This document is a Technical Question Responses attachment related to Solicitation #36C77623R0193 for the Women's Clinic and Radiology Addition project at the Minneapolis, MN VA Medical Center.
The key details are:
- The openings in the glazed aluminum curtainwall do not need to meet AAMA 501.8-14 test standards, as originally referenced.
- The curtainwall does not have a minimum STC rating requirement, but higher STC ratings are preferred.
- The interior storefront does not need to meet impact rating or condensation resistance factor requirements.
- The walls do not require lead materials or lead-lined products, but the doors to the Mammography rooms will be lead-lined as indicated in the Opening Schedule.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLICITATION # 36C77623R0193
PROJECT NAME: WOMEN’S CLINIC AND RADIOLOGY ADDITION – MINNEAPOLIS, MN
TECHNICAL QUESTIONS AND VA RESPONSE TRACKING SHEET
ITEM
NO.
DATE
QUESTION
RECEIVED
DATE
QUESTION
ANSWERED
QUESTION GOVERNMENT RESPONSE
1. 3/5/2024 4/2/2024 Will all the openings need to meet AAMA 501.8-14 test standards? This is referenced in 1.7-B. in the glazed aluminum curtainwall specs in the applicable publications portion of the specifications, but not listed in the performance requirements section.
The openings will not need to meet AAMA 501.8-14. This reference can be disregarded.
2. 3/5/2024 4/2/2024 Will the curtainwall need to meet an STC rating of 50 (or greater)? We have reviewed 4-5 other blast curtainwall products, and they publish STC ratings ranging between 29-37.
The STC rating of 50 is not a minimum requirement, however higher STC ratings are preferred.
3. 3/5/2024 4/2/2024 Will the interior storefront need to be impact rated or meet a condensation resistance factor of 45?
The interior storefront does not need to meet an impact rating or condensation resistance rating.
4. 3/5/2024 4/2/2024 13 49 00 – Radiation Protection – Please confirm that none of the walls types require lead materials or lead lined products.
Lead lined walls & are not required.
However, doors to the Mammography rooms will be lead lined as indicated in Opening Schedule.