Rheem High Efficiency Air Handler
FORM NO. H11-553 REV. 5
RH1T/RH2T- Series Constant Torque Motor (ECM) Efficiencies up to 16 SEER
• RH1T/RH2T feature a Constant Torque motor (ECM) which provides enhanced SEER performance with most Rheem out-door units.
• Versatile 4-way convertible design for upflow, downflow, horizontal left and horizontal right applications.
• Factory-installed indoor coil.
• Sturdy cabinet construction with 1.0 inch [25.4 mm] of foil faced insulation for excellent sound and insulating characteristics.
• Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect.
• 11/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between 421/2 to 57 inches [1080 to 1448 mm] tall and 22 inches [559 mm] deep.
• All models meet or exceed 330 to 400 CFM [156 to 189 L/s] per ton at .3 inches [.7 kPa] of external static pressure.
• Enhanced airflow up to .7" external static pressure.
• Evaporator is constructed of aluminum fins bonded to inter-nally grooved aluminum tubing.
• Suitable for application in mobile homes.
• Cabinet air leakage less than 2.0% at 1.0 inch H2O when tested in accordance with ASHRAE Standard 193.
Air Air Handlers RH1T/RH2T Series
Air Table of Contents RH1T/RH2T Series
TABLE OF CONTENTS
Engineering Features
Model Number Identification
Dimensional Data ........................................................................................5-6
Airflow Directional Data
Airflow Performance Data RH1T ..................................................................8-14
Electrical Data RH1T ................................................................................15-18
Airflow Performance Data RH2T ................................................................19-22
Electrical Data RH2T ................................................................................23-24
Electrical Wiring
Accessories
Limited Warranty
Engineering Features RH1T/RH2T Series
Engineering Features RH1T/RH2T- Series
• The most compact unit design available, all standard heat air handler models only 421/2 to 57 inches [1079 to 1448 mm] high.
• Attractive pre-painted cabinet exterior.
• Rugged wall steel cabinet construction, designed for added strength and versatility.
• 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance.
• Four leg blower motor mount.
• Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience.
• Traditional open wire element design for heat applications.
• Field convertible for vertical downflow, horizontal left hand or right hand air supply.
• 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors.
• Indoor coil design provides low air side pressure drop, high performance and extremely compact size.
• Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil.
• Coils are constructed of aluminum fins bonded to internally grooved aluminum tubing.
• Coils are tested at the factory with an extensive refrigerant leak check.
• Coils have copper sweat refrigerant connections.
• Coils utilize chatleff metering device connections.
• Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils.
• Supply duct flanges provided as standard on air handler cabinet.
• Provisions for field electrical, connections available from either side or top of the air handler cabinet.
• Connection point for high voltage wiring is inside the air han-dler cabinet. Low voltage connection is made on the outside of the air handler cabinet.
• Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 11/2 inch [38 mm] conduit.
• Front refrigerant and drain connections.
[ ] Designates Metric Conversions
Model Number Identification RH1T/RH2T Series
Available Models at 115V A Voltage
RH1T2417STANAA
RH1T3617STANAA
RH1T3621MTANAA
RH1T3621HTANAA
RH1T4821STANAA
RH1T4821MTANAA
RH1T6021STANAA
RH1T4824STANAA
RH1T6024STANAA
Available Models at 208V J Voltage
RH1T2417STANJA
RH1T3617STANJA
RH1T3621MTANJA
RH1T3621HTANJA
RH1T4821MTANJA
RH1T4821STANJA
RH1T4824STANJA
RH1T6021STANAA
RH1T6024STANJA
RH2T2421MTANJA
RH2T3621MTANJA
RH2T4824MTANJA
RH2T6024STANJA
R H 1 T 24 17 S T A N A A ***
Option Code (see ADS-3803) Blank = None
Minor Series A = First
Voltage A = 115/1/60 D = 480V/3/60 J = 208/240/1/60
Controls C = Communicating N = Non-Communicating
Major Series A = First
Metering Device
T = TEV
E = EEV
P = Piston
Coil Efficiency S = Standard M= Medium H = High
Width 17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (800-1600 CFM) 24 = 24.5" [609.6 mm] (1400-1800 CFM)
Nominal Capacity 24 = 18,000 [5.27 kW]-24,000 [7.03 kW] BTU/H 36 = 30,000 [8.79 kW]-36,000 [10.55 kW] BTU/H 48 = 42,000 [12.31 kW]-48,000 [14.06 kW] BTU/H 60 = 60,000 [17.58 kW] BTU/H
Motor Type T = Constant Torque (ECM)
Stages of Air Flow 1 = Single 2 = Two Stage
Product Category H = Air Handler
Rheem
[ ] Designates Metric Conversions
Available Models at 480V D Voltage
RH1T6024STANDA
Dimensional Data RH1T/RH2T Series
ELECTRICAL CONNECTIONS
MAY EXIT TOP OR EITHER SIDE
HIGH VOLTAGE CONNECTION 7/8� [22.2 mm], 13/32� [27.8 mm], 131/32� [50 mm] DIA. KNOCKOUTS.
LOW VOLTAGE CONNECTION
5/8� [15.9 mm] AND 7/8� [22.2 mm] KNOCKOUT
VAPOR LINE CONNECTION
COPPER (SWEAT)
PRIMARY DRAIN CONNECTION
3/4� [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3/4� [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION
COPPER (SWEAT)
AUXILIARY DRAIN CONNECTION
3/4� [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
UPFLOW UNIT SHOWN:
UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW,
HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
NOTE: 24� CLEARANCE REQUIRED IN FRONT OF
UNIT FOR FILTER AND COIL MAINTENANCE.
A
W
H
191/2� [495 mm]
RETURN AIR
OPENING
2111/16� [551 mm]
105/16� [262 mm]
SUPPLY AIR
Unit Dimensions
515/16� [151 mm] 41/8�
[105 mm] 31/16� [76 mm] 13/16� [48 mm] 11/8� [29 mm]
11/16� [27 mm]
13/8� [35 mm]
213/16� [71 mm] 51/4�
[133 mm] 53/8�
[136 mm]
UPFLOW UNIT SHOWN:
UNIT MAY BE INSTALLED UPFLOW,
DOWNFLOW, HORIZONTAL RIGHT
OR LEFT AIR SUPPLY.
Model Cabinet Size
Return Air Opening Width
(Inches)
Return Air Opening Depth/Length
(Inches)
17 157/8 193/4 21 193/8 193/4 24 227/8 193/4
Return Air Opening Dimensions
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
HORIZONTAL ADAPTER KIT
VAPOR LINE
CONNECTION
AUXILIARY HORIZONTAL
DRAIN CONNECTION
PRIMARY DRAIN
CONNECTION
AUXILIARY UPFLOW/DOWNFLOW
DRAIN CONNECTION
LIQUID LINE
CONNECTION
VERTICAL DRAIN PAN
Dimensional Data RH1T/RH2T Series
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
Model Size
RH1T
Refrigerant Connections Sweat (In.) [mm] ID Unit
Width “W” In. [mm]
Unit Height
“H” In. [mm]
Supply Duct
“A” In. [mm]
Air Flow CFM (Nom.) [L/s]
Unit Weight/Shipping Weight (Lbs.) [kg]
Liquid Vapor Lo Hi Unit With Coil (Max. KW)
2417ST 3/8 [9.53] 3/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406] 600 [283] 800 [378] 92/106 [42/48]
3617ST 3/8 [9.53] 3/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406] 1000 [472] 1200 [566] 96/110 [44/50]
3621HT 3/8 [9.53] 7/8 [22.23] 211/2 [533] 571/2 [1448] 191/2 [495] 1000 [472] 1200 [566] 137/149 [62/68]
3621MT 3/8 [9.53] 7/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1000 [472] 1200 [566] 126/142 [57/64]
4821MT 3/8 [9.53] 7/8 [22.23] 211/2 [533] 571/2 [1448] 191/2 [495] 1400 [661] 1600 [755] 139/151 [63/68]
4821ST 3/8 [9.53] 7/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1400 [661] 1600 [755] 128/144 [56/65]
4824ST 3/8 [9.53] 7/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [585] 1600 [755] — 142/160 [64/72]
6021ST 3/8 [9.53] 7/8 [22.23] 211/2 [533] 571/2 [1448] 191/2 [495] 1600 [755] 1725 [814] 139/151 [63/68]
6024ST 3/8 [9.53] 7/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [585] — 1800 [850] 159/176 [72/80]
*Maximum dehumidification airflow.
Unit Dimensions & Weights
Model Size
RH2T
Refrigerant Connections Sweat (In.) [mm] ID Unit
Width “W” In. [mm]
Unit Height
“H” In. [mm]
Supply Duct
“A” In. [mm]
Air Flow CFM (Nom.) [L/s]
Unit Weight/Shipping Weight (Lbs.) [kg]
Liquid Vapor Lo Hi Unit With Coil (Max. KW)
2421MT 3/8 [9.53] 3/4 [19.05] 211/2 [533] 421/2 [1080] 191/2 [495] 525 [248] 700 [330] 111/126 [50/57]
3621MT 3/8 [9.53] 7/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 800 [377] 1050 [495] 129/145 [59/66]
4824MT 3/8 [9.53] 7/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584] 1050 [495] 1400 [660] 128/146 [58/66]
6024ST 3/8 [9.53] 7/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584] 1200 [566] 1600 [755] 161/178 [73/81]
Unit Dimensions & Weights
Airflow Directional Data RH1T/RH2T Series
UPFLOW DOWNFLOW
Airflow Directional Data
HORIZONTAL RIGHT
HAND AIRFLOW
HORIZONTAL LEFT
HAND AIRFLOW
Airflow Performance Data RH1T/RH2T Series
Airflow Performance Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows oper-ation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. For opti-mum blower performance, operate the unit in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C.
external static range.
Airflow Operating Limits Model Cabinet Width 17 17/21
Cooling BTUH x 1,000 Cooling Tons Nominal
-18 1.5
-24
-30 2.5
-36
-42 3.5
-48
-48
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal)
[319]
[425]
[531]
[637]
[743]
[850]
[850]
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal)
[283]
[378]
[472]
[566]
[661]
[755]
[755]
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,200 BTUH) (360 CFM [170 L/s]/Ton Nominal)
[255]
[340]
[425]
[510]
[595]
[680]
[680]
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s]
487 [230]
617 [291]
814 [384]
1054 [497]
1171 [553]
1502 [709]
1502 [709]
Maximum Electric Heat Rise °F [°C] 80 [26.7] 63 [17.2] 66 [18.9] 51 [10.6] 49 [9.4] 50 [10] 50 [10]
-60
[911]
[850]
[765]
1666 [786]
54 [12.2]
RH1T/RH2T Series
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts (No Filter)
RPM 592
Blower Size/ Motor
HP [W]
# of Speed
3617ST
No Heater
Tonnage Application
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
719 778 — —
Watts 108 90 97 82 73 — —10x8
1/3 HP [249]
5 Speed CFM — — — — 808 [381] 629 [297] 584 [276]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
— — — — 789 842
RPM 565 587 630 692 751 — —
Model No.
RH1T
2417ST
with 13 kW
Heater
2417ST
No Heat
2417ST
with 13 kW
Heater
2417ST
No Heat
Watts 95 81 88 74 66 — —10x8
1/3 HP [249]
5 Speed
3617ST
No Heater
RPM
1.5 Ton 683/485
[322/229 L/s]
CFM — — — — 683 [322] 615 [290] 572 [270]
CFM 814 [384] 692 [326] 589 [278] 535 [252]
RPM — — — — 789 842 892
467 [220] — —
Watts — — — — 148 168 163
RPM 596 645
3617ST
with 18 kW
Heater
694 741 791
816 846 882
Watts 105 108 116 121 130 — —10x8
1/3 HP [249]
5 Speed CFM
926 —
— — — — 858 [276] 816 [385] 770 [363]
RPM — — — — 834 879 925
Watts 237 249 259 268 277
2 Ton 858/697 [405/329 L/s]
CFM 902 [426] 846 [399] 788 [372] 742 [350] 679 [320] — —
Watts — — — — 185 182 214
RPM 595 670 719 767 817 — —
Watts 113 125 124 129 197 — —10x8
1/3 HP [249]
5 Speed CFM — — — — 833 [393] 791 [373] 746 [352]
RPM — — — — 852 898 944
— —10x8
1/2 HP [373]
5 Speed CFM — —
2 Ton 683/485 [322/229 L/s]
CFM 882 [416] 827 [390] 769 [363] 723 [341] 661 [312] — —
Watts — — — — 192 189 222
RPM 671 725 764 809 852 — —
Watts 153 168 174 180 188 — —10x8
1/2 HP [373]
5 Speed CFM — — — — 1084 [512] 1040 [491] 1001 [472]
RPM — — —
1.5 Ton
683/485 [322/229 L/s]
CFM 837 [395] 713 [366] 608 [287] 554 [261] 485 [229] — —
936 971
— 1275 [602] 1244 [587] 1211 [571]
Watts — — — — 140 159 155
RPM — —
2.5 Ton 935/1084 CFM
[441/512 L/s]
CFM 1093 [516] 1050 [496] 1017 [480] 977 [461] 935 [441] — —
Watts — — — — 249 257 261
RPM 711 765 804 849 892 — —
Watts 164 179 185 191 199 — —10x8
1/2 HP [373]
5 Speed CFM — — — — 1059 [500] 1015 [479] 976 [461]
RPM — — — — 936 976 1011
— — 963 999 1029
3 Ton 1130/1275 CFM [533/602 L/s]
2.5 Ton 910/1059 CFM
[429/500 L/s]
CFM 1068 [504] 1025 [484] 992 [468] 952 [449] 910 [429] — —
Watts — — — — 260 268 272
CFM 1270 [599] 1237 [584] 1199 [566] 1165 [550] 1130 [533] — —
Watts — — — — 338 348 363
Motor Speed From
Factory
3617ST
with 18 kW
Heater
RPM 815 856 886 922 966 — —
Watts 248 260 270 279 288 — —10x8
1/2 HP [373]
5 Speed CFM — — — — 1250 [590] 1219 [575] 1186 [560]
RPM — — — — 1003 1039 1069
3 Ton 1105/1250 CFM [521/590 L/s]
CFM 1245 [588] 1212 [572] 1174 [554] 1140 [538] 1105 [521] — —
Watts — — — — 349 359 374
Motor Speed
115V/208V/240V/460V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor)
RH1T/RH2T Series
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts (No Filter)
RPM 637
Blower Size/ Motor
HP [W]
# of Speed
Tonnage Application
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Motor Speed
801 847 — —
Watts 130 142 153 165 176 — —10x10
1/2 HP [373]
5 Speed
CFM — — — — 1103 [521] 1059 [500] 1000 [472]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
— — — — 917 957 1001
Model No.
RH1T
3621MT
No Heater
3621MT
with 18 kW
Heater
3621MT
No Heater
3621MT
with 18 kW
Heater
2.5 Ton 854/1103 CFM
[403/521 L/s]
CFM 1073 [506] 1016 [479] 963 [454] 906 [428] 854 [403] — —
Watts — — — — 262 271 285
RPM 678 734 791 844 883 — —
Watts 141 155 158 171 182 — —10x10
1/2 HP [373]
5 Speed
CFM — — — — 1016 [479] 961 [454] 904 [427]
RPM — — — — 939 968 1015
2.5 Ton 828/1016 CFM
[391/479 L/s]
CFM 1044 [493] 988 [466] 936 [442] 880 [415] 828 [391] — —
Watts — — — — 233 243 265
RPM 724 761 814 868 900 — —
Watts 198 208 222 237 245 — —10x10
1/2 HP [373]
5 Speed
CFM — — — — 1288 1244 1200
RPM — — — — 974 [608] 1012 [587] 1044 [566]
3 & 3.5 Ton 1070/1288 CFM [505/608 L/s]
CFM 1264 [597] 1223 [577] 1171 [553] 1112 [525] 1070 [505] — —
Watts — — — — 345 362 371
RPM 759 794 845 915 933 — —
Watts 219 215 227 251 26110x10
1/2 HP [373]
5 Speed
CFM — — — — 1257 [593] 1213 [572] 1169 [552]
RPM — — — — 1020 1023 1054
3 & 3.5 Ton 1042/1257 CFM [492/593 L/s]
CFM 1233 [582] 1193 [563] 1142 [539] 1084 [512] 1042 [492] — —
Watts — — — — 355 368 376
Motor Speed From
Factory
Notes: Constant Torque motor speed changes.
All Constant Torque motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
Constant Torque air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, (-)H1T-HM2417JA is always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the Constant Torque motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage) and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
115V/208V/240V/460V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor) (con’t.)
RH1T/RH2T Series
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts (No Filter)
RPM 660
Blower Size/ Motor
HP [W]
# of Speed
4821ST
with 20 kW
Heater
Tonnage Application
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Motor Speed
762 795 — —
Watts 297 311 326 340 353 — —11x11
3/4 HP [559]
5 Speed
CFM — — — — 1732 [817] 1683 [794] 1630 [769]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
— — — — 840 872 899
Model No.
RH1T
4824ST
No Heater
4824ST
with 25 kW
Heater
RPM
4 Ton 1545/1732 CFM [729/817 L/s]
CFM 1748 [825] 1669 [788] 1639 [773] 1599 [755] 1545 [729] — —
Watts — — — — 448 467 480
RPM 680 736
4821ST
No Heater
760 790 820
875 919 954
Watts 305 330 341 350 361 — —11x11
3/4 HP [559]
5 Speed
CFM
989 —
— — — — 1692 [798] 1643 [775] 1590 [750]
RPM — — — — 865 890 1014
Watts 277 295 313 319 325
4 Ton 1505/1692 CFM [710/798 L/s]
CFM 1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710] — —
Watts — — — — 460 470 481
— —10x10
3/4 HP [559]
5 Speed
CFM — — — — 1333 [629] 1300 [613] 1267 [598]
RPM — —
RPM 781 825 867 905 949 — —
Watts 257 271 303 307 315 — —10x10
3/4 HP [559]
5 Speed
CFM — — — — 1447 [683] 1433 [676] 1402 [662]
RPM — — — — 987 1034 1065
— — 1011 1046 1080
3.5 Ton 1297/1333 CFM
[612/629 L/s]
3.5 Ton 1337/1447 CFM
[631/683 L/s]
CFM 1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631] — —
Watts — — — — 394 406 405
CFM 1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612] — —
Watts — — — — 350 364 377
4821ST
No Heater
RPM 853 893 934 968 1015 — —
Watts 351 387 401 406 422 — —10x10
3/4 HP [559]
5 Speed
CFM — — — — 1654 [781] 1624 [766] 1563 [738]
RPM — — — — 1036 1078 1095
4 Ton 1535/1654 CFM [724/781 L/s]
CFM 1665 [786] 1631 [770] 1601 [756] 1572 [742] 1535 [724] — —
Watts — — — — 500 513 523
4821ST
with 25 kW
Heater
RPM 894 932 970 1020 1052 — —
Watts 389 400 410 430 450 — —10x10
3/4 HP [559]
5 Speed
CFM — — — — 1614 [762] 1584 [748] 1523 [719]
RPM — — — — 1085 1090 1105
4 Ton 1495/1614 CFM [706/762 L/s]
CFM 1625 [767] 1591 [751] 1561 [737] 1532 [723] 1495 [706] — —
Watts — — — — 514 520 530
Motor Speed From
Factory
6024ST
No Heater
6024ST
with 30 kW
Heater
RPM 712 749 787 815 856 — —
Watts 389 409 419 432 459 — —11x11
3/4 HP [559]
5 Speed
CFM — — — — 1905 [899] 1866 [881] 1832 [865]
RPM — — — — 894 924 950
5 Ton 1739/1905 CFM [821/899 L/s]
CFM 1902 [898] 1862 [879] 1809 [854] 1781 [840] 1739 [821] — —
Watts — — — — 565 570 592
RPM 750 790 810 850 880 — —
Watts 410 420 430 455 479 — —11x11
3/4 HP [559]
5 Speed
CFM — — — — 1865 [880] 1826 [862] 1792 [846]
RPM — — — — 920 945 970
5 Ton 1699/1865 CFM [802/880 L/s]
CFM 1862 [879] 1822 [860] 1769 [835] 1741 [822] 1699 [802] — —
Watts — — — — 565 587 610
115V/208V/240V/460V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor) (con’t.)
RH1T/RH2T Series
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts (No Filter)Blower Size/ Motor
HP [W]
# of Speed
Tonnage Application
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Motor Speed
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Model No.
RH1T
6024ST
No Heater
6024ST
with 30 kW
Heater
2 RPM 663 701 741 782 819 — —
Watts 292 309 321 343 357 — —11x11
3/4 HP [559]
5 Speed
CFM — — — — 1697 [801] 1646 [777] 1601 [756]
RPM — — — — 857 895 920
4 & 5 Ton 1517/1699 CFM [716/801 L/s]
CFM 1705 [800] 1661 [703] 1632 [770] 1572 [741] 1517 [915] — —
Watts — — — — 447 466 920
RPM 698 739 763 816 842 — —
Watts 308 317 329 361 373 — —11x11
3/4 HP [559]
5 Speed CFM — — — — 1661 [784] 1611 [760] 1566 [739]
RPM — — — — 882 915 939
4 & 5 Ton 1482/1661 CFM [700/784 L/s]
CFM 1669 [788] 1625 [767] 1596 [753] 1537 [725] 1482 [700] — —
Watts — — — — 447 480 487
Motor Speed From
Factory
115V/208V/240V/460V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor) (con’t.)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
Airflow Performance Data RH1T/RH2T Series
Model No.
RH1T
Nonimal Cooling Capacity
Tons
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Blower Size/ Motor
HP [W]
# of Speed
Motor Speed From
Factory
Motor Speed
CFM [L/s] Air Delivery/RPM/Watts (No Filter)
External Static Pressure—Inches W.C. [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
3621H No Heat 2.5
10x10
1/2 HP [373]
2 Speed dual voltage
CFM 1305 1251 1205 1154 1101 1046 995
RPM 668 727 752 797 832 888 914
Watts 193 187 183 208 210 213 247
CFM 1249 1193 1138 1082 1026 970 914
RPM 732 780 828 877 925 973 1021
Watts 114 123 133 142 151 161 170
3621H 18 Kw Heat 2.5
10x10 1/2 Hp [373]
2 Speed dual voltage
CFM 1280 1228 1176 1124 1072 1020 968
RPM 695 736 777 817 858 899 939
Watts 189 191 197 208 223 243 267
CFM 1221 1166 1110 1054 998 942 886
RPM 756 804 853 901 949 997 1045
Watts 119 128 137 147 156 165 175
3621H No Heat 3
10x10 1/2 Hp [373]
2 Speed dual voltage
CFM 1468 1421 1377 1332 1285 1240 1192
RPM 739 773 822 863 901 937 974
Watts 238 268 276 307 313 302 297
CFM 1272 1220 1174 1124 1067 1016 961
RPM 658 706 753 797 838 877 925
Watts 180 189 189 190 225 202 246
3621H 18 Kw Heat 3
10x10 1/2 Hp [373]
2 Speed dual voltage
CFM 1445 1399 1354 1308 1262 1216 1170
RPM 759 799 839 878 918 958 997
Watts 252 277 295 305 308 303 290
CFM 1249 1197 1145 1093 1042 990 938
RPM 684 728 772 816 859 903 947
Watts 183 186 192 202 214 230 248
4821M No Heat 3.5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1590 1546 1512 1476 1443 1412 1378
RPM 831 878 909 953 982 1012 1049
Watts 377 373 379 390 406 420 427
CFM 1489 1441 1401 1359 1316 1278 1231
RPM 750 801 843 882 904 943 985
Watts 244 270 282 277 288 288 290
4821M 20 Kw Heat 3.5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1567 1532 1497 1462 1427 1393 1358
RPM 856 892 927 963 998 1034 1069
Watts 374 379 386 396 408 423 440
CFM 1465 1423 1381 1338 1296 1254 1212
RPM 779 816 854 891 929 967 1004
Watts 257 270 281 287 290 289 285
4821M No Heat 4
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1803 1760 1217 1683 1648 1612 1576
RPM 886 919 952 988 1019 1053 1088
Watts 437 430 451 487 489 505 481
CFM 1681 1641 1598 1564 1528 1494 1452
RPM 825 855 907 940 956 1010 1045
Watts 338 358 388 397 388 422 434
115V/208V/240V/480V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor) (con’t.)
RH1T/RH2T Series
Model No.
RH1T
Nonimal Cooling Capacity
Tons
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Blower Size/ Motor
HP [W]
# of Speed
Motor Speed From
Factory
Motor Speed
CFM [L/s] Air Delivery/RPM/Watts (No Filter)
External Static Pressure—Inches W.C. [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
4821M 20 Kw Heat 4
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1779 1742 1704 1667 1630 1592 1555
RPM 903 936 970 1003 1037 1070 1104
Watts 440 451 463 474 486 497 509
CFM 1659 1621 1584 1546 1509 1471 1434
RPM 843 879 916 952 988 1025 1061
Watts 352 367 382 397 412 427 442
6021S No Heat 4 & 5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1841 1798 1758 1728 1699 1660 1629
RPM 898 930 967 997 1027 1057 1092
Watts 469 470 484 490 498 512 531
CFM 1716 1669 1631 1594 1555 1522 1483
RPM 861 887 911 948 984 1015 1050
Watts 359 375 379 397 427 419 427
6021S 30 Kw Heat 4 & 5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 1817 1783 1748 1713 1679 1644 1609
RPM 915 947 979 1011 1043 1076 1108
Watts 470 476 484 494 507 521 538
CFM 1691 1653 1615 1577 1538 1500 1462
RPM 871 903 935 967 999 1031 1063
Watts 367 379 392 404 416 428 440
6021S No Heat 5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 2042 2003 1968 1931 1903 1868 1835
RPM 962 994 1043 1050 1102 1135 1159
Watts 612 632 616 649 673 657 711
CFM 1886 1849 1809 1776 1741 1704 1677
RPM 917 948 981 1012 1047 1076 1108
Watts 491 501 509 525 540 560 569
6021S 30 Kw Heat 5
10x10 3/4 Hp [559]
2 Speed dual voltage
CFM 2021 1987 1953 1918 1884 1850 1816
RPM 980 1014 1047 1080 1113 1147 1180
Watts 618 625 636 650 668 690 715
CFM 2004 1970 1936 1901 1867 1833 1799
RPM 997 1030 1064 1097 1130 1163 1196
Watts 617 633 649 666 682 698 714
115V/208V/240V/480V Airflow Performance Data—RH1T (Constant Torque (ECM) Motor) (con’t.)
Electrical Data RH1T/RH2T Series
Model RH1T Voltage Application
Phase* Hertz HP [W] RPM Speeds Circuit Amps.
Minimum Circuit
Ampacity
Maximum Circuit
Protector
2417ST
208/240 1 & 3 60
1/3 [249] 300-1100 4 1.6 2 15
3617ST 1/2 [373] 300-1100 4 2.7 4 15
3621MT/3621H 1/2 [373] 300-1100 4 3.8 5 15
4821ST/4821M/6021S 3/4 [559] 300-1100 4 3.8 5 15
6024ST/4824ST 3/4 [559] 300-1100 4 4.6 6 15
2417ST
115 1 60
1/3 [249] 300-1100 4 4.8 6 15
3617ST 1/2 [373] 300-1100 4 6.8 9 15
3621MT/3621H 1/2 [373] 300-1100 4 6.8 9 15
4821ST/4821M/6021S 3/4 [559] 300-1100 4 8.4 11 15
6024ST 3/4 [559] 300-1100 4 8.4 11 15
6024ST 480 3 60 3/4 [559] 300-1100 4 3.2 4 15
Electrical Data – Blower Motor Only – No Electric Heat RH1T
* Blower motors are all single phase motors.
RH1T/RH2T Series
Air Handler Model
RH1T
Heater Model No.
Heater kW (208/240V)
(480V) PH/HZ No. Elements kW Per
Type Supply Circuit Single
Circuit Multiple
Circuit Amps.
Motor Ampacity
Minimum Circuit
Ampacity
Maximum Circuit
Protector
2417STAN
RXBH-17?03J 2.2/3 1/60 1 - 3 SINGLE 10.8/12.5 2.8 18/20 20/20
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE 17.3/20 2.8 26/29 30/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE 26/30 1.6 35/40 35/40
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE 34.6/40 2.8 47/54 50/60
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE 20/23.1 2.8 29/33 30/35
RXBH-1724A13J 9.4/12.5 1/60 3 - 4.17 SINGLE 45.1/52.1 2.8 60/69 60/70
RXBH-1724A13J 3.1/4.2 1/60 1 - 4.17 MULTIPLE CKT 1 15/17.4 2.8 23/26 25/30
RXBH-1724A13J 6.3/8.3 1/60 2 - 4.17 MULTIPLE CKT 2 30.1/34.7 0 38/44 40/45
3617STAN
RXBH-17?03J 2.2/3 1/60 1 - 3 SINGLE 10.8/12.5 4.1 19/21 20/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE 17.3/20 4.1 27/31 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE 26/30 4.1 38/43 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE 34.6/40 4.1 49/56 50/60
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE 20/23.1 4.1 31/35 35/35
RXBH-1724A13J 9.4/12.5 1/60 3 - 4.17 SINGLE 45.1/52.1 4.1 62/71 70/80
RXBH-1724A13J 3.1/4.2 1/60 1 - 4.17 MULTIPLE CKT 1 15/17.4 4.1 24/27 25/30
RXBH-1724A13J 6.3/8.3 1/60 2 - 4.17 MULTIPLE CKT 2 30.1/34.7 0 38/44 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE 30/34.6 4.1 43/49 45/50
RXBH-1724A15J 10.8/14.4 1/60 3 - 4.8 SINGLE 51.9/60 4.1 70/81 70/90
RXBH-1724A15J 3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1 17.3/20 4.1 27/31 30/35
RXBH-1724A15J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3 - 5.67 SINGLE 61.6/70.8 4.1 83/94 90/100
RXBH-1724A18J 4.3/5.7 1/60 1 - 5.67 MULTIPLE CKT 1 20.5/23.6 4.1 31/35 35/35
RXBH-1724A18J 8.5/11.3 1/60 2 - 5.67 MULTIPLE CKT 2 41.1/47.2 0 52/60 60/60
3621HTAN/
4821MTAN/
4821STAN/
6021STAN
RXBH-1724?03J 2.2/3 1/60 1 - 3 SINGLE 10.8/12.5 4.1 19/21 20/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE 17.3/20 4.1 27/31 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE 26/30 4.1 38/43 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE 34.6/40 4.1 49/56 50/60
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE 20/23.1 4.1 31/35 35/35
RXBH-1724A13J 9.4/12.5 1/60 3 - 4.17 SINGLE 45.1/52.1 4.1 62/71 70/80
RXBH-1724A13J 3.1/4.2 1/60 1 - 4.17 MULTIPLE CKT 1 15/17.4 4.1 24/27 25/30
RXBH-1724A13J 6.3/8.3 1/60 2 - 4.17 MULTIPLE CKT 2 30.1/34.7 0 38/44 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE 30/34.6 4.1 43/49 45/50
RXBH-1724A15J 10.8/14.4 1/60 3 - 4.8 SINGLE 51.9/60 4.1 70/81 70/90
RXBH-1724A15J 3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1 17.3/20 4.1 27/31 30/35
RXBH-1724A15J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
Electrical Data – With Electric Heat RH1T Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
RH1T/RH2T Series
Electrical Data – With Electric Heat RH1T (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
Air Handler Model
RH1T
Heater Model No.
Heater kW (208/240V)
(480V) PH/HZ No. Elements kW Per
Type Supply Circuit Single
Circuit Multiple
Circuit Amps.
Motor Ampacity
Minimum Circuit
Ampacity
Maximum Circuit
Protector
3621HTAN/
RXBH-1724A18J 12.8/17 1/60 3 - 5.67 SINGLE 61.6/70.8 4.1 83/94 90/100
RXBH-1724A18J 4.3/5.7 1/60 1 - 5.67 MULTIPLE CKT 1 20.5/23.6 4.1 31/35 35/35
RXBH-1724A18J 8.5/11.3 1/60 2 - 5.67 MULTIPLE CKT 2 41.1/47.2 0 52/60 60/60
RXBH-24A20C 14.4/19.2 3/60 6 - 3.2 SINGLE 40/46.2 4.1 56/63 60/70
RXBH-24A20C 7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1 20/23.1 4.1 31/35 35/35
RXBH-24A20C 7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2 20/23.1 0 25/29 25/30
RXBH-24A20J 14.4/19.2 1/60 4 - 4.8 SINGLE 69.2/80 4.1 92/106 100/110
RXBH-24A20J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1 34.6/40 4.1 49/56 50/60
RXBH-24A20J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-24A25C 18/24 3/60 6 - 4 SINGLE 50/57.8 4.1 68/78 70/80
RXBH-24A25C 9/12 3/60 3 - 4 MULTIPLE CKT 1 25/28.9 4.1 37/42 40/45
RXBH-24A25C 9/12 3/60 3 - 4 MULTIPLE CKT 2 25/28.9 0 32/37 35/40
RXBH-24A25J 18/24 1/60 6 - 4 SINGLE 86.4/99.9 4.1 114/130 125/150
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 1 28.8/33.3 4.1 42/47 45/50
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 2 28.8/33.3 0 37/42 40/45
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 3 28.8/33.3 0 37/42 40/45
3621MTAN
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE 17.3/20 4.1 27/31 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE 26/30 4.1 38/43 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE 34.6/40 4.1 49/56 50/60
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE 20/23.1 4.1 31/35 35/35
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE 30/34.6 4.1 43/49 45/50
RXBH-1724A15J 10.8/14.4 1/60 3 - 4.8 SINGLE 51.9/60 4.1 70/81 70/90
RXBH-1724A15J 3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1 17.3/20 4.1 27/31 30/35
RXBH-1724A15J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3 - 5.67 SINGLE 61.6/70.8 4.1 83/94 90/100
RXBH-1724A18J 4.3/5.7 1/60 1 - 5.67 MULTIPLE CKT 1 20.5/23.6 4.1 31/35 35/35
RXBH-1724A18J 8.5/11.3 1/60 2 - 5.67 MULTIPLE CKT 2 41.1/47.2 0 52/60 60/60
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
RH1T/RH2T Series
Air Handler Model
RH1T
Heater Model No.
Heater kW (208/240V)
(480V) PH/HZ No. Elements kW Per
Type Supply Circuit Single
Circuit Multiple
Circuit Amps.
Motor Ampacity
Minimum Circuit
Ampacity
Maximum Circuit
Protector
4824STAN/
6024STAN
RXBH-1724?03J 2.2/3 1/60 1 - 3 SINGLE 10.8/12.5 6 21/24 25/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE 17.3/20 6 30/33 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE 26/30 6 40/45 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE 34.6/40 6 51/58 60/60
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE 20/23.1 6 33/37 35/40
RXBH-1724A13J 9.4/12.5 1/60 3 - 4.17 SINGLE 45.1/52.1 6 64/73 70/80
RXBH-1724A13J 3.1/4.2 1/60 1 - 4.17 MULTIPLE CKT 1 15/17.4 6 27/30 30/30
RXBH-1724A13J 6.3/8.3 1/60 2 - 4.17 MULTIPLE CKT 2 30.1/34.7 0 38/44 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE 30/34.6 6 45/51 45/60
RXBH-1724A15J 10.8/14.4 1/60 3 - 4.8 SINGLE 51.9/60 6 73/83 80/90
RXBH-1724A15J 3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1 17.3/20 6 30/33 30/35
RXBH-1724A15J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3 - 5.67 SINGLE 61.6/70.8 6 85/97 90/100
RXBH-1724A18J 4.3/5.7 1/60 1 - 5.67 MULTIPLE CKT 1 20.5/23.6 6 34/38 35/40
RXBH-1724A18J 8.5/11.3 1/60 2 - 5.67 MULTIPLE CKT 2 41.1/47.2 0 52/60 60/60
RXBH-24A20C 14.4/19.2 3/60 6 - 3.2 SINGLE 40/46.2 6 58/66 60/70
RXBH-24A20C 7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1 20/23.1 6 33/37 35/40
RXBH-24A20C 7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2 20/23.1 0 25/29 25/30
RXBH-24A20J 14.4/19.2 1/60 4 - 4.8 SINGLE 69.2/80 6 94/108 100/110
RXBH-24A20J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1 34.6/40 6 51/58 60/60
RXBH-24A20J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-24A25C 18/24 3/60 6 - 4 SINGLE 50/57.8 6 70/80 70/80
RXBH-24A25C 9/12 3/60 3 - 4 MULTIPLE CKT 1 25/28.9 6 39/44 40/45
RXBH-24A25C 9/12 3/60 3 - 4 MULTIPLE CKT 2 25/28.9 0 32/37 35/40
RXBH-24A25J 18/24 1/60 6 - 4 SINGLE 86.4/99.9 6 116/133 125/150
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 1 28.8/33.3 6 44/50 45/50
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 2 28.8/33.3 0 37/42 40/45
RXBH-24A25J 6/8 1/60 2 - 4 MULTIPLE CKT 3 28.8/33.3 0 37/42 40/45
RXBH-24A30C 21.6/28.8 3/60 6 - 4.8 SINGLE 60/69.4 6 83/95 90/100
RXBH-24A30C 10.8/14.4 3/60 3 - 4.8 MULTIPLE CKT 1 30/34.7 6 45/51 45/60
RXBH-24A30C 10.8/14.4 3/60 3 - 4.8 MULTIPLE CKT 2 30/34.7 0 38/44 40/45
RXBH-24A30J 21.6/28.8 1/60 6 - 4.8 SINGLE 103.8/120 6 138/158 150/175
RXBH-24A30J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1 34.6/40 6 51/58 60/60
RXBH-24A30J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2 34.6/40 0 44/50 45/50
RXBH-24A30J 7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 3 34.6/40 0 44/50 45/50
RXBH-24A07D 7.2 3/60 2 - 3.6 SINGLE 8.7 2.2 14 15
RXBH-24A10D 9.6 3/60 3 - 3.2 SINGLE 11.6 2.2 18 20
RXBH-24A15D 14.4 3/60 3 - 4.8 SINGLE 17.3 2.2 25 25
RXBH-24A18D 17 3/60 3 - 5.68 SINGLE 20.4 2.2 29 30
RXBH-24A20D 19.2 3/60 6 - 3.2 SINGLE 23.2 2.2 32 35
RXBH-24A25D 24 3/60 6 - 4.0 SINGLE 28.8 2.2 39 40
RXBH-24A30D 28.8 3/60 6 - 4.8 SINGLE 34.6 2.2 46 50
Electrical Data – With Electric Heat RH1T (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
M od el N o.
R
H 2T
N om in al
Co ol in g
Ca pa ci ty
To ns
M ot or Sp ee d
Fr om
Fa ct or y
M an uf ac tu re r R ec om m en de d
Ai r-
Fl ow
R an ge (M in /M ax ) C
FM
Bl ow er S iz e/
M ot or H
P of S pe ed s
Y1 , Y
Sp ee d
M ot or Sp ee d
X-
W et
C oi l N o
Fi lte r C
FM
A ir
D el iv er y/ R
PM
/W at ts
-2
V ol ts
Ex te rn al
S ta tic P re ss ur e—
In ch es W
.C kP a]
0.
0.
0.
0.
0.
0.
0.
0.
0.
1.
M T
N o
H ea te r
2.
Y1 T ap
Y2 T ap
Y1 =3
/8
C
FM
[1
/3
] L
/s Y2
=4
/9
C
FM
[2
/4
] L /s
X8
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
M T
W ith kW H ea te r 2.
Y1
T ap
Y2
T ap
Y1 =2
/7
C
FM
[1
/3
] L
/s Y2
=4
/9
C
FM
[2
/4
] L /s
X8
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Ai rf lo w
P er fo rm an ce
D at a
RH
2T
No te s:
C on st an t T or qu e (E
CM
) m ot or s pe ed c ha ng es
Al l C on st an t T or qu e (E
CM
) m ot or s ha ve s pe ed ta bs . S pe ed ta b is fo r c on tin uo us fa n.
S pe ed ta b
(lo w s ta tic ) a nd S pe ed ta b
(h ig h st at ic ) a re fo r l ow er to nn ag e.
Sp ee d ta b
(lo w s ta tic
) a nd
S pe ed ta b
(h ig h st at ic
) a re fo r h ig he r t on na ge
Co ns ta nt T or qu e ai r h an dl er s ar e al w ay s sh ip pe d fro m fa ct or y at
S pe ed ta b 5, e xc ep t f or
, w hi ch is s et a t S pe ed ta b
3.
F or in st an ce
H2
T is a lw ay s sh ip pe d at hi gh s ta tic
-t on a irf lo w (S pe ed ta b
5) . T o ch an ge to
.5 -t on a irf lo w , m ov e th e bl ue w ire to S pe ed ta b or o n th e Co ns ta nt T or qu e (E
CM
) m ot or
Th e lo w s ta tic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic b el ow
.5
W C.
T he h ig h st at ic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic e xc ee di ng
.5
W C.
M ov e th e bl ue w ire to th e ap pr op ria te S pe ed ta b as re qu ire d by th e ap pl ic at io n ne ed s.
Th e ai rfl ow fo r c on tin uo us fa n (S pe ed ta b
1) is a lw ay s se t a t 5 0% o f t he S pe ed ta b
4.
Th e ab ov e ai rfl ow ta bl e lis ts th e ai rfl ow in fo rm at io n fo r a ir ha nd le rs w ith ou t h ea te r a nd a ir ha nd le r w ith m ax im um h ea te r a llo w ed fo r e ac h m od el
Th e fo llo w in g fo rm ul a ca n be u se d to c al cu la te th e ap pr ox im at e ai rfl ow
, i f a s m al le r ( N kW ) t ha n th e m ax im um h ea te r k it is in st al le d.
Ap pr ox im at e Ai rfl ow
A irf lo w w ith ou t h ea te r –
(A irf lo w w ith ou t h ea te r – A irf lo w w ith m ax im um h ea te
r) x
(N k
W /m ax im um h ea te r k W
D es ig na te s
M et ri c
C o nv er si o ns
Air
RH1T/RH2T Series
M od el N o.
R
H 2T
N om in al
Co ol in g
Ca pa ci ty
To ns
M ot or Sp ee d
Fr om
Fa ct or y
M an uf ac tu re r R ec om m en de d
Ai r-
Fl ow
R an ge (M in /M ax ) C
FM
Bl ow er S iz e/
M ot or H
P of S pe ed s
Y1 , Y
Sp ee d
M ot or Sp ee d
X-
W et
C oi l N o
Fi lte r C
FM
A ir
D el iv er y/ R
PM
/W at ts
-2
V ol ts
Ex te rn al
S ta tic P re ss ur e—
In ch es W
.C kP a]
0.
0.
0.
0.
0.
0.
0.
0.
0.
1.
M T
N o
H ea te r
3.
Y1 T ap
Y2 T ap
Y1 =4
/1
CF
M
[2
/4
] L /s
Y2 =7
/1
CF
M
[3
/6
] L /s
X1
3/
H p sp ee d
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
M T
W ith kW H ea te r 3.
Y1
T ap
Y2
T ap
Y1 =4
/9
C
FM
[1
/4
] L
/s Y2
=6
/1
CF
M [3
/6
] L
/s
X1
3/
H p sp ee d
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Ai rf lo w
P er fo rm an ce
D at a
RH
2T
No te s:
C on st an t T or qu e (E
CM
) m ot or s pe ed c ha ng es
Al l C on st an t T or qu e (E
CM
) m ot or s ha ve s pe ed ta bs . S pe ed ta b is fo r c on tin uo us fa n.
S pe ed ta b
(lo w s ta tic ) a nd S pe ed ta b
(h ig h st at ic ) a re fo r l ow er to nn ag e.
Sp ee d ta b
(lo w s ta tic
) a nd
S pe ed ta b
(h ig h st at ic
) a re fo r h ig he r t on na ge
Co ns ta nt T or qu e ai r h an dl er s ar e al w ay s sh ip pe d fro m fa ct or y at
S pe ed ta b 5, e xc ep t f or
, w hi ch is s et a t S pe ed ta b
3.
F or in st an ce
H2
T is a lw ay s sh ip pe d at hi gh s ta tic
-t on a irf lo w (S pe ed ta b
5) . T o ch an ge to
.5 -t on a irf lo w , m ov e th e bl ue w ire to S pe ed ta b or o n th e Co ns ta nt T or qu e (E
CM
) m ot or
Th e lo w s ta tic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic b el ow
.5
W C.
T he h ig h st at ic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic e xc ee di ng
.5
W C.
M ov e th e bl ue w ire to th e ap pr op ria te S pe ed ta b as re qu ire d by th e ap pl ic at io n ne ed s.
Th e ai rfl ow fo r c on tin uo us fa n (S pe ed ta b
1) is a lw ay s se t a t 5 0% o f t he S pe ed ta b
4.
Th e ab ov e ai rfl ow ta bl e lis ts th e ai rfl ow in fo rm at io n fo r a ir ha nd le rs w ith ou t h ea te r a nd a ir ha nd le r w ith m ax im um h ea te r a llo w ed fo r e ac h m od el
Th e fo llo w in g fo rm ul a ca n be u se d to c al cu la te th e ap pr ox im at e ai rfl ow
, i f a s m al le r ( N kW ) t ha n th e m ax im um h ea te r k it is in st al le d.
Ap pr ox im at e Ai rfl ow
A irf lo w w ith ou t h ea te r –
(A irf lo w w ith ou t h ea te r – A irf lo w w ith m ax im um h ea te
r) x
(N k
W /m ax im um h ea te r k W
D es ig na te s
M et ri c
C o nv er si o ns
RH1T/RH2T Series
M od el N o.
R
H 2T
N om in al
Co ol in g
Ca pa ci ty
To ns
M ot or Sp ee d
Fr om
Fa ct or y
M an uf ac tu re r R ec om m en de d
Ai r-
Fl ow
R an ge (M in /M ax ) C
FM
Bl ow er S iz e/
M ot or H
P of S pe ed s
Y1 , Y
Sp ee d
M ot or Sp ee d
X-
W et
C oi l N o
Fi lte r C
FM
A ir
D el iv er y/ R
PM
/W at ts
-2
V ol ts
Ex te rn al
S ta tic P re ss ur e—
In ch es W
.C kP a]
0.
0.
0.
0.
0.
0.
0.
0.
0.
1.
M T
N o
H ea te r
4.
Y1 T ap
Y2 T ap
Y1 =7
/1
CF
M
[3
/5
] L /s
Y2 =9
/1
CF
M
[4
/7
] L /s
X1
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
M T
W ith kW H ea te r 4.
Y1
T ap
Y2
T ap
Y1 =6
/1
CF
M
[3
/5
] L /s
Y2 =9
/1
CF
M
[4
/7
] L /s
X1
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Ai rf lo w
P er fo rm an ce
D at a
RH
2T
No te s:
C on st an t T or qu e (E
CM
) m ot or s pe ed c ha ng es
Al l C on st an t T or qu e (E
CM
) m ot or s ha ve s pe ed ta bs . S pe ed ta b is fo r c on tin uo us fa n.
S pe ed ta b
(lo w s ta tic ) a nd S pe ed ta b
(h ig h st at ic ) a re fo r l ow er to nn ag e.
Sp ee d ta b
(lo w s ta tic
) a nd
S pe ed ta b
(h ig h st at ic
) a re fo r h ig he r t on na ge
Co ns ta nt T or qu e ai r h an dl er s ar e al w ay s sh ip pe d fro m fa ct or y at
S pe ed ta b 5, e xc ep t f or
, w hi ch is s et a t S pe ed ta b
3.
F or in st an ce
H2
T is a lw ay s sh ip pe d at hi gh s ta tic
-t on a irf lo w (S pe ed ta b
5) . T o ch an ge to
.5 -t on a irf lo w , m ov e th e bl ue w ire to S pe ed ta b or o n th e Co ns ta nt T or qu e (E
CM
) m ot or
Th e lo w s ta tic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic b el ow
.5
W C.
T he h ig h st at ic
S pe ed ta b
(lo w er to nn ag
e) a nd
(h ig he r t on na ge ) a re u se d fo r e xt er na l s ta tic e xc ee di ng
.5
W C.
M ov e th e bl ue w ire to th e ap pr op ria te S pe ed ta b as re qu ire d by th e ap pl ic at io n ne ed s.
Th e ai rfl ow fo r c on tin uo us fa n (S pe ed ta b
1) is a lw ay s se t a t 5 0% o f t he S pe ed ta b
4.
Th e ab ov e ai rfl ow ta bl e lis ts th e ai rfl ow in fo rm at io n fo r a ir ha nd le rs w ith ou t h ea te r a nd a ir ha nd le r w ith m ax im um h ea te r a llo w ed fo r e ac h m od el
Th e fo llo w in g fo rm ul a ca n be u se d to c al cu la te th e ap pr ox im at e ai rfl ow
, i f a s m al le r ( N kW ) t ha n th e m ax im um h ea te r k it is in st al le d.
Ap pr ox im at e Ai rfl ow
A irf lo w w ith ou t h ea te r –
(A irf lo w w ith ou t h ea te r – A irf lo w w ith m ax im um h ea te
r) x
(N k
W /m ax im um h ea te r k W
D es ig na te s
M et ri c
C o nv er si o ns
RH1T/RH2T Series
M od el N o.
R
H 2T
N om in al
Co ol in g
Ca pa ci ty
To ns
M ot or Sp ee d
Fr om
Fa ct or y
M an uf ac tu re r R ec om m en de d
Ai r-
Fl ow
R an ge (M in /M ax ) C
FM
Bl ow er S iz e/
M ot or H
P of S pe ed s
Y1 , Y
Sp ee d
M ot or Sp ee d
X-
W et
C oi l N o
Fi lte r C
FM
A ir
D el iv er y/ R
PM
/W at ts
-2
V ol ts
Ex te rn al
S ta tic P re ss ur e—
In ch es W
.C kP a]
0.
0.
0.
0.
0.
0.
0.
0.
0.
1.
ST
N o H ea te r 5.
Y1
T ap
Y2
T ap
Y1 =7
/1
CF
M
[3
/6
] L /s
Y2 =1
9/
C
FM
[5
/8
] L /s
X1
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
ST
W ith kW
H ea te r
5.
Y1 T ap
Y2 T ap
Y1 =7
/1
CF
M
[3
/6
] L /s
Y2 =1
9/
C
FM
[5
/8
] L /s
X1
3/ hp s pe ed
Y1 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y2 Lo w S ta tic
Ta p
CF
M
R
PM
W at ts
Y1 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Y2 H ig h
St at ic Ta p
CF
M
R
PM
W at ts
Ai rf lo w
P er fo rm an ce
D at a
RH
2T
RH1T/RH2T Series
Model RH2T Voltage Phase* Hertz HP RPM Speeds Circuit
Amps.
Minimum Circuit
Ampacity
Maximum Circuit
Protector
2421MT
208/240 1 & 3 60
1/3 300-1100 4 1.6 2 15
3621MT 3/4 300-1100 4 3.8 5 15
6024ST/4824MT 3/4 300-1100 4 4.6 6 15
Air Handler Model
RH2T
Heater Model
No.
Heater kW (208/240V)
(480V) Ph/Hz
No.
Elements
- kW Per
Type Supply Circuit
Single Circuit Multiple Circuit
Circuit Amps.
Motor Ampacity
Minimum Circuit
Ampacity
Maximum Circuit
Protector
2421MT
RXBH-1724?03J 2.25/3.0 1/60 1-3.0 SINGLE 10.8/12.51.6 1.6 16/18 20/20
RXBH-1724?05J 3.6/4.8 1/60 1-4.8 SINGLE 17.3/20.0 1.6 24/27 25/30
RXBH-1724?07J 5.4/7.2 1/60 2-3.6 SINGLE 26.0/30.0 1.6 35/40 35/40
RXBH-1724?10J 7.2/9.6 1/60 2-4.8 SINGLE 34.6/40.0 1.6 46/52 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE 45.1/52.1 1.6 59/68 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1 15.0/17.4 1.6 21/24 25/25
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2 30.1/34.7 0 38/44 40/45
RXBH-1724A10C 7.2/9.6 3/60 3-3.2 SINGLE 20.0/23.1 1.6 27/31 30/35
3621MT
RXBH-1724?05J 3.6/4.8 1/60 1-4.8 SINGLE 17.3/20.0 3.8 27/30 30/30
RXBH-1724?07J 5.4/7.2 1/60 2-3.6 SINGLE 26.0/30.0 3.8 38/43 40/45
RXBH-1724?10J 7.2/9.6 1/60 2-4.8 SINGLE 34.6/40.0 3.8 48/55 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE 51.9/60.0 3.8 70/80 70/80
RXBH-1724A15J
3.6/4.8 1/60 1-4.8 MULTIPLE CKT 1 17.3/20.0 3.8 27/30 30/30
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17.0 1/60 4-4.26 SINGLE 61.6-70.8 3.8 82/94 90/100
RXBH-1724A18J
6.4/8.5 1/60 2-4.26 MULTIPLE CKT 1 30.8/35.4 3.8 44/49 45/50
6.4/8.5 1/60 2-4.26 MULTIPLE CKT 2 30.8/35.4 0.0 39/45 40/45
RXBH-1724A10C 7.2/9.6 3/60 3-3.2 SINGLE 20.0/23.1 3.8 30/34 30/35
RXBH-1724A15C 10.8/14.4 3/60 3-4.8 SINGLE 30.0/34.6 3.8 43/48 45/50
RXBH-1724B05J 3.6/4.8 1/60 1-4.8 SINGLE 17.3/20.0 3.8 27/30 30/30
RXBH-1724B07J 5.4/7.2 1/60 2-3.6 SINGLE 26.0/30.0 3.8 38/43 40/45
RXBH-1724B10J 7.2/9.6 1/60 2-4.8 SINGLE 34.6/40.0 3.8 48/55 60/60
* Blower motors are all single phase motors.
• ? Heater Kit Connection Type A = Breaker B = Terminal Block C = Pullout Disconnect ➀ D Voltage = 480 Volts.
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• Largest motor load is included in single circuit or circuit 1 of multiple circuits.
• Heater loads are balanced on 3 phase models with 3 or 6 heaters only.
• No electrical heating elements are permitted to be used with A voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase 208/240V volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
[ ] Designates Metric Conversions
Electrical Data – With Electric Heat Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
Electrical Data – Blower Motor Only – No Electric Heat RH2T
RH1T/RH2T Series
Air Handler Model
RH2T
Heater Model
No.
Heater kW (208/240V)
(480V) Ph/Hz
No.
Elements
- kW Per
Type Supply Circuit
Single Circuit Multiple Circuit
Circuit Amps.
Motor Ampacity
Minimum Circuit
Ampacity
Maximum Circuit
Protector
4824MT/
6024ST
RXBH-1724?07J 5.4/7.2 1/60 2-3.6 SINGLE 26.0/30.0 4.6 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2-4.8 SINGLE 34.6/40.0 4.6 49/56 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE 51.9/60.0 4.6 71/81 80/90
RXBH-1724A15J
3.6/4.8 1/60 1-4.8 MULTIPLE CKT 1 17.3/20.0 4.6 28/31 30/35
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 4-4.26 SINGLE 61.8/70.8 4.6 83/95 90/100
RXBH-1724A18J
6.4/8.5 1/60 2-4.26 MULTIPLE CKT 1 30.8/35.4 4.6 45/50 45/50
6.4/8.5 1/60 2-4.6 MULTIPLE CKT 2 30.8/35.4 0 39/45 40/45
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE 69.2/80 4.6 93/106 100/110
RXBH-24A20J
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1 34.6/40.0 4.6 49/56 50/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE 86.4/99.9 4.6 114/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1 28.8/33.3 4.6 42/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2 28.8/33.3 0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 3 28.8/33.3 0 36/42 40/45
RXBH-24A30J
(5-ton only) 21.6/28.8 1/60 6-4.8 SINGLE 103.8/120 4.6 136/156 150/175
RXBH-24A30J
(5-ton only)
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1 34.6/40.0 4.6 49/56 56/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0 44/50 56/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 3 34.6/40.0 0 44/50 56/60
RXBH-1724A10C 7.2/9.6 3/60 3-3.2 SINGLE 20.0/23.1 4.6 31/35 35/35
RXBH-1724A15C 10.8/14.4 3/60 3-4.8 SINGLE 30.0/34.6 4.6 44/49 45/50
RXBH-24A20C* 14.4/19.2 3/60 3-3.2 SINGLE 40.0-46.2 4.6 56/64 60/70
RXBH-24A20C
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 1 20.0/23.1 4.6 31/35 35/35
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 2 20.0/23.1 0 25/29 25/30
RXBH-24A25C* 18.0/24.0 3/60 6-4.0 SINGLE 50.0/57.8 4.6 69/78 70/80
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1 25.0/28.9 4.6 37/42 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2 25.0/28.9 0 32/37 35/40
RXBH-24A30C*
(5-ton only) 21.6/28.8 3/60 6-4.8 SINGLE 60.0/69.4 4.6 81/93 90/100
RXBH-24A30C
(5-ton only)
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 1 30.0/34.7 4.6 44/50 45/50
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 2 30.0/34.7 0 38/44 40/45
• ? Heater Kit Connection Type A = Breaker B = Terminal Block C = Pullout Disconnect ➀ D Voltage = 480 Volts.
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater…