This document contains details regarding a federal solicitation for mechanical construction services. The solicitation number is 36C77623R0193 and is for the Women's Clinic and Radiology Addition project at the Minneapolis VA Medical Center. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The solicitation seeks mechanical construction and installation services to support additions to the Women's Clinic and Radiology department at the Minneapolis VAMC. The response due date and anticipated award date are not provided in this document.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL ABBREVIATIONS
AD AREA DRAIN
A.F.F. ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ANB ACID NEUTRALIZING BASIN
AP ACCESS PANEL
ARCH ARCHITECT
AS AIR SEPARATOR
BD BUTTERFLY DAMPER
B/G BELOW GRADE
BTU BRITISH THERMAL UNIT
BWV BACKWATER VALVE
CCF HUNDRED CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CO CLEAN OUT
CONTR CONTRACTOR
CONV CONVECTOR
CUH CABINET UNIT HEATER
CW COLD WATER
DB DECIBEL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DISCH DISCHARGE
DMPR DAMPER
DN DOWN
DR DRAIN
DS DOWNSPOUT
DWG DRAWING
EAT ENTERING AIR TEMPERATURE
EDR EQUIVALENT DIRECT RADIATION
EP ELECTRIC-PNEUMATIC
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION
F FAHRENHEIT
FC FAN COIL
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FLR FLOOR
FLEX FLEXIBLE
FM FIRE MAIN
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET OR FOOT
F&T FLOAT AND THERMOSTATIC
FTG FOOTING
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIBB
HD HEAD
HOA HANDS-OFF-AUTOMATIC
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATION,
AND AIR CONDITIONING
HYD HYDRANT
HW HOT WATER
GCO GRADE CLEANOUT
INSUL INSULATION
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LWT LEAVING WATER TEMPERATURE
MBH BTU PER HOUR (THOUSANDS)
MCF THOUSAND CUBIC FEET
MH MANHOLE
NC NOISE CRITERIA OR
NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP OR DIFFERENCE
PE PNEUMATIC-ELECTRIC
PLBG PLUMBING
PRV PRESSURE REDUCING VALVE
OR POWER ROOF VENTILATOR
PSIA POUNDS/SQ INCH ABSOLUTE
PSIG POUNDS/SQ INCH GAUGE
PVC POLY VINYL CHLORIDE
RA RETURN AIR
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RECIRC RECIRCULATING
REG REGISTER
RET RETURN
RH RELATIVE HUMIDITY
RHT REHEAT
RHC REHEAT COIL
RHW RECIRCULATED HOT WATER
RM ROOM
RPM REVOLUTIONS PER MINUTE
RPZ REDUCED ZONE BACKFLOW
PREVENTER
SA SUPPLY AIR
SAN SANITARY
SCFM CFM, STANDARD CONDITIONS
SD SMOKE DAMPER
SP STATIC PRESSURE
SPECS SPECIFICATIONS
SUP SUPPLY
SQ SQUARE
STM STEAM
TD TEMPERATURE DIFFERENCE
TEMP TEMPERATURE
TONS TONS OF REFRIGERATION
T-STAT THERMOSTAT
TYP TYPICAL
UB UP-BLAST
UG UNDERGROUND
UH UNIT HEATER
UR URINAL
V SANITARY VENT
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W SANITARY WASTE
W/ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
W/0 WITHOUT
WTR WATER
PLUMBING
ACID VENT BELOW GRADE
ACID VENT ABOVE GRADE
ACID WASTE BELOW GRADE
ACID WASTE ABOVE GRADE
DEIONIZED WATER
FILTERED WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. INDICATED)
DOMESTIC RECIRC. HOT WATER
HARD COLD WATER
OVERFLOW STORM DRAIN BELOW GRADE
OVERFLOW STORM DRAIN ABOVE GRADE
REVERSE OSMOSIS WATER
SANITARY VENT BELOW GRADE
SANITARY VENT ABOVE GRADE
SANITARY WASTE
SANITARY SEWER
SOIL DRAINAGE TILE
SOFTENED COLD WATER
SOFTENED HOT WATER
TEMPERED WATER
STORM DRAIN BELOW GRADE
STORM DRAIN ABOVE GRADE
WELL WATER
EXISTING PLUMBING TO REMAIN
EXISTING PLUMBING TO BE REMOVED
AV
AV
AW
AW
DI
HARD
SDT
OSD
RO
V
V
SS
W
SOFT
SHW
TW
OSD
SD
SD
WW
MECHANICAL PIPING
BOILER FEED
CHILLED WATER SUPPLY
CHILLED WATER RETURN
COMPRESSED AIR (PSI INDICATED)
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FUEL OIL FILL
GLYCOL SUPPLY
GLYCOL RETURN
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
LABORATORY VACUUM
LABORATORY AIR
LIQUIFIED PETROLEUM GAS
NATURAL GAS (PSI INDICATED)
PLANT VACUUM
PUMPED CONDENSATE
RADIATION WATER SUPPLY
RADIATION WATER RETURN
REFRIGERANT LIQUID
BF
CWS
CWR
10#A
CD
FOS
LV
GS
GR
HRS
HRR
HWR
HWS
LA
LPG
2#G
FOF
PV
PC
RADS
CS
CR
FOR
FOV
RADR
RL
REFRIGERANT SUCTION
REFRIGERANT HOT GAS BYPASS
REHEAT WATER SUPPLY
REHEAT WATER RETURN
REMOTE RADIATOR SUPPLY
REMOTE RADIATOR RETURN
SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURN
SNOW MELT SUPPLY
SNOW MELT RETURN
STEAM SUPPLY (PSI INDICATED)
STEAM RETURN (PSI INDICATED)
EXISTING PIPING TO REMAIN
RRS
RS
RHG
RHR
RHS
RRR
SHWS
SHWR
SMS
SMR
10#STM
10#R
PLUMBING /PIPING
ELBOW DOWN
PIPE CAP
ELBOW UP
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
CONNECTION, TOP
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE CONNECTION
PIPE ANCHOR
ALIGNMENT GUIDE
CHECK VALVE
SHUTOFF VALVE
PLUG VALVE
COMBINATION BALANCE VALVE
AND FLOW METER
STRAINER
STRAINER W/BLOWDOWN
CAP AND VALVE
PRESSURE REDUCING VALVE
(SETTING AS NOTED, PSI)
MEDICAL GAS
MEDICAL VACUUM
WASTE ANESTHETIC GAS DISPOSAL
CARBON DIOXIDE
OXYGEN
NITROGEN
NITROUS OXIDE
MEDICAL AIR
WAGD
CO2
O
N
MV
N2O
MA
CONTROLS
AQUA STAT
TAMPERPROOF THERMOSTAT
HUMIDISTAT OR R.H. SENSOR
REFRIGERANT SENSOR
SMOKE DETECTOR
SPACE TEMPERATURE SENSOR
STATIC PRESSURE SENSOR
DUCTWORK
SUPPLY AIR
RETURN AIR
EXHAUST AIR
STANDARD BRANCH, NO SPLITTER -
SUPPLY FLOW TO RIGHT -
RETURN/EXHAUST FLOW TO LEFT
BELLMOUTH WITH BALANCING
DAMPER
FLEXIBLE DUCT
TURNING VANES
FLEXIBLE CONNECTION
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
FIRE DAMPER & ACCESS
PANEL
SMOKE DAMPER &
ACCESS PANEL
COMBINATION FIRE/SMOKE
DAMPER & ACCESS PANEL
SUPPLY GRILLE OR REGISTER
T
T
P P
ROOM PRESSURE
MONITOR
H
R
SD
TS
SP
T THERMOSTAT
THERMOSTAT W/GUARDT
EXPANSION JOINT
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
AUTOMATIC AIR VENT
MANUAL AIR VENT
PRESSURE RELIEF/SAFETY
VALVES(SETTING AS NOTED, PSI)
DRAIN VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE ANGLE VALVE
0. S.& Y. VALVE
REDUCED PRESSURE ZONE
BACK FLOW PREVENTER
SOLENOID VALVE
FLOW LIMITING VALVE
DIAPHRAGM
GLOBE VALVE
REFRIGERANT SIGHT GLASS
GAS PRESSURE REGULATOR VALVE
BACKWATER VALVE
REFRIGERANT DRYER
FLOW DIRECTION
FLOW DIRECTION W/PITCH
DUPLEX STRAINER
PIPE UNION
PIPE FLANGE
PUMP
THERMOMETER
PRESSURE/TEMPERATURE TEST PORT
STEAM TRAP (TYPE INDICATED)
FLOW MEASURING STATION
(FLOW INDICATED)
FLOW SWITCH
PRESSURE GAUGE W/PIGTAIL &
PETCOCK
PRESSURE SWITCH
SHOCK ABSORBER
ELBOW
FLOOR DRAIN
DRAIN ABOVE
FLOOR SINK
WALL HYDRANT
HOSE BIBB
TEE
WALL CLEANOUT
ROOF DRAIN
CATCH BASIN
MANHOLE
HB
RETURN DUCT UP, NEGATIVE
PRESSURE
SUPPLY DIFFUSER/REGISTER
BLANKOFF INDICATED
RETURN OR EXHAUST GRILLE
OR REGISTER
SUPPLY DUCT UP, POSITIVE
PRESSURE
EXHAUST DUCT UP, NEGATIVE
PRESSURE
RETURN GRILLE/REGISTER
EXHAUST GRILLE/REGISTER
LINEAR DIFFUSER
CONCENTRIC DUCT TRANSITION
ECCENTRIC DUCT TRANSITION
RECTANGULAR-TO-ROUND DUCT
TRANSITION
VAV BOX
REHEAT COIL
VAV BOX W/REHEAT COIL
DUCT OFFSETS
DUCT CUTLINE
M
FD
VERTICALHORIZONTAL
FD
SD
VERTICAL
VERTICALHORIZONTAL
FSD FSD
RETURN DUCT DN, NEGATIVE
PRESSURE
SUPPLY DUCT DN, POSITIVE
PRESSURE
EXHAUST DUCT DN, NEGATIVE
PRESSURE
DROPRISE
FIRE PROTECTION
DFP
F FIRE PROTECTION
FIRE PROTECTION (DRY SYSTEM)
POST INDICATOR VALVE (PIV)
FIRE HYDRANT WITH SHUTOFF VALVE
RECESSED FIRE DEPT CABINET
SURFACE MOUNTED FIRE DEPT CABINET
FIRE PROTECTION RISER
UPRIGHT SPRINKLER HEAD W/GUARD
PENDANT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
BUTTERFLY VALVE W/TAMPER SWITCH
DETECTOR CHECK W/BYPASS METER
GRADE FIRE DEPT CONNECTION
FLUSH FIRE DEPT CONNECTION
FIRE DEPT VALVE W/CAP AND CHAIN
O.S. & Y. VALVE W/TAMPER SWITCH
DRY PIPE VALVE
PREACTION VALVE
GPM
AM
S
FS
PS
TS
FDVC
FDVC
FDV
TS
SD
HORIZONTAL
GAS COCK VALVE
CLEANOUT
WH
GR GRILLE
VAV VARIABLE AIR VOLUME
VTR VENT THROUGH ROOF
CARBON MONOXIDE SENSORCO
ANNOTATION
(4)A-12"Ø
GRILLE, REGISTER, &
DIFFUSER IDENTIFICATION
QUANTITY
CFM
TYPE
SIZE
X X
X X
X X
X X
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
EQUIP DESIGNATION
EQUIP NUMBER
POINT OF CONNECTION, NEW TO EXISTING
POINT OF DISCONNECTION
FTR/RP 01
6'-5"
0.5
HYDRONIC FINNED TUBE
RADIATION & RADIANT
PANEL IDENTIFICATION
TYPE ACTIVE
ELEMENT
LENGTHGPM
EBR 01
6'-5"
ELECTRIC BASEBOARD
RADIATION
IDENTIFICATION
ACTIVE
ELEMENT
LENGTH
ZONE VALVE BOXZVB
AREA ALARM PANELAAP
MASTER ALARM PANELMAP
COMBINATION AREA/MASTER ALARM PANELCAP
NPCW NON-POTABLE COLD WATER
NPHW NON-POTABLE HOT WATER
INV INVERT
RLF RELIEF
FW
HW
RHW
GW GREASE WASTE
ISO ISOLATION EXHAUST
GEXH GREASE EXHAUST
MECHANICAL SYMBOLS LEGEND
EXISTING PIPING TO BE REMOVED
TYPE
DOMESTIC COLD WATERCW
CO2 CARBON DIOXIDE SENSOR
CLEAR WATER VENTCWV
CLEAR WATER WASTECWW
INTERRUPTIBLE GASIG
PROCESS AND LABORATORY
LABORATORY AIR
LABORATORY VACUUM
CLEAN DRY AIR
REVERSE OSMOSIS
DEIONIZED WATER
NITROGEN
HOUSE VACUUM
LV
CDA
RO
DI
LA
N
HV
PLANT VACUUMPV
ACID VENTAV
ACID WASTEAW
INSTRUMENT AIRIA
DOM. RECIRC. HOT WATER (TEMP. INDICATED)140 RHW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:1
A
M
1375-M000
MECHANICAL TITLE SHEET WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
MECHANICAL SHEET LIST
SHEET
NUMBER SHEET NAME
1375-M000 MECHANICAL TITLE SHEET
1375-MH111 FIRST LEVEL HVAC PLAN
1375-MP111 FIRST LEVEL PIPING PLAN
1375-M121 MECHANICAL ROOF PLAN
1375-M400 MECHANICAL ROOM ENLARGED PLANS
1375-M500 AIR HANDLING UNIT DETAILS
1375-M501 BUILDING SYSTEM - PIPING AND FLOW DIAGRAMS
1375-M502 MECHANICAL DETAILS
1357-M503 MECHANICAL DETAILS
1375-M504 SEQUENCE OF OPERATION
1375-M600 MECHANICAL SCHEDULES
1375-M601 MECHANICAL/ ELECTRICAL SCHEDULES
1375-M602 MECHANICAL/ ELECTRICAL SCHEDULES
1375-FP111 FIRST LEVEL FIRE PROTECTION PLAN
1375-PG111 FIRST LEVEL MEDICAL GAS PLAN
1375-PG112 FIRST LEVEL MEDICAL GAS PLAN - DEDUCT ALT#1
1375-PP101 UNDERFLOOR PLUMBING PLAN
1375-PP111 FIRST LEVEL PLUMBING PLAN
1375-PP400 WASTE AND VENT RISER DIAGRAM
1375-PP401 DOMESTIC WATER DIAGRAM
1375-P500 PLUMBING DETAILS
1375-P600 PLUMBING/ ELECTRICAL SCHEDULES
SHEET TOTAL: 22
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023Revisions: Date:
benz Snapshot
MM
M
KEY NOTES:
GENERAL NOTES:
M
B
C
D
E
F
1 2 3 5 6
4 5.7
A
1.5 2.1
80-148
80-149
80-C1-06
80-120
80-119
80-118
80-C1-03
80-114
80-113
80-112 80-111
80-110
80-C1-02
80-C1-01
80-109
80-108
80-104
80-105
80-123
Unoccupied
Unoccupied
80-126
80-127
80-128 80-129 80-130
80-100
80-103
80-100A
80-101
80-131
80-C1-04
80-133
80-134
80-138
80-136 80-137
80-135
M400
12x10 x x x
16x12
10x10
20x14BOD: 14' - 7" x
12x12 x
10ø
8x12 x x x x
8x10
14x14 x
26x16 x
22x16 x x x x x x
44x24
32x18 30x16
10x10
10x12
38x18 34x18 x x
18x14BOD: 14' - 7" x x
48x18 x ø x
16x14
12x10
16x16 UP
(EF 01)
VAV
1-03
VAV
1-10
VAV
1-04
VAV
1-05
VAV
1-06
VAV
1-07
VAV
1-08
VAV
1-09
VAV
1-11
VAV
1-14
VAV
1-13
VAV
1-12
VAV
1-21
VAV
1-18
VAV
1-16
VAV
1-17
VAV
1-15
VAV
1-22
VAV
1-27
VAV
1-19
VAV
1-28
VAV
1-26
VAV
1-23
VAV
1-20
VAV
1-24
VAV
1-25
VAV
1-29
VAV
1-30
VAV
1-02
(2)A-10"
J-8"
G-12"
A-10"
H-8"
(2)A-10"
H-12"
(2)A-10"
A-6" 50 J-8"
A-6"
A-6"
H-8"
H-12"
J-8"
A-8"
A-8"
H-10"
A-10"
A-8"
A-8"
J-8"
H-8"
A-8"
J-8"
H-8"
(2)A-10"
H-10"
J-8"
(2)F-8"
H-8"
(2)B-6" x
(2)A-10"
H-10"
(2)A-10"
H-10"
J-8"
A-8"
A-8" 135 A-8"
A-8"
A-8"
H-8"
H-8"
H-8"
A-6"
(3)A-10"
A-10"
A-10"
H-8"
H-8"
A-8"
H-8"
A-8"
A-8"
H-8"
A-8"
H-8"
A-8"
H-8"
H-8"
A-8" 135 J-8"
A-8"
A-8"
H-8"
H-8"
H-8"
A-8"
J-8"
J-8"
(10)B-6"
12x8
10x10
G-16"
(5)A-10"
G-16"
(3)A-8"
H-8"
H-8"
H-8"
H-10"
H-8"
G-14"
J-8"
(2)B-8"
B-6"
A-8"
A-10"
A-8"
H-10"
A-8"
14x14
10x12
10x6
38x18
12x10
A-8"
A-8"
D-6"
6ø
B-6"
G-14"
24x14 x 416x10 x
8ø
G-16"
G-14"
A-10"
H-14" x
RISE
DROP
R
IS
E
R
IS
E
RISE
D R
O P
DROP
10x12
UP
DN
ø ø ø ø
10x10 x
24x12
RISE
12ø
38x18
38x18
R
IS
E
R
IS
E x x
18x12
22x12
F-12"
26x16
80-106
80-107
E-12"
(2)F-12" x
A-8"
D-6"
80-124 ø
28x16
BOD: 14' - 9"
BOD: 11' - 9"
38x16
BOD: 14' - 5"
BOD: 13' - 0"
K-6"
K-6"
BOD: 13' - 7"
BOD: 12' - 0"
60x24 x x x x
REFER TO M400 FOR DUCT
SIZING, NOTES, & DETAILS
WITHIN MECHANICAL ROOM
H-6"
H-6"
K-6"
K-6"
K-6"
E-12"
VAV
1-32 x
C-12x10
C-12x10
A-8"
A-8"
A-8"
A-8"
A-8"
16ø
J-8"
ELECTRICAL
80-150
A.
B.
C.
D.
E.
F.
G.
H.
COORDINATE ALL DUCTWORK ROUTING WITH ALL OTHER TRADES TO
INSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER OF RECORD. PROVIDE ALL OFFSETS AND
TRANSITIONS AS REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL DUCTWORK DIRECTLY TO STRUCTURE. DO NOT
SUPPORT ANY DUCTS FROM DUCTWORK, CONDUIT, OR OTHER PIPING
ENCOUNTERED.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO VAV BOXES SHALL BE
THE SAME SIZE AS THE VAV INLET CONNECTION.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO DIFFUSERS, GRILLES
AND REGISTERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR
GRILLE/REGISTER CONNECTION.
ALL FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS
INSTALLED IN SHAFT WALLS SHALL BE INSTALLED TO ALLOW FOR
SERVICE OF THEIR FUSABLE LINK/ACTUATOR PER FACILITY
STANDARDS. ANY CONFLICTS WHICH WILL PREVENT ACCESS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER OF
RECORD.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD. DO NOT INSTALL VALVES,
VAV BOXES, SENSOR, OR DAMPERS ABOVE GYPSUM BOARD CEILINGS.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD CEILINGS AND
BULKHEADS. ADJUST PIPE AND DUCT THAT RUN PARALLEL TO
BULKHEAD FRAMING TO BE EITHER OUTSIDE OF FRAMING OR
BETWEEN FRAMING. MECHANICAL CONTRACTOR SHALL COORDINATE
WITH GENERAL CONTRACTOR FOR MODIFIED BULKHEAD FRAMING
WHERE EXISTING AND NEW PIPING AND DUCT WILL CAUSE
INTERFERENCE.
PROVIDE EACH NEW SUPPLY DIFFUSER/GRILLES WITH A SINGLE BLADE
TAKE-OFF DAMPER WITH QUADRANT LOCKING DEVISE. PERFORM ALL
BALANCING OF NEW DIFFUSERS THROUGH THOSE TAKE-OFF
DAMPERS. ALL NEW RETURN/EXHAUST GRILLES WILL BE PROVIDED
WITH OPPOSED BLADE BALANCING DAMPERS POSITIONED UPSTREAM
PAST A MINIMUM OF ONE TRANSITION FOR SOUND ABATEMENT.
BALANCING ANY DIFFUSERS/GRILLES USING INTEGRAL DAMPERS WILL
NOT BE AN APPROVED METHOD OF BALANCING.
DO NOT ROUTE DUCTWORK OVER THIS ROOM.
PROVIDE AND INSTALL FOUR (4) DUROZONE , EXTERNAL GEAR DRIVEN
CABLE OPERATED DAMPER IN LOCATION SHOWN. PROVIDE TWO (2)
WITH 15'-0" CABLES AND TWO (2) WITH 5'-0" CABLES. VERIFY CABLE
LENGTHS. (BALANCING OF RETURN AIR DIFFUSERS IN ROOMS 80-100,
80-103, 80-104 AND 80-124.)
PROVIDE AND INSTALL TWO (2) DUROZONE, EXTERNAL GEAR DRIVEN
CABLE OPERATED DAMPER IN LOCATION SHOWN. PROVIDE TWO (2)
WITH 19'-0" CABLES. VERIFY CABLE LENGTHS. (BALANCING OF SUPPLY
AIR DIFFUSERS IN ROOM 80-101.)
PROVIDE AND INSTALL TWELVE (12) DUROZONE, EXTERNAL GEAR
DRIVEN CABLE OPERATED DAMPER IN LOCATION SHOWN. PROVIDE
FOUR (4) WITH 26'-0" CABLES, THREE (3) WITH 24'-0", THREE (3) WITH
22'-0" CABLES, AND TWO (2) WITH 15'-0" CABLES. VERIFY CABLE
LENGTHS. (BALANCING OF SUPPLY AIR DIFFUSERS IN ROOMS 80-100.)
C
2 3 6 75.7
A
2.1
B
80-126
80-127 80-129
80-100
80-100A
80-101
80-131
80-C1-04
80-133
80-134
Unoccupied
80-138
80-136 80-137
80-135
22x16 x
44x24
32x18 30x16
18x14BOD: 14' - 7" x
16x14 12x10
16x16 UP
(EF 01)
VAV
1-03
VAV
1-10
VAV
1-04
VAV
1-05
VAV
1-06
VAV
1-07
VAV
1-08
VAV
1-09
VAV
1-11
VAV
1-14
VAV
1-13
VAV
1-12
VAV
1-02
J-8"
A-8"
A-8"
H-10"
A-10"
A-8"
J-8"
J-8"
(2)F-8"
H-8" x
H-8" 135H-8"
H-8"
10x10
10x12
10x6
A-8"
24x14 x
16x10
G-16"
G-14"
RISE
R
IS
E
RISE
10x10 x
24x12
18x12
22x12
F-12"
E-12"
(2)F-12" x ø
28x16
BOD: 14' - 9"
BOD: 13' - 0"
H-6"
H-6"
K-6"
K-6"
E-12"
E
F
2 32.1
80-119
80-118
BOD: 14' - 7"
x
10ø
10x10
38x18 x x
VAV
1-27
VAV
1-28
VAV
1-26
VAV
1-29
A-10"
J-8"
(10)B-6"
12x8
G-16"
RISE
R
IS
E
BOD: 14' - 5"
K-6"
D
2 32.1
80-123
80-135 x
12x12 8x12 x
44x24
10x12 x
48x18
VAV
1-10
VAV
1-09
VAV
1-26
VAV
1-25
J-8"
A-6"
(3)A-10"
10x10
14x14
A-8"
RISE
DROP
10x12
RISE
38x18
R
IS
E
R
IS
E ø
BOD: 11' - 9"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:1
A
M
1375-MH111
FIRST LEVEL HVAC PLAN WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
1/8" = 1'-0"
FIRST LEVEL HVAC PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023
1/8" = 1'-0"
FIRST LEVEL HVAC PLAN - DEDUCT ALTERNATE #3
1/8" = 1'-0"
FIRST LEVEL HVAC PLAN - DEDUCT ALTERNATE #4
1/8" = 1'-0"
FIRST LEVEL HVAC PLAN - DEDUCT ALTERNATER #5
Revisions: Date:
L
IG
H T
E D
L
IG
H T
E D
L
IG
H T
E D
R E
M O
V A
B L
E L
IG
H
T E
D L
IG
H
T E
D
R E
M O
V A
B L
E
R E
M O
V A
B L
E
R E
M O
V A
B L
E
R E
M O
V A
B L
E
L
IG
H T
E D
KEY NOTES:
GENERAL NOTES:
B
C
D
E
F
1 2 3 5 6
4 5.7
A
1.5 2.1
HOUSEKEEPING
AIDES CLOSET
80-148
TELECOMMUNICATIONS
ROOM
80-149
CORRIDOR
80-C1-06
TOILET, STAFF
80-119
TOILET, EXAM
ROOM
80-118
CORRIDOR
80-C1-03
EXAM ROOM
80-114
TOILET, EXAM
ROOM
80-113
EXAM ROOM
80-112
EXAM ROOM
80-111
EXAM ROOM
80-110
PATIENT
CORRIDOR
80-C1-02
PATIENT
CORRIDOR
80-C1-01
M.H. CONSULT
ROOM
80-109
M.H. CONSULT
ROOM
80-108
SHARED
MEDICAL APPT.
ROOM
80-104
CONSULT ROOM
(NEIGHBORS)
80-105
STORAGE
MEDICAL
EQUIPMENT
80-123
PROCEDURE
ROOM,
GYNECOLOGY
80-126
EXAM ROOM
80-127
EXAM ROOM
80-128
EXAM ROOM
80-129
NEGATIVE AIR
EXAM ROOM
80-130
GENERAL
WAITING
80-100
LACTATION
ROOM
80-103
VESTIBULE
80-100A
RECEPTION
80-101TOILET
BARIATRIC
80-131
CORRIDOR
80-C1-04
STERILE
STORAGE
80-133
UTILITY ROOM
CLEAN
80-134
BREAK AND
LOCKER ROOM
80-138
UTILITY ROOM
SOILED
80-136
TOILET, STAFF
80-137
WORKSTATION
PROGRAM
COORDINATOR
80-135
VAV
1-02
VAV
1-03 VAV
1-04
VAV
1-05
VAV
1-06
VAV
1-07
VAV
1-08
VAV
1-09
VAV
1-10
VAV
1-11
VAV
1-12
VAV
1-13
VAV
1-14
VAV
1-15
VAV
1-16
VAV
1-17
VAV
1-20
VAV
1-21
VAV
1-23
VAV
1-22
VAV
1-24
VAV
1-25
VAV
1-26
VAV
1-27
VAV
1-29
VAV
1-30
VAV
1-18
VAV
1-19
T VAV 1-03 TVAV 1-04 TVAV 1-05 TVAV 1-06
T VAV 1-07
T
FTR
VAV 1-08
T VAV 1-14
TVAV 1-13TVAV 1-12
TVAV 1-11
T VAV 1-10
TVAV 1-09
T VAV 1-25
T VAV 1-28
T VAV 1-26
T VAV 1-24
T VAV 1-23
T VAV 1-22T VAV 1-27
TVAV 1-30
T VAV 1-29
T
FTR
VAV 1-15
T
FTR
VAV 1-16
TVAV 1-17
TVAV 1-20
T VAV 1-18
T VAV 1-19
M400
VAV
1-28
AC
1-01
7' - 6"
FTR 01
16' - 0"
FTR 01
7' - 0"
FTR 01
3' - 6"
FTR 01
18' - 0"
FTR 01
14' - 0"
FTR 02
6' - 0"
FTR 02
7' - 6"
FTR 01
3' - 0"
FTR 02
4' - 6"
FTR 01
3' - 0"
FTR 02
4' - 0"
FTR 01
T
FTR
AC 1-01
T
FTR
T
FTR
2" SMS
2" SMR
2" SMS
2" SMR
SHWP
1-01
CONSULT ROOM
(NEIGHBORS)
80-106
CONSULT ROOM
(NEIGHBORS)
80-107
TVAV 1-21
PACT AREA
80-124
13 13 13
13131313 13 13
BALANCE FINNED
TUBE AT FLOOR -
2.5 GPM
ABOVE CEILING -
1.2 GPM
BALANCE FINNED
TUBE AT FLOOR -
1.1 GPM
ABOVE CEILING -
0.5 GPM
3.4 GPM
1.0 GPM 0.6 GPM
SNOWMELT
MANIFOLD #1
SNOWMELT
MANIFOLD #2
1230 SQ FT AREA SERVED BY SNOWMELT MANIFOLD #2. SPACE
TUBING TO ACHIEVE 185 BTU/SQ FT. RESULTS TO AN ESTIMATED
10 ZONES EACH WITH 250' OF 5/8" PEX TUBING. SNOW MELT
SYSTEM MANUFACTURER TO PROVIDE COMPLETE ZONING
PLANS FOR REVIEW AND APPROVAL BY ENGINEER-OF-RECORD.
325 SQ FT AREA SERVED BY SNOWMELT MANIFOLD #1.
SPACE TUBING TO ACHIEVE 185 BTU/SQ FT. RESULTS
TO AN ESTIMATED 3 ZONES EACH WITH 250' OF 5/8"
PEX TUBING. SNOW MELT SYSTEM MANUFACTURER
TO PROVIDE COMPLETE ZONING PLANS FOR REVIEW
AND APPROVAL BY ENGINEER-OF-RECORD.
1 1/2" SMS
1 1/2" SMR
1 1/2" SMS
1 1/2" SMR
REFER TO M400 FOR PIPE
SIZING, NOTES, & DETAILS
WITHIN MECHANICAL ROOM
1" HWS 1 1/2" HWS
3" HWR 3" HWR
2" HWS2" HWS
3" HWR
2" HWS
/2
H W
R
/2
H W
S
/2
H W
S
/2
H W
R
H
W S
3" HWS
1 1/2" HWR
2 1/2" HWR
3" HWS
1 1/2" HWR1" HWR 1" HWR
3" HWS
/4
H
W S
/4
H
W R
3/4" HWR
3" HWS
/4
H
W S
H W
R
H
W R
1 1/2" HWR
1 1/2" HWS
H W
S
H
W R
1 1/2" HWS
1" HWR
1" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWS
3/4" HWR
BALANCE FINNED
TUBE AT FLOOR -
0.6 GPM
ABOVE CEILING -
0.3 GPM
BALANCE FINNED
TUBE AT FLOOR -
0.6 GPM
ABOVE CEILING -
0.3 GPM
H
OFFICE NURSE
MANAGER
80-120
OFFICE
MEDICAL
DIRECTOR
80-121
WORKSTATION -
RN CARE
MANAGER
80-122
EXAM ROOM
CANCER
SCREEN
80-117
EXAM ROOM
GYNECOLOGY
80-116
EXAM ROOM
80-115
PROCEDURE
ROOM,
MAMMOGRAPHY
80-140
RADIOLOGIST
READ ROOM
80-139
STORAGE
MAMMO
EQUIPMENT
80-142
PROCEDURE
ROOM,
MAMMOGRAPHY
80-143
OFFICE
MAMMOGRAPHY
SUPERVISOR
80-141
PROCEDURE
ROOM, BREAST
ULTRASOUND
80-144
WORKROOM
80-132
TOILET,
IMAGING
80-145
PROCEDURE
ROOM,
UROLOGY
80-125
TOILET
PROCEDURE
ROOM
80-126A
PACT AREA
80-124
PACT AREA
80-124 MEDICATION
ALCOVE
80-160
ELECTRICAL
80-150
/4
H
W R
/4
H
W S
MOISTURE SENSOR
(ON ROOF)
1 DO NOT ROUTE PIPING OVER THIS ROOM.
ROUTE 3/4" HEATING WATER SUPPLY AND RETURN PIPING DOWN IN
WALL TO MANIFOLD. PROVIDE 24"X24" RECESSED WALL BOX WITH
PRIMED STEEL PANEL TO ENCLOSE MANIFOLD. LOCATE A LOCKABLE
ACCESS DOOR IN DRESSING ROOM 80-146A. PAINT TO WALL COLOR.
LOCATE FTR-02 ABOVE CEILING, NEAR EXTERIOR OF BUILDING.
PEDESTAL FTR HAS DOUBLE ROW ELEMENTS ALONG ENTIRE LENGTH.
CONTRACTOR TO USE TOP ROW FOR SUPPLY WATER CONNECTION,
AND BOTTOM ROW TO RETURN WATER. CONCEAL PIPING BETWEEN
WALL PENETRATION AND FTR COVER AS MUCH AS POSSIBLE
OFFSET PIPING TO AVOID STRUCTURAL BEAM.
BALANCE FINNED TUBE RADIATION TO GPM INDICATED.
PROVIDE TWO CONTROL VALVES. ONE VALVE TO SERVE FINNED TUBE
RADIATION LOCATED AT THE FLOOR. ANOTHER VALVE TO SERVE
FINNED TUBE RADIATION LOCATED IN CEILING PLENUM. BALANCE TO
GPMS INDICATED ON PLAN.
INSTALL THERMOSTAT ABOVE CEILING.
PROVIDE SNOW MELT SYSTEM TO COVER THE AREA INDICATED.
VERIFY EXACTY POINT OF TERMINATION INTO EXISTING SIDEWALK
COVERED BY PCC SNOWMELT. SNOW MELT SYSTEM SHALL BE FULLY
DESIGNED BY THE SNOW MELT MANUFACTURER AND VERIFIED BY THE
ENGINEER. SYSTEM SIZED AT 185 BTUH/SQ FT. INCLUDE MOISTURE
SENSOR AND PACKAGED SNOWMELT CONTROLLER TO BE INTEGRATED
TO BUILDING AUTOMATION. SEE SPECIFICATIONS AND SEQUENCE OF
OPERATIONS FOR ADDITIONAL INFORMATION.
SNOW MELT MANIFOLD LOCATION. INSTALL MANIFOLD WITHIN A WALL
MOUNTED, IP65 RATED, ELECTRICAL BOX WITH ALL PIPING
PENETRATION TO/FROM BOTTOM SIDE (APPROXIMATELY 24"X24"X8").
ROUTE 1.5" SNOWMELT SUPPLY AND RETURN PIPING THROUGH
EXTERIOR WALL TO ENTER INTO MANIFOLD BOX FROM BOTTOM.
PROVIDE IN FLOOR RADIATION WITHIN HATCHED AREA. AREA IS
APPROXIMATELY 185 SQUARE FEET. RADIATION SYSTEM SHALL BE
FULLY DESIGN BY THE IN FLOOR RADIATION MANUFACTURER AND
VERIFIED BY THE ENGINEER. SYSTEM SIZED AT 30 BTUH/ SQ FT. SEE
SPECIFICATION FOR ADDITIONAL INFORMATION.
DASHED SQUARE BOX REPRESENTS 24"X24" ACCESS AREA FOR BOTH
VAV BOX ACTUATOR AND REHEAT COIL PIPING COMPONENTS SHOWN
ON DETAIL 12/M502. LOCATE VAV BOX 2 FEET ABOVE CEILING MAXIMUM.
PROVIDE A 24"X24" ACCESS PANEL TO ALLOW FOR SERVICE OF
SNOWMELT MANIFOLDS WITHIN WALL CAVITY SHOWN. PROVIDE SHEET
METAL ENCLOSURE AND MOUNTING BRACKETS FOR MANIFOLDS AND
ROUTE ALL PEX TUBING THROUGH FOUNDATION WALL SLEEVES
DESCRIBED IN KEY NOTE BELOW. NOTE WALL SLEEVE WILL BE BELOW
GRADE AND SHOULD BE PROVIDED WITH WIDE RADIUS ELBOW, OR
DEPRESSION IN SLAB TO ACCOMODATE.
PROVIDE 8" UNDERGROUND PIPING SLEEVES (EXACT QUANTITY TBD)
FOR ALL SUPPLY AND RETURN PEX PIPING THROUGH FOUNDATION
WALL. SLEEVE SHALL HAVE LINK SEAL ASSEMBLIES AND INFILLED WITH
EXPANDABLE FOAM TO SEAL ALL GAPS BETWEEN PEX TUBING.
PROVIDE ROOF MOUNTED MOISTURE SENSOR FOR MAIN ENTRY
SIDEWALK SNOWMELT SYSTEMS, TEKMAR MODEL 95 OR EQUAL. NOTE
THIS SENSOR WILL BE INDEPENDANT OF ADJACENT PCC SNOWMELT
SYSTEM. COORDINATE SENSOR LOCATION WITH ARCHITECT/ENGINEER
WITHIN SHOP DRAWING SUBMITTALS PRIOR TO INSTALLATION.
PROVIDE NEW 2" PC AND 1-1/2" HPS VALVES AT THIS LOCATION.
COORDINATE OUTAGE WITH VA FACILITIES TO ISOLATE MAINS TO
ALLOW FOR TAKE-OFF TEE TO BE INSTALLED.
EXISTING 1" PC VALVE NOT LARGE ENOUGH. LEAVE IN PLACE.
ROUTE 3/4" PIPING HWS & HWR PIPING BEHIND COLUMN. CONCEAL
WITHIN CHASE WALL AS REQUIRED.
PROVIDE A HUMIDISTAT (IN ADDITION TO DEDICATED THERMOSTAT) TO
CONTINUALLY RECORD BOTH TEMPERATURE AND RELATIVE HUMIDITY
OF STERILE STORAGE AREA. COORDINATE STORAGE OF DATA LOGS
WITH VA COR FOR APPROPRIATE METHOD OF SAVING DATA.
PROVIDE A LAMINATED AS-BUILT DRAWING OF ALL SNOWMELT TUBING
ZONES/LAYOUT WITHIN MANIFOLD BOX FOR REFERENCE USE.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
MECHANICAL CONTRACTOR WILL BE RESPONSIBLE TO REVIEW
ACCESSIBILITY TO AREAS OUTSIDE THE CONSTRUCTION LIMITS TO
DETERMINE APPROXIMATE AMOUNT OF OVERTIME REQUIRED TO
PERFORM ALL MECHANICAL WORK INDICATED. COORDINATION OF
SCHEDULES WITH ADJACENT DEPARTMENTS AND CLEANING OF ALL
DEBRIS AFTER EACH WORK SHIFT SHOULD BE ASSUMED IN THE BASE
BID SCOPE.
ANY MAJOR OUTAGES INDICATED ON THESE DRAWINGS SHALL BE
SCHEDULED TO BE PERFORMED AFTER NORMAL BUSINESS HOURS OR
DURING WEEKEND PERIODS TO MINIMIZE DISRUPTION.
COORDINATE ALL NEW PIPE ROUTING WITH ALL OTHER TRADES TO
ENSURE ADEQUATE CLEARANCES FOR DUCTWORK, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER OF RECORD. PROVIDE ALL OFFSETS AND
TRANSITIONS AS REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL PIPING DIRECTLY TO STRUCTURE. DO NOT SUPPORT
ANY PIPING FROM DUCTWORK, CONDUIT, OR OTHER PIPING
ENCOUNTERED.
WHERE MECHANICAL SYSTEMS TO REMAIN ARE DAMAGED, OR
DISTURBED, DURING THE COURSE OF CONSTRUCTION THE
CONTRACTOR WILL BE RESPONSIBLE TO REMOVE DAMAGED
PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL QUALITY AND
FUNCTIONALITY.
ALL EXISTING PIPING THROUGH NEW FIRE RATED WALLS SHALL BE
ADEQUATELY FIRE SEALED AS REQUIRED.
THE MECHANICAL CONTRACTOR SHALL MAINTAIN ACCURATE RECORD
DRAWINGS SHOWING ALL DISCREPANCIES WITH ANY EXISTING PIPING
INDICATED OR REVISIONS TO THE NEW PLUMBING LAYOUTS. ALL
CHANGES WILL BE UPDATED WITHIN THE FINAL RECORD DRAWING SET.
THE SMALLEST ALLOWABLE PIPE SIZE FOR HEATING WATER SUPPLY
AND RETURN WILL BE 3/4".
UNLESS NOTED OTHERWISE, HEATING WATER SUPPLY AND RETURN
PIPING TAKE-OFFS TO REHEAT COILS SHALL BE 3/4" DIAMETER.
HEATING WATER SUPPLY AND RETURN PIPING TAKE-OFFS SHALL BE
OFF THE TOP OF MAIN.
PROVIDE 1/2" DRAIN VALVE AT NEW HEATING WATER SUPPLY AND
RETURN PIPE LOW POINTS, DOWNSTREAM OF ISOLATION VALVES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:2
A
M
1375-MP111
FIRST LEVEL PIPING PLAN WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
1/8" = 1'-0"
FIRST LEVEL PIPING PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023Revisions: Date:
GENERAL NOTES:
EF
6"RD-1
3,460 SQFT
INCLUDES 370
SQFT SIDEWALL
6"RD-1
3,310 SQFT
INCLUDES 370
SQFT SIDEWALL
6"RD-1
3,400 SQFT
INCLUDES 370
SQFT SIDEWALL
6"RD-1
3,450 SQFT
INCLUDES 370
SQFT SIDEWALL
6"ORD-1
3,460 SQFT
INCLUDES 370
SQFT SIDEWALL
6"ORD-1
3,310 SQFT
INCLUDES 370
SQFT SIDEWALL
6"ORD-1
3,400 SQFT
INCLUDES 370
SQFT SIDEWALL
6"ORD-1
3,450 SQFT
INCLUDES 370
SQFT SIDEWALL
4" VTR
4" VTR
4" VTR
IGV
3"ORD-1
223 SQFT
INCLUDES 168
SQFT SIDEWALL
3"RD-1
225 SQFT
INCLUDES 168
SQFT SIDEWALL
2" STEAM RELIEF VENTS
R
' - 0
" 18"x18" PENETRATION FOR
16"X16" EXHAUST DUCT DOWN
52"x52" PENETRATION FOR
48"X48" INTAKE DUCT DOWN
3"ORD-1
260 SQFT
3"RD-1
260 SQFT
PROVIDE NEW ROOFTOP HYDRANT,
WOODFORD MODEL SRH-MS, WITH
DOUBLECHECK BACKFLOW
PREVENTER, ASSE 1052 APPROVED.ACCU
SERVING
CRAC-01
REFRIGERANT PIPING DOWN THROUGH
ROOF. PROVIDE CURBED DOGHOUSE TO
PROTECT FROM WATER INFILTRATION.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
COORDINATE ALL DUCTWORK, PIPING AND PLUMBING ROUTING WITH
ALL OTHER TRADES TO INSURE ADEQUATE CLEARANCES FOR
DUCTWORK, PLUMBING, ELECTRICAL CONDUIT, STRUCTURAL
SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE CONFLICTS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER OF
RECORD. PROVIDE ALL OFFSETS AND TRANSITIONS AS REQUIRED FOR
A CLEAN INSTALLATION.
THE EXACT LOCATION OF EQUIPMENT ROUGH-INS SHALL BE VERIFIED
WITH THE STAMPED APPROVED SHOP DRAWINGS PRIOR TO ANY FIELD
INSTALLATION.
SUPPORT ALL DUCTWORK, PIPING AND PLUMBING DIRECTLY TO
STRUCTURE. DO NOT SUPPORT ANY PIPING FROM DUCTWORK,
CONDUIT, OR OTHER PIPING ENCOUNTERED.
THE MECHANICAL CONTRACTOR SHALL MAINTAIN ACCURATE RECORD
DRAWINGS SHOWING ALL DISCREPANCIES WITH ANY EXISTING PIPING
INDICATED OR REVISIONS TO THE NEW DUCTWORK, PIPING AND
PLUMBING LAYOUTS. ALL CHANGES WILL BE UPDATED WITHIN THE
FINAL RECORD DRAWING SET.
MECHANICAL CONTRACTOR WILL BE RESPONSIBLE TO REVIEW
ACCESSIBILITY TO AREAS OUTSIDE THE CONSTRUCTION LIMITS TO
DETERMINE APPROXIMATE AMOUNT OF OVERTIME REQUIRED TO
PERFORM ALL MECHANICAL WORK INDICATED. COORDINATION OF
SCHEDULES WITH ADJACENT DEPARTMENTS AND CLEANING OF ALL
DEBRIS AFTER EACH WORK SHIFT SHOULD BE ASSUMED IN THE BASE
BID SCOPE.
ANY MAJOR OUTAGES INDICATED ON THESE DRAWINGS SHALL BE
SCHEDULED TO BE PERFORMED AFTER NORMAL BUSINESS HOURS OR
DURING WEEKEND PERIODS TO MINIMIZE DISRUPTION.
WHERE MECHANICAL SYSTEMS TO REMAIN ARE DAMAGED, OR
DISTURBED, DURING THE COURSE OF CONSTRUCTION THE
CONTRACTOR WILL BE RESPONSIBLE TO REMOVE DAMAGED PORTIONS
AND INSTALL NEW PRODUCTS OF EQUAL QUALITY AND FUNCTIONALITY.
ALL EXISTING PIPING THROUGH NEW FIRE RATED WALLS SHALL BE
ADEQUATELY FIRE SEALED AS REQUIRED.
HEATING WATER SUPPLY AND RETURN PIPING TAKE-OFFS SHALL BE
OFF THE TOP OF MAIN.
PROVIDE 1/2" DRAIN VALVE AT NEW HEATING WATER SUPPLY AND
RETURN PIPE LOW POINTS, DOWNSTREAM OF ISOLATION VALVES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:1
A
M
1375-M121
MECHANICAL ROOF PLAN WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
1/8" = 1'-0"
MECHANICAL ROOF PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023Revisions: Date:
KEY NOTES:
GENERAL NOTES:
B
C
D
A
1.5
HOUSEKEEPING
AIDES CLOSET
80-148
TELECOMMUNICATIONS
ROOM
80-149
VAV
1-01
M400 x x x x
AHU
1-01 x ø
J-8"
A-6"
(2)A-14"
(2)G-14"
C-12x10
I-18x12
60x30
70x30
42ø ø x
RISE
RISE
48X48 UP
THROUGH ROOF
TO IGV-01
x
70x30 DN
60x30 DN
118" (L) x 46" (H)
LOUVER WITH 36"
DEEP PLENUM
60x24 x
M400 VAV
1-31
RF
32x18
SUPPLY DUCT
SMOKE DETECTOR
RETURN DUCT
SMOKE DETECTOR
12x10
C-12x10
C-12x10
I-18x12
CRAC
1 PROVIDE AND INSTALL RUSKIN, MODEL PRD18, PRESSURE RELIEF
DOOR. SET BLOWOUT PRESSURE AT 4.0" W.C. LOCATE ON SIDE OF
DUCT WHERE SHOWN.
ROUTE 3" STEAM AND 2" PUMPED CONDENSATE PIPING THROUGH
WALL AS REQUIRED. REFER TO DRAWING MP111 FOR
CONTINUATION AND CONNECTION INTO PCC PIPING MAINS.
ROUTE 4" CHILLED WATER SUPPLY AND RETURN PIPING THROUGH
EXISTING WALL CONSTRUCTION, COORDINATE WITH ARCHITECTURAL
AND STRUCTURAL DETAILS. REFER TO DRAWING MP111 FOR
CONTINUATION AND CONNECTION INTO PCC PIPING MAINS.
3" HEATING WATER SUPPLY AND RETURN PIPING TO PENETRATE NEW
PRECAST PANEL AS REQUIRED. REFER TO DRAWING MH111 FOR
CONTINUATION AND CONNECTION INTO PCC PIPING MAINS.
ROUTE 3/4" CONDENSATE PIPE FROM COOLING COIL DRAIN TO FLOOR
DRAIN. USE MANUFACTURER FAN DATA TO CALCULATE TRAP DEPTH.
COORDINATE A MINIMUM OF 36" CLEARANCE IN FRONT OF VFD
CONTROLLER MOUNTED TO AHU. COORDINATE ON-SITE WIRING AND
INSTALLATION REQUIREMENTS WITH MANUFACTURER AND
ELECTRICAL SUBCONTRACTOR AS REQUIRED. PERFORM START-UP
AND PROGRAMMING WITH CONTROLS CONTRACTOR ASSISTANCE.
INTEGRAL FACE AND BYPASS STEAM COIL TO BE PROVIDED WITH
TWO(2) INTERNALLY SEPARATE PIPING CIRCUITS. DOUBLE-UP ALL
CONTROLS AND PIPING COMPONENTS PER PIPING DIAGRAM ON
DRAWING M501. COORDINATE PRIMARY CIRCUIT WITH SIDE THAT
INCLUDES TRAP MONITORING INTEGRATED WITH BAS.
NOT USED.
NOT USED.
NOT USED.
NOT USED.
INLINE PUMPS FOR SNOWMELT SYSTEM ARE SIZED FOR REDUNDANT
OPERATION AND ARRANGED IN PARALLEL USING MOUNTING
BRACKETS SECURED TO WALL WITH NEOPRENE ISOLATION. REFER
TO PIPING DIAGRAM FOR ALL REQUIRED COMPONENTS.
STEAM TRAPS AND CONDENSATE PIPING ALONG BACK SIDE OF UNIT
TO ALLOW ENOUGH ELEVATION TO SLOPE TO FLASH TANK WITHOUT
PIT. COORDINATE HUMIDIFIER / PREHEAT COIL MOUNTING HEIGHTS.
ROUTE 3/4" CONDENSATE PIPE FROM HUMIDIFIER DRAIN TO FLOOR
DRAIN. PROVIDE APPROPRIATELY SIZED P-TRAP WITH CLEANOUT.
MECHANICAL CONTRACTOR TO PROVIDE 15" RAIL TO PROTECT
STEAM AND CHILLED WATER ASSEMBLIES USING A ULINE SAFETY
GUARD MODEL H-7719 (OR H-7721) AND TWO(2) ULINE SAFETY POSTS
MODEL H-3715. MECHANICAL CONTRACTOR TO VERIFY LAYOUT.
MECHANICAL CONTRACTOR TO PROVIDE THREE(3) ULINE SAFETY
GUARDS MODEL H-4899 AND FOUR(4) ULINE SAFETY POSTS MODEL
H-3715. CONTRACTOR TO VERIFY WITH COND PUMP EQUIPMENT.
PROVIDE A 118"X46" DRAINABLE BLADE LOUVER (VERIFY EXACT
OPENING SIZE WITH PRECAST PANEL SUPPLIER). LOUVER SHALL BE
A GREENHECK MODEL EHM-601 OR EQUAL AND COME WITH A
1/2"X1/2" STAINLESS STEEL BIRDSCREEN SECURED TO BACKSIDE OF
ASSEMBLY. LOUVER FINISH SHALL BE AAMA 2605 COATING
CONSISTING OF 2-COAT OF 70% KYNAR (SUBMIT 6"X6" METAL COLOR
SAMPLES TO ARCHITECT FOR APPROVAL. INCLUDE A FLANGE ON ALL
SIDES TO CONCEAL ROUGH EDGES OF WALL OPENING AND SECURE
AS REQUIRED WITH HIGH GRADE SEALANT/CAULKING.
NOTE THAT ALL PRECAST PANELS UNDERNEATH THIS LOUVER SHALL
BE REMOVABLE TO ALLOW EQUIPMENT TO BE TRANSPORTED INTO
BUILDING AFTER PRECAST PANELS AND ROOF ARE INSTALLED. ALSO
NOTE THAT THIS ENTRY POINT MAY STILL REQUIRE A CRANE TO
LOWER INTO THIS CONFINED AREA BEHIND BUILDING
ROUTE 1-1/2" 125# STEAM TO STEAM CONDENSATE PUMP SCP 01
REDUCE DOWN TO 3/4" PIPE FOR CONNECTION TO EQUIPMENT.
PROVIDE EITHER STEEL TUBING OR UNISTRUT STAND, OR HIGH 12"
CONCRETE BASE, FOR RETURN FAN SUPPORT ABOVE FLOOR. REFER
TO DETAIL 2/M503 UTILITY SET RETURN FAN MOUNTING.
ROUTE 2" 30# STEAM RETURN FROM HEATING COIL, HUMIDIFIER AND
HEAT EXCHANGERS, 1" 30# STEAM RETURN FROM STEAM MAIN DRIP
TRAPS AND 1" 125# STEAM RETURN FROM HIGH PRESSURE STEAM
TRAP TO SEPARATE FLASH TANK CONNECTIONS. REFER TO M501
FOR PIPING SCHEMATIC.
PROVIDE AN AIR HANDLER ACCESS DOOR ON BACK SIDE OF AIR
HANDLING UNIT. REFER TO SHEET M500 FOR LOCATION.
A.
B.
C.
D.
E.
F.
G.
H.
COORDINATE ALL DUCTWORK ROUTING WITH ALL OTHER TRADES TO
INSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER OF RECORD. PROVIDE ALL OFFSETS AND
TRANSITIONS AS REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL DUCTWORK DIRECTLY TO STRUCTURE. DO NOT
SUPPORT ANY DUCTS FROM DUCTWORK, CONDUIT, OR OTHER PIPING
ENCOUNTERED.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO VAV BOXES SHALL BE
THE SAME SIZE AS THE VAV INLET CONNECTION.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO DIFFUSERS, GRILLES
AND REGISTERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR
GRILLE/REGISTER CONNECTION.
ALL FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED
IN SHAFT WALLS SHALL BE INSTALLED TO ALLOW FOR SERVICE OF
THEIR FUSIBLE LINK/ACTUATOR PER FACILITY STANDARDS. ANY
CONFLICTS WHICH WILL PREVENT ACCESS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND ENGINEER OF RECORD.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD. DO NOT INSTALL VALVES,
VAV BOXES, SENSOR, OR DAMPERS ABOVE GYPSUM BOARD CEILINGS.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD CEILINGS AND BULKHEADS.
ADJUST PIPE AND DUCT THAT RUN PARALLEL TO BULKHEAD FRAMING
TO BE EITHER OUTSIDE OF FRAMING OR BETWEEN FRAMING.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR FOR MODIFIED BULKHEAD FRAMING WHERE EXISTING
AND NEW PIPING AND DUCT WILL CAUSE INTERFERENCE.
PROVIDE EACH NEW SUPPLY DIFFUSER/GRILLES WITH A SINGLE BLADE
TAKE-OFF DAMPER WITH QUADRANT LOCKING DEVISE. PERFORM ALL
BALANCING OF NEW DIFFUSERS THROUGH THOSE TAKE-OFF DAMPERS.
ALL NEW RETURN/EXHAUST GRILLES WILL BE PROVIDED WITH
OPPOSED BLADE BALANCING DAMPERS POSITIONED UPSTREAM PAST A
MINIMUM OF ONE TRANSITION FOR SOUND ABATEMENT. BALANCING
ANY DIFFUSERS/GRILLES USING INTEGRAL DAMPERS WILL NOT BE AN
APPROVED METHOD OF BALANCING.
B
C
D
A
1.5
M400
S T
M
2" SMR
2" SMS
UH
1-02
HEX
1-03
UH
1-01
AHU
1-01
TELECOMMUNICATIONS
ROOM
80-149
HOUSEKEEPING
AIDES CLOSET
80-148
T UH 1-01
TUH 1-02
T VAV 01
T V
A V
-0
FT
SCP
SMP
0-01
SMP
0-02AS
0-02
ET
0-02
2" STEAM VENTS
UP THRU ROOF
GFS
0-02
S T
M
R
C W
R
C W
S
M400
NOTE THAT ALL END OF MAIN
DRIP TRAPS TO BE ROUTED BACK
TO FLASH TANK WITH DEDICATED
PIPING, NOT ALL SHOWN ON PLAN
VIEW FOR LEGIBILITY PURPOSES.
1 1/4" 30#STM
P C
P C
/2
S T
M
/2
S T
M
1 1/2" 125#STM
/2
R
2" PC
TVAV 31
ELECTRICAL
80-150 CRAC
FIRST LEVEL
0"
LEVEL 1 INTERSTITIAL
10'-3 1/2"
TOP OF ROOF SLAB
18'-8"
Grade -1'-0"
TOP OF PRECAST PANEL
20'-8"
1.5
M400
FIRST FLOOR
0' - 0"
T.O. ROOF SLAB
18' - 8"
T.O. PARAPET
20' - 11"
ROOF
13' - 5"
T/ PARAPET
14' - 8 1/2"
STORM RESISTANT LOUVER, SEE
DRAWING M400 KEY NOTES
24"X24" INSULATED
DOOR ACCESS PANEL
WITH CAM LATCHES
PROVIDE CLEARANCE
AROUND REAR OF AHU
FOR SERVICE ACCESS
36" DEEP PLENUM CONSTRUCTED OF
GALAVANIZED STEEL AND COVERED IN 3"
FIBERBOARD INSULATION WITH FSK FACING
(SLOPE BOTTOM TO DRAIN OUT LOUVER FACE)
RETURN/EXHAUST FAN MOUNTED
ON SPRING ISOLATOR SECURED
TO TALL 12" EQUIPMENT PAD.
24x60
24x60
70x30
AHU
1-01
80x24 44x24 18x32
3" HWR
FIRST LEVEL
0"
LEVEL 1 INTERSTITIAL
10'-3 1/2"
TOP OF ROOF SLAB
18'-8"
Grade -1'-0"
BC A
M400
FIRST FLOOR
0' - 0"
T.O. ROOF SLAB
18' - 8"
ROOF
13' - 5"
T/ PARAPET
14' - 8 1/2"
30x70 x
24x60 14x18
10x12 x x
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:2
A
M
1375-M400
MECHANICAL ROOM ENLARGED
PLANS
WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
1/4" = 1'-0"
ENLARGED MECHANICAL ROOM - HVAC PLAN
MECHANICAL ROOM - ISOMETRIC
1/4" = 1'-0"
ENLARGED MECHANICAL ROOM - PIPING PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023
1/4" = 1'-0"
MECHANICAL ROOM SECTION AT LOUVER (FACING NORTH)
1/4" = 1'-0"
MECHANICAL ROOM SECTION LOOKING TOWARD AHU (FACING WEST)
Revisions: Date:
C H W
EP1
A
A
Drain Conn.
R
S
R
S
D D
ID
(A) 72 2145 lbs
(B) 136 5194 lbs
(C) 48 1200 lbs
(D) 6 243 lbs
(E) 78 4023 lbs
(F) 72 1990 lbs
20Ga Galv Foam 20Ga 304 SS Foam 20Ga Galv Foam
ID
PL1
CHW
M8
SF
M15 FF
PL2
HUM
VIFB
CB1
6 6 6 6 6
RA
RA
OSA
ITEM # DESCRIPTION FURNISHED BY: INSTALLED BY:
LOW VOLTAGE
(WIRE AND CONDUIT)
LINE POWER
(WIRE AND CONDUIT) OTHER NOTES
BUILDING AUTOMATION CONTROL PANELS
(INCLUDES UNITARY CONTROLLERS & MCU)
CC CC CC CC (SEE NOTE) HIGH VOLTAGE WIRING VIA LICENSED ELECTRICIAN PAID THROUGH CC BID
VAV BOX ACTUATOR CC MC/EM (NOTE 1) CC CC/EC (SEE NOTE 2)
1) MC MAY OPT TO HAVE VAV CONTROLLER FACTORY MOUNTED, OR FIELD INSTALLED AT EXPENSE OF MC
2) CC TO INCLUDE ALL ELECTRIAL COSTS FOR 120/1 CONNECTIONS TO 24 VOLT TRANSFORMER
3 VAV BOX CONTROLLER CC CC CC CC/EC (SEE NOTE) CC TO INCLUDE ALL ELECTRICAL COSTS FOR 120/1 CONNECTIONS TO 24 VOLT TRANSFORMER
AUTOMATIC CONTROL DAMPERS
(DUCT OR PLENUM MOUNTED) CC MC CC EC (SEE NOTE) CC TO SUBCONTRACT EC FOR WIRING 120/1 DAMPER ACTUATORS, ALL LOW VOLTAGE BY CC4
AUTOMATIC CONTROL DAMPERS
(AHU OR EQUIPMENT MOUNTED) EM (WITHIN MC BID) EM CC EC (SEE NOTE) CC TO SUBCONTRACT EC FOR WIRING 120/1 DAMPER ACTUATORS, ALL LOW VOLTAGE BY CC5
6 MANUAL ISOLATION VALVES PC PC NA NA -
7 AUTOMATIC CONTROL VALVES CC PC CC EC (SEE NOTE) CC TO SUBCONTRACT EC FOR WIRING TO 120/1 VALVE ACTUATORS, ALL LOW VOLTAGE BY CC
PIPE INSERTION DEVICES AND TAPS
(THERMOWELLS, FLOW OR PRESS. SENSORS)
CC PC CC NA CC TO COORDINATE INSTALLED LOCATION WITH PC FOR WELL, OR TAP INSTALLATION8
DUCT MOUNTED SENSORS
(TEMPERATURE, HUMIDSTAT, ETC.)
CC CC/MC (SEE NOTE) CC NA MC TO SEAL ALL DUCT PENETRATIONS AS REQUIRED FOR DUCT LEAKAGE RATING9
AIR HANDLING UNIT MOUNTED SENSORS
(TEMPERATURE, HUMIDSTAT, ETC.)
CC CC/MC (SEE NOTE) CC NA MC TO INSURE PENETRATIONS THROUGH AIR HANDLER CASING WILL NOT IMPACT LEAKAGE RATING10
11 DUCT MOUNTED AIRFLOW SENSORS CC CC/MC (SEE NOTE) CC NA MC TO SEAL ALL DUCT PENETRATIONS AS REQUIRED FOR DUCT LEAKAGE RATING
12 AHU/FAN MOUNTED AIRFLOW SENSORS EM (WITHIN MC BID) EM (SEE NOTE) CC NA EQUIPMENT MANUFACTURER TO INSTALL/POSITION AND PROVIDE SITE CALIBRATION INSTRUCTIONS
13 CURRENT SWITCHES CC CC CC EC (SEE NOTE) EC TO COORDINATE HIGH VOLTAGE WIRING INSTALLATION WITH CC FOR PLACEMENT OF SENSOR
VARIABLE FREQUENCY DRIVES
(PUMPS, INDIV. FANS, ETC.)
CC EC CC EC (SEE NOTE) EC TO COORDINATE HIGH VOLTAGE WIRING INSTALLATION WITH CC FOR PLACEMENT OF SENSOR14
VARIABLE FREQUENCY DRIVES
(AHU OR FACTORY MOUNTED EQUIPMENT) EM (WITHIN MC BID) EC (NOTE1) CC EC (NOTE 2)
1) EC TO CONFIRM SINGLE OR MULTIPLE POINT CONNECTION SUBMITTALS
2) EC TO COORDINATE HIGH VOLTAGE WIRING INSTALLATION WITH DRWINGS/CC PRIOR TO BID
BOILER CONTROL PACKAGES EM (SEE NOTE) EM/PC CC EC
EM TO VERIFY PACKAGES CONTROLS ARE COMPATIBLE WITH CC SYSTEMS. EM RESPONSIBLE FOR ANY GATEWAYS, SENSORS OR
PROTOCOL CONVERSION REQUIRED FOR FULL INTEGRATION TO BAC.
CHILLER CONTROL INTERFACE EM (SEE NOTE) EM/PC CC EC
EM TO VERIFY PACKAGES CONTROLS ARE COMPATIBLE WITH CC SYSTEM. EM RESPONSIBLE FOR ANY GATEWAYS, SENSORS OR
PROTOCOL CONVERSION REQUIRED FOR FULL INTEGRATION TO BAC.
CHILLER/BOILER PROVIDED FLOW SWITCHES AND
EXTERNALLY MOUNTED SAFETY DEVICES EM PC CC EC ALL TRADES TO COORDINATE WITH EQUIPMENT SUPPLIER PRIOR TO BIDS.18
19 COOLING TOWER BASIN HEATERS EM CC EC ALL TRADES TO COORDINATE WITH EQUIPMENT SUPPLIER PRIOR TO BIDS
20 REFRIGERANT MONITORS CC CC EC (SEE NOTE) CC TO INCLUDE ALL ELECTRICAL COSTS ASSOCIATED 120/1 CONNECTIONS TO CONTROL PANEL
21 BOILER SHUT DOWN SWITCH(ES) CC CC EC (SEE NOTE) CC TO PAY ALL ELECTRICAL COSTS ASSOCIATED WITH HIGH VOLTAGE CONNECTION TO SHUNT TRIP BREAKER
22 ROOM PRESSURE MONITORS CC CC NA CC TO INTEGRATE ALL ROOM PRESSURE MONITORS INTO BAC FOR REMOTE ALARM MONITORING
PC
CC
CC
CC
MEDICAL GAS ALARM PANELS
(FOR BOTH AREA OR MASTER) PC PC MC OR PC EC (SEE NOTE)
EC TO INCLUDE ALL ELECTRICAL COSTS ASSOCIATED WITH 120___
CONNECTIONS TO ALARM PANEL. PC TO INCLUDE ALL LOW
VOLTAGE WIRING BETWEEN ALARM PANEL AND REMOTE SENSORS.
COMPUTER ROOM COOLING UNIT
(WITH FACTORY MOUNTED CONTROLS) EM (WITHIN MC BID) EM/MC CC NA
EM TO CONFIRM COMPATIBILITY WITH CC SYSTEM. ANY REQUIRED GATEWAYS (SITELINK PANELS), OR NETWORK INTEGRATION
CARDS TO BE INCLUDED WITH MANUFACTURER'S QUOTE IF NECESSARY.
PACKAGED RTU CONTROLS EM (WITHIN MC BID) EM/MC CC NA25
FIRE/SMOKE DAMPERS
(WITH DUCT MOUNTED SMOKE DETECTORS) MC MC (NOTE 1) FAC EC (NOTE 2)
1) DAMPER AND ANY LOOSE DUCT DETECTORS TO BE INSTALLED/MOUNTED BY MC.
2) DAMPERS WITH 120/1 VOLT POWER CONNECTIONS BY EC. MC TO COORDINATE DURING BID.
FIRE/SMOKE DAMPERS
(CONTROLLED FROM AREA DETECTORS) MC MC (NOTE 1) FAC EC (NOTE 2)27
AHU SMOKE DETECTORS MC MC CC/FAC (SEE NOTE) NA
CC TO MOUNT SENSORS AND WIRE INTO BAC. FAC TO PROVIDE MODULE TO INTEGRATE INTO FIRE ALARM SYSTEM TO DIRECTLY
SHUT-DOWN UNIT.
DAMPER END SWITCHES
(BOTH MOTORIZED CONTROL DAMPERS) CC MC CC EC (SEE NOTE) CC TO SUBCONTRACT EC FOR WIRING TO 120/1 DAMPER ACTUATORS, ALL LOW VOLTAGE BY CC.29
DAMPER END SWITCHES
(FIRE/SMOKE DAMPERS) MC MC CC (SEE NOTE) NA CC TO COORDINATE ANY ADDITIONAL INTEGRATION WITH FAC AS REQUIRED.30
EM TO CONFIRM COMPATIBILITY WITH CC SYSTEM. ANY REQUIRED GATEWAYS (SITELINK PANELS), OR NETWORK INTEGRATION
CARDS TO BE INCLUDED WITH MANUFACTURER'S QUOTE.
1) DAMPER AND ANY LOOSE DUCT DETECTORS TO BE INSTALLED/MOUNTED BY FAC.
2) DAMPERS WITH 120/1 VOLT POWER CONNECTIONS BY EC. MC TO COORDINATE DURING BID.
31 STARTERS AND HOA SWITCHES EC CC EC EC AND CC TO COORDINATE TYPE AND LOCATION FOR EACH PIECE OF EQUIPMENT IDENTIFIED.EC
KEY:
CC = CONTROLS CONTRACTOR *
MC = MECHANICAL CONTRACTOR **
EC = ELECTRICAL CONTRACTOR
PC = PIPING OR PLUMBING CONTRACTOR **
GC = GENERAL CONTRACTOR
EM = EQUIPMENT MANUFACTURER
FAC = FIRE ALARM CONTRACTOR
OWN = OWNER'S FACILITY ENGINEERS
*CONTROLS CONTRACTOR MAY BE SUBCONTRACTED OR DIRECT CONTRACT TO OWNER, ALL ITEMS WITH TABLE APPLY IN EITHER SCENARIO.
*** MECHANICAL AND PIPING/PLUMBING CONTRACTS COMBINE INTO SINGLE CONTRACT IN MOST PROJECTS.
NOTE = MANUFACTURER'S PROVIDING LOOSE CONTROL COMPONENTS (FLOW SWITCHES, TEMP SENSORS, ETC.) WILL BE COMPLETELY MOUNTED/WIRED/ INSTALLED BY THE CONTRACTOR PURCHASING THAT EQUIPMENT. ONLY LOW VOLTAGE CONNECTIONS TO BAC BY CC.
MATRIX OF RESPONSIBILITIES FOR BUILDING AUTOMATION CONTROLS COMPONENTS
1 2 3 4
PRE-FILTERS.
HEATING COIL.
COOLING COIL.
HUMIDIFIER.
SUPPLY FAN.
FINAL FILTER.
CHANNEL BLENDER
KEY NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7301 OHMS LANE
SUITE #215
(952) 854-9302 TEL.
© PROPERTY OF ADVANCED
STRUCTURAL TECHNOLOGIES.
THIS DOCUMENT MAY NOT BE
USED OR COPIED WITHOUT THE
PRIOR WRITTEN CONSENT OF
ADVANCED STRUCTURAL
TECHNOLOGIES.
EDINA, MN 55439
ASTENG.COM
C R e v it P ro je c ts
\M
V A
M P
L S
W
C
M A
R ja s o n g o tt w a lt
.r v t
/2
/2
:1
:2
A
M
1375-M500
AIR HANDLING UNIT DETAILS WOMEN'S CLINIC AND
MAMMOGRAPHY ADDITION
1 VETERANS DRIVE
618-181
05/26/2023 JRG TNH15328
NO SCALE
AHU 1-01
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
05/26/2023Revisions: Date:
R
S
R
S
D
M
IN
[1 m m
2"-30#R
STEAM
CONDENSATE
RETURN
TEMPERATURE SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR FINAL LAYOUT
D U
C T
H E
IG
H
T
H1 /3
H /3
H /3
H
CONTROL VALVE
(TYPICAL)
RETURN
SUPPLY
BALL OR
BUTTERFLY
VALVE
STRAINER
COOLING
COIL
A
A
THERMOMETER
(TYPICAL)
AUTOMATIC AIR AIR VENT PIPED TO F.D. AND ALSO INCLUDE BALL
VALVE FOR MANUAL VENT (TYPICAL)
NOTES:
1. PIPE COILS COUNTER-FLOW TO AIR FLOW.
2. LOCATE UNIONS TO ALLOW FOR COIL REMOVAL.
3. MOUNT THERMOMETERS AND GAUGES NO MORE THAN 8'-0" A.F.F.
4. REDUCE TO CALIBRATED ORIFICE BALANCING VALVE AS REQUIRED.
5. WINTER OPERATION: CLOSE CWS AND CWR ISOLATION VALVES AT MAINS AND DRAIN
CHILLED WATER COIL, LEAVE DRAIN VALVES OPEN. OPEN LOCKING BALL VALVE TO
ALLOW AIR FROM AIR HANDLING UNIT DRY VALVE.
6. COOLING SEASON: CLOSE LOCKING BALL VALVE AND DRAIN VALVES. OPEN CWS AND
CWR ISOLATION VALVES AT MAINS.
PRESSURE
GAUGE WITH
VALVE
(TYPICAL)
SEE NOTES 5
& 6 BELOW
AIR HANDLING UNIT STEAM PREHEAT
COIL PIPING DETAIL (2-WAY VALVE)
NO SCALE4b
AIR HANDLING UNIT COOLING COIL
PIPING DETAIL (2-WAY VALVE)
NO SCALE4a
SUPPLY "B"
RETURN "B"
STRAINER (TYPICAL)
SUPPLY "A"
HEAT EXCHANGER
RETURN "A"
BUTTERFLY VALVE
(TYPICAL)
MODULATING 2-WAY
CONTROL VALVE
(TYPICAL)
FLANGE (TYPICAL)
THERMOSTAT
(TYPICAL)
PRESSURE GAUGE
(TYPICAL)
T
PLATE AND FRAME
EXCHANGER PIPING DETAIL
NO SCALE4c
STEAM HUMIDIFIER DETAIL (for AH1WC-01) NO SCALE4e
SARCO TRAP MONITOR TIED
INTO BUILDING AUTOMATION
REDUCER
(TYPICAL)
UNION
(TYPICAL)
DUAL 50/50 STEAM SYSTEM CONTROL VALVES FOR
DEDICATED MV CIRCUITS (see dwgs)
FROM STEAM MAIN
DRIP TRAP
ASSEMBLY
TO CONDENSATE
RETURN
FLOAT AND THERMOSTATIC SIZED FOR 3
TIMES NORMAL COIL LOAD. PROVIDE
ONE(1) WITH REMOTE STEAM MONITOR
TO BUILDING AUTOMATION
STRAINER
(TYPICAL)
GATE VALVE
(TYPICAL)
FLEX CONNECTION
STRAINER WITH
BLOW DOWN
VALVE
VACUUM BREAKER
AIR VENT
SARCO TRAP MONITOR TIED INTO
BUILDING AUTOMATION
SARCO TRAP MONITOR TIED
INTO BUILDING AUTOMATION
PRESSURE GAUGE
BALL VALVE
CHECK VALVE
UNION
TRAP PUMP WITH
STEAM MOTIVE
VALVE/CAP FOR FUTURE STEAM
CONDENSATE RETURNS
FULL SIZE BY-PASS PIPED
TO FLOOR DRAIN
BASKET STRAINER
-1
/2
P C
ASME RATED FLASH TANK WITH 2 RETURN TAPS
-1"HIGH PRESSURE CONDENSATE
-2"LOW PRESSURE CONDENSATE AND
LOW PRESSURE DRIP RETURNS
HIGH PRESSURE CONDENSATE FROM DRIP TRAP
AT STEAM MOTIVE CONDENSATE PUMP
PROVIDE SUPPORTS HIGH ENOUGH FROM
BOTTOM OF PIT TO ALLOW FOR PITCHED
DRAIN INTO CONDENSATE PUMP
2"VENT THROUGH ROOF
PRESSURE GAUGE WITH
PIGTAIL AND VALVE
STRAINER WITH
BLOWDOWN VALVE
STEAM TRAPS (X2) WITH SARCO
MONITOR ON PRIMARY TRAP
DIRT LEG
GLYCOL FEEDER SYSTEM
WITH TANK AND PUMP
2" TO SNOW MELT DISTRIBUTION
MANIFOLDS
2" FROM SNOW MELT
DISTRIBUTION MANIFOLDS
THERMOMETER (TYP)
STRAINER W/ BLOWDOWN VALVE
AND CAP (TYP)
PRESSURE GAUGE (TYP)
1"
1"
3/4"
EXPANSION
TANK
AUTOMATIC
AIR VENT AIR VENT
DRAIN
AUTOMATIC
QUICK CONNECT
PIPE TO FLOOR DRAIN
BLOWDOWN
VALVE
DRAIN VALVE
WITH HOSE END
TEMPERATURE
SENSOR
TEST PLUG
MANUAL AIR
VENT (TYP)
TWO-WAY VALVE
UNION, TYPICAL
BUTTERFLY OR BALL
VALVE, TYPICAL
WATER TO WATER BRAZED
PLATE HEAT EXCHANGER
TO 1ST FLOOR FTR
AND VAV REHEAT COILS
VESTIBULE/LOBBY UNDERFLOOR HEAT
SMP
0-02
SMP
0-01
ET
0-02
AS
0-02
HEX
1-03
(50% PROPYLENE)
GFS
0-02
SUPPLY/RETURN PIPING MANIFOLDS IN LOCKABLE
WALL PANEL IN ROOM 80-145A
2"-30#R
PISTON VALVE
HIGH PRESSURE MOTIVE STEAM SUPPLY TO BE
TRAPPED AND FREE OF CONDENSATE
FT
SCP
CIRC PUMP SHWP 1-01
FOR RADIANT FLOORING
NOTE THAT STEAM COIL HAS 2
SEPARATED INTERNAL PIPING
CIRCUITS. PRIMARY CIRCUIT
WILL HAVE MONITORED STEAM
TRAP WITH BACK-UP CIRCUIT
FOR EMERGENCY OR 100%
OUTDOOR AIR OPERATION.
TEST TEE (TYP.)
1-1/4"-30#STM
MANIFOLD
TEST TEE (TYP)
LOW PRESSURE CONDENSATE
FOR END OF MAIN DRIP TRAPS
NOTE THAT CONTRACTOR WILL BE RESPOSIBLE TO SEPARATELY PROVIDE DEDICATED
STEAM LINES FOR BOTH HIGH PRESSURE CONDENSATE, AND LOW PRESSURE CONDENSATE
FOR NON-MODULATING END OF MAIN DRIPS. THOSE PIPES ARE NOT DIRECTLY SHOWN ON
THIS FLOW DIAGRAM OR PLAN VIEW DETAILS.
VENT THRU
ROOF
PIPE REDUCER 2" TO 3/4"
RIGHT BEFORE CONNECTION
SAFETY RELIEF SET FOR 150 PSIG
S
T M
S
T M
OUTLINE SPECIFICATION FOR NEW PISTON VALVES:
Piston valves shall be KLINGER model KVN, or equal, with integral bypass valve (bypass valve to also be a smaller version of the primary piston valve). Any other manufacturer submitted for equivalency shall pass the highest quality requirements of ISO 9001: 2008 along with a helium leakage test at the factory.