHALL BE SUBMITTED FOR REVIEW. SUBMITTED DRAWINGS SHALL
CONTAIN ALL CONCRETE CURBS, FORM OUTLINES, AND EMBEDDED ITEMS. DIMENSIONS AND
OUTLINES DEVELOPED BY THE CONTRACTOR MAY VARY FROM THOSE SHOWN BY THE
ARCHITECT AND ENGINEER AS NECESSARY BASED ON THE DEPENDENCY ON ADJACENT
MATERIALS THAT ARE DETERMINED BY THE CONTRACTOR AND/OR SUPPLIER (EXTERIOR
CLADDING, ELEVATOR EQUIPMENT, FINAL MEP SHAFT SIZES, ETC.). CONCRETE OUTLINES
SHALL BE ADJUSTED AS NECESSARY TO ACCOUNT FOR CONSTRUCTION METHODS. THE
CONCRETE OUTLINE DEVELOPED BY THE CONTRACTOR SHALL NOT MATERIALLY ALTER THE
DESIGN INTENT SHOWN IN THE STRUCTURAL DRAWINGS.
DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE ENGINEER OF RECORD;
THEREFORE, THEY SHALL BE VERIFIED BY THE CONTRACTOR. THE CONTRACTOR SHALL
REVIEW AND STAMP DRAWINGS PRIOR TO REVIEW BY THE ENGINEER OF RECORD. THE
CONTRACTOR SHALL REVIEW DRAWINGS FOR CONFORMANCE WITH THE MEANS, METHODS,
TECHNIQUES, SEQUENCES, AND OPERATIONS OF CONSTRUCTION, AND ALL SAFETY
PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO.
SUBMITTALS SHALL BE PROVIDED ELECTRONICALLY WHENEVER POSSIBLE AND WILL BE
MARKED AND RETURNED ELECTRONICALLY. WHEN HARD COPY SUBMITTALS ARE REQUIRED,
ONE ORIGINAL AND ONE COPY SHALL BE PROVIDED; THE REPRODUCIBLE COPY WILL BE
MARKED AND RETURNED.
SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS.
THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE
TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT, BY
INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED, AND BY
DETAILING THE INTENDED FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS,
DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWINGS SUBMITTALS AND THE
CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING
SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DESIGN DRAWINGS AND
SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED.
SPECIAL INSPECTION
THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION AND TESTING PER CBC
SECTION 1705. THIS WORK SHALL BE PERFORMED BY A CERTIFIED SPECIAL INSPECTOR
CERTIFIED TO PERFORM THE TYPES OF INSPECTIONS AND TESTS SPECIFIED. THE
FREQUENCY OF INSPECTIONS AND TESTING SHALL BE AS OUTLINED IN THE CBC TABLE
ITEMS LISTED BELOW. DEFICIENCIES SHALL BE REPORTED DAILY TO THE CONTRACTOR.
SUMMARY REPORTS SHALL BE DISTRIBUTED WEEKLY TO THE OWNER, ARCHITECT,
CONTRACTOR, BUILDING OFFICIAL, AND STRUCTURAL ENGINEER. SEE THE SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS FOR SPECIAL INSPECTION AND TESTING.
DESCRIPTION (REFER TO
ITEM CBC SECTION 1705) CBC REFERENCE
STRUCTURAL STEEL STRUCTURAL STEEL THAT IS SECTION 1705.2
AND WELDING PART OF THE STRUCTURE.
HIGH STRENGTH SEE SPECIFICATIONS FOR SECTION 1705.2
BOLTING PROCEDURES FOR INSPECTION
AND TESTING.
S.101
36 37 38 39
3B
3C
3B.9
3B.8
3A.8
(E) BM 24"x19" (E) BM 24"x19"
(E
B M
4" x1 9"
(E
B M
4" x1 9"
(E) BM 24"x15"
(E
B M
4" x1 9"
(E
B M
4" x1 9"
(E
B M
4" x1 9"
(E
B M
4" x1 9"
(E
B M
8" x1 5"
(E
B M
8" x1 5"
(E) BM 24"x19"
EXHAUST FAN AND
PREFAB CURBS
PER MEP, (2) LOCS
14"x14" DUCT OPNG AND
METAL CURB PER ARCH,
SEE NOTES 3 & 4
NOTES:
1. EXISTING CONSTRUCTION HAS BEEN ESTABLISHED BASED ON REVIEW OF THE
AVAILABLE RECORD CONSTRUCTION DOCUMENTS FOR THE ORIGINAL BUILDING.
ONLY LIMITED VERIFICATION HAS BEEN PERFORMED.
2. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS TO CONFIRM CONFORMANCE
WITH THE DOCUMENTS. THE CONTRACTOR SHALL ALERT THE ARCHITECT WHERE
EXISTING CONDITION IS DIFFERENT FROM WHAT IS SHOWN.
3. CONTRACTOR TO COORDINATE LOCATION OF NEW ROOF SLAB OPENING WITH
ARCHITECTURAL AND MEP DRAWINGS, AND WITH NEW EQUIPMENT.
4. DO NOT OVERCUT CORNERS OF NEW CONCRETE ROOF SLAB OPENING.
(E) EXT WALL
OUTLINE OF ROOM
2309 BELOW
S.601
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
C
R e v it
P ro je c t
F ile s \F
D A
-I rv in e S
T R
U C
R
C
K M
K A
.r v t
/1
/2
:4 :1
A
M
B2291.01
GJR
CK
06/20/25
ROOF LEVEL
DRAWINGS
FDA IRVINE
S.101
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
ROOF LEVEL - WING THREE - EXISTING FRAMING PLAN
1/8" = 1'-0"7
ROOF LEVEL - WING THREE - PARTIAL FRAMING PLAN
S.102
36 37 38 39
3B.9
3B.8
3A.8
(E) W10x17
(E) W10x17
(E) W10x12
(E) W10x12
(E) W10x12 (E) W10x12
(E) W10x12 (E) W10x12
(E) W10x12 (E) W10x12
(E) W10x17(E) W10x17
(E
W x2
(E
W x2
(E
W x2
(E) W10x17
(E) W10x12
(E) W10x12
(E) W10x12
(E) W10x12
(E) W10x17
11" DIA DUCT OPNG
PER ARCH, TYP
GUY WIRES AT
EXHAUST STACK
PER ARCH, TYP
NOTES:
1. EXISTING CONSTRUCTION HAS BEEN ESTABLISHED BASED ON REVIEW OF THE AVAILABLE RECORD CONSTRUCTION DOCUMENTS FOR THE ORIGINAL BUILDING. ONLY LIMITED VERIFICATION HAS BEEN
PERFORMED.
2. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS TO CONFIRM CONFORMANCE WITH THE
DOCUMENTS. THE CONTRACTOR SHALL ALERT THE ARCHITECT WHERE EXISTING CONDITION IS
DIFFERENT FROM WHAT IS SHOWN.
3. CONTRACTOR TO COORDINATE LOCATION OF NEW UPPER ROOF DECK OPENING WITH ARCHITECTURAL
AND MEP DRAWINGS, AND WITH NEW EQUIPMENT.
4. DO NOT OVERCUT CORNERS OF NEW UPPER ROOF DECK OPENING.
5. CONTRACTOR TO INSTALL NEW STEEL FRAMING PRIOR TO CUTTING NEW UPPER ROOF DECK OPENING.
C6x8.2, TYP
S.601
S.601
SIM,
TYP
TYP
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
C
R e v it
P ro je c t
F ile s \F
D A
-I rv in e S
T R
U C
R
C
K M
K A
.r v t
/1
/2
:4 :2
A
M
B2291.01
GJR
CK
06/20/25
SHED ROOF LEVEL
DRAWINGS AND
DETAILS
FDA IRVINE
S.102
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
SHED ROOF LEVEL - WING THREE - EXISTING FRAMING PLAN
1/8" = 1'-0"7
SHED ROOF LEVEL - WING THREE - PARTIAL FRAMING PLAN
3C
METAL CURB
PER ARCH
EXHAUST FAN
PER MEP
EXHAUST DUCT
PER MEP, TYP
(E) ROOF DECK
GUY WIRE
BRACING, TYP
(E) ROOF SCREEN
(E) CONC
ROOF SLAB
ROOF
HIGH ROOF
S.601
S.601
TYP
3" TYP
(E) ROOF DECK
#8 SMS SCREWS @ 12" OC
PL3/8x3, TYP
(E) WF HIGH
ROOF BM, TYP
CHANNEL
TYP
3/16
3/16
(3) SIDES,
TYP3/16
NOTES:
1. INSTALL CHANNEL TIGHT TO UNDERSIDE OF EXISTING DECK. PROVIDE SHIMS AS REQUIRED.
2. ALL CHANNELS AND PLATES TO BE GALVANIZED OR TO RECEIVE PROTECTIVE HIGH
PERFORMANCE COATING. REMOVE GALVANIZING OR PAINT AT FIELD WELDS, AND REPAIR
AFTER WELDING WITH GALVANIC PAINT OR APPROVED HIGH PERFORMANCE COATING.
3. ALL FASTENERS TO BE GALVINZED OR STAINLESS STEEL.
DUCT BY MEP
UNISTRUT
(E) STUD WALL
NOTES:
1. ALL FITTINGS, FASTENERS, BOLTS AND CONNECTORS
TO BE GALVANIZED OR STAINLESS STEEL.
SECTION
DUCT BY MEP
UNISTRUT P1026 ADJUSTABLE
HINGE W/ (2) 1/2" DIA BOLTS, ES
UNISTRUT P1354
ADJUSTABLE HINGE W/
(4) 1/2" DIA BOLTS, EA END
UNISTRUT P1000 HORIZ BRACE
UNISTRUT P1000
1/4" SMS SCREW AT
EA STUD, (4) MIN
(E) STUD WALL
14GA x 2" WIDE
GALVANIZED SHEET
METAL COLLAR STRAP
1/2" DIA BOLT, TYP
(± 10 DEG)45°
1' -6
M
A X
M
AX
HSS3x3x3/16
GALVANIZED
3/16" PRESTRETCHED
GALVANIZED AIRCRAFT
CABLE 7x19
STRAND CORE
UNISTRUT P1843
ADJUSTABLE HINGE
(E) DECK
(E) WF HIGH
ROOF BM
CAP PL3/8
GALVANIZED
DUCT
BY MEP
3/16
1/8
1/8
NOTES:
1. ALL FITTINGS, FASTENERS, BOLTS AND CONNECTORS
TO BE GALVANIZED OR STAINLESS STEEL.
2. REMOVE GALVANIZING AT FIELD WELDS, AND REPAIR
AFTER WELDING WITH GALVANIC PAINT.
3. IN LIEU OF STAINLESS STEEL SCREWS, DUCT COLLAR
CAN BE WELDED TO DUCT AT CONTRACTOR'S OPTION.
P E
R M
E P 14 GA x 2" WIDE S316
STAINLESS STEEL SHEET
METAL COLLAR STRAP
SECTION
DUCT BY MEP
AIRCRAFT
CABLE, TYP
SHEET METAL
COLLAR
#8 SELF TAPPING S316
STAINLESS STEEL SCREWS,
SEE NOTE 3, TYP
The Miller Hull Partnership, LLP Architecture and Planning
Polson Building 71 Columbia, Sixth Floor Seattle, WA 98104
Phone: 206.682.6837
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
C
R e v it
P ro je c t
F ile s \F
D A
-I rv in e S
T R
U C
R
C
K M
K A
.r v t
/1
/2
:4 :2
A
M
B2291.01
GJR
CK
06/20/25
SECTIONS AND
DETAILS
FDA IRVINE
S.601
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
1/2" = 1'-0"7
SECTION
1 1/2" = 1'-0"11
SECTION
1 1/2" = 1'-0"5
DETAIL
1 1/2" = 1'-0"6
DETAIL
DI
DO
AI
AO
CT
AI
DP
MD
HS
DP
P
SD
T
TPI
VFD
ECM
H
FS
SP
CONTROL DIAGRAM SYMBOLS LIST
SYMBOLS
ANALOG INPUT
ANALOG OUTPUT
ELECTRIC CURRENT TRANSMITTER
DIRECT DIGITAL CONTROL
DIGITAL INPUT
DIGITAL OUTPUT
DIFFERENTIAL PRESSURE SENSOR
HIGH STATIC PRESSURE SENSOR
MOTOR STARTER
MOTORIZED DAMPER
PRESSURE SENSOR
SMOKE DETECTOR
TEMPERATURE SENSOR/ROOM THERMOSTAT
THIRD PARTY INTERFACE (BACNET)
VARIABLE FREQUENCY DRIVE
DDC
M/S
ABBREVIATIONS
AFMS AIR FLOW MEASURING STATION
AI ANALOG INPUT
AO ANALOG OUTPUT
BMS/BAS BUILDING MANAGEMENT SYSTEM
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
CT ELECTRIC CURRENT TRANSMITTER
DDC DIRECT DIGITAL CONTROL
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DP PRESSURE SENSOR
EA EXHAUST AIR
ECM ELECTRONICALLY COMMUTATED MOTOR
EF EXHAUST FAN
HS HIGH STATIC
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
M MOTORIZED
MAU MAKE UP AIR UNIT
M/S MOTOR STARTER
MD MOTORIZED DAMPER
OA OUTSIDE AIR
P PRESSURE SENSOR
PPM PARTS PER MILLION
RA RETURN AIR / RELIEF AIR
RF RETURN FAN / RELIEF FAN
SA SUPPLY AIR
SF SUPPLY FAN OR SQUARE FOOT
SD SMOKE DETECTOR
T TEMPERATURE SENSOR
/ ROOM THERMOSTAT
TPI THIRD PARTY INTERFACE
VFD VARIABLE FREQUENCY DRIVE
ELECTRONICALLY COMMUTATED MOTOR
NETWORK
BACNET COMMUNICATION LINE
WITH DEVICE / CONTROLLER
ROOM / DUCT RELATIVE HUMIDITY
SENSOR / TRANSMITTER
FLOW SWITCH
SPACE PRESSURE SENSOR
FLOW METER
GENERAL SHEET NOTES
A. PROVIDE ALL THIRD PARTY BACNET INTERFACES WHERE NOT PROVIDED BY EQUIPMENT
MANUFACTURER.
B. SEE ELECTRICAL DRAWINGS FOR 120 VOLT JUNCTION BOXES FOR POWER SUPPLY. PROVIDE
ADDITIONAL 120V POWER SUPPLY AS REQUIRED, AND PROVIDE 120V TO 24V TRANSFORMERS
FOR LOW VOLTAGE CONTROL POWER. PROVIDE 24V POWER TO ALL CONTROL DEVICES.
PROVIDE CONTROL WIRING PER DIV. 23 & 26 SPECIFICATIONS. PROVIDE PLENUM RATED
CABLE ABOVE REMOVABLE TILE CEILING, AND RACEWAY ABOVE HARD LID CEILINGS.
C. PROVIDE 120V POWER FOR AIRFLOW MEASURING STATIONS, LARGE VALVES, AND BMS
CONTROL SYSTEMS INCLUDING ALL PANELS. FOLLOW DIV. 26 SPECIFICATIONS FOR PRODUCTS
AND INSTALLATION RELATED TO 120V POWER DISTRIBUTION. PROVIDE EMERGENCY POWER
FOR ASSOCIATED BMS CONTROLLERS AND TERMINAL UNITS WHERE AHU IS ON EMERGENCY
POWER.
D. PROVIDE COMMUNICATION WIRING AND CONNECT TO THE BUILDING AND/OR
CAMPUS' IP NETWORK.
E. CONTROL DIAGRAMS, SEQUENCES, AND SPECIFICATIONS ARE PERFORMANCE BASED.
PROVIDE FINAL SEQUENCES, POINT LIST, TRENDING LIST, CONTROL DIAGRAMS, AND
ARCHITECTURAL RISER DIAGRAMS (SEE SPECIFICATIONS).
F. PROVIDE FLOOR LEVEL AND BUILDING LEVEL CONTROLLERS, AS NEEDED.
G. MODIFY ADJUSTABLE SETPOINTS DURING FUNCTIONAL TESTING AND COMMISSIONING
STAGE FOR PROPER SYSTEMS' OPERATION.
FE FLOW ELEMENT
TT TEMPERATURE TRANSMITTER
The Miller Hull Partnership, LLP Architecture and Planning
Point Loma Marina 4980 North Harbor Drive, Suite 100 San Diego, CA 92106
Phone: 619-220-0984
Issue Date:
Kevin Carpenter
SHEET
Drawn:
Checked:
M|H Proj No.:
REVISIONS
SUBMITTAL
STAMP
KEY PLAN
Exp: 06/30/26
C
R e v it L o c a l F ile s \F
D A
-I R
V
IE
I- M
R je s u s rS
P D
B B
.r v t
/7
/2
:1 :3
P
M
A21.0030.01
SCH
JR
06/20/25
SYMBOL &
NOTES -
MECHANICAL
FDA IRVINE
M.001
BID SET
JUNE 20, 2025
19701 Fairchild Rd, Irvine, CA 92612
RM 2309
EXHAUST
DESIGN
GENERAL MECHANICAL NOTES
M.001 SYMBOL & NOTES - MECHANICAL
M.101 FLOOR PLANS -…